Site topography and features Site elevation Site meteorology Annual temperature duration curves Prevailing wind speeds and directions Extreme conditions (hottest day, freezing conditions) Topography and obstructions Nearby hills, valleys, etc. Nearby structures, coal piles, etc. Nearby heat sources, including auxiliary coolers, plant vents, etc. Other heat sources or interferences. Noise limitations at the ACC itself or at some specified distance, as set by neighboring communities or open space sanctuaries Maximum height restrictions Footprint constraints (length, width) Location restrictions, particularly distance from turbine exhaust Seismic loads, requirements, and zones
Plant capacity: Exhaust steam flow: Exhaust steam enthalpy: Exhaust steam back pressure: Ambient temperature a. Minimum : b. Maximum : c. Design ambient temperature : Type of fin : Relative humidity a. Minimum: b. Maximum : c. Average : Plant location : Site elevation or Mean sea level : Wind speed : Seismic zone : Dump steam arrangement, if any : Plant layout : HMBD from steam turbine
Fan motors/Pump motors Supplied with pumps can be split) Cables , Instrumentation & Power Cable MCC Distribution board/Control panel Lightning Protection System
Instrumentation scope
Fan vibration, alarm, and cutout switches remote Gearbox lube oil pressure and level local Steam duct temperature sensors remote Steam duct pressure sensors remote Condensate return temperature sensors Condensate level sensors remote Vacuum pump skid hogging flow rate
Wind speed and direction sensor
ACC Vendors
Potential Vendor
GEA Cooling tower India Shriam cooling Tower Cortell India Paharpur Cooling Tower Thermax SPX GEI Cooling system
For a given ACC, the heat load Q [Btu/hr (W/s)] is related to the ITD by
Q/ITD = Constant Equation - 2 Alternatively, for a given heat load, the size (number of cells, heat transfer surface) is inversely related to the ITD as ACC Size 1/ITD Equation -3 where a low ITD corresponds to a large ACC.
For a given ACC, the heat load Q [Btu/hr (W/s)] is related to the ITD by
Q/ITD = Constant Equation - 2 Alternatively, for a given heat load, the size (number of cells, heat transfer surface) is inversely related to the ITD as ACC Size 1/ITD Equation -3 where a low ITD corresponds to a large ACC.