You are on page 1of 2

A

Saving in Water cooled condenser in comparision to air cooled condenser


Condensor Vacuum
Conditions

Units
Design

ata

kg/cm2

0.10

0.88

Actual Vacuum with WCC - Basis


Ambient Temp. >= 42 Deg C
Ambient Temp. 35 - 41 Deg C
Ambient Temp. 27 - 34 Deg C

0.12
0.23
0.19
0.13

0.86
0.75
0.79
0.84

Difference
Running
in Vaccum
with Actual Hours / year
kg/cm2
hrs/year

0.11
0.07
0.02

Conditions

Saving in petcoke

Rs (in Lacs)/ year

Kcal / kwh

MKcal / year

12 Kcal / kwh /
0.01 vacuum
130.8
80.4
19.2

19 MW
generation
795.3
10143.3
13716.5
24655

Rs 5660 / Ton @
8000 kcal /kg
0.6
7.2
9.7
17.4

4456
Saving in water cooled condenser in compare to air cooled condenser due to high power Generation
Generation

Total extra heat

consumed

Total

Condensor Vacuum

32
664
3760

Excess heat

Running

Less power

Total generation

Loss due to less

Hours / year

generation

loss per year

power generation

ata
kg/cm2
MW
hrs/year
Rs (in Lacs)/ year
Units
kwh
Mwh
Design
0.10
0.88
19.0
Actual Vacuum with WCC - Basis
0.12
0.86
19.0
Rs 6 /kwh
Ambient Temp. >= 42 Deg C
0.23
0.75
17.5
32
1520
0.486
2.9
Ambient Temp. 35 - 41 Deg C
0.19
0.79
18.3
664
690
4.582
27.5
Ambient Temp. 27 - 34 Deg C
0.13
0.84
18.7
3760
270
10.152
60.9
Total
91.3
4456
15.22
Loss in water cooled condenser in comparision to air cooled condenser due to higher aux power,water cost,chemical and O & M cost of
water treatment
Running

Aux power cost

Water cost

Rs

Rs

100 Kwh @ Rs 6 /

3.25 kl /
kwh @ Rs
25 / kl
68.78

Hours /
Conditions
Units

Total

year
hrs/year

Basis

kwh
4456

26.7

A+B-C
Overall loss of running Water cooled condensor

12.8

Chemical
and WTP
Maint.
Charged
Rs

Total Cost

Rs / Year

Rs. 14000 / day

26.0

121.5

Lacs

Assumption / Basis:
1. Below ambient temperature 27 Deg C the condenser vacuum will be same for water cooled condenser and air cooled condenser.
2. In a Year about 4456 Hrs ambient temperature is above than 27 Deg C.
3. Water cost of WCC is about Rs 3.25 / kwh @ Rs 25 / kl
4. Auxiliary power consumption of WCC is 100 kwh, in earlier assumption of 187 Kwh consider
5. Chemical and Water treatment plant maint. Cost is about Rs 14000 / day

6. Power generations at different vacuum are as per TDPS.