User Manual
Rev. 5/2/2012 Verify that you have the most current version of this document. Go to http://accounts.automatedlogic.com, then select Support > Download > Documents > Manuals.
Contents
Chapter 1 Chapter 2 Chapter 3 Chapter 4 What's new in the EIKON LogicBuilder v5.5 application ............................................. 3 What is the EIKON LogicBuilder application? ............................................................ 6 Getting to know the EIKON LogicBuilder workspace ................................................... 8 Determining the control program type ....................................................................... 10 Normal for all controllers except U line or ZN line ......................................................... 10 UNI for U line controllers ............................................................................................. 11 ZN for ZN line controllers ............................................................................................ 12 Chapter 5 Developing the logic ................................................................................................ 14 To begin a control program ......................................................................................... 14 To place microblocks .................................................................................................. 15 To draw wires and labels ............................................................................................. 16 To view errors ............................................................................................................. 17 To add comments ....................................................................................................... 18 To add lines and shapes ............................................................................................. 19 To add an image ......................................................................................................... 20 To create a custom microblock ................................................................................... 21 Chapter 6 Preparing logic for the WebCTRL interface .............................................................. 22 Chapter Formatting Properties pages ......................................................................... 22 To reorder items on the Properties page ....................................................... 22 To use the Text microblock to format text ...................................................... 23 Editing Properties page text using special characters ................................... 25 Formatting a microblock property ................................................................ 26 To use custom alarm and schedule categories............................................................. 30 Chapter 7 Simulating a control program ................................................................................... 32 Chapter 8 EIKON LogicBuilder productivity tools .................................................................... 34 To create and use symbols .......................................................................................... 34 To view or edit microblock common properties ............................................................ 35 To find a microblock or label ....................................................................................... 36 To find identical labels ............................................................................................... 37 To show a logical path ................................................................................................ 37 To show a wire's source microblock ............................................................................ 37 Chapter 9 Defining display options for ZS sensors ..................................................................... 38 To set the order of information displayed on a sensor .................................................. 38 To create custom Rnet tags ......................................................................................... 39 Chapter 10 To omit _# at the end of BACnet object names ......................................................... 40 Chapter 11 To select properties for ViewBuilder graphics ........................................................... 41 Chapter 12 Miscellaneous EIKON LogicBuilder menu commands and features ......................... 42 Chapter 13 Working with control programs created in the EIKON for WebCTRL application ......... 44 Index ..................................................................................................................................... 46
2012 Automated Logic Corporation. All rights reserved throughout the world. Automated Logic, WebCTRL, EIKON, and BACview are registered trademarks, and EnergyReports, Environmental Index, and Eco-Screen are trademarks of Automated Logic Corporation. BACnet is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies.
Chapter 1
What's new in the EIKON LogicBuilder v5.5 application
Improvement EquipmentBuilder is now installed with a WebCTRL system as a standalone application. The EIKON LogicBuilder File > EquipmentBuilder menu selection opens the application. The zone temp input to the Setpoint microblock can come from a label to allow for smoothing algorithms. To indicate an alarm condition in a zone (for example, to turn the zone coral due to an equipment failure) you may use 1 Set Color if True microblock in addition to a Setpoint microblock. When true, the Set Color if True microblock determines the equipment color but does not overwrite the Setpoint microblock's color output.
Revised microblocks
BACnet Binary Value Parameter BACnet Analog Value Parameter BACnet Multi-State Value Parameter BACnet Binary Value Status BACnet Analog Value Status BACnet Multi-State Value Status The above microblocks have been revised to support the new ZS Sensors, which will be in a separate release. The BACnet Multi-State Value Parameter and BACnet Multi-State Value Status microblocks now support 20 states, retiring the following microblocks.
BACnet Multi-State Value Parameter (20 state) BACnet Multi-State Value Status (20 state)
The new Sensor Display Order (page 38) menu option lets you define the order that microblock values will be displayed on a Sensor. The Microblock Common Properties Editor has a new Rnet tab. The EIKON LogicBuilder application has pre-defined Rnet tags that identify system values. You can create custom Rnet tags (page 39) if needed.
New in v5: Microblock Common Properties Editor (page 35) ZN microblock rules (page 12) You can view or edit common properties for the I/O, Network, Display, and BACnet microblocks in a control program. A ZN control program can now have: Integrator microblock is non-volatile "Always upload" feature in BACnet Analog Value Parameter microblock A maximum of 350 microblocks (previously 200) Up to 2 PID microblocks in addition to the zone controller microblock (previously 1 PID)
The integrator microblock now retains its output magnitude through a power loss, controller reset, or controller restart. Using a combination of logic that writes critical parameters within a control program to a BACnet Analog Value Parameter microblock and a new property of the BACnet Analog Value Parameter microblock, you can retain critical values through a power loss, through a controller restart, and (if the reference name of the microblock is unchanged) through a memory download. This new microblock provides improved PID algorithm and BACnet accessibility. NOTE A control program with this microblock works only with v5.2 or later WebCTRL systems and v4.x or later drivers.
20-state BACnet Multistate Value Parameter and 20-state BACnet Multistate Value Status microblocks OCL microblock system variable for weekday
To be consistent with the System Variable microblock, the weekday system variable has changed to WKDAY, where Monday = 1 to Sunday = 7. The previous weekday system variable, WDAY, will continue to work in existing control programs using Sunday = 1 to Saturday = 7. Use an * in a Network Input or Total Analog microblock's address to have the microblock automatically locate the nearest device that contains the object specified in the address. This feature eliminates the need for specific device addresses when retrieving values from common objects. For example, control programs on a campus that need oa_temp can automatically retrieve the value from the nearest device that contains that object name. You can edit the addresses that you created with the Third-Party BACnet Utility. Or, you can convert a control program into an integration program by changing I/O microblocks to Network or Display microblocks and setting the microblock addresses.
These allow the use of Network I/O and Display microblocks in the same program, and efficient re-use of programs for multiple instances of thirdparty equipment. NOTE You must enable Use Static Bindings on the WebCTRL System Settings > Communications tab. For more information or alternatives, see the BACnet Integration Guide (http://accounts.automatedlogic.com/tilib.nsf/0/16B62CAA979B5D8A 8525717200678C60/$FILE/BACnet%20Integration%20Guide.pdf).
Mark certain properties as You can right-click some properties in the EIKON LogicBuilder Read-only application and select Make Editable or Make Read-Only to determine that property's functionality in the WebCTRL interface. Remove all Property Page Text (page 42) Keep historical trends for ___days Use unitary naming (page 40) You can use this Tools menu add-on to remove property page text for all microblocks in a control program. You can now define this setting in the EIKON LogicBuilder application for I/O and Log microblocks. Previously, this setting was only in the WebCTRL interface. You can set your control program to use unitary naming to omit __# at the end of BACnet object names.
Immediate Triggered Write The Immediate Triggered Write property was removed from ANO2 and BNO2 microblocks. These microblocks automatically write their value as soon as they are enabled.
Chapter 2
What is the EIKON LogicBuilder application?
The EIKON LogicBuilder application creates control programs to control equipment, from single pieces of equipment to complex energy management functions. You build control programs using individual blocks of programming code called microblocks. You determine the properties for each microblock and connect the microblocks with graphical wires to create a sequence of operation. A control program is assigned to a piece of equipment in the SiteBuilder application, then the WebCTRL application downloads it into the controller that will directly control and monitor the equipment. You can change editable properties and view non-editable properties of control programs in the WebCTRL interface.
The typical procedure for creating a control program includes the following steps: 1 2 3 4 Determine the control program type (page 10). Develop the logic (page 14). Format Properties pages (page 22). Simulate the control program (page 32).
Or, you can use EquipmentBuilder to generate a control program and, optionally, the corresponding equipment graphic. Select File > EquipmentBuilder to open the application.
Chapter 3
Getting to know the EIKON LogicBuilder workspace
TIPS If the Property Editor is not visible, double-click an object in the workspace. You can use the Property Editor as a free-standing window, or you can select Options > Dock Property Editor to dock it in the EIKON LogicBuilder workspace.
Keyboard shortcuts are shown beside their corresponding commands in the menus. Press Ctrl + an arrow key to nudge selected objects. Press Shift+Ctrl while using the arrow keys to increase the size of the nudge. Click to undo 1 action, or click the drop-down arrow next to it to undo multiple actions at one or its drop-down arrow to redo actions. The number of actions you can undo or redo time. Click depends on the size of your computer's memory. The workspace size has no limit. Press Home to position the upper left corner of the workspace in the upper left corner of the window. Press End to jump to the bottom of the control program. Use the arrow keys or your mouse's scroll wheel to scroll through the workspace. From the Options menu you can:
Hide or show the workspace grid Enable Snap Figures and Text to Grid to constrain movement to 8 pixels for quick alignment; disable this feature for 1-pixel movement Zoom the view to 50, 100, or 200%
Chapter 4
Determining the control program type
Before you create a control program, first determine the control program type (Normal, UNI, or ZN), and then follow the appropriate rules below.
1 Setpoint microblock 1 Set Color microblock 1 or more Set Color If True microblocks
Each Time Clock microblock in a control program must have a unique schedule category. To use one or more ZS Sensors, the control program must have one Sensor Binder microblock and one BACnet Analog Sensed Value microblock for each value type, such as temperature or humidity, that will be read from the sensor network. To use an RS sensor, the control program must have an RS Zone Sensor microblock. To use a basic LogiStat or LogiStat Plus sensor with an SE line controller, the control program must have a LogiStat Zone Sensor microblock or an RS Zone Sensor microblock.
10
The following are not supported if the microblock's Rnet functionality is enabled: BACnet Binary Value Parameter BACnet Analog Value Parameter BACnet Multi-State Value Parameter BACnet Binary Value Status BACnet Analog Value Status BACnet Multi-State Value Status
NOTES Each Time Clock microblock in a control program must have a unique schedule category. The setpoint microblock's cooling setpoint must be wired to a PID Direct Acting microblock. The setpoint microblock's heating setpoint must be wired to a PID Reverse Acting microblock. Set time delay functions and trend intervals to at least 1 minute because U line controllers do not support time-critical applications. To use a LogiStat sensor, the control program must have a LogiStat Zone Sensor microblock. NOTE The U220 does not support any LogiStat sensor. For the actuator in a v+ controller to be protected by the controller warranty, the control program must contain the following microblocks: Zone Controller U-line Airflow Control The U220 is designed to handle miscellaneous pieces of equipment such as exhaust fans and room lighting. In many cases, these applications will not meet the unitary control criteria required to enable the UNI option. You may use any of the standard U220 zone control programs in the EquipmentBuilder Library.
11
You can download ZN control programs into a UNI. If your control program does not meet UNI rules, try saving it as a ZN control program. If your control program does not meet UNI or ZN rules but is appropriate for a zone control application, you can get the control program tagged by Automated Logic. Review Automated Logic's tagging policy (http://accounts.automatedlogic.com/sales/policy.nsf/7efc5bb11196e87185256b3c00785ad2 /eaffdfa1ccd769d88525735b004e7864!OpenDocument) on the accounts.automatedlogic.com website, then follow the instructions under "How do I get a control program tagged?".
Microblocks not supported Setpoint Optimization Set Color Toggle Lead/Standby Total Analog Input Average Analog Input Minimum Analog Input Maximum Analog Input
BACnet Analog Sensed Value Input BACnet Analog Input Analog Network Input Analog Network Input 2 LogiStat or RS Zone Sensor
NOTE Required microblocks must be located in the opening pane (1024 x 600 pixels) of the control program. NOTES Each Time Clock microblock in a control program must have a unique schedule category. The Zone Controller microblock provides primary heating and cooling PID control loops. If you need additional control loops, you may use up to 2 additional PID microblocks, but no more than 2.
12
To indicate an alarm condition in a zone (for example, to turn the zone coral due to an equipment failure) you may use 1 Set Color if True microblock in addition to a Setpoint microblock. When true, the Set Color if True microblock determines the equipment color but does not overwrite the Setpoint microblock's color output. To use one or more ZS Sensors, the control program must have one Sensor Binder microblock and one BACnet Analog Sensed Value microblock for each value type, such as temperature or humidity, that will be read from the sensor network. To use an RS sensor, the control program must have an RS Zone Sensor microblock. To use a basic LogiStat or LogiStat Plus sensor, the control program must have a LogiStat Zone Sensor microblock or an RS Zone Sensor microblock. NOTE The ZN220 does not support any LogiStat sensor. Other ZN's do not support the LogiStat Pro.
A ZN control program can have a maximum of 350 microblocks (excluding labels, text, and status microblocks). For the actuator in a v+ controller to be protected by the controller warranty, the control program must contain the following microblocks: Zone Controller Airflow Control The ZN220 is designed to handle miscellaneous pieces of equipment such as exhaust fans and room lighting. In many cases, these applications will not meet the zone criteria required to enable the ZN option. You may use any of the standard ZN220 zone control programs in the EquipmentBuilder Library. Tagging:
A control program that does not meet the above ZN criteria but is appropriate for a zone control or miscellaneous monitoring application can be tagged by Automated Logic as a ZN control program. Only tagged OCL microblocks can be used in a ZN control program. Get a tagged OCL microblock from http://accounts.automatedlogic.com (http://accounts.automatedlogic.com). Select Engineering > StdAppLibrary > Standard Application Library > WebCTRL > ZN551 & ZN253 Zone Applications & OCL Microblocks. Or, get Automated Logic to tag your own OCL microblock. Each microblock inside an untagged custom microblock counts against the ZN 350microblock limit. However, a tagged custom microblock counts as only 1 microblock. You can use tagged custom microblocks available in some applications in EquipmentBuilder. Or, get Automated Logic to tag your own custom microblock. To get a control program, OCL microblock, or custom microblock tagged, review Automated Logic's tagging policy (http://accounts.automatedlogic.com/sales/policy.nsf/7efc5bb11196e87185256b3c0078 5ad2/eaffdfa1ccd769d88525735b004e7864!OpenDocument) on the accounts.automatedlogic.com website, then follow the instructions under "How do I get a control program tagged?".
13
Chapter 5
Developing the logic
Use the following procedures to develop your control program.
2 3 4
NOTES For a Normal or UNI control program, you can select Control Program > Suppress Logic Page so that it cannot be seen in the WebCTRL interface. Select File > Info to view the file's name, location and dates. You can also select a Custom Icon that the WebCTRL navigation tree will show for the equipment. To use C for setpoint microblocks in a control program, select Control Program > Metric. If you change the Metric option for an existing control program, you must delete and reinsert all setpoint microblocks. To have Metric enabled for all future control programs, select Options > Preferences, then select Create new control programs as metric.
14
To place microblocks
1 Right-click the Microblock palette.
2 3
Click the icon of the microblock you want to use. Move the cursor into the workspace. NOTE Press and hold Shift if you want to place 2 or more of the selected microblock. Click to place the microblock. Edit the microblock's properties in the Property Editor. NOTES
4 5
If the Property Editor is not open, double-click the microblock. Red text in a field indicates an invalid value. You can right-click some properties and select Make Editable or Make Read-Only to determine that property's functionality in the WebCTRL interface.
TIPS Place all input microblocks on the left side of the workspace and all output microblocks on the right. Arrange microblocks so that logic flows from left to right and the sequence of operation can be easily followed. Hold Ctrl as you move a microblock to detach it from its wire. Use the Microblock Common Properties Editor (page 35) to view, compare, and edit common properties of I/O microblocks. The order of items on a WebCTRL Properties page is determined by the order in which microblocks are placed when developing the control program in the EIKON LogicBuilder application. To change the order, see To reorder items on the Properties page (page 22).
15
To draw wires
1 Click and drag from a microblock nib in the direction you want the wire to go. NOTE A wire automatically makes a 90 turn if you drag away from a straight line. To create additional 90 turns, right-click while continuing to hold down the left mouse button. 2 Release the left mouse button to end the wire. NOTE When drawing wires between closely placed microblocks, you can temporarily disable the snap-to feature by pressing Ctrl while drawing a wire.
Click and drag any wire segment in the direction of the move icon. Right-click where you want to add a joint on a wire, then select Add Joint. Right-click a green wire joint, then select Remove Joint. Click a wire, then select a different wire from the Type drop-down list.
16
To add labels
1 Select the Label tool.
Move the cursor to the nib of a microblock or to the end of a wire, then click the workspace. TIP To quickly change the label's direction, press I (for Input label) or O (for Output label) while moving the label.
Type a name in the Label Text field of the Property Editor. NOTE If the Property Editor is not open, double-click the label. Optional: Change the Direction of the label in the Property Editor.
To view errors
The EIKON LogicBuilder application checks for errors as you build your control program and indicates errors with red dots, wires, and boxes. 1 2 Click in the lower right corner or select Control Program > Errors on the menu bar to view the errors. Click an error in the list to highlight its location in the workspace.
17
To add comments
Use the Text tool to add comments to the control program. 1 Select the Text tool.
2 3
Click in the workspace where you want the text to begin. Edit the text and its properties in the Property Editor. See table below. NOTE If the Property Editor is not open, double-click the text.
Notes Type the comment you want to add to the control program. Select a font. Be sure that all system computers have the font installed. Choose a point size from the drop-down list. Select the Bold or Italic checkbox or both. Click the color swatch to select the color of the text. Select this checkbox to remove the background color and pattern. Click the color swatch to select the color of the box behind the text.
NOTE To change the default settings for all text that you will add to the control program, select Options > Palette. Change the settings on the Font tab.
18
NOTE To change the shape of an existing figure, right-click the figure, then select Edit Shape. Click and drag a green point to move it.
19
To arrange figures
1 2 Select 1 or more figures. Right-click 1 of the figures, then select 1 of the following: Bring Forward Bring to Front Send Backward Send to Back
To add an image
Select Edit > Insert Image to add a .gif, .png, .jpg, or .bmp image to your control program.
20
21
Chapter 6
Preparing logic for the WebCTRL interface
Formatting Properties pages
Making a control program automatically creates a WebCTRL Properties page. The initial properties displayed on a Properties page are defined in the EIKON LogicBuilder Property Editor. You can preview Properties pages by running the system without connecting to controllers.
In the control program, you can change the way text appears on the Properties page by using a Text microblock or by editing a microblock's Property Page Text field in the Property Editor. NOTE If you change a control program after downloading it to the controller, you must: 1 2 Reload the control program. See "Working with control programs" in WebCTRL Help. Download the control program. See "Downloading to controllers" in WebCTRL Help.
22
3 4
Use the buttons at the right to move, cut, or paste microblocks. Click OK.
NOTES To find a single microblock in the Edit Order dialog box, do one of the following: Right-click the microblock in the workspace, then select Show in Edit Order. In the Edit Order dialog box, click .
To edit a microblock's Property Page Text from the Edit Order dialog box, do one of the following: Double-click the microblock. Select it and then click .
You must also insert a Text microblock with the Text Type set as Expand End at the end of the section you wish to group together.
23
Notes To align data in a table, insert a Text microblock with the Text Type set as Table Begin. To complete the table, insert a Text microblock with the Text Type set as Table End after the last item you want to include in the table.
NOTE When working with a table within an expanded section, make sure the table begins after the Expand Begin and ends before the Expand End. Conditional Hide Begin Conditional Hide End You can hide part of the Properties page based on a value from a specific microblock. For example, you can specify that the Properties page text from an Analog Input microblock will only appear on the Properties page if the value is above 85. The expression is evaluated relative to the entire control program, not at that particular microblock. Place a Text microblock with the Text Type set as Conditional Hide Begin before the microblock to be evaluated and another set to Conditional Hide End after it. Enter a conditional expression in the Properties Page Text field of the Text microblock. Microblock properties may be referenced between the dollar signs ($), and the expression must be Boolean. For example, to show the microblock Properties page text only when the present value of the point named Zone Temp is greater than 85, the expression would be "$Zone_Temp/present_value$ >85". NOTES When referring to the name of a point, use the RefName rather than the Display Name. Technical Support does not provide assistance with writing and editing Javascript. Please see Javascript textbooks, available in most bookstores, for help with Javascript.
TIP If you are adding the Conditional Hide formatting after the control program has been designed or would prefer to group all of the Text microblocks within the control program, use the Reorder menu to correctly place the Text microblocks.
24
^## if Property Page Text field is empty. If the Property Page Text field shows the default text, delete the text.
MB#1: Enable when Supply Temp is more than $Constant$ (F) ^$ MB#2: Disable when $Hyst$ (F) below Zone Temp. Displays:
25
Time for daily trend report:^\ ___ hh:mm 24 hr Displays: Time for daily trend report: 02:00 hh:mm 24 hr
Bold text
!{text!}
!{NOTE!} Displays:
NOTE Must be enabled for... Make a line of text not wrap in the action pane Display one of the following characters: ^\${}[]|! ^( at the beginning of the text and ^) at the end \x, where x is the character you want to display Do not change \! Displays: Do not change!
Breakdown of an expression
The entire expression is between 2 dollar signs. A microblock property Example: Period
26
A colon Type a colon after the microblock property to add a control. control= A control determines how a property is displayed on the Properties page. Include a control= statement in the expression only if you want to use a control other than the default. Type control=, followed by the control name .
A control Example: "minsec" Type the control between quotation marks. See table below. A space Type a space after a control statement or a parameter statement. A parameter Example: editable= You can add one or more parameters to the expression. To specify a control, type the name of the parameter (see table below), an equal sign, and then a value A parameter value See table below. Example: "true" .
Parameter
Parameter value WidgetImageButton.TOGGLE true or false (Default value is true.) true or false (Default value is true.)
editable truewhendown Check mark appears when the value is false instead of true. button type editable truewhendown Button is selected when the value is false instead of true.
Radio button
WidgetImageButton.RADIO true or false (Default value is true.) true or false (Default value is true.)
27
To display a...
Data must be.. Integer Example: An analog parameter's present value or Enumerated Example: A binary, analog, or multi-state parameter's present value
Control
Parameter index For integer or enumerated values, index is the number of the state the radio button is to represent.
Text
Character string Example: A point's display name Date Example: A wire lock's begin date/end date
charstring
editable
Date
date
editable hasdayofweek Displays the day of the week with the date.
true or false (Default value is true.) true or false (Default value is true.)
Number
number
true or false (Default value is true.) number of digits (Default value is null.) number of digits (Default value is null.) true or false (Default value is false.)
28
To display a...
Data must be.. (has decimal) Example: An analog parameter's present value or Unsigned Example: Any point's expander number
Control
Parameter scalingfactor Multiplies the actual value by the scalingfactor value. Example, to convert watts to kilowatts, use .001 as the scaling factor value.
Parameter value any floating point number except 0 (Default value is 1.)
Droplist
Enumerated Example: A binary, analog, or multi-state parameter's present value Time Example: A wire lock's begin time/end time
droplist
editable
Time
time
editable displaywhat
true or false (Default value is true.) One of the following: ControlTimeInput.HMSD ControlTimeInput.HMS ControlTimeInput.MSD ControlTimeInput.HM ControlTimeInput.SD ControlTimeInput.MS ControlTimeInput.H ControlTimeInput.M ControlTimeInput.S ControlTimeInput.D where H=hour, M=minutes, S=seconds, D=milliseconds (Default value is ControlTimeInput. HMSD.)
29
Data must be.. Unsigned numbers used as a timer Example: A duty cycle's time
Control minsec
Parameter editable scalingfactor Multiplies the actual value by the scalingfactor value. Example: To convert watts to kilowatts, use .001 as the scalingfactor value. showhours showseconds
Parameter value true or false (Default value is true.) any floating point number except 0 (Default value is 1.)
true or false (Default value is false.) true or false (Default value is true.)
3 4
Click
30
NOTES
This name must be identical to the reference name that you give the category when you add it in the WebCTRL interface. Do not use occupancy as the category name. The name can contain lowercase letters, numbers, hyphens, and underscores (no spaces); it cannot begin with a number.
Click OK twice.
The new category will now appear in a microblock's Category droplist. NOTES Do not delete the existing categories on the Sched. Category tabs if your system uses any control programs created in the EIKON for WebCTRL application. See Working with control programs created in the EIKON for WebCTRL application (page 44). To copy all custom category information to another computer, click Export below the category tabs, then save the file. On the other computer, click Import, then select the exported file.
31
Chapter 7
Simulating a control program
In simulation mode, you can specify microblock properties and define an operating environment to see how a control program will operate. To simulate a control program: 1 2 3 4 Select Control Program > Simulate. In the Simulator window, select Options > Setup. Define the simulation conditions. See table below. Do one of the following: 5 6 7 Click to run the simulation continuously until you click to stop it. Set the Time Increment fields (see table below) to define how fast the simulation will run. Click to run the simulation one step at a time.
to run the simulation as fast as possible. Click Click a microblock, then select its Simulation tab to enter values that will help you check the programming. See NOTES below. Verify that the logic performs the desired sequence of operation. Close the simulation window to return to the workspace. Notes Enter the starting Time and Date for the simulation. Select the Communications Ok checkbox to simulate normal communication. Clear this checkbox to simulate lost communication. The Step Every value determines how often the simulation recalculates values in real time. The One Step = value determines how much simulation time passes between each step. For example, to see 30 minutes of simulation in 1 second of real time, use the following settings: Step Every 00:01 (mm:ss) One Step = 30:00 (mm:ss) TIP Set your One Step = shorter than the shortest delay in your control program to avoid stepping over the delay in the simulation.
32
NOTES For simulation only, decimal values smaller than hundredths are rounded to the nearest hundredth. For example .025 is rounded to .03. The Simulator has the same options as the main EIKON LogicBuilder workspace for locating items in the control program. See: To find a microblock or label (page 36) To find identical labels (page 37) To show a logical path (page 37) To show a wire's source microblock (page 37) Hold the cursor over a wire or label to see its value.
33
Chapter 8
EIKON LogicBuilder productivity tools
Use the following features to work efficiently.
To export a symbol
1 2 3 4 5 Select the items in a control program that you want in the symbol. Select Edit > Export Symbol. Type a File Name. The application will automatically add the .logicsymbol file extension. Select the Selected Items Only checkbox. Click Save.
To import a symbol
1 2 3 4 Open the control program you want to paste a symbol into. Select Edit > Import Symbol. Browse to the symbol, then double-click it. Click in the workspace to place the symbol.
NOTE You can drag a .logicsymbol from Windows Explorer to the EIKON LogicBuilder workspace. Select multiple items to drag them simultaneously. Hold down Ctrl as you drag and drop the .logicsymbol into the workspace to have it open as a separate file.
34
To organize favorites
1 2 Select Favorites > Organize. Use the buttons on the right to:
Add new favorite Remove favorite Edit favorite's name or description Move up Move down Open selected favorite in main view for editing
35
NOTES Select File > Export to write the data to a CSV (Comma Separated Values) text file so that you can edit the file in a spreadsheet program. Click File > Import to import the CSV file back into the Microblock Common Properties Editor. CAUTION Do not change any column header name or microblock reference name in the spreadsheet program. To undo changes made in the Editor, close the Editor, then use the Undo feature See Microblock Reference Help for a description of each property. .
36
37
Chapter 9
Defining display options for ZS sensors
To set the order of information displayed on a sensor
If the control program contains multiple microblocks whose values will appear on a ZS sensor screen, you can define the order in which the values will appear. EXAMPLES If you assigned 3 microblocks to the Home screen, you can set the order that they will cycle through when no user is interacting with the sensor. If you assigned 3 microblocks to the Info screen, you can set the order that they will appear in when a user presses the sensor's button.
To set the order: 1 2 Select Reorder > Sensor Display Order. Select the microblock(s) you want to move, then click NOTES
or
Use Ctrl+click, Shift+click, or both to select multiple items. The first microblock in the list must be the first microblock that will appear on the Home screen. To highlight just the microblocks assigned to a particular screen or defined as Maintenance or Alarm, select an option in the Highlight list.
Optional: If you assigned multiple microblocks to the Home screen, the sensor will display the first microblock for 10 seconds by default. To shorten the time, select 3 seconds at the bottom of the window. Click OK.
38
The EIKON LogicBuilder application has pre-defined Rnet tags like those described above, but you can add custom tags if needed. 1 2 3 4 5 Select Options > Preferences. On the Rnet Tags tab, select the tab (Binary, Analog, or Multi-state) for the type of microblock for which you are adding the tag. Click .
Type a descriptive Display Name for of the Rnet tag. Optional: The Rnet Tag Number field is prefilled with the next available tag number for the type of tag you are adding. (Binary tags are in the 1100's, Analog tags are in the 1300's, and Multi-State tags are in the 1500's.) You can change this number if needed. Click OK twice.
The new Rnet tag will appear in a microblock's Rnet Tag droplist. CAUTION If you create a control program with a custom Rnet tag and then open the program in another instance of the EIKON LogicBuilder application that has the same tag number defined for a different value, the EIKON LogicBuilder application will replace its tag name with the tag name from the control program. NOTES To delete a custom Rnet tag, select it, and then click .
To copy all custom Rnet tags to another computer, click Export, then save the file. On the other computer, click Import, then select the exported file.
39
Chapter 10
To omit _# at the end of BACnet object names
BACnet object names are used in Network microblock addresses or by third-party equipment. To prevent duplicate object names in a controller with multiple control programs, SiteBuilder automatically adds an instance number to the end of every object name (Example: lstat_5). The instance number added to every object in a control program is unique to that control program. A controller with only one control program does not have duplicate objects, so it does not need instance numbers. In this case, you can keep SiteBuilder from adding instance numbers by selecting Control Program > Use Unitary Naming. NOTE If you select this option for a control program that will be downloaded into a multi-equipment device, all reference names in all of the device's control programs must be unique.
40
Chapter 11
To select properties for ViewBuilder graphics
The EIKON LogicBuilder application lets you select the microblock property values that you want to appear on a WebCTRL graphic. This allows the graphics creator to see the property values and quickly obtain their paths in ViewBuilder. These microblock property selections are saved when you save the control program. To select properties for graphics: 1 2 Right-click a microblock in the workspace, then choose Select Properties For Graphics. Select the checkbox for any property whose value you want to display on a graphic. NOTE To see all properties, clear the checkbox Show properties typically shown on graphics. 3 Optional: To add a comment for a property such as "Do not include units", select the property and then click , or you can double-click the property.
NOTE Select Control Program > Properties For Graphics to see all the properties that you selected in the control program. In the Comments box, you can type a comment that is not for a specific property. To delete a property, select it and then click .
41
Chapter 12
Miscellaneous EIKON LogicBuilder menu commands and features
Menu command Edit > Third Party BACnet Addresses Notes Use to edit control programs generated by the Third-Party BACnet Utility. See the BACnet Integration Guide (http://accounts.automatedlogic.com) for instructions on using this feature. When making a control program for use in a non-English system, use this command to embed the translation files in the control program, omitting the need to maintain separate files. See Setting up your system for non-English languages in WebCTRL Help. These apply to the EIKON LogicBuilder application, not just the current file. On this tab... General You can... Define the file format that will be the default when you select File > Save As. See To begin a control program (page 14) for more information. Set the metric option as the default for all future control programs. See To begin a control program. (page 14) Guarantee that all control program file names do not contain spaces. Add custom alarm or schedule categories. See To use custom alarm and schedule categories (page 30). Import custom alarm templates, alarm categories, or schedule categories from the ems.ini file used by control programs created in the EIKON for WebCTRL application. See Working with control programs created in the EIKON for WebCTRL application (page 44). Add custom Rnet tags. See To create custom Rnet tags (page 39). Export custom tags from one computer and import them on another.
Alarm/Schedule Categories
Rnet Tags
42
Menu command
Notes Droplist Options Customize the following droplists in certain microblocks: HTML Viewer BACNET Engineering Units (Airflow, AO, AI) Output types (AO) Actuator types (AO) Input types (AI) Sensor types (AI)
Edit the location of your HTML Viewer. To... Convert EIKON for WebCTRL .equipment files to EIKON LogicBuilder .equipment files. See Working with control programs created in the EIKON for WebCTRL application (page 44). Disable the Show Property Page Text field for all microblocks in the current control program. See information about the current control program. For example, the number of microblocks, number of ZN-counted microblocks, etc.
Click Add, then select a file(s) to add the following to the Tools menu. Click this option... Convert EIKON for WebCTRL Equipment
Window Help > Tip of the Day Help > Apply Update Help > About
Select another currently open file to view or edit. Clear the Show tips on startup checkbox if you don't want to see the tips when you start the application. Use this command to install WebCTRL service packs or patches. Technical support may ask you for this version, license, or Java VM information.
Restricted files If you received a .equipment file and a permissions key created by an original equipment manufacturer (OEM), you must install the key on the WebCTRL System Settings > Security tab. appears on When you open the .equipment file in the EIKON LogicBuilder application, the status bar at the bottom of the window. If you click on Restricted, the Permissions dialog box will show you what you are allowed to do with the file.
43
Chapter 13
Working with control programs created in the EIKON for WebCTRL application
Some functionality of a WebCTRL Logic page (for example, jumping to labels) requires that the control program be an EIKON LogicBuilder .equipment file. To quickly upgrade multiple EIKON for WebCTRL .equipment files to EIKON LogicBuilder .equipment files, see "Upgrading EIKON for WebCTRL .equipment files" below. To edit an EIKON for WebCTRL control program in the EIKON LogicBuilder application, you can import the .eiw file or open the .equipment file. See "Editing EIKON for WebCTRL control programs" below. IMPORTANT If you used custom schedule categories, alarm categories, or alarm templates in the EIKON for WebCTRL application, you must import them into the EIKON LogicBuilder application before you upgrade or edit the EIKON for WebCTRL files.
NOTE Before the upgrade takes place, all the control programs in the selected folder are copied to a new backup folder.
NOTE After you edit a .eiw file, consider doing one of the following to prevent using it as the starting point for future control program edits. Move the .eiw file to a folder named Obsolete. Add -obsolete to the .eiw file name.
44
To import custom categories and templates from the EIKON for WebCTRL application
If you used custom schedule categories, alarm categories, or alarm templates in the EIKON for WebCTRL application, you must import those custom items from the ems.ini file. CAUTION Importing deletes any custom categories or templates that you may have defined in the EIKON LogicBuilder application. To import from the ems.ini file: 1 2 3 4 Select Options > Preferences. On the Alarm/Schedule Categories tab, click Import from INI. Open the ems.ini file located in your previous system's Eikon folder. Click OK.
NOTE If needed for v2.0 or earlier alarms, you can add templates on the Alarm Template tab. V2.5 or later alarms use the Universal template.
45
Index
A
alarm categories 30, 44 alarm templates 44 apply update 42
K
keyboard shortcuts 8
L
labels 16, 36, 37 Logic pages 8, 14
B
background color 14 bundled resources 30, 42
M
metric 8, 14 microblock common properties 35 microblock properties 41 microblocks 8, 10, 14, 22, 34 retired 42
C
category alarm 30, 42 schedule 10, 30, 42 control programs 10, 14 Normal 10, 14 simulating 32 UNI 11, 14 ZN 12, 14 controllers 10 custom icon 14 custom microblock 21
N
Normal control program 10, 14
P
properties 15, 22, 41 Properties pages 15, 22, 42 Property Editor 8, 15
D
drawing lines/shapes 19
R
reorder items 22 Rnet tags 39, 42
E
EIKON for WebCTRL 44 error indicator 17 errors 17 expressions 22
S
schedule categories 10, 30, 44 service packs and patches 42 shortcuts, mouse and keyboard 8 simulate a control program 32 symbols 34
F
font 18
G
graphics 41
T
text 23, 25 third-party BACnet addresses 30, 42
H
highlight connections 37
U
UNI control program 11, 14
I
images 20
W
wires 16 workspace options 8
J
joints 14
46
Z
ZN control program 12, 14 ZS sensor 38
47