You are on page 1of 6

Transformer Differential

RET 316

A
AI 1,2,3

DIFF

A
AI 7,8,9

Transformer Differential
for 3-windings

RET 316
AI 4,5,6

DIFF

AI 1,2,3

A
D
AI 7,8,9

Fault outside protected zone Low


short circuit current Load
I < (1.5...3) * Irated

I1

I2

I
4

cos = 1

IH I1 I2 cos
IH = I1 = I2 =
ILoad < (1.5...3)*Irated

3
2

v=50%

1
g
1

IH

Fault outside protected zone


High short circuit current
Isc I > (1.5....3) * I
rated

I1

I2

v= infinite

4
cos = 1

IH I1 I2 cos
IH = I1 = I2

3
2
1

v=50%

g
1

IH

Fault inside protected zone

I1

I2

I
4
3

cos < 0
IH = 0

2
1
g
1

IH

Calcul des facteurs dadaptation en amplitude en


rgime nominal:
Ip = 40MVA/(60KV*1,732) =384,91A
Is = 40MVA/(10KV*1,732) =2309,47A
a1 = TCp/ Ip = 600/ 384,91 = 1,56
a2 = TCs/ Is = 3000/ 230947 = 1,29