Design an art gallery Art gallery must be located somewhere beside

TOP VIEW OF PLAN

DESIGN PARAMETER

THERMAL COMFORT

Condition of mind which expresses satisfaction with the thermal environment


PERSONAL Insulating value of clothing Metabolic Rate = 0.4 CLO 1.0 CLO = 1.2 MET (70W/m2)

MEASUREABLE PARAMETER Temperature Relative humidity PSYCHOLOGICAL = 22C-25C = 35%-50%

Artificial lighting Comfort Level Environment control for objects and collections

= (150-300)lux = (50-150)lux

INDOOR AIR QUALITY

air quality of the building that affects the health and comfort of the occupants
Remove 50% dust Minimum Efficiency Reporting Value of 13

Filtration

Ventilation

diluted odor Decrease CO2

DESIGN CONDITION

INTERNAL COOLING LOAD


People Lighting Appliances Ventilation and infiltration Heat gain to duct

EXTERNAL COOLING LOAD


Wall Roof Conduction through glass Solar through glass

LIGHTING
MR16 lamps are halogen incandescent light sources

90 Lux (lumen/m2)
Each output 625 lumens, 50 watts. Thus , require 150 bulb for art galleries and 53 for cafateria.

LIGHTING

Lumilux T5 HE high effficiency tubular . Ticket sales area , toilet and store. Lux require for ticket sales room and toilet is 250 , for store room is 150 need. Each produce 1900 lumen and 21 watts. Sales ticket room need 15 bulb, store room need 9 bulb, toilet need 11bulb.

TYPE OF ROOF

WALL
4in heavy weight concrete block secondary meterial selected as (stucco and plaster) determine CLTD melaka 2.27N (Latitude), 102.25 E (longtitude)
At 3 pm noon wall facing south, (CLTD) = 42 wall facing north, (CLTD) = 29 wall facing east (CLTD) = 31 wall facing west (CLTD) = 61

INTERNAL COOLING LOAD CALCULALATED RESULTS

EXTERNAL COOLING LOAD CALCULATED RESULTS

DUCTING

Three most common methods to determine duct size


Velocity reduction Equal friction Static regain

CONCLUSION
Designing a building need a better understanding of thermal comfort, cooling load. Not all the condition are suitable.

RECOMMENDATION

Green building Solar panel