You are on page 1of 6

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

Bus Loading Summary Report


Directly Connected Load
Constant kVA

Bus
ID

kV

Rated Amp

MW
0

Constant Z

Mvar
0

MW

Bus 1 H_1

1.000

Bus 2

H_2

1.000

21.700

Bus 3

H_3

1.000

94.200

Bus 4

H_4

1.000

Bus 5

H_5

Bus 6

L_6

Bus 7

Z_7

1.000

Bus 8

T_8

1.000

Bus 9

L_9

1.000

29.500

16.600

0.002

Bus 10

L_10

1.000

9.000

5.800

Bus 11

L_11

1.000

3.500

1.800

Bus 12

L_12

1.000

6.100

1.600

Bus 13

L_13

1.000

13.500

Bus 14

L_14

1.000

14.900

Total Bus Load

Constant I

Mvar

MW

Generic

Mvar

MW

Mvar

MVA

% PF

Amp

233.298

99.6

127070.3

12.700

197.799

97.4

109281.6

19.000

97.477

96.6

55721.3

47.800

-3.900

117.138

98.7

66454.1

1.000

7.600

1.600

114.531

99.0

64857.3

1.000

11.200

7.500

48.748

90.5

26303.4

32.907

85.3

17898.0

17.635

0.0

9341.1

51.320

86.0

28060.7

10.707

84.1

5881.9

8.075

90.4

4411.1

8.066

95.6

4413.4

5.800

20.581

93.0

11312.6

5.000

15.717

94.8

8762.7

-21.184

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).

Percent
Loading

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

Branch Loading Summary Report

Transformer
CKT / Branch
ID

Cable & Reactor


Type

Ampacity
(Amp)

Loading
Amp

Capability
(MVA)

Loading (input)
MVA

Loading (output)

MVA

4_7

Transformer

100.000

30.293

30.3

29.696

29.7

4_9

Transformer

100.000

16.174

16.2

16.087

16.1

5_6

Transformer

100.000

45.819

45.8

44.817

44.8

* Indicates a branch with operating load exceeding the branch capability.

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

Branch Losses Summary Report

CKT / Branch
ID

From-To Bus Flow

Losses

To-From Bus Flow

% Bus Voltage

Vd
% Drop
in Vmag

MW

Mvar

MW

Mvar

kW

kvar

From

To

1_2

156.888

-20.405

-152.590

27.678

4297.9

7272.8

106.0

104.5

1.50

1_5

75.516

3.844

-72.753

2.241

2763.2

6085.6

106.0

102.0

4.05

2_3

73.237

3.560

-70.914

1.602

2323.3

5162.4

104.5

101.0

3.50

2_4

56.133

-1.562

-54.456

3.033

1676.8

1470.6

104.5

101.8

2.73

2_5

41.519

1.157

-40.615

-2.085

903.8

-927.9

104.5

102.0

2.55

3_4

-23.286

4.461

23.659

-4.824

373.4

-362.7

101.0

101.8

0.77

4_5

-61.155

15.816

61.670

-14.194

514.3

1622.3

101.8

102.0

0.18

4_7

28.071

-9.689

-28.070

11.392

1.7

1703.1

101.8

106.2

4.38

4_9

16.081

-0.435

-16.080

1.740

1.3

1304.9

101.8

105.6

3.82

5_6

44.099

12.437

-44.094

-8.016

4.4

4421.3

102.0

107.0

5.05

6_11

7.357

3.564

-7.302

-3.448

55.4

116.1

107.0

105.7

1.31

6_12

7.787

2.504

-7.715

-2.354

71.8

149.5

107.0

105.5

1.48

6_13

17.750

7.218

-17.538

-6.801

212.1

417.8

107.0

105.0

1.96

7_8

0.000

-17.174

0.000

17.635

461.1

106.2

109.0

2.85

7_9

28.070

5.782

-28.070

-4.980

801.9

106.2

105.6

0.56

9_10

5.224

4.216

-5.211

-4.182

12.9

34.1

105.6

105.1

0.49

9_14

9.424

3.608

-9.308

-3.361

116.1

246.9

105.6

103.6

2.04

10_11

-3.789

-1.618

3.802

1.648

12.6

29.5

105.1

105.7

0.59

12_13

1.615

0.754

-1.609

-0.749

6.3

5.7

105.5

105.0

0.48

13_14

5.647

1.749

-5.592

-1.639

54.1

110.2

105.0

103.6

1.49

13401.5

30125.3

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

Alert Summary Report


% Alert Settings
Marginal

Critical
Loading
Bus

100.0

95.0

Cable

100.0

95.0

Reactor

100.0

95.0

Line

100.0

95.0

Transformer

100.0

95.0

Panel

100.0

95.0

Protective Device

100.0

95.0

Generator

100.0

95.0

OverVoltage

105.0

102.0

UnderVoltage

95.0

98.0

OverExcited (Q Max.)

100.0

95.0

UnderExcited (Q Min.)

100.0

Bus Voltage

Generator Excitation

Critical Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

Bus 1 H_1

Bus

Over Voltage

1.000

kV

1.060

106.0

3-Phase

Bus 10 L_10

Bus

Over Voltage

1.000

kV

1.051

105.1

3-Phase

Bus 11 L_11

Bus

Over Voltage

1.000

kV

1.057

105.7

3-Phase

Bus 12 L_12

Bus

Over Voltage

1.000

kV

1.055

105.5

3-Phase

Bus 13 L_13

Bus

Over Voltage

1.000

kV

1.050

105.0

3-Phase

Bus 6

L_6

Bus

Over Voltage

1.000

kV

1.070

107.0

3-Phase

Bus 7

Z_7

Bus

Over Voltage

1.000

kV

1.062

106.2

3-Phase

Bus 8

T_8

Bus

Over Voltage

1.000

kV

1.090

109.0

3-Phase

Bus 9

L_9

Bus

Over Voltage

1.000

kV

1.056

105.6

3-Phase

Gen_1

Generator

Under Excited

0.000

Mvar

-16.561

0.0

3-Phase

Gen_1

Generator

Overload

232.400

MW

232.404

100.0

3-Phase

Gen_2

Generator

Overload

40.000

MW

40.000

100.0

3-Phase

Gen_3

Generator

Under Power

0.000

MW

0.000

0.0

3-Phase

Gen_6

Generator

Under Power

0.000

MW

0.000

0.0

3-Phase

Gen_8

Generator

Under Power

0.000

MW

0.000

0.0

3-Phase

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

Marginal Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

Bus 14 L_14

Bus

Over Voltage

1.000

kV

1.036

103.6

3-Phase

Bus 2

Bus

Over Voltage

1.000

kV

1.045

104.5

3-Phase

H_2

Project:

ETAP

IEEE 14 BUS

7.5.0

Location:

Page:

Date:

10-01-2013

Contract:

SN:

12345678

Engineer:

Revision:

Base

Config.:

Normal

Filename:

Study Case: LF
IEEE14BUS

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW

Mvar

MVA

% PF

232.404

-16.561

232.993

99.75 Leading

40.000

99.003

106.778

37.46 Lagging

Total Demand:

272.404

82.441

284.605

95.71 Lagging

Total Motor Load:

259.000

73.500

269.227

96.20 Lagging

Total Static Load:

0.002

-21.184

21.184

0.01 Leading

Total Constant I Load:

0.000

0.000

0.000

Total Generic Load:

0.000

0.000

0.000

Apparent Losses:

13.401

30.125

System Mismatch:

0.000

0.000

Source (Swing Buses):


Source (Non-Swing Buses):

Number of Iterations: 2