You are on page 1of 7

Page 1 of 7

CSMM : DRIVE CONTROL WITH MAINTENED ORDER


PRINT

SUMMARY
1 REPRESENTATION 2 FUNCTION 3 ARGUMENTS 4 PROCESSING 4.1 Drive ON/OFF order 4.2 Alarm & Signalling 4.3 cMSig processing (VRE for Centralog) 4.3.1 Validity bit : SIG_V 4.3.2 Off status (cMSig = 1) 4.3.3 On Status (cMSig = 2) 4.3.4 Alarm On Status (cMSig = 4) 4.3.5 Alarm Off Status (cMSig = 5) 4.3.6 Double indication alarm (cMSig = 6) 5 MVM ASSOCIATION

1 REPRESENTATION

Output elaboration ON_DS ON_ORD OFF_DS REM_ATH ALARM ON_TLTE OFF_TLTE SIG SIG_V

NOTA concerning the output SIG (multiple state variables for HMI): -In the CONTRECAD 3.2.x version, SIG is a single output. It is a booleans table (length 8). -In the CONTRECAD 3.3.x version, there are 2 outputs in this purpose, one is a word (SIG) and the other is a boolean validator (SIG_V).

2 FUNCTION

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 2 of 7

This Function Block provides standard logic for the control and signalling of actuators (pumps, ventilation fans ) driven by motors supplied via contactors from low voltage or medium voltage switchboards. One maintained output is used for ON/OFF order (= 1 for ON order , = 0 for OFF order).

3 ARGUMENTS
Name Description Type Neg Range Mand. Connection Def. Value Mand. Data Advised First parameters scan value value

Inputs ON_A ON_M ON_A_ATH ON_M_ATH ON_PS ON_PS_V OFF_A OFF_M OFF_A_ATH OFF_M_ATH OFF_PS OFF_PS_V FLT_IN AV MANU TLTE F_TP Outputs ON_DS ON_ORD OFF_DS REM_ATH ALARM ON_TLTE OFF_TLTE SIG SIG_V On automatic command On manual command On auto command authorization On manual command authorization Feedback On Feedback On validant Off automatic command Off manual command Off auto command authorization Off manual command authorization Feedback Off Feedback Off validant Fault Availability Manual mode selected TLTE value Fault temporization B B B B B B B B B B B B B B B D D N N N N Y Y N N N N Y Y N N Y N N N N N N Y N N N N N Y N Y Y N N N 0 0 1 1 1 0 0 1 1 1 1 10 5 Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y -

On order On command disabled Off command disabled Remote control authorization Alarm (filtered input OFF_PS) On TLTE Off TLTE Multiple state variables For HMI Multiple state validator

B B B B B B B B W B

N N N N N N N N N N

Y N N N N N N N N N

Y Y Y Y Y Y Y Y Y Y

4 PROCESSING 4.1 Drive ON/OFF order

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 3 of 7

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 4 of 7

4.2 Alarm & Signalling

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 5 of 7

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 6 of 7

4.3 cMSig processing (VRE for Centralog) 4.3.1 Validity bit : SIG_V

4.3.2 Off status (cMSig = 1)

4.3.3 On status (cMSig = 2)

4.3.4 Alarm On status (cMSig = 4)

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007

Page 7 of 7

4.3.5 Alarm Off status (cMSig = 5)

4.3.6 Double indication alarm (cMSig = 6)

5 MVM ASSOCIATION
AP - Pump equipment (KKS) - C8035 AP2K - Pump equipment (KKS) - CE2000 PO - Pump variable (ISA) - C8035 PO2K - Pump variable (ISA) - CE2000 ZV - Fan variable (ISA) - C8035 ZV2K - Fan variable (ISA) - CE2000 ZX - Generic variable (ISA) - C8035 ZX2K - Generic variable (ISA) - CE2000

file://\\lifebook-8210\P320share\Ccad\dailog\Hydref\CSMM.html

9/24/2007