505E Digital Governor Manual 85018V1

206 Woodward

Appendix.
505E Program Mode Worksheet
Governor Serial Number ______________________
Application ________________________________ Date ___________
TURBINE START
Manual Start YES _____ NO ____
Automatic Start YES _____ NO _____
Semiautomatic Start YES _____ NO _____
Rate to Min (RPM/Sec) 3.00 RPM/SEC
Valve Lmtr Rate (%/Sec) 1% %/SEC
Use Idle/Rated?
YES _____ NO _____
Idle Setpt (RPM) 1000 RPM
Rated Setpt (5650RPM) RPM
Idle/Rtd Rate (RPM/SEC) 3 RPM/SEC
Use Auto Start Sequence YES _____ NO _____
Cold Start = ( > xx Hrs ) HRS
Hot Start = ( < xx Hrs) HRS
Low Idle Setpt (RPM) RPM
Low Idle Delay (Cold) MIN
Low Idle Delay (Hot) MIN
Rate to Hi Idle (Cold) RPM/SEC
Rate to Hi Idle (Hot) RPM/SEC
High Idle Setpt (RPM) RPM
High Idle Delay (Cold) MIN
High Idle Delay (Hot) MIN
Rate to Rated (Cold) RPM/SEC
Rate to Rated (Hot) RPM/SEC
Rated Setpt (RPM) RPM
Auto Halt at Idle Setpts YES ____NO ____
Ext Trips in Trip Relay? YES ____NO ____
Reset Clears Trip Output YES ____NO ____
SPEED CONTROL
Teeth Seen by MPU 20
Gear Ratio 1 :
Failed Speed Level(RPM) RPM
Use Speed Input #2? YES ____NO _____
Failed Speed Level(RPM) RPM
Off-Line Prop Gain %
Off-Line Int Gain rps
Off-Line Deriv Ratio %
On-Line Prop Gain %
On-Line Int Gain rps
On-Line Deriv Ratio %
SPEED SETPOINT VALUES
Overspeed Test Lmt (RPM) RPM
Overspeed Trip (RPM) RPM
Max Governor Speed (RPM) RPM
Min Governor Speed (RPM) RPM
Setpt Slow Rate(RPM/SEC) RPM/SEC
Use Remote Speed Setpt ? YES ____NO _____
Rmt Spd Setpt Max Rate RPM/SEC
Use Critical Speeds? YES _____ NO _____
Critical Speed Rate RPM/SEC
ritical Speed 1 Max RPM
Critical Speed 1 Min RPM
Use Critical Band 2 ? YES _____NO _____

Critical Speed 2 Max RPM


Critical Speed 2 Min RPM
OPERATING PARAMETERS
Generator Application? YES _____NO _____
Use Gen Brkr Open Trip ? YES _____NO _____
Use Tie Brkr Open Trip ? YES _____NO _____
Use KW Droop? YES _____NO _____
KW Max Load KW
Droop (%) %
Rated Spd Setpt RPM
Use Freq Arm/Disarm ? YES _____ NO _____
Use Local/Remote YES _____ NO _____
EXTR / ADM CONTROL
Lost E/A Input = Trip ? YES _____NO _____
Lost E/A Input = Max LP? YES _____NO _____
Lost E/A Input = Min LP? YES _____NO _____
Invert Extr/Adm Input? YES _____ NO _____
Min Extr/Adm Setpt Units
Max Extr/Adm Setpt Units
Setpt Rate (units/sec) Units
Setpt Initial Value Units
Extr/Adm Droop %
PID Proportional Gain %
PID Integral Gain rps
PID Derivative Ratio %
iebrkr Open E/A Disable YES _____NO _____
Genbrkr Open E/A Disable YES ____NO _____
E/A Speed Enable Setting RPM
Use Remote Setting? YES _____ NO _____
Remote Setpt Max Rate Units
Ext/Adm Units Of Measure

Manual 85018V1 505E Digital Governor


Woodward 207
TURB PERFORMANCE VALUES
Use Decoupling ? YES _____ NO _____
Decouple Inlet (HP) ? YES _____ NO _____
Decouple Exhaust(LP) ? YES _____ NO _____
Decouple HP & LP ? YES _____ NO _____
Max Power Units
Max HP Flow Units
Extraction Only ? YES _____ NO _____
Admission Only ? YES _____ NO _____
Extraction & Admission? YES _____ NO _____
EXTRACTION STEAM MAP DATA
Use Automatic Enable? YES _____NO _____
Max Power @ Min Extr Units
Max HP Flow @ Min Extr Units
Min Power @ Max Extr Units
Min HP Flow @ Max Extr Units
Min Power @ Min Extr Units
Min HP Flow @ Min Extr Units
ADMISSION STEAM MAP DATA
Max Power @ Max Adm Units
Max HP Flow @ Max Adm Units
Max Admission Flow Units
Min Power @ Min Adm Units
Min HP Flow @ Min Adm Units
Max Power @ Min Adm Units
Max HP Flow @ Min Adm Units
EXTR AND ADMISSION STEAM MAP
Max Power @ 0 Extr/Adm Units

Max HP Flow @ 0 Extr/Adm Units


Max Admission Flow Units
Min Power @ Max Extr Units
Min HP Flow @ Max Extr Units
Min Pwr @ 0 Extr/Adm Units
Min HP Flow @ 0 Extr/Adm Units
DECOUPLED HP & LP DATA
Extraction Only ? YES _____ NO _____
Use Automatic Enable? YES _____ NO _____
Admission Only ? YES _____ NO _____
Extraction & Admission? YES _____ NO _____
SHARED DATA
Extr/Adm Demand Rate %/SEC
Use Setpoint Tracking ? YES _____NO _____
Min HP Lift (%) %
Min LP Lift (%) %
LP Valve Limiter Rate %/SEC
Speed Control Priority? YES _____NO _____
LP Max Lmt E/A Priority? YES ____NO _____
Auto Switch E/A Priority YES _____NO _____
DRIVER CONFIGURATION
Act #1 (HP) is 4-20mA? YES _____NO _____
Invert Driver Output ? YES _____NO _____
Use Act 1 Flt Shutdown YES _____NO _____
Act 1 (HP) Dither mA
Act 1 Cal Min mA
Act 1 Cal Max mA
Act #2 (LP) is 4-20mA? YES _____NO _____
Invert Driver Output ? YES _____NO _____
Use Act 2 Flt Shutdown YES _____NO _____
Act 2 (LP) Dither mA
Act 2 Cal Min mA
Act 2 Cal Max mA
ANALOG INPUTS
nalog Input # 1 Function Extr/Admission
Input 1 4mA Value Units
Input 1 20mA Value ____ Units
nalog Input # 2 Function
Input 2 4mA Value Units
Input 2 20mA Value Units
Analog Input # 3 Function
Input 3 4mA Value Units
Input 3 20mA Value Units
Analog Input # 4 Function
Input 4 4mA Value Units
Input 4 20mA Value Units
Analog Input # 5 Function
Input 5 4mA Value Units
Input 5 20mA Value Units
Analog Input # 6 Function
Input 6 4mA Value Units
Input 6 20mA Value Units
CONTACT INPUTS
Contact Input 1 Function
Contact Input 2 Function
Contact Input 3 Function
Contact Input 4 Function
Contact Input 5 Function
Contact Input 6 Function
Contact Input 7 Function
Contact Input 8 Function

Contact Input 9 Function


Contact Input 10 Fctn
ontact Input 11 Fctn
Contact Input 12 Fctn
FUNCTION KEYS
F3 Key Performs
Blink when not Active? YES _____NO _____
F4 Key Performs
Blink when not Active? YES _____NO _____

505E Digital Governor Manual 85018V1


AUXILIARY CONTROL
Use Auxiliary Control ? YES _____ NO _____
Lost Aux Input Shutdown? YES_ ____ NO _____
Use KW Input ? YES _____ NO _____
Invert Aux ? YES _____ NO _____
Min Aux Setpt Units
Max Aux Setpt Units
Aux Setpt Rate units/sec Units / SEC
Use Aux Enable? YES _____ NO _____
Setpt Initial Value Units
Aux Droop %
Aux PID Prop Gain %
Aux PID Integral Gain rps
Aux Derivative Ratio %
Tiebrkr Open Aux Disable YES ____NO _____
Genbrkr Open Aux Disable YES ____NO _____
Use Remote Aux Setting YES _____ NO ____
Remote Aux Max Rate Units / SEC
Aux Units of Measure
CASCADE CONTROL
Use Cascade Control? YES _____NO _____
Invert Cascade ? YES _____NO _____
Min Cascade Setpt Units
Max Cascade Setpt Units
Casc Setpt Rate (/sec) Units/SEC
Use Setpoint Tracking ? YES _____NO _____
Setpt Initial Value Units
Speed Setpt Lower Limit RPM
Speed Setpt Upper Limit RPM
Max Speed Rate(RPM/sec) RPM/Sec
Cascade Droop %
Casc PID Prop Gain %
Casc PID Integral Gain rps
Casc Derivative Ratio %
Use Remote Casc Setting YES _____NO _____
Remote Casc Max Rate Units/SEC
Casc Units of Measure
READOUTS
Analog Readout 1 Is
Readout 1 4mA Value Units
Readout 1 20mA Value Units
Analog Readout 2 Is
Readout 2 4mA Value Units
eadout 2 20mA Value Units
Analog Readout 3 Is
Readout 3 4mA Value Units
Readout 3 20mA Value Units
Analog Readout 4 Is
Readout 4 4mA Value Units
Readout 4 20mA Value Units
Analog Readout 5 Is

Readout 5 4mA Value Units


Readout 5 20mA Value Units
Analog Readout 6 Is
Readout 6 4mA Value Units
Readout 6 20mA Value Units
RELAYS
Use Relay #1? YES ____NO _____
Relay # 1 is Level Switch? YES ____NO _____
Relay 1 Is Level Sw For
Relay 1 ON Level Units
Relay 1 OFF Level Units
Relay 1 Energizes On
Use Relay # 2? YES _____NO _____
Relay # 2 is Level Switch? YES ____NO _____
Relay 2 Is Level Sw For
Relay 2 On Level Units
Relay 2 Off Level Units
Relay 2 Energizes On
Use Relay # 3? YES _____NO _____
Relay # 3 is Level Switch? YES ____NO _____
Rly 3 Is Level Sw For
Relay 3 On Level Units
Relay 3 Off Level Units
Relay 3 Energizes On
Use Relay # 4? YES _____NO _____
Relay # 4 is Level Switch? YES ____NO _____
Rly 4 Is Level Sw For
Relay 4 On Level Units
Relay 4 Off Level Units
Relay 4 Energizes On
Use Relay # 5? YES _____NO _____
Relay # 5 is Level Switch? YES ____NO _____
Rly 5 Is Level Sw For
Relay 5 On Level Units
Relay 5 Off Level Units
Relay 5 Energizes On
Use Relay # 6? YES _____NO _____
Relay # 6 is Level Switch? YES ____NO _____
Rly 6 Is Level Sw For
Relay 6 On Level Units
Relay 6 Off Level Units
Relay 6 Energizes On
COMMUNICATIONS
Use Communications ? YES _____ NO _____
Use Modbus Port 1? YES _____ NO _____
Mode Ascii=1 Rtu=2
ModBus Device #
Port#1 Driver
Port#1 Baud Rate
Port#1 Stop Bits
Port#1 Parity
Use Modbus Port 2? YES _____NO _____
Mode: Ascii=1 Rtu=2
ModBus Device#
Port#2 Driver
Port#2 Baud Rate
Port#2 Stop Bits
Port#2 Parity