Design of two-way slab

Panel No = S1
Input data: ACI Moment Coefficients
Case No = 2
la = 16 ft m = 0.75
lb = 21 ft Ca
neg
= 0.069
f'c = 2.5 ksi Cb
neg
= 0.022
fy = 40 ksi Ca
dl
= 0.028
DL add = 0.057 k/ft
2
Cb
dl
= 0.009
LL = 0.06 k/ft
2
Ca
ll
= 0.045
h, cal = 4.93 in Cb
ll
= 0.014
h, used = 6 Wa = 0.760
Wb = 0.240
Loads Calculation: Moments Calculation:
DL wu = 0.185 k/ft
2
Ma(-ve) = 60.83 k-in
LL wu = 0.102 k/ft
2
Mb(-ve) = 33.41 k-in
TL wu = 0.287 k/ft
2
Ma(+ve) = 30.01 k-in
Mb(+ve) = 16.37 k-in
Steel Calculation:
d
a
= 5 in Moments As
req
#4(in c/c)#3(in c/c)
d
b
= 4.75 in Ma(-ve) 0.358 6.7 3.7
b
1
= 0.85 Mb(-ve) 0.202 11.9 6.5
As
max
= 1.322 in
2
Ma(+ve) 0.171 12 7.7
As
min
= 0.144 in
2
Mb(+ve) 0.144 12 9.2
S
max
= 12
Load Transfer:
Load Transfer To Longer Beam = 1.745 k/ft
Load Transfer To Shorter Beam = 0.723 k/ft