You are on page 1of 238

08 /03/2015

SER

1
1.1
1. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

POWER TRANSFORMERS

33KV & 34.5 KV PRIMARY


Applicable Standards:

POWER TRANSFORMERS UP TO 30 MVA


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

53-TMSS-01

Based on TS&SD letter# 09-F01546/03-03032301 dated


19th. Aug 2009, it is pre-qualified for Power Transformer
up to 132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including


short circuit test) as per SEC specifications/standards shall
be carried out on the first unit to be supplied to SEC in
securing an order in the presence of three (3) SEC
engineers & one (1) approved independent inspection
agency Inspector.

Seven (7) years warranty from the date of PAC of


the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ABB TRANSIT OY

FINLAND

Yes

AREVA

GERMANY

Yes

BEST

TURKEY-Balikesir (ASB Factory)

Yes

Based on TS&SD Letter # 06-789-03032300 dated July 25,


2006, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # EAI-2301061500 dated January 23, 2006.

Page 1 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Electric Systems Zrt. (previously GANZ
Transelektro Electric Co., Ltd.)

FACTORY LOCATION
HUNGARY-Budapest

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter 11-01981-1-03032301 dated July
11, 2011, it is pre-qualified for Power Transformers rated
up to 132kV/100MVA as conforming to SEC Specification
# 53-TMSS-01, Rev.0, with the following conditions:
All Type, Special & Routine tests as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the next unit to be supplied to SEC in an accredited
Testing Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # 10513/10/CG dated
July 04, 2011 and letter# 20338/12/CG dated August 04,
2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated June 15, 2010.
Pre-Qualification & Participation for current & future
SEC's Projects subjected to the fulfillment of confirmation
letter # 20342/12/CG dated August 14, 2012 by
manufacturer.

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

FUJI Electric Co.

JAPAN--

Yes

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 2 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GETRA Power S.P.A

FACTORY LOCATION
ITALY-Marcianise (CE)

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-04523-01-03504401 dated 7th
July 2014, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid, SA in an Approved
Independent Testing Laboratory and/or in the
manufacturers Testing Laboratory in the presence of three
(03) National Grid SA Engineers & one (01) Approved
Independent Inspection Agency (IIA) Inspector. All the
costs of which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer through their
letter # GPJLT/SECNG/SSD/009, dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # GPJLT/SECNG/SSD/0010 dated 8th June
2014

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 3 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ILJIN Electric Co. Ltd.

FACTORY LOCATION
SOUTH KOREA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03077-30504401 dated
September 15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is
pre-qualified for Power Transformers 33kV & 34.5kV rated
up to 30MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following conditions:
All Type, Routine and Special testes as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the First unit to be supplied to SEC of Power
Transformers 33kV and/or 34.5kV rated up to 30MVA in
The Manufacturer's Testing Laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer ILJIN ELECTRIC
Co. Ltd. through their letter # IJ-20120725-01 dated July
25, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by the manufacturer ILJIN ELECTRIC
Co. Ltd. through their letter # IJ-20120628-01 dated June
28, 2012.

JEUMONT SCHNEIDER

FRANCE

Yes

Koncar D&ST Inc.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-03217-1-30504401 dated May


18, 2014, it is pre-qualified for Power Transformer up to
67MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be
supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing
Laboratory in presence of three (03) National Grid SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated May
04, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated May 04, 2014.

Page 4 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar Power Transformers Ltd.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014,
it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the Approved
Independent Testing Laboratory or in the manufacturers
Testing Laboratory in presence of three (03) National Grid
SA Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated
01-04-2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # 2014/02, dated 01-04-2014.

Liaoning - Efacec Electrical Equipment Co., Ltd


(LEEEC)

CHINA-Liaoning Province

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.
The old remark before suspension was:
Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to
30 MVA as conforming to SEC Specification# 53-TMSS-01
with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by Liaoning - Efacec
Electrical Equipment Co., Ltd (LEEEC) through their letter
# Nil dated April 18, 2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 5 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated
December 31, 2013, it is pre-qualified for Power
Transformers rated up to 100 MVA, 132 kV as conforming
to National Grid SA specification # 53-TMSS-01, Rev.01,
with the following conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements
together (with Thermal & Dynamic short-circuit calculations
per IEC 60076-5) shall be carried out on the next unit to
be supplied to SEC/ National Grid SA in an Accredited
Testing Laboratory in the presence of three (3) National
Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter 1/115-2261 dated August 15, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # 1/115-2266 dated August 15, 2011.

SC ELECTROPUTERE SA

Romania-Craiova

Yes

Based on TS&SD letter # 11-002054-1-03032300


dated10/7/2011, it is prequalified for Power Transformer
up to 132kV, 100MVA, as conforming to National Grid SA
specification # 53-TMSS-01, Rev.0 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order.
This was confirmed by SC Electroputere SA through letter
27500 dated 14/06/2010.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

Previously "AREVA-Turkey", the name has been changed to


Schneider Electric-Turkey based on Schneider Electric letter
# MKT-18.01.11 dated 18/01/2010 and AREVA T&D letter
# BF/BL 25.11.2010.

Page 6 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Enerji Endustrisi San VE TIC A.S

FACTORY LOCATION
TURKEY-Cayirova-Kocaeli

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-02364-1-30504401 dated April
01, 2014, it is pre-qualified for Power Transformers up to
67 MVA, 132 kV conforming to National Grid SA
specification 53-TMSS-01, Rev. 01, with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the manufacturer
Testing Laboratory in the presence of three (03) National
Grid SA Engineers & one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter # MKT_132KV Trafo_005, dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova,
Istanbul, Turkey has confirmed that improvement needs
implementation will be complied during the FAT for the first
transformer order confirmed through letter # MKT_132KV
Trafo_010 dated February 12, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # MKT_132KV Trafo_007-1 dated March 19,
2014.

SCHORCH

GERMANY

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Total =

1.2
1. 2. 1

31

69 KV PRIMARY
Applicable Standards:

POWER TRANSFORMERS UP TO 67 MVA


ABB

SWITZERLAND

Yes

ABB

SWEDEN

Yes

53-TMSS-01

Page 7 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

REMARKS

Based on TS&SD letter# 09-F01546/03-03032301 dated


19th. Aug 2009, it is pre-qualified for Power Transformer
up to 132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including


short circuit test) as per SEC specifications/standards shall
be carried out on the first unit to be supplied to SEC in
securing an order in the presence of three (3) SEC
engineers & one (1) approved independent inspection
agency Inspector.

Seven (7) years warranty from the date of PAC of


the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

ABB TRANSIT OY

FINLAND

Yes

AREVA

GERMANY

Yes

BEST

TURKEY-Balikesir (ASB Factory)

Yes

Pre-Qualification & Participation for current & future SEC's


Projects subjected to the mutual agreement between SEC
& ABB dated 09 March 2009

Based on TS&SD Letter # 06-789-03032300 dated July 25,


2006, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # EAI-2301061500 dated January 23, 2006.

Page 8 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Electric Systems Zrt. (previously GANZ
Transelektro Electric Co., Ltd.)

FACTORY LOCATION
HUNGARY-Budapest

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter 11-01981-1-03032301 dated July
11, 2011, it is pre-qualified for Power Transformers rated
up to 132kV/100MVA as conforming to SEC Specification
# 53-TMSS-01, Rev.0, with the following conditions:
All Type, Special & Routine tests as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the next unit to be supplied to SEC in an accredited
Testing Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # 10513/10/CG dated
July 04, 2011 and letter# 20338/12/CG dated August 04,
2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated June 15, 2010.
Pre-Qualification & Participation for current & future
SEC's Projects subjected to the fulfillment of confirmation
letter # 20342/12/CG dated August 14, 2012 by
manufacturer.

CG POWER SYSTEMS

BELGIUM

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

EFACEC

PORTUGAL

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 9 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GETRA Power S.P.A

FACTORY LOCATION
ITALY-Marcianise (CE)

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-04523-01-03504401 dated 7th
July 2014, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in an Approved
Independent Testing Laboratory and/or in the
manufacturers Testing Laboratory in the presence of three
(03) National Grid, SA Engineers & one (01) Approved
Independent Inspection Agency (IIA) Inspector. All the
costs of which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer through their
letter # GPJLT/SECNG/SSD/009, dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # GPJLT/SECNG/SSD/0010 dated 8th June
2014.

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 10 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ILJIN Electric Co. Ltd.

FACTORY LOCATION
SOUTH KOREA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03077-30504401 dated
September 15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is
pre-qualified for Power Transformers 69kV rated up to 67
MVA as conforming to SEC Specification # 53-TMSS-01,
Rev.0, with the following conditions:
All Type, Routine and Special testes as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the First unit to be supplied to SEC of Power
Transformers 69kV rated up to 67MVA in The
Manufacturer's Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer ILJIN ELECTRIC Co. Ltd.
through their letter # IJ-20120725-01 dated July 25, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by the manufacturer ILJIN ELECTRIC
Co. Ltd. through their letter # IJ-20120628-01 dated June
28, 2012.

JEUMONT SCHNEIDER

FRANCE

Yes

Koncar D&ST Inc.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-03217-1-30504401 dated May


18, 2014, it is pre-qualified for Power Transformer up to
67MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be
supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing
Laboratory in presence of three (03) National Grid SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated May
04, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated May 04, 2014.

Page 11 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar Power Transformers Ltd.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-08041-01-03504401 dated
13/02/2014 & 14-08041-02-03504401 dated 25/03/2014,
it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the Approved
Independent Testing Laboratory or in the manufacturers
Testing Laboratory in presence of three (03) National Grid
SA Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated
01-04-2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # 2014/02, dated 01-04-2014.

Liaoning - Efacec Electrical Equipment Co., Ltd


(LEEEC)

CHINA-Liaoning Province

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.
The old remark before suspension was:
Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to
67 MVA as conforming to SEC Specification# 53-TMSS-01
with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by Liaoning - Efacec
Electrical Equipment Co., Ltd (LEEEC) through their letter
# Nil dated April 18, 2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 12 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated
December 31, 2013, it is pre-qualified for Power
Transformers rated up to100 MVA, 132 kV as conforming
to National Grid SA specification # 53-TMSS-01, Rev.01,
with the following conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements
together (with Thermal & Dynamic short-circuit calculations
per IEC 60076-5) shall be carried out on the next unit to
be supplied to SEC/ National Grid SA in an Accredited
Testing Laboratory in the presence of three (3) National
Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter 1/115-2261 dated August 15, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # 1/115-2266 dated August 15, 2011.

SC ELECTROPUTERE SA

Romania-Craiova

Yes

Based on TS&SD letter # 11-002054-1-03032300


dated10/7/2011, it is prequalified for Power Transformer
up to 132kV, 100MVA, as conforming to National Grid SA
specification # 53-TMSS-01, Rev.0 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order.
This was confirmed by SC Electroputere SA through letter
27500 dated 14/06/2010.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

Previously "AREVA-Turkey", the name has been changed to


Schneider Electric-Turkey based on Schneider Electric letter
# MKT-18.01.11 dated 18/01/2010 and AREVA T&D letter
# BF/BL 25.11.2010.

Page 13 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Enerji Endustrisi San VE TIC A.S

FACTORY LOCATION
TURKEY-Cayirova-Kocaeli

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-02364-1-30504401 dated April
01, 2014, it is pre-qualified for Power Transformers up to
67 MVA, 132 kV conforming to National Grid SA
specification 53-TMSS-01, Rev. 01, with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the manufacturer
Testing Laboratory in the presence of three (03) National
Grid SA Engineers & one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter # MKT_132KV Trafo_005, dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova,
Istanbul, Turkey has confirmed that improvement needs
implementation will be complied during the FAT for the first
transformer order confirmed through letter # MKT_132KV
Trafo_010 dated February 12, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # MKT_132KV Trafo_007-1 dated March 19,
2014.

Siemens AG (Dresden)

GERMANY-Dresden

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TAMINI

ITALY

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

based on TS&SD letter# 09-01501-03032301 dated 25th


May 2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0
with the following conditions:

All type, special & routine tests for each voltage class
as per SEC specifications/standards shall be carried out on
the first batch to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 14 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
WILSON TRANSF

FACTORY LOCATION
AUSTRALIA-MELBOURNE

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

1.3
1. 3. 1

33

110 KV TO 132 KV PRIMARY


Applicable Standards:

POWER TRANSFORMERS UP TO 100 MVA


ABB

SWITZERLAND

Yes

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Bilbao

SPAIN-Bilbao

Yes

53-TMSS-01

Based on TS&SD letter# 09-F01546/03-03032301 dated


19th. Aug 2009, it is pre-qualified for Power Transformer
up to 132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, rev.0 with the following conditions:

All type, design, special & routine tests (including


short circuit test) as per SEC specifications/standards shall
be carried out on the first unit to be supplied to SEC in
securing an order in the presence of three (3) SEC
engineers & one (1) approved independent inspection
agency Inspector.

Seven (7) years warranty from the date of PAC of


the turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

ABB TRANSIT OY

FINLAND

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA

GERMANY

Yes

Pre-Qualification & Participation for current & future SEC's


Projects subjected to the mutual agreement between SEC
& ABB dated 09 March 2009

Previously AREVA T&D-Turkey [The name has been


changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

Page 15 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BEST

FACTORY LOCATION
TURKEY-Balikesir (ASB Factory)

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 06-789-03032300 dated July 25,
2006, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # EAI-2301061500 dated January 23, 2006.

BEST

TURKEY-Balikesir (OSB Factory)

Yes

Based on S&SD Letter # 14-07386/03-030504401 dated


December 21, 2014, it is pre-qualified for Power
Transformer up to 133MVA, 132kV as confirming to
National Grid SA specification # 53-TMSS-02, Rev.01 with
the following conditions:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # OV-2013200311525 dated March 26, 2013.

CG Electric Systems Zrt. (previously GANZ


Transelektro Electric Co., Ltd.)

HUNGARY-Budapest

Yes

Based on TS&SD Letter 11-01981-1-03032301 dated July


11, 2011, it is pre-qualified for Power Transformers rated
up to 132kV/100MVA as conforming to SEC Specification
# 53-TMSS-01, Rev.0, with the following conditions:
All Type, Special & Routine tests as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the next unit to be supplied to SEC in an accredited
Testing Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter # 10513/10/CG dated
July 04, 2011 and letter# 20338/12/CG dated August 04,
2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated June 15, 2010.
Pre-Qualification & Participation for current & future
SEC's Projects subjected to the fulfillment of confirmation
letter # 20342/12/CG dated August 14, 2012 by
manufacturer.
Page 16 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

EFACEC

PORTUGAL

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

GETRA Power S.P.A

ITALY-Marcianise (CE)

Yes

Based on S&SD Letter # 14-04523-01-03504401 dated 7th


July 2014, it is pre-qualified for Power Transformer up to
100MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD.

All Type, Special & Routine tests as per National Grid SA


Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in an Approved
Independent Testing Laboratory and/or in the
manufacturers Testing Laboratory in the presence of three
(03) National Grid SA Engineers & one (01) Approved
Independent Inspection Agency (IIA) Inspector. All the
costs of which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer through their
letter # GPJLT/SECNG/SSD/009, dated 8th June 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # GPJLT/SECNG/SSD/0010 dated 8th June
2014.
HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 17 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Hyundai Heavy Industries Co. Bulgaria

FACTORY LOCATION
Bulgaria-Sofia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-00438-03-03032301 dated
15/05/2011, it is prequalified for Power Transformers up to
132kV, 100MVA as confirming to SEC specification #
53-TMSS-01, Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards
for Power Transformers up to 132kV, 100MVA shall be
carried out in case of contract award or SEC direct
purchase order at SEC approved independent laboratory or
at manufacturers testing laboratory in presence of three
(3) SEC Engineers and one (1) SEC approved independent
inspection agency. All the related costs for witnessing of
the tests will be borne by the manufacturer. This was
confirmed by HHIBulgaria through letter # D-0353 dated
20/08/2010.
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by HHIBulgaria through letter # D-0355 dated
20/08/2010.

ILJIN Electric Co. Ltd.

SOUTH KOREA--

Yes

Based on S&SD Letter 12-03077-30504401 dated


September 15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is
pre-qualified for Power Transformers 110kV to 132kV rated
up to 100MVA as conforming to SEC Specification #
53-TMSS-01, Rev.0, with the following conditions:
All Type, Routine and Special testes as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the First unit to be supplied to SEC of Power
Transformers with voltage class of 110kV or 115kV or
132kV rated up to 100MVA in The Manufacturer's Testing
Laboratory in the presence of three (3) SEC Engineers &
one (1) SEC approved Independent Inspection Agency
(IIA) Inspector. All costs of which shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer ILJIN ELECTRIC Co. Ltd. through their letter
# IJ-20120725-01 dated July 25, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by the manufacturer ILJIN ELECTRIC
Co. Ltd. through their letter # IJ-20120628-01 dated June
28, 2012.

JEUMONT SCHNEIDER

FRANCE

Yes

Page 18 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Koncar D&ST Inc.

FACTORY LOCATION
CROATIA-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-03217-1-30504401 dated May
18, 2014, it is pre-qualified for Power Transformer up to
67MVA, 132kV as confirming to National Grid SA
specification # 53-TMSS-01, Rev.01 with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications shall be carried out on the first unit to be
supplied to National Grid SA in the Approved Independent
Testing Laboratory or in the manufacturers Testing
Laboratory in presence of three (03) National Grid SA
Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated May
04, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated May 04, 2014.

Koncar Power Transformers Ltd.

CROATIA-Zagreb

Yes

Based on S&SD Letter # 14-08041-01-03504401 dated


13/02/2014 & 14-08041-02-03504401 dated 25/03/2014,
it is pre-qualified for Power Transformer up to 100MVA,
132kV as confirming to National Grid SA specification #
53-TMSS-01, Rev.01 with the following conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the Approved
Independent Testing Laboratory or in the manufacturers
Testing Laboratory in presence of three (03) National Grid
SA Engineers & one (01) Approved Independent Inspection
Agency (IIA) Inspector. All the costs of which shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil, dated
01-04-2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order, as confirmed by the manufacturer through
their letter # 2014/02, dated 01-04-2014 dated April 06,
2014.

Page 19 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Liaoning - Efacec Electrical Equipment Co., Ltd
(LEEEC)

FACTORY LOCATION
CHINA-Liaoning Province

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
SUSPENDED for all SEC/National Grid SA ongoing and
forthcoming projects based on VP, Engineering letter #
13-07937-30504401 dated December 24, 2013.
The old remark before suspension was:
Based on S&SD Letter 12-01675-30504401 dated May 20,
2012. It is prequalified for Power Transformers rated up to
100 MVA as conforming to SEC Specification# 53-TMSS-01
with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by Liaoning - Efacec
Electrical Equipment Co., Ltd (LEEEC) through their letter
# Nil dated April 18, 2012.

MITSUBISHI

JAPAN--

Yes

NISSIN ELECTRIC

JAPAN

Yes

PJSC Zaporozhtransformator (ZTR)

Ukraine-Zaporizhia

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Based on S&SD letter# 13-07568-30504401 dated


December 31, 2013, it is pre-qualified for Power
Transformers rated up to 100MVA, 132 kV as conforming
to National Grid SA specification # 53-TMSS-01, Rev.01,
with the following conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements
together (with Thermal & Dynamic short-circuit calculations
per IEC 60076-5) shall be carried out on the next unit to
be supplied to SEC/ National Grid SA in an Accredited
Testing Laboratory in the presence of three (3) National
Grid SA Engineers & one (1) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter 1/115-2261 dated August 15, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # 1/115-2266 dated August 15, 2011.

Page 20 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SC ELECTROPUTERE SA

FACTORY LOCATION
Romania-Craiova

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-002054-1-03032300
dated10/7/2011, it is prequalified for Power Transformer
up to 132kV, 100MVA, as conforming to National Grid SA
specification # 53-TMSS-01, Rev.0 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order.
This was confirmed by SC Electroputere SA through letter
27500 dated 14/06/2010.

Schneider Enerji Endustrisi San VE TIC A.S

TURKEY-Cayirova-Kocaeli

Yes

Based on S&SD letter# 14-02364-1-30504401 dated April


01, 2014, it is pre-qualified for Power Transformers up to
67 MVA and, 132 kV conforming to National Grid SA
specification 53-TMSS-01, Rev. 01, with the following
conditions:
All Type, Special & Routine tests as per National Grid SA
Specifications/Standards shall be carried out on the first
unit to be supplied to National Grid SA in the manufacturer
Testing Laboratory in the presence of three (03) National
Grid SA Engineers & one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter # MKT_132KV Trafo_005, dated June 18, 2013.
Schneider Electric Transformer Factory - Cayirova,
Istanbul, Turkey has confirmed that improvement needs
implementation will be complied during the FAT for the first
transformer order confirmed through letter # MKT_132KV
Trafo_010 dated February 12, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # MKT_132KV Trafo_007-1 dated March 19,
2014.

Page 21 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Siemens AG (Dresden)

GERMANY-Dresden

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

REMARKS
based on TS&SD letter# 09-01501-03032301 dated 25th
May 2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0
with the following conditions:

All type, special & routine tests for each voltage class
as per SEC specifications/standards shall be carried out on
the first batch to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Total =

1.4
1. 4. 1

37

230 KV PRIMARY
Applicable Standards:

POWER TRANSFORMERS UP TO 400 MVA


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

53-TMSS-02

Page 22 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Cordoba

FACTORY LOCATION
SPAIN-Cordoba

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter# 09-F011657/03-03032301 dated
August 16, 2009. It is pre-qualified for Power Transformer
up to 380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
All type, design, special (exclude Short-Circuit Test) &
routine tests as per SEC Specifications/Standards together
with Thermal & Dynamic short-circuit calculations per IEC
60076-5 shall be carried out on the first unit to be supplied
to SEC in an accredited Independent Testing Laboratory or
in the manufacturer's testing laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter # PPTR-002.2 dated February 14, 2009 and the
submitted "Confirmation Letter" # Nil dated November 18,
2008. [this condition has been modified based on S&SD
letter# 12-0395-01-30504001 dated February 12, 2012]
Seven (7) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order. This was confirmed in writing by the manufacturer
through their submitted "Guarantee/Warranty Certificate"
# Nil dated May 25, 2009.

ABB Elektrik Sanayi A.S. [previously ABB ESAS]

TURKEY-Istanbul/Kartal

Yes

Based on S&SD letter# 14-02898/03-030504401 dated


June 17, 2014, it is pre-qualified for Power Transformer up
to 380kV, 250MVA as confirming to National Grid SA
specification # 53-TMSS-02, Rev.01 with the following
conditions:
All Type, Routine and Special testes as per NG
Specifications/Standards and IEC requirement together
with Thermal & Dynamic short-circuit calculations per IEC
60076-5 shall be carried out on the First unit to be supplied
to SEC/NG of Power Transformers in the Manufacturer's
Testing Laboratory in the presence of three (3) SEC/NG
Engineers & one (1) SEC/ NG approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nill
dated February 04, 2013 .
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter #Nill dated May 24, 2013.

Page 23 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA

GERMANY

Yes

CG POWER SYSTEMS

BELGIUM

Yes

DAIHEN CORPORATION

JAPAN-OSAKA

Yes

FUJI Electric Co.

JAPAN--

Yes

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

Based on TS&SD fax#09-F01255/02-03032301 dated 25th.


July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Previously AREVA T&D-Turkey [The name has been


changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 24 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ILJIN Electric Co. Ltd.

FACTORY LOCATION
SOUTH KOREA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03077-30504401 dated
September 15, 2012, ILJIN ELECTRIC Co. Ltd - Korea is
pre-qualified for Power Transformers 230kV rated up to
166.7MVA only as conforming to SEC Specification #
53-TMSS-02, Rev.0, with the following conditions:
All Type, Routine and Special testes as per SEC
Specifications/Standards together with Thermal & Dynamic
short-circuit calculations per IEC 60076-5 shall be carried
out on the First unit to be supplied to SEC of Power
Transformers 230kV rated up to 166.7MVA only in The
Manufacturer's Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer ILJIN ELECTRIC Co. Ltd.
through their letter # IJ-20120725-01 dated July 25, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by the manufacturer ILJIN ELECTRIC
Co. Ltd. through their letter # IJ-20120628-01 dated June
28, 2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Siemens AG (Dresden)

GERMANY-Dresden

Yes

based on TS&SD letter# 09-01501-03032301 dated 25th


May 2009 , Siemens AG from Germany-Dresden for Power
Transformer up to 230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 & 53-TMSS-02, rev.0
with the following conditions:

All type, special & routine tests for each voltage class
as per SEC specifications/standards shall be carried out on
the first batch to be supplied to SEC in securing an order in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

WILSON TRANSF

AUSTRALIA-MELBOURNE

Yes

UP TO 100 MVA ONLY


Total =

20

Page 25 of 238

SER
1.5
1. 5. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

380KV PRIMARY
Applicable Standards:

POWER TRANSFORMERS UP TO 500 MVA


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ABB Cordoba

SPAIN-Cordoba

Yes

53-TMSS-02

Based on TS&SD letter# 09-F011657/03-03032301 dated


August 16, 2009. It is pre-qualified for Power Transformer
up to 380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:
All type, design, special (exclude Short-Circuit Test) &
routine tests as per SEC Specifications/Standards together
with Thermal & Dynamic short-circuit calculations per IEC
60076-5 shall be carried out on the first unit to be supplied
to SEC in an accredited Independent Testing Laboratory or
in the manufacturer's testing laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer through their
letter # PPTR-002.2 dated February 14, 2009 and the
submitted "Confirmation Letter" # Nil dated November 18,
2008. [this condition has been modified based on S&SD
letter# 12-0395-01-30504001 dated February 12, 2012]
Seven (7) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order. This was confirmed in writing by the manufacturer
through their submitted "Guarantee/Warranty Certificate"
# Nil dated May 25, 2009.

Page 26 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Elektrik Sanayi A.S. [previously ABB ESAS]

FACTORY LOCATION
TURKEY-Istanbul/Kartal

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-02898/03-030504401 dated
June 17, 2014, it is pre-qualified for Power Transformer up
to 380kV, 250MVA as confirming to National Grid SA
specification # 53-TMSS-02, Rev.01 with the following
conditions:
All Type, Routine and Special testes as per NG
Specifications/Standards and IEC requirement together
with Thermal & Dynamic short-circuit calculations per IEC
60076-5 shall be carried out on the First unit to be supplied
to SEC/NG of Power Transformers in the Manufacturer's
Testing Laboratory in the presence of three (3) SEC/NG
Engineers & one (1) SEC/ NG approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nill
dated February 04, 2013 .
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) and
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter #Nill dated May 24, 2013.

ALSTOM Grid

TURKEY-Gebze

Yes

First Unit to be Type Tested in the presence of 3 SEC


Engineers & 1 SEC approved Independent Inspector;
Extended Warranty of Six years.
Previously AREVA T&D-Turkey [The name has been
changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

AREVA

GERMANY

Yes

CG POWER SYSTEMS

BELGIUM

Yes

FUJI Electric Co.

JAPAN--

Yes

HAWKER SIDDELEY

United Kingdom

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 27 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

REMARKS
Based on TS&SD fax#09-F01255/02-03032301 dated 25th.
July 2009, it is pre-qualified for Power Transformer up to
380kV, 500MVA as confirming to SEC specification #
53-TMSS-02, rev.0 with the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.

Seven (7) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

2
2.1
2. 1. 1

16

PAD MOUNTED DISTRIBUTION TRANSFORMERS

13.8 KV, 33KV & 34.5 KV PRIMARY


DIST. TRANSFORMERS UP TO 2 MVA

Applicable Standards:

ABB

Saudi Arabia-RIYADH

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

51-TMSS-01

Based on TS&SD letter # 11-03272-03032301 dated


16/11/2011 and S&SD letter # 14-02494-01-30504401
dated 24/04/2014, it is prequalified for Station Service
Transformer up to 2.5MVA as conforming to SEC/National
Grid SA specification # 51-TMSS-01, Rev.01 with the
following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
from the date of first delivery of direct material supply
order. This was confirmed by ALFANAR Electrical Systems
(AES)Riyadh through letter # Nil dated 09/04/2011.

FEDERAL TRANSFORMERS CO.

United Arab Emirates-ABU DHABI Yes

UP TO 1.5 MVA

Page 28 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

KONCAR D&ST

Croatia/Hrvatska

Yes

UP TO 2.5 MVA. Complete Type, Routine / Sample tests for


first order & 10 Years Warranty from the date of PAC is
required.

Saudi Federal Transformers L.L.C.

Saudi Arabia-Riyadh

Yes

Based on S&SD Letters# 12-01572-2-30504401 dated May


27, 2012 & 13-06464-1-30504401 dated December 11,
2013, it is pre-qualified for Power Transformers rated up to
36KV & 2MVA as confirming to SEC Specification #
51-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty in respect of defects
due to design , manufacturing, installation and
workmanship from the date of PAC of the first turnkey
project (in case of contract award) or from the date of first
delivery of direct material supply order as confirmed
through Saudi Federal Transformers L.L.C., Riyadh letter #
SFTL/TES/545/2012 dated May 05, 2012.

SAUDI TRANSFORMERS CO.

Saudi Arabia-DAMMAM

Yes

UP TO 13.8 KV ONLY

United Transformers Electric Co. (UTEC)

Saudi Arabia-Riyadh

Yes

Prequalified up to 2.5 MVA

WESCOSA

Saudi Arabia-DAMMAM

Yes

UP TO 13.8 KV ONLY
Total =

3
3.1
3. 1. 1

PAD MOUNTED GROUNDING TRANSFORMERS UP TO 2 MVA

13.8 KV, 33KV & 34.5 KV PRIMARY


Applicable Standards:

GROUNDING TRANSFORMERS
*

---

Yes

ABB

United States

Yes

ABB

Saudi Arabia-RIYADH

Yes

ABB ( T& D)

ITALY

Yes

ABB SECHERON

SWITZERLAND-GENEVA

Yes

CG POWER SYSTEMS

BELGIUM

Yes

CROMPTON GREAVES

INDIA

Yes

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

HYUNDAI

KOREA, Republic of-Ulsan

Yes

52-TMSS-01
ALL APPROVED POWER TRANSFOREMER
MANUFACTURERS, EXCEPT DISTRIBUTION
TRANSFORMER MANUFACTURERS ARE ALSO ACCEPTABLE
FOR GROUNDING TRANSFORMERS

SUSPENDED FOR SEC 2005 PROJECTS AND ONWARD

Page 29 of 238

SER

4
4.1
4. 1. 0

5
5.1
5. 1. 1

5.2
5. 2. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

6.1
6. 1. 1

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

Total =

Total =

Total =

DRY TYPE TRANSFORMERS

36 KV PRIMARY
Applicable Standards:

36 KV PRIMARY
ABB/AEIL

Saudi Arabia

Yes

SIEMENS

GERMANY

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

COMPACT SUBSTATION

69KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


Applicable Standards:

UNIT SUBSTATION, 69KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


ABB (BBC SECHERON)

SWITZERLAND-GENEVA

Yes

CG POWER SYSTEMS

BELGIUM

Yes

110-132 KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


Applicable Standards:

UNIT SUBSTATION, 110 - 132 KV PRIMARY, 13.8 KV OR 34.5 KV SECONDARY


ABB ( T& D)

FACTORY LOCATION

United States-N/A

Yes

REACTOR

OIL IMMERSED REACTORS


Applicable Standards:

33 KV TO 69 KV OIL IMMERSED REACTORS


ABB

SWEDEN

58-TMSS-01

Yes

Page 30 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

CG Power Systems Belgium NV

BELGIUM-Mechelen

Yes

REMARKS
Previously AREVA T&D-Turkey [The name has been
changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

Based on S&SD letter# 14-08521-2-30504401 dated


December 10, 2014, it is pre-qualified for Shunt Reactors
rated up to 132kV as conforming to National Grid SA
specification # 58-TMSS-01, Rev.1, with the following
conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements
[excluding Short circuit test ] shall be carried out on the
first unit to be supplied to SEC/National Grid SA in the
manufacturer Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA
approved Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer through their
letter #Nil dated November 10, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter #Nil dated 25 November 2014.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 31 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National
Grid SA specification # 58-TMSS-01, Rev.01 with the
following conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC
standards & technical requirements shall be conducted at
Manufacturer's Testing Laboratory in presence of three (3)
SEC/National Grid SA engineers & one (1) company
approved independent inspection agency Inspector, at the
sole expenses of manufacturer on the first unit to be
supplied to SEC/National Grid SA. This was confirmed
through their letter # HS-SR-141027-01 dated October 27,
2014.
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case
of direct material supply order shall be provided as
confirmed by the manufacturer and subsequently reduced
yearly in case of future project award through their letter#
HS-SRPQ-150107-01 dated January 7, 2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with
the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
from the date of first delivery of direct material supply
order and subsequently reduced yearly in case of future
project award. This was confirmed by HHI Korea through
letter # S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 32 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated
December 31, 2013, it is pre-qualified for Shunt Reactors
rated up to 132 kV as conforming to National Grid SA
specification # 58-TMSS-01, Rev.0, with the following
conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements shall
be carried out on the first/next unit to be supplied to
SEC/National Grid SA in an Accredited Testing Laboratory
in the presence of three (3) National Grid SA Engineers &
one (1) National Grid SA approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-3553 dated
December 14, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # 1/115-3552 dated December 14, 2011.

SCHNEIDER ELECTRIC

TURKEY-Kocaeli

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

Based on S&SD Letter 12-03420-30504401 dated October


02, 2012, Schneider Electric from Turkey-Kocaeli is
pre-qualified for Shunt Reactors up to 33kV only.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

6. 1. 2

Applicable Standards:

110 KV TO 132 KV REACTORS


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

14

58-TMSS-01

Previously AREVA T&D-Turkey [The name has been


changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

Page 33 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
CG Power Systems Belgium NV

FACTORY LOCATION
BELGIUM-Mechelen

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-08521-2-30504401 dated
December 10, 2014, it is pre-qualified for Shunt Reactors
rated up to 132kV as conforming to National Grid SA
specification # 58-TMSS-01, Rev.1, with the following
conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements
[excluding Short circuit test ] shall be carried out on the
first unit to be supplied to SEC/National Grid SA in the
manufacturer Laboratory in the presence of three (3)
National Grid SA Engineers & one (1) National Grid SA
approved Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer through their
letter #Nil dated November 10, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter #Nil dated 25 November 2014.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 34 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National
Grid SA specification # 58-TMSS-01, Rev.01 with the
following conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC
standards & technical requirements shall be conducted at
Manufacturer's Testing Laboratory in presence of three (3)
SEC/National Grid SA engineers & one (1) company
approved independent inspection agency Inspector, at the
sole expenses of manufacturer on the first unit to be
supplied to SEC/National Grid SA. This was confirmed
through their letter # HS-SR-141027-01 dated October 27,
2014.
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case
of direct material supply order shall be provided as
confirmed by the manufacturer and subsequently reduced
yearly in case of future project award through their letter#
HS-SRPQ-150107-01 dated January 7, 2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with
the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
from the date of first delivery of direct material supply
order and subsequently reduced yearly in case of future
project award. This was confirmed by HHI Korea through
letter # S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 35 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PJSC Zaporozhtransformator (ZTR)

FACTORY LOCATION
Ukraine-Zaporizhia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07568-30504401 dated
December 31, 2013, it is pre-qualified for Shunt Reactors
rated up to 132kV as conforming to National Grid SA
specification # 58-TMSS-01, Rev.0, with the following
conditions:
All Type, Special & Routine tests as per latest National
Grid SA Specifications/Standards & IEC requirements shall
be carried out on the first/next unit to be supplied to
SEC/National Grid SA in an Accredited Testing Laboratory
in the presence of three (3) National Grid SA Engineers &
one (1) National Grid SA approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer through their letter 1/115-3553 dated
December 14, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # 1/115-3552 dated December 14, 2011.

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

6. 1. 3

Applicable Standards:

230 KV OIL IMMERSED REACTORS


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

FUJI Electric Co.

JAPAN--

Yes

14

58-TMSS-01

Previously AREVA T&D-Turkey [The name has been


changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 36 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

Based on S&SD letter # 14-10289-02-30504401 dated 18


January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National
Grid SA specification # 58-TMSS-01, Rev.01 with the
following conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC
standards & technical requirements shall be conducted at
Manufacturer's Testing Laboratory in presence of three (3)
SEC/National Grid SA engineers & one (1) company
approved independent inspection agency Inspector, at the
sole expenses of manufacturer on the first unit to be
supplied to SEC/National Grid SA. This was confirmed
through their letter # HS-SR-141027-01 dated October 27,
2014.
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case
of direct material supply order shall be provided as
confirmed by the manufacturer and subsequently reduced
yearly in case of future project award through their letter#
HS-SRPQ-150107-01 dated January 7, 2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with
the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
from the date of first delivery of direct material supply
order and subsequently reduced yearly in case of future
project award. This was confirmed by HHI Korea through
letter # S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 37 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TOSHIBA CORPORATION, T&D

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL
2005.
Total =

6. 1. 4

Applicable Standards:

380 KV OIL IMMERSED REACTORS


ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM Grid

TURKEY-Gebze

Yes

12

58-TMSS-01

Based on S&SD letter# 13-04034-2-30504401 dated


September 12, 2013, it is pre-qualified for 380 kV Oil
Immersed Shunt Reactors as conforming to National Grid
SA specification # 58-TMSS-01, Rev.0, with the following
conditions:
All type/special, routine tests for 380 kV Oil Immersed
Shunt Reactors on one unit of each rating supplied to SEC
shall be conducted at Manufacturer's Testing Laboratory in
presence of three (3) SEC/National Grid SA engineers &
one (1) SEC approved independent inspection agency
Inspector, all the related costs for witnessing the tests will
be borne by the manufacturer. This was confirmed by
Alstom Grid, Turkey through their letter # Nil dated July
22, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed by Alstom Grid, Turkey through their
letter # Nil dated July 22, 2013.

AREVA_(ST. QUEN)

FRANCE-(ST. QUEN)

Yes

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 38 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10289-02-30504401 dated 18
January 2015, the manufacturer is prequalified for Oil
Immersed Reactor up to 380 KV as conforming to National
Grid SA specification # 58-TMSS-01, Rev.01 with the
following conditions:
All type, special, routine tests for Oil Immersed Shunt
Reactors per National Grid SA specifications and IEC
standards & technical requirements shall be conducted at
Manufacturer's Testing Laboratory in presence of three (3)
SEC/National Grid SA engineers & one (1) company
approved independent inspection agency Inspector, at the
sole expenses of manufacturer on the first unit to be
supplied to SEC/National Grid SA. This was confirmed
through their letter # HS-SR-141027-01 dated October 27,
2014.
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case
of direct material supply order shall be provided as
confirmed by the manufacturer and subsequently reduced
yearly in case of future project award through their letter#
HS-SRPQ-150107-01 dated January 7, 2015.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

Based on TS&SD Letters # 10-02438-02-03032301 dated


August 31,2010 and 13-05782-1-30504401 December 11,
2013, it is pre-qualified for Shunt Reactor as conforming to
National Grid SA specification # 58-TMSS-01, Rev.0 with
the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
from the date of first delivery of direct material supply
order and subsequently reduced yearly in case of future
project award. This was confirmed by HHI Korea through
letter # S370-1008-0182 dated 18/08/2010.

MITSUBISHI

JAPAN--

Yes

SIEMENS AG (NURNBERG)

GERMANY-NURNBERG

Yes

SIEMENS TRANSFORMERS AUSTRIA GMBH &


CO KG

AUSTRIA- WEIZ

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

12

Page 39 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

6.2

AIR CORE SERIES REACTOR

6. 2. 1

230 KV AIR CORE SERIES REACTORS

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

REMARKS

58-TMSS-02

---

Yes

ALL POWER TRANSFORMER AND OIL IMMERSED


REACTOR MANUFACTURERS ARE ACCEPTABLE TO SUPPLY
AIR CORE SERIES REACTORS FROM 13.8KV TO 230 KV

NOKIAN ALSTOM Grid oy Ltd

FINLAND-Tampere

Yes

Based on S&SD letter # 14-03642-01-30504401 dated


June 11, 2014, NOKIAN ALSTOM Grid oy Ltd. TampereFinland is pre-qualified for Air Core Series Reactors up to
145 kV as confirming to National Grid SA Specification #
58-TMSS-02, Rev.01 with the following conditions:
The first batch of Air Core Series Reactors up to 145kV to
be supplied SEC/National Grid SA shall be tested for Type,
Special, and Routine tests in presence of three (3)
SEC/National Grid SA Engineers and one SEC/National Grid
SA approved IIA Inspector and all costs pertaining to the
tests shall be borne by the manufacturer as confirmed
through their letter # Nil dated 02nd September 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed by the manufacturer through their
letter # Nil, dated 20th June 2012.

TRENCH AUSTRIA GMBH

AUSTRIA-Leonding, Linz

Yes

Based on TS&SD letter 10-01317-1-03032301 dated May


10, 2010. TRENCH AUSTRIA GMBH is pre-qualified for Air
Core Series Reactors as confirming to SEC Specification
58-TMSS-02, Rev.0 with the following conditions:
Extended Warranty: Seven (7) years Extended Warranty
shall be applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH AUSTRIA GMBH as confirmed
through their letter # NIL dated April 28, 2010.
Test Witnessing: Factory Tests on the first batch of
Reactors to be supplied to Contract # 10931162/00 and
Contract # 10931163/00 for Dynamic Reactive Power
Compensation Projects in Central Operating Area shall be
conducted in presence of three (3) SEC Engineers and one
(1) IIA Inspector, under the sole expense of the
Manufacturer as confirmed through their Letter Letter #
NIL dated April 28, 2010.

Page 40 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TRENCH CANADA

FACTORY LOCATION
CANADA-Scarborough, Ontario

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter 10-01317-1-03032301 dated May
10, 2010. TRENCH CANADA is pre-qualified for Air Core
Series Reactors as confirming to SEC Specification
58-TMSS-02, Rev.0 with the following conditions:
Extended Warranty: Seven (7) years Extended Warranty
shall be applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH CANADA as confirmed through
their letter # NIL dated April 28, 2010.
Test Witnessing: Factory Tests on the first batch of Air
Core Series Reactors to be supplied to Contract #
20931030/00 for Taif BSP & Kayber/Bawat S/S shall be
conducted in presence of three (3) SEC Engineers and one
(1) IIA Inspector, under the sole expense of the
Manufacturer as confirmed through their Letter # NIL
dated April 27, 2010.
Free Replacement: TRENCH CANADA shall supply one
complete three phase set of Reactors (3 units) to SEC
(Tabouk City) free of charge as already confirmed through
their letter # NIL dated November 06, 2009.
Total =

6.3
6. 3. 1

AIR CORE REACTORS


Applicable Standards:

230 KV AIR CORE REACTORS


ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

Power Economy Middle East Co.

United Arab Emirates-Abu Dhabi

Yes

52-TMSS-02,58-TMSS-02

Limited to 34.5kV Only; First unit of 34.5kV Air Core


Reactor shall be type tested in an independent lab. in the
presence of 3 SEC Engineers & 1 SEC Approved
Independent Inspection Agency; 10 years of Extended
Warranty.
Total =

7
7.1
7. 1. 1

SWITCHGEARS

METAL CLAD SWITCHGEARS


Applicable Standards:

13.8 KV UP TO 34.5 KV
ABB ( T& D)

United States-N/A

32-TMSS-01

Yes

Page 41 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB/AEIL

FACTORY LOCATION
Saudi Arabia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
For 33kV AIS:
classic ZS3 type with current rating up to 2500A@ 40C;
CB type VD43620-25(2000A), VD43612-25(1250A &
800A); ES type EK5, 3007N280.
For 13.8kV AIS:
The remark was modified based on S&SD Letter
13-01329-30504401 dated March 13, 2013.
13.8kV switchgear type UniGear ZS1 (CT on upper &
lower side of CB) with rated current of incomer, Bus
Section, Bus Riser 3003A and 1756A, Out Going Feeder
with rated current 924A and 682A @ 40C, 60Hz, 25kA
(3s).
Out Going Feeder (CT on lower side of CB) with rated
current 991A and 648A @ 40C, 60Hz, 25kA (3s).
CB types (VD4 embedded pole): VD4 17.31-25
(interrupter VG6), ABB Italy and VD4 17.16-25 (interrupter
VG4/S), VD4 17.12-25 (interrupter VG4) & VD4 17.06-25
(interrupter VG4), ABB, Italy.
Circuit breaker for Capacitor bank back to back switching
(BC2-630A); VD4 17.12-40 (interrupter VG6), HD4
17.12-25 (interrupter SF6), HD4 24.12-25 (interrupter
SF6), and (BC2- 900A); HD4 17.16-25 (interrupter SF6)
ABB, Italy.
All VD4 Poles and Interrupters are from ABB Calor Emg,
Germany (DECMS).
EL Operating Mechanism form ABB-SACE Italy (ITABB).
Earthing switch type EK6, ABB-EJF, Czech.
CT & VT: ABB-EJF, Czech or WTW make, Germany
Old version: Classic ZS1.
Based on S&SD Letter 12-03120-01-30504401 dated
August 14, 2012, 13.8kV UniGear ZS1 AIS is pre-qualified
for current rating 3600/4000A @ 40C, 60Hz with forced
cooling, with the following dimensions of the panels:
Incomer
(100017802595), VCB-VD4
1731-25,Interrupter-VG6
Bus section
(100017802595), VCB-VD4
1731-25,Interrupter-VG6
Bus riser
(80014002595)
Page 42 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ABB-CALOR EMAG

GERMANY-CALOR EMAG

Yes

AEL -SIEMENS

Saudi Arabia-JEDDAH

Yes

For 13.8kV AIS:


type 8BK20 with CB type 3AH.
for 33kV AIS:
type 8BT2 is not acceptable, as the VT is situated in a
separate compartment and connected by cable.

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-02613-01-03032301 dated


13th September 2009, ALFANAR ELECTRICAL SYSTEMS
from Saudi Arabia-Riyadh for 13.8kV Switchgear type
NES-H with degree protection IP4X; vacuum CB (rating
3150A & 1250A) and ES from LSIS (South Korea) - details
of types are mentioned in the TS&SD letter; as confirming
to SEC specification # 32-TMSS-01, rev.0 with the
following condition:
Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order.
Based on S&SD Letter 11-01668-03032301 dated June 01,
2011, 13.8kV NES-H AIS is pre-qualified for current rating
4000A @ 40C, 60Hz with forced cooling and 2906A @
40C, 60Hz with natural cooling with busbar dimension
3x100x10mm and with the following dimensions of the
panels:
Incomer
(100018802793),
VCB-LVB-17M-40D/301E2H, Interrupter-10403
Bus section
(100018802793),
VCB-LVB-17M-40D/301E2H, Interrupter-10403
Bus riser
(100018802793)

AREVA (MACON CEDEX 9)

FRANCE-(MACON CEDEX 9)

Yes

EFACEC

PORTUGAL

Yes

ELEKTROBUDOWA SA

Poland-Konin

Yes

based on TS&SD letter# 09-01092-03032301 dated 18th.


April 2009 it is prequalified for for 13.8kV Air Insulated
Switchgear type D-17P with SCC of 25kA/3sec, degree of
protection IP4X and rated current of 3000A @ 40oC, 60Hz;
CB type VD4 which approved by SEC from ABB-Germany
(3000A) & ABB-Italy (2500A); ES type UMR from
ELECTROBUDOWA SA-Poland as confirming to SEC
specification # 32-TMSS-01, rev.0 with Ten (10) years
warranty from the date of PAC of the Turnkey project in
case of contract award or date of delivery in case of direct
material supply order.

Page 43 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
EPS LTD. (GROUPE SCHNEIDER)

FACTORY LOCATION
Saudi Arabia-RIYADH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
For 13.8kV AIS:
Pre-qualified since 24/02/1420H for 13.8kV SWG type
MC-Set with CB type LF3-3150-(2500A), LF2- 2500
(2000A), LF2-1250 (800A), LF2-630 (400A) and warranty
of (7)years from commissioning date of the first delivery
for any onward project or order in the first two years and
then shall be (3)years from PAC.
Based on S&SD Letter 12-02860-01-30504401 dated July
24, 2012, 13.8kV MC-Set AIS is pre-qualified for current
rating 3600A @ 40C, 60Hz with forced cooling, with the
following dimensions of the panels:
Incomer
(90017002500), CB-LF3,
Interrupter-LF3-3150A
Bus section
(90017002500), CB-LF3,
Interrupter-LF3-3150A
Bus riser
(90017002500)
For 33kV AIS:
Based on TS&SD fax ref. #09-00073-2-03032301 dated
04/02/2009. Pre-Qualified for 34.5 kV SWG type
(F400NL)1250/2500 A @40C &60Hz with IP4X,SF6 CB
type SF2(France),ES type TFCM(France), & (10)years
warranty.
Old version:
33kV AIS type F400G with current rating up to 2500A @
40C with CB type SF & SF2

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

KONCAR

Croatia/Hrvatska

Yes

LIMITED TO DTA ONLY; FOR CTA PREQUALIFICATION


UNDER PROGRESS

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

POWER CON

United States

Yes

SWITCHGEAR NOT YET TYPE TESTED

S&C

United States

Yes

SIEMENS

United States

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 44 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

VA TECH

FRANCE

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

REMARKS

Total =
7. 1. 2

Applicable Standards:

110 KV TO 132 KV GIS


ABB

GERMANY

Yes

19

32-TMSS-02
Old Version:
145kV GIS type ELK-04 with CB type ELK-SW04, Hydraulic
spring mechanism; DS type ELK-TE0 (3 POS), MES type
ELK-TE0 (3 POS)/ TE03-DR04; HES type ELK-EB03.
New Version:
Based on TS&SD letter # 11-00455-5-03032301 dated
April 04, 2011, the new version 145kV GIS type ELK-04
with CB type ELK-CB0 (Hydraulic Spring Mech. HMB-1), DS
type ELK-DE0-3POS, MES type ELK-DE0, HSES type
ELK-ES0 (Motor Spring Mech.) is pre-qualified as
conforming to SEC specification # 32-TMSS-02, Rev.01
with the following condition:
Ten (10) Years Extended Guarantee/Warranty from the
date of PAC of project (in case of contract award) and from
date of delivery for the direct material supply order. This
was confirmed in writing by ABB Germany via their letter #
PTPH/GVS.Nb, 10_year-warranty.doc dated May 14, 2010.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

ABB

SWITZERLAND

Yes

CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 45 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid AG

FACTORY LOCATION
SWITZERLAND-Oberentfelden

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version:
Based on S&SD letter# 13-4433-01-30504401, dated 16
January 2013, it is pre-qualified for 145kV GIS type F35
with rated current, 3150A @40C, 60Hz, CB typeF35-CB4 / Opr. Mech: FK3-2 (spring charged), Line &
Busbar DS-F35-DES-4/ Opr. Mech: ME1-3,
MES-F35-DES-4/ Opr. Mech: ME1-3, HES-F35-EFZ/Opr.
Mech:MF-3 (spring charged), CT-F35-CT4, against
specification # 32-TMSS-02, Rev.1 with the following
condition:
1. Eight (8) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order. This was confirmed through manufacturer lletter ref:
Q1F35_210409 dated 21 April 2009.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
Old Version:
145kV GIS type B65 with CB type B65-CB Motor spring
mechanism; DS type B65-DS; ES type B65-ES; HES type
B65-EF.
Previously " Areva T &D AG, SWITZERLAND-Oberentfelden
", the name has been changed to ALSTOM Grid AG,
Oberentfelden, Switzerland, based on ALSTOM Grid Letter
# Nil dated July 11, 2012.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.
Old version:
145kV GIS type SDA5 (SDA514) with CB type BAK5,
Hydraulic mechanism.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 46 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HITACHI Ltd.

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Originally JAPAN AE POWER SYSTEM CORP and
subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.
New version: 145kV GIS type CFTA with CB type
CFPT-120-40L, FAR3 Motor spring mechanism; DS type
CFL-120; ES type CFL-120.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Old version: 145kV GIS type CFT with CB type
CFPT-140-40L, FAR3,C Pneumatic mechanism; DS type
SFL-EA; HES type SFGM-FA.

HYOSUNG (HICO)

KOREA, Republic of-Changwon

Yes

New Model approved on 10-04-2007, Model Type


HSG-144A 145KV GIS with CB type HCSP-144A
Motor spring mechanism; DS type HDMO-144A; MES type
HDMO-144A, HES type HEMS-144A.
All Type and Design tests have been carried out completely
& accepted as mentioned in TS&SD
letter#08-F02926-03032301 dated 22/11/2008.
Provide extended Guarantee/Warranty for Seven(7) Years
from the date of PAC
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES
Old version: 145kV GIS type 145HGS40 with CB type
145HCB,145PL40; DS type 145SDSV/SDSH; MES type
145SESM; HES type 145SESA

Page 47 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYUNDAI

FACTORY LOCATION
KOREA, Republic of-Ulsan

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version: 145kV GIS type 145SP-1 with CB type
145SP-K1
Motor spring mechanism; BDS type 145SP-3PS1; LDS type
145SP-3PS2; MES type 145-3PS2; HES type 145SP-LES2.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO
Old version: 145kV GIS type 145SP with CB type 145SP-K
Hydraulic mechanism; DS type 145SP-DS; MES type
145SP-ES; HES type 145SP-LES
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

KONCAR

Croatia/Hrvatska

Yes

GIS & ADAPTORS; LIMITED TO DTA ONLY; FOR CTA


PREQUALIFICATION UNDER PROGRESS
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

LS Industrial System Co.

SOUTH KOREA-Cheongju

Yes

Based on S&SD letter# 13-07921-2-30504401 dated


January 06, 2014,it is pre-qualified for 145kV GIS type
GESG-1440NHS with rated current, 3150A, 60Hz, CB typeGEDB-1440NHS / Opr. Mech. Type: GGA204155 (spring
charged), LDS type- GESG 1440-ACSF/ Opr. Mech: Motor,
BDS type-GESG 1440-ACSB / Opr. Mech: Motor, MES typeGESG 1440-ACSB/ Opr. Mech: Motor, HES type- GESG
1440-MSES /Opr. Mech: Motor spring & CT- JK GIS,
against specification # 32-TMSS-02, Rev.1 with the
following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated November 25, 2013.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: YES

Page 48 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
MITSUBISHI

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL
2005.
New version 145kV GIS type 100GMKD with CB type
120-SFMT-40CJ; DS type 120GRD/GLD; MES type
120GRED/GRE; HES type 120 GRED/GRE-A.
Old version: 145kV GIS 120GMKM with CB type
120-SFMT-40,
Pneumatic mechanism; DS type 120-GR-20,
120-GL-20; MES type 120-GRE, 120-GREC; HES type
120-GREA.
Old version: 145kV GIS 100GMKD with CB type
120-SFMT-40CE
Motor spring mechanism; DS type 120GLD; HES type
120-GREA.
CB Capability for:
Inductive load switching: YES
Capacitor bank back to back Switching: NO

SIEMENS

FRANCE-GRENOBLE

Yes

New version:
145kV GIS type TH7m with CB type TH7m AF8ER(Motor
spring); BDS type CM002, CM003 (3-position); LDS type
CM002, CM003 (2-position); MES type CM002,CM003; HES
type CM002, CM003.
Old version: 145kV GIS type HEXABOLIC-TH7 with CB type
DTH7 Hydraulic mechanism; BDS type SITH7; LDS type
ITH7, SI TH7; ES type ST TH7.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

SIEMENS

GERMANY

Yes

New version: 145kV GIS type 8DN8-II with CB type 8DN8


Motor spring mechanism; DS type 8DN8; ES type 8DN8.
Old version: 145kV GIS type 8DN8 with CB type 8DN6(P1)
Motor spring mechanism; DS type 8DN8; ES type 8DN8.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO

Page 49 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TOSHIBA CORPORATION, T&D

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL
2005.
145kV GIS type with CB type GSPK-145AP; BDS type
KTM-120PW, DTM-120PW, DLM-120PW; LDS type
KTM-120PW, DTM-120PW; MES type EBM-120W; HES type
EAP-120W.
CB Capability for:
Inductive load switching: NO
Capacitor bank back to back Switching: NO
Total =

7. 1. 3

Applicable Standards:

230 KV -GIS
ABB

SWITZERLAND

Yes

13

32-TMSS-02
Based on S&SD letter # 14-00064-30504101 dated
January 26, 2014 and ABB Letter # PPHV-300GIS CH-05
dated February 02, 2014, the designation has been
corrected to the following:
230 kV GIS Type: ELK-14/300 (1HC0071250M0040), Rated
current: 4000A, 40C, @ 60Hz, CB Type: ELK-SP14/300
(1HC0071250M0040) / Opr. Mech: HMB4
(1HC0071250M0040), LDS & BDS Type: ELK-TK14/300
(1HC0071250M0040) / Opr. Mech: BAC
(1HC0071250M0040), MES Type: ELK-TK14/300
(1HC0071250M0040) / Opr. Mech: BAC
(1HC0071250M0040), HES Type: ELK-EB14/300
(1HC0071250M0040) / Opr. Mech: BAE
(1HC0071250M0040), CT Type: ELK-CN14/300
(1HC0071250M0040), Cable compartment Type: ELK-HK
14/300 (1HC0071250M0040).
Capacitor Bank Back to Back switching type test will be
performed when required in the project, confirmed by ABB
letter # PPHV-140120/GIS-1, dated 21-01-2014.
Old Designation:
230kV GIS Type: ELK-1, CB Type: ELK SP2-1.

ALSTOM Grid SAS

FRANCE-AIX-LES BAINS

Yes

230kV GIS type B105 with CB type B105-CB; DS type CLT


Previously "AREVA T&D FRANCE-(AIX-LES BAINS) ", the
name has been changed to ALSTOM Grid SAS-France
based on ALSTOM Grid-France letter # Nil, dated
December 07, 2012.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 50 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HITACHI Ltd.

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Originally JAPAN AE POWER SYSTEM CORP and
subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.
230kV GIS type MFPT MFPTB-300-63L with CB type
MFPTB-300-63LA, HAR/MFTB-300-563L; BDS type FL-EA,
LDS type FMG-FA/FG.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

SIEMENS

GERMANY-Berlin

Yes

Based on S&SD letter # 13-05708-1-30504401, dated


October 10, 2013, it is pre-qualified for 245kV GIS type
8DN9 with rated current, 3150A @40C, 60Hz, CB type8DN9-245kV-50kA/Opr. Mech: spring charged, Line &
Busbar DS-8DN9-245kV-50kA/Opr. Mech: Motor,
MES-8DN9-245kV-50kA/Opr. Mech: Motor,
HES-8DN9-245kV-50kA/Opr. Mech: spring charged, as
conforming to National Grid SA specification #
32-TMSS-02, Rev.01, with the following conditions:
CB capability for Capacitor bank back to back switching
(BC1/BC2) is applicable for 145kV only.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by SIEMENS, Germany-Berlin
through their letter # Nil dated June 19, 2010.

Page 51 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Old Version

230kV GIS type 8DN40-8DN4 with CB 8DN401-8DN4;


BDS type 8DN4-8DQ1; LDS type 8DP4; MES type 8DN4;
HES type 8DP4.

Based on SIEMENS letter# 30179023-A1 dated


02/05/2011, this type is already obsolete/phased out.
New Version
Based on TS&SD letter # 11-00267/01-03032301 dated
02/02/2011, it is pre-qualified for 300kV GIS type 8DN9,
rated current 4000A, short time current rating of 63kA, CB
(Single Break) type 8DN9-300-63-4000 with motor spring
mechanism, Busbar & line DS type 8DN9-300-63-4000 with
motor drive mechanism, MES type 8DN9-300-63-with
motor drive mechanism & HES type 8DN9-300-63-4000
with motor drive mechanism as confirming to SEC
specification # 32-TMSS-02,Rev.01, with the following
conditions:

Ten (10) years extended warranty starting from


project "Safaniyah 380/230kV project" as confirmed
through SIEMENS letter # PQ_8DN9_02 dated
26/06/2010.

This GIS shall only be used for 245kV, 63kA


applications.

SIEMENS

FRANCE-GRENOBLE

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

7. 1. 4

380 KV - GIS

Applicable Standards:

32-TMSS-02

Page 52 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWITZERLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 13-00748-30504101 dated
November 06, 2013, it is pre-qualified for 420 kV GIS type
ELK-3/420 (1HC0071250M0070) @ 4000A, 60Hz, CB type
ELK-SP3/420, Operating Mechanism-HMB8, Line & Busbar
DS type ELK-TK3/420, Operating Mechanism-ELK-BAC,
MES type ELK-TK3/420, Operating Mechanism-ELK-BAC,
HES type ELK-EB3 420, Operating Mechanism-ELK-BAE, CT
type ELK-CN3, Cable compartment type ELK-HK3.
HYBRID GIS:
Base on S&SD letter # 14-03182-01-30504401, dated
29-01-2015, Pre-qualified ABB, Switzerland GIS type
ELK-3/420 (1HC0071250M0070) with its components are
acceptable for Hybrid GIS up to current rating @ 3150A,
55C, 60Hz.

ALSTOM Grid SAS

FRANCE-AIX-LES BAINS

Yes

420kV GIS type T155 with CB type FB2T (Hydraulic Mech.)


Previously "AREVA T&D FRANCE-(AIX-LES BAINS) ", the
name has been changed to ALSTOM Grid SAS-France
based on ALSTOM Grid-France letter # Nil, dated
December 07, 2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.
420kV GIS type 1FT

Page 53 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HYOSUNG (HICO)

FACTORY LOCATION
KOREA, Republic of-Changwon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-F-02299/02-03032301 dated
25/10/2010, it is pre-qualified for 420kV GIS type HSG
426A, 63kA, CB (Single Break) type HCHY 426A with
Hydraulic Mechanism, Busbar DS type HDMO 426A, Line
DS type HDMO 426B,ES type HEMO 426A&H-ES type
HEMS 426A as confirming to SEC specification #
32-TMSS-02,Rev.01, with the following conditions:

Supply one complete spare bay" free of charge" (for


not repeating the short circuit test of circuit breaker type
HCHY 426A) on the first supply of 420kV GIS type HSG
426A to SEC. This was confirmed in writing by Hyosung
Corp (Korea) through letter #Nil dated 28th December
2009.

Repeat/carry out the temperature rise test at 55C (it


was carried out before at 50C) of the main circuit on the
first supply of the 420kV GIS type HSG 426A to SEC. This
was confirmed in writing by Hyosung Corp (Korea) through
letter #HS-420GIS-100830-1 dated 30th August 2010.

Back to back switching tests for the capacitor bank


shall be conducted in an independent test laboratory
whenever there is project requirement. This was confirmed
in writing by Hyosung Corp (Korea) through letter #HS420GIS-100830-1 dated 30th August 2010.

Ten (10) years extended warranty for the proposed


420kV GIS type HSG 426A from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed in writing by Hyosung Corp (Korea) through
letter #HS-420GIS-100830-1 dated 30th August 2010.

HYUNDAI

KOREA, Republic of-Ulsan

Yes

420 kV; 63kA; TYPE-550 SR; CB-550 SR-K (Single Break);


DS-550 DRM 1&2; ES-550 ERM; HES-550 LES; back to
back capacitor switching test for C.B. shall be done in
independent laboratory iin the presence of SEC Engineers
whenever there is a requirment for this test iin th PTS of
forthcoming SEC projects.
- 10 Years extended warranty.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

SIEMENS

FRANCE-GRENOBLE

Yes

420kV GIS type YGII with CB type SPD; DS ype YGII

SIEMENS

United Kingdom-HEBBUM

Yes

Page 54 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
New version:
550kV GIS type 8DQ1 with CB type 8DQ1-P2; DS type
8DQ1; ES type 8DQ1. with ten (10) years extended
warranty from the date of Provisional Acceptance
Certificate (PAC) of the Turnkey project (In case of
contract award) and from the date of delivery for the direct
material supply order. The guarantee/warranty shall cover
all the cost of materials and labor as per
warranty/guarantee of materials and workmanship and
subsequently reduced yearly in case of future project
award.
HYBRID GIS:
Base on S&SD letter # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 550kV GIS
type 8DQ1 with its components are acceptable for Hybrid
GIS up to current rating 3150A, 55 C, 60Hz.
Old version:
420kV GIS type 8DQ1 with CB type 8DQ1-T2, DOUBLE
BREAK, Hydraulic mechanism; DS type 8QD1

Siemens AG

GERMANY-Berlin

Yes

Based on S&SD letter# 14-00569-2-30504401 dated


February 09, 2014,it is pre-qualified for 420KV GIS, type
8DQ1-6, 63KA, Single Break with rated current 4000A,
60Hz, CB type-8DQ1 6-P1 (Single break)/ Opr. Mech.
Type: Spring type (FA5), LDS type- 8DQ1 6 DS / Opr.
Mech: Motor, BDS type-8DQ1 6 DS / Opr. Mech: Motor,
MES type- 8DQ1 6 ES / Opr. Mech: Motor, HES type- 8DQ1
6 HSES /Opr. Mech: Motor spring & CT- 8DQ1 6 against
specification # 32-TMSS-02, Rev.1 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer
(Siemens AG-Germany) through their letter # Nil dated
May 30, 2012.
HYBRID GIS:
Base on S&SD letter # # 15-05204-01-30504401, dated
28-01-2015, Pre-qualified Siemens, Germany 420 kV GIS
type 8DQ1-6 with its components are acceptable for Hybrid
GIS up to current rating 3150A, 55 C, 60Hz.

Page 55 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TOSHIBA CORPORATION, T&D

FACTORY LOCATION
JAPAN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-05807-2-30504401, dated
September 08, 2014, it is pre-qualified for 420 kV GIS type
GID, Rated current 3150A @ 40 C, 60Hz, 63kA (1s).
CB type GSRK-420CHK (Single break) with internal grading
capacitor 860pF, Operating Mechanism: Hydraulic
GSRK-420CHK, Busbar & Line DS type DTM, Operating
Mechanism DTM (motor), MES type EBM, Operating
Mechanism EBM (motor), HES type EYP, Operating
Mechanism EAP (motor spring charged) as confirming to
National Grid SA Specification # 32-TMSS-02, Rev.01, With
following condition:
Ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the Turnkey
project (In case of contract award) and from the date of
delivery for the direct material supply order. The
guarantee/warranty shall cover all the cost of materials and
labor as per warranty/guarantee of materials and
workmanship and subsequently reduced yearly in case of
future project award. This was confirmed by the
manufacturer through their letter #
TSB/TDS/AK/130206/2145-R1 dated August 12, 2014.
Old version: 420kV GIS type GID with CB type GSR
400R2B/GSRK, DOUBLE BREAK, Hydraulic mechanism.
*TOSHIBA CORPORATION, T&D JAPAN- ORIGINALLY
TMT&D CORP. & DISSOLVED DURING APRIL 2005.
Total =

7. 1. 5

33 KV GIS

11

Applicable Standards:

Page 56 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 15-0186-01-30504401, dated
January 22, 2015 and TS&SD Letter #
10-02461-02-03032301, dated August 31, 2010, the
manufacturer is prequalified for 36kV GAS Insulated
Medium Voltage SWGR Type 8DA10, rated current 2500A
@ 40C, 60Hz and short time current rating of 25kA(3sec),
CB type 3AH49 with vacuum interrupter type VSG 40040
(rated current up to 2500A, 40C, 60Hz & Capacitor bank
back to back switching current 400A),
CB type 3AH49 with vacuum interrupter type VS 30040
(40kA) for current rating up to 2375A C, 60Hz,
as conforming to National Grid SA specification #
32-TMSS-03, Rev.0 with the following condition:
Seven (7) years extended warranty for the proposed
36kV GIS ,type 8DA10 from the date of PAC of the turnkey
project in case of contract award or date of delivery in case
of direct material supply order. This was confirmed by
Siemens trough letter # 8DA10_PQR_R1 dated
24/08/2010.
Total =

8
8.1
8. 1. 0

BATTERY EQUIPMENT

BATTERY LEAD ACID


Applicable Standards:

BATTERY LEAD ACID


BAE BERLINER BATTERIE FABRIK- G

GERMANY

Yes

C&D

United States

Yes

CEAC

FRANCE

Yes

ENERSYS S.A.R.L.

FRANCE--

Yes

EXIDE

United States

Yes

FIAMM

ITALY

Yes

GOULD (GNB)

United States

Yes

HOPPECKE

GERMANY

Yes

TOVARNA AKUMULATORSKIH BATERIJ

SLOVENIA

Yes

TUNGSTONE (HAWKER TUNGSTONE)

United Kingdom

Yes

46-TMSS-01

PREVIOUSLY KNOWN AS HAWKER S.A.R.L - FRANCE; FIVE


YEARS OF EXTENDED WARRANTY

Page 57 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

VARTA

GERMANY

Yes

YUASA

JAPAN

Yes

REMARKS

Total =

8.2
8. 2. 0

BATTERY LEAD ACID, VALVE REGULATED LEAD ACID (VRLA)


Applicable Standards:

BATTERY LEAD ACID, VALVE REGULATED LEAD ACID (VRLA)


AEG Power Solutions SAS

FRANCE--

Yes

C&D

United States

Yes

CHLORIDE (HAWKER CHLORIDE)

United Kingdom

Yes

FIAMM

ITALY

Yes

GNB

United States

Yes

HAWKER LTD.

United Kingdom

Yes

HOPPECKE

GERMANY

Yes

SAB

GERMANY

Yes

SEC

United States

Yes

VARTA

GERMANY

Yes

YUASA EXIDE

United States

Yes

46-TMSS-04
originally was SAFT Power System SAS-France

Total =

8.3
8. 3. 0

12

11

BATTERY NICKEL CADMIUM (NiCD)


Applicable Standards:

BATTERY NICKEL CADMIUM (NiCD)


ALCAD

SWEDEN

Yes

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

EMISA

SPAIN

Yes

EXIDE

United States

Yes

FRIWO

GERMANY

Yes

46-TMSS-06

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based
on Emerson Network Power Industrial Systems letter # nill
dated 12/04/2013.

MERGED WITH SAFT NIFE -SWEDEN

Page 58 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

GAZ Gerate- und Akkumulatorenwerk Zwickau


GmbH

GERMANY-Zwickau

Yes

GNB

United States

Yes

SAFT-NIFE

SWEDEN

Yes

VARTA HAWKER

GERMANY

Yes

REMARKS
Based on TS&SD fax ref.#08-F02675/03-03032301 dated
10/01/2009. Pre-Qualified for Nicd Battery with this
conditions:
-First batch shall be type tested in Independent Laboratory
iin presence of (3) SEC engineers & (1) independent
inspector.
-(07) years warranty

370 TO 1390AH

Total =

8.4
8. 4. 1

BATTERY CHARGER
Applicable Standards:

BATTERY CHARGER

46-TMSS-02

AEG Power Solutions SAS

FRANCE--

Yes

BENNING

FRANCE

Yes

Benning Elektrotechnik & Elektronik GmbH &


Co.kG.

GERMANY--

Yes

Previously "Theo-Benning-Germany", the name has been


changed to Benning Elektrotechnik & Elektronik GmbH &
Co. KG -Germany based on TS&SD/ESD letter #
11-00334-03032301 dated 30/01/2011.

BORRI S.P.A

ITALY-Arezzo

Yes

Based on S&SD Letter # 14-03226-01-030504401 dated


June 4, 2014, it is pre-qualified for Battery Charger
(125VDC, Type RTB.e) as conforming to National Grid SA
specification # 46-TMSS-02, Rev.0 with the following
conditions:

Originally was SAFT Power System SAS-France

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer through
letter # Nil dated May 23, 2011.

Page 59 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BRAGA MORO

FACTORY LOCATION
ITALY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03794-01-30504401 dated
November 18, 2012, Braga Moro- Italy is pre-qualified for
Battery Chargers 125V DC as conforming to National Grid
SA Specification # 46-TMSS-02, Rev.0, with the following
conditions:
All Type, Routine and Special testes as per National Grid
SA Specifications/Standards together shall be carried out
on the First unit to be supplied to SEC/National Grid SA of
Battery Chargers 125V DC in an Independent Testing
Laboratory in the presence of three (3) SEC/National Grid
SA Engineers & one (1) SEC/National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by Braga Moro-Italy. This was
confirmed in writing by Braga Moro-Italy through their
letter # SEC Prequalification dated April 13, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by Braga Moro- Italy through their
letter # SEC Prequalification dated April 13, 2011.

C&D

United States

Yes

CEG

ITALY-BIBIENA

Yes

Based on TS&SD letter# 09-F001363/02-03032301 dated


2nd May 2009 & S&SD letter# 14-05308-01-30504401
dated 21st July 2014 as confirming to National Grid SA
specifications # 46-TMSS-02, rev.0 ; with the following
conditions:
Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based
on Emerson Network Power Industrial Systems letter # nill
dated 12/04/2013.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "AEES ", the name has been changed to


Emerson Network Power Industrial Systems - France based
on Emerson Network Power Industrial Systems letter # nill
dated 12/04/2013.

EMISA (ELECTRO MERCANTIL INDUSTRIAL


S.A. SPAIN)

SPAIN

Yes

ERSKINE

United Kingdom

Yes

EXIDE

United States

Yes

GUTOR ELECTRONIC LTD.

SWITZERLAND

Yes

Page 60 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
JESUS MARIA AGUIRRE SA (JEMA)

FACTORY LOCATION
SPAIN-Lasarte-Oria

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-00193-030504001 dated January
17, 2012. It is prequalified for Battery Charger as
conforming to SEC Specification# 46-TMSS-02, Rev.0 with
the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of each types of Battery Chargers in an
Independent Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nil dated
June 17, 2011.
Ten (10) years extended warranty from the date of PAC
of the FIRST turnkey project in case of contract award or
date of FIRST delivery in case of direct material supply
order. This was confirmed in writing by the manufacturer
through their letter # Nil dated June 17, 2011.

Statron AG

SWITZERLAND-Maegenwil

Yes

Based on S&SD Letter 12-03254-01-30504401 dated


August 29, 2012, it is pre-qualified for Battery Chargers
125V DC (Models BDT) as conforming to SEC Specification
# 46-TMSS-02, Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of each types of Battery Chargers 125V
DC in an Independent Testing Laboratory in the presence
of three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer Statron AG
through their letter # bm dated August 13, 2012.
Ten (10) years extended warranty in respect of defects
due to design, manufacturing, installation and
workmanship from the date of PAC of the first turnkey
project (in case of contract award) or from the date of first
delivery of direct material supply order as confirmed by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Total =

8. 4. 2

UPS, 5 THROUGH 100KVA

Applicable Standards:

15

46-TMSS-03

Page 61 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BORRI S.P.A

FACTORY LOCATION
ITALY-Arezzo

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter # 14-03226-01-030504401 dated
June 4, 2014, it is pre-qualified for UPS, 5 THROUGH 100
kVA as conforming to National Grid SA specification #
46-TMSS-03, Rev.0 with the following conditions:
Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer through
letter # Nil dated May 23, 2011.

BRAGA MORO

ITALY

Yes

Based on S&SD Letter 12-03794-01-30504401 dated


November 18, 2012, Braga Moro- Italy is pre-qualified for
UPS as conforming to National Grid SA Specification #
46-TMSS-03, Rev.0, with the following conditions:
All Type, Routine and Special testes as per National Grid
SA Specifications/Standards together shall be carried out
on the First unit to be supplied to SEC/National Grid SA of
UPS in an Independent Testing Laboratory in the presence
of three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
Braga Moro-Italy. This was confirmed in writing by Braga
Moro-Italy through their letter # SEC Prequalification dated
April 13, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by Braga Moro- Italy through their
letter # SEC Prequalification dated April 13, 2011.

CEG

ITALY-BIBIENA

Yes

Based on TS&SD letter# 09-F001363/02-03032301 dated


2nd May 2009 & S&SD letter# 14-05308-01-30504401
dated 21st July 2014 as confirming to National Grid SA
specifications # 46-TMSS-02, rev.0 ; with the following
conditions:
Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order.

GUTOR ELECTRONIC LTD.

SWITZERLAND

Yes

Page 62 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
JESUS MARIA AGUIRRE SA (JEMA)

FACTORY LOCATION
SPAIN-Lasarte-Oria

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-00193-030504001 dated January
17, 2012. It is prequalified for UPS up to 100kVA as
conforming to SEC Specification# 46-TMSS-03, Rev.0 with
the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of each types of UPS up to 100kVA in an
Independent Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nil dated
June 17, 2011.
Ten (10) years extended warranty from the date of PAC
of the FIRST turnkey project in case of contract award or
date of FIRST delivery in case of direct material supply
order. This was confirmed in writing by the manufacturer
through their letter # Nil dated June 17, 2011.

Statron AG

SWITZERLAND-Maegenwil

Yes

Based on S&SD Letter 12-03254-01-30504401 dated


August 29, 2012, it is pre-qualified for UPS (S2000 series)
as conforming to SEC Specification # 46-TMSS-03, Rev.0
with the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of each types of UPS in an Independent
Testing Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Ten (10) years extended warranty in respect of defects
due to design, manufacturing, installation and
workmanship from the date of PAC of the first turnkey
project (in case of contract award) or from the date of first
delivery of direct material supply order as confirmed by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.
Total =

8. 4. 3

Applicable Standards:

BATTERY CHARGER, 48 VDC


AEG Power Solutions SAS

FRANCE--

Yes

BENNING

FRANCE

Yes

46-TMSS-02,46-TMSS-05
originally was SAFT Power System SAS-France

Page 63 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
BRAGA MORO

FACTORY LOCATION
ITALY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
I. Prequalified for BATTERY CHARGER, 48 VDC (For
Telecom Applications).
II. Prequalified for DC-DC Converters, 48 Volts based on
S&SD Letter 12-03794-01-30504401 dated November 18,
2012 as conforming to National Grid SA Specification #
46-TMSS-07, Rev.0 with the following conditions:
All Type, Routine and Special testes as per National Grid
SA Specifications/Standards together shall be carried out
on the First unit to be supplied to SEC/National Grid SA of
DC-DC Converters, 48 Volts Output in an Independent
Testing Laboratory in the presence of three (3)
SEC/National Grid SA Engineers & one (1) SEC/National
Grid SA approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by Braga
Moro-Italy. This was confirmed in writing by Braga
Moro-Italy through their letter # SEC Prequalification dated
April 13, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by Braga Moro-Italy through their letter
# SEC Prequalification dated April 13, 2011.

COM 10 INTERNATIONAL PTY. LTD.

AUSTRALIA-ALPHA

Yes

SWITCH MODE RECTIFIERS / BATTERY CHARGERS ONLY


FOR TELECOM APPLICATION.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

Previously "CHOLORIDE ", the name has been changed to


Emerson Network Power Industrial Systems - France based
on Emerson Network Power Industrial Systems letter # nill
dated 12/04/2013.

Emerson Network Power Industrial Systems

FRANCE-Lyon

Yes

- Previously "AEES ", the name has been changed to


Emerson Network Power Industrial Systems - France based
on Emerson Network Power Industrial Systems letter # nill
dated 12/04/2013.
- ACCEPTABLE FOR APPLICATIONS OTHER THAN
TELECOM

EMISA (ELECTRO MERCANTIL INDUSTRIAL


S.A. SPAIN)

SPAIN

Yes

Page 64 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ERSKINE

United Kingdom

Yes

Based on TS&SD letter# 09-F02210/03-03032301 dated


1st . September 2009, ERSKIN System Ltd. (a division of
Dale Power Solution plc) from United
Kingdom-Scarborough for 48V DC battery Charger as
confirming to SEC specification # 46-TMSS-05, rev.0 with
the following conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the
manufacturer's laboratory in the presence of three (3) SEC
engineers & one (1) approved independent inspection
agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

EXIDE

United States

Yes

SCR TYPE ONLY

HAMMER & SIMMONS

United Kingdom

Yes

Statron AG

SWITZERLAND-Maegenwil

Yes

Based on S&SD Letter 12-03254-01-30504401 dated


August 29, 2012, it is pre-qualified for Battery Chargers
48V DC (Models BDT and MPS) as conforming to SEC
Specification # 46-TMSS-02, Rev.0 & 46-TMSS-05, Rev.0,
with the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of each types of Battery Chargers 48V DC
in an Independent Testing Laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer Statron AG
through their letter # bm dated August 13, 2012.
Ten (10) years extended warranty in respect of defects
due to design, manufacturing, installation and
workmanship from the date of PAC of the first turnkey
project (in case of contract award) or from the date of first
delivery of direct material supply order as confirmed by the
manufacturer Statron AG through their letter # bm dated
August 13, 2012.

T.D.I

United States

Yes

SWITCH MODE RECTIFIERS ONLY FOR TELECOM


APPLICATIONS
Total =

9
9.1

12

LV DISTRIBUTION PANELS

AC & DC DIST. PANELS


Page 65 of 238

SER
9. 1. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

AC & DC DIST. PANELS

REMARKS

31-TMSS-02

ABB/AEIL

Saudi Arabia

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

EAST & WEST FACTORY

Saudi Arabia-DAMMAM

Yes

ELECTRICAL PANEL BOARD FACTORY/HAWA


TRADING

Saudi Arabia-DAMMAM

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

ETA-PCS

United Arab Emirates-DUBAI

Yes

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

META Switchgear Company

Saudi Arabia-Riyadh

Yes

Based on based on S&SD letter # 14-02218-01-30504401


dated March 23, 2014 & TS&SD letter
#11-F03210/01-03032301 dated 29/11/2011, it is
pre-qualified for AC&DC Panels as confirming to SEC
specification # 31-TMSS-02, Rev.0 with the following
conditions:
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by MEMF-ETA Switchgear Manufacturing
Company through letter # Nil dated 08/12/2010.
Previously MEMF-ETA Switchgear Manufacturing Company,
Riyadh, Saudi Arabia [The name has been changed based
on S&SD letter # 14-02218-01-30504401 dated March 23,
2014].

MOHAMMAD AL OJAIMI FACTORY

Saudi Arabia-RIYADH

Yes

MUSAID SWITCHGEAR

Saudi Arabia-RIYADH

Yes

REMAL

Saudi Arabia-DAMMAM

Yes

SIEMENS

Saudi Arabia-JEDDAH

Yes

Page 66 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Waha Electric Supply Co. of Saudi Arabia(WESCOSA)-Dammam

FACTORY LOCATION
Saudi Arabia-Dammam

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 11-01751/01-03032301 dated
27/06/2011, it is pre-qualified for Auxiliary AC & DC Panels
up to 132kV only as confirming to SEC specification #
31-TMSS-02, Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards shall be carried out on the first
batch of each type of Auxiliary AC&DC Panels to be
supplied to SEC in case of securing an order in the
presence of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector in an
independent testing laboratory. All the related costs for
witnessing the tests will be borne by the manufacturer.
This was confirmed by WESCOSA-Dammam through letter
# Nil dated 18/05/2010.
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by WESCOSA-Dammam through letter # Nil
dated 30/08/2010.

10

Total =

12

Total =

LOAD BREAK SWITCHES UPTO 34.5 KV & RING MAIN UNITS, 15 KV

10 . 1

LOAD BREAK SWITCHES UPTO 34.5 KV

10. 1. 0

LOAD BREAK SWITCHES UPTO 34.5 KV

10 . 2

RMU, 15 KV

10. 2. 0

RMU, 15 KV

Applicable Standards:

ABB/AEIL

Saudi Arabia

Yes

AREVA

FRANCE

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

FRITZ DRIESCHER

GERMANY

Yes

HITACHI

JAPAN

Yes

KONCAR

Croatia/Hrvatska

Yes

SIEMENS

GERMANY

Yes

Applicable Standards:

32-TMSS-07

Page 67 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

Pre-Qualified
Manufacturers
By SEC

ABB

Saudi Arabia-RIYADH

Yes

AREVA

FRANCE

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

FRITZ DRIESHER KG

GERMANY

Yes

GULF REYROLLE LTD

Saudi Arabia-DAMMAM

Yes

MERLIN GERIN

FRANCE

Yes

SAUDI LUCY

Saudi Arabia-AL KHOBAR

Yes

SIEMENS AG EVM

GERMANY-FRANKFURT

Yes

THE INTERNATIONAL ELECTRICAL PRODUCTS


CO.

Saudi Arabia-DAMMAM

Yes

W. LUCY

United Kingdom

Yes

10 . 3

SPARE PARTS FOR RMU & EOS

10. 3. 0

SPARE PARTS FOR RMU & EOS

REMARKS

Total =

10

Total =

Applicable Standards:
CELLMEC

11

FACTORY LOCATION

BAHRAIN

Yes

NEUTRAL EARTHING RESISTORS UP TO 33 KV

11 . 1

NER, UP TO 33 KV

11. 1. 0

NER, UP TO 33 KV

Applicable Standards:
CRESSAL RESISTOR

United Kingdom

Yes

FURSE

United Kingdom

Yes

M.S.Resistances

FRANCE--

Yes

METAL DEPLOYE

FRANCE

Yes

NATIONAL

INDIA

Yes

57-TMSS-01

EXTENDED GUARANTEE / WARRANTY FOR 10 YEARS

Total =

12
12 . 1

BARE CONDUCTORS

TYPE ACAR / ACSR / AAAC


Page 68 of 238

SER
12. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

BARE CONDUCTOR, ACAR / ACSR / AAAC


ALCOA

United States

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

REMARKS

10-TMSS-01

Based on S&SD letter# 13-02020-01-30504401 dated July


30, 2013, it is pre-qualified for ACSR, ACAR and AAAC type
Bare Overhead Line Conductors conforming to National
Grid SA specification # 10-TMSS-01, Rev.01 with the
following conditions:
Only ACSR Condor Conductor 795kcmil (402.83mm)
was successfully type tested in accredited Kinectrics
Laboratory-Canada in the presence of SEC/National Grid SA
Engineers with acceptable results (Kinectrics Report #
K-419415-RC-0001-R01, dated 11th Feb 2013).
The first batch of ACAR and AAAC conductors to be
supplied to SEC/National Grid SA shall be type tested in an
independent accredited test laboratory in the presence of
three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved independent inspection
agency Inspector and all costs pertaining to the tests shall
be borne by the manufacturer.
Ten (10) years extended warranty from the date of
Provisional Acceptance Certificate (PAC) of the first turnkey
project in case of contract award or date of first delivery in
case of direct material supply order. This was confirmed in
writing by the manufacturer through their letter #
C-PRQ-2013-02 dated June 17, 2013.

Page 69 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-NALAGARH

FACTORY LOCATION
INDIA-NALAGARH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Bar Conductors as
confirming to SEC specification # 10-TMSS-01, Rev.01 with
the following conditions:

The first batch of each type of conductors to be


supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall
be borne by the manufacturer. This has been confirmed in
writing by the manufacturer, through letter #
AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer; through
letter # AIL/BRD/ SEC/PQ/19 dated 22nd May 2010.

APAR Industries Ltd-SILVASSA

INDIA-SILVASSA

Yes

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010 & Letter # 14-03608/02-030504401 dated
04th June 2014, it is pre-qualified for Bare Conductors as
confirming to SEC/National Grid SA specification #
10-TMSS-01, Rev.01 with the following conditions:

AAAC Conductor (500 mm) was successfully type


tested in accredited VEIKI-VNL Laboratory-Budapest,
Hungary in the presence of SEC/National Grid SA Engineers
with acceptable results (VEIKI-VNL Ltd. Report #
7765/VNL, dated 3rd Feb 2014).

The first batch of ACAR & ACSR conductors to be


supplied to SEC/National Grid SA shall be type tested in an
independent accredited test laboratory in the presence of
three (3) SEC/National Grid SA Engineers & one (1)
SEC/National Grid SA approved Independent Inspection
Agency Inspector and all costs pertaining to the tests shall
be borne by the manufacturer.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer; through
letter # AIL/BRD/SEC/PQ/19 dated 22nd May 2010.

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

Page 70 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

STERLITE (INDIA)

INDIA--

Yes

REMARKS
FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN
INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER
INTL. STANDARDS, IN PRESENCE OF SEC ENGINEERS
AND ALL COST SHALL BE BORNE BY THE
MANUFACTURER.10 YEARS EXTENDED WARRANTY.

Based on TS&SD Letter # 10-F001691/01-03032301 dated


June 19, 2010 and S&SD Letter 12-02686-1-30504401
dated July 23, 2012, it is pre-qualified for Bare Conductors
types (ACAR, ACSR & AAAC) as confirming to SEC
Specification # 10-TMSS-01, Rev.01 with the following
condition:
ACAR, ACSR & AAAC conductors were successfully type
tested in accredited laboratory in the presence of SEC
Engineers with acceptable results.
Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.
Total =

12 . 2

TYPE ACSR/AW

12. 2. 1

BARE CONDUCTOR, ACSR/AW

Applicable Standards:
ALCOA

United States

10

01-TMSS-01,10-TMSS-01

Yes

Page 71 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-NALAGARH

FACTORY LOCATION
INDIA-NALAGARH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Bar Conductors as
confirming to SEC specification # 10-TMSS-01, Rev.01 with
the following conditions:

The first batch of each type of conductors to be


supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall
be borne by the manufacturer. This has been confirmed in
writing by the manufacturer, through letter #
AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer; through
letter # AIL/BRD/ SEC/PQ/19 dated 22nd May 2010.

APAR Industries Ltd-SILVASSA

INDIA-SILVASSA

Yes

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010, it is pre-qualified for Bar Conductors as
confirming to SEC specification # 10-TMSS-01, Rev.01 with
the following conditions:

The first batch of each type of conductors to be


supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall
be borne by the manufacturer. This has been confirmed in
writing by the manufacturer, through letter #
AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer; through
letter # AIL/BRD/ SEC/PQ/19 dated 22nd May 2010.

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

FIRST LOT OF EACH TYPE SHALL BE TYPE TESTED IN AN


INDEPENDENT LABORATORY PER 10-TMSS-01 & OTHER
INTL. STANDARDS, IN PRESENCE OF SEC ENGINEERS
AND ALL COST SHALL BE BORNE BY THE
MANUFACTURER.10 YEARS EXTENDED WARRANTY.

Page 72 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

STERLITE (INDIA)

INDIA--

Yes

REMARKS

Based on TS&SD Letter # 10-F001691/01-03032301 dated


19/06/2010, it is pre-qualified for Bare Conductors type
(ACSR/AW) as confirming to SEC specification #
10-TMSS-01 Rev.01 with the following condition:

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.
Total =

12 . 3

GROUND WIRE

12. 3. 1

GROUND WIRE

Applicable Standards:
ALCOA

United States

Yes

APAR Industries Ltd-NALAGARH

INDIA-NALAGARH

Yes

10

10-TMSS-03

Based on TS&SD Letter # 10-01566-2-03032300 dated


14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as
confirming to SEC specification # 10-TMSS-03, Rev.0 with
the following conditions:

The first batch of Aluminum Clad Steel (ACS) type to


be supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall
be borne by the manufacturer. This has been confirmed in
writing by the manufacturer through letter #
AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer through
letter # AIL/BRD/ SEC/PQ/19 dated 22nd May 2010.

Page 73 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
APAR Industries Ltd-SILVASSA

FACTORY LOCATION
INDIA-SILVASSA

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-01566-2-03032300 dated
14/06/2010, it is pre-qualified for Overhead Ground Wire
(OGW) of Aluminum Clad Steel (ACS) Type only as
confirming to SEC specification # 10-TMSS-03, Rev.0 with
the following conditions:

The first batch of Aluminum Clad Steel (ACS) type to


be supplied to SEC shall be type tested in an independent
accredited test laboratory in the presence of three (3) SEC
engineers & one (1) SEC approved independent inspection
agency Inspector and all cost pertaining to the tests shall
be borne by the manufacturer. This has been confirmed in
writing by the manufacturer through letter #
AIL/BRD/PQ/SEC/19 dated 22nd May 2010.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order. This has
been confirmed in writing by the manufacturer through
letter # AIL/BRD/ SEC/PQ/19 dated 22nd May 2010.

ECN CG SA

SPAIN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

MIDAL CABLE LTD.

BAHRAIN-MANAMA

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SOUTHWIRE

United States

Yes

TREFILEUROPE

FRANCE

Yes
Total =

12 . 4

COPPER CLAD, STEEL GROUNDING CONDUCTOR & GROUNDING ROD

12. 4. 1

COPPER CLAD STEEL GROUNDING CONDUCTOR AND GROUNDING ROD

Applicable Standards:

ComScope Bimetals USA

United States-Statesville, NC

Yes

FM Sudafix

United Kingdom-Nottingham

Yes

FURSE

Saudi Arabia

Yes

GANSEC SHENGYUEAN WIRE & CABLE CO.


LTD.

CHINA

Yes

ILJIN CORP./JIWOONG ELECTRIC CO.

SOUTH KOREA

Yes

LTV COPPERWELD

United States

Yes

10

10-TMSS-05

Including Exothermic Welding and Grounding connectors.

Page 74 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SAUDI ELECTRIC INDUSTRIES CO. LTD.

FACTORY LOCATION
Saudi Arabia-JEDDAH

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

12 . 5

COMPOSITE OPTICAL OH GROUND WIRE (OPGW)

12. 5. 1

OPGW

Applicable Standards:

10-TMSS-04

AFL TELECOMMUNICATIONS EUROPE LTD

United Kingdom--

Yes

PREVIOUSLY ALCOA FUJIKURA LTD (AFL).

AFL Telecommunications GmbH

GERMANY-Monchengladbach

Yes

EXTENDED GUARANTEE/WARRANTY FOR A PERIOD OF 10


YEARS.

BRUGG TELECOM AG

SWITZERLAND

Yes

CORNING CABLES (BICC)

United Kingdom-PRESCOT

Yes

DRAKA NK

FINLAND

Yes

FUJIKURA

JAPAN

Yes

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Jiangsu Zhongtian Technology Co.Ltd (ZTT)


-China

CHINA-Nantong

Yes

Previously Draka Comteq Germany GmbH & KG.

Based on TS&SD Letter # 10-01654-03032301 dated June


05, 2010 and S&SD Letter 12-05204-1-30504401 dated
February 04, 2013. It is prequalified for OPGW as
conforming to National Grid SA specification #
10-TMSS-04, Rev.0, with the following conditions:
OPGW type ZTT 13.3mm & ZTT 17.3mm 48 fibers is
successfully type tested as per SEC/National Grid SA
requirements as mentioned below:
-KEMA witness report TIC 3170-12 for ZTT 13.3mm OPGW
-SECRI Type Test Report 12-2009-1 for ZTT 13.3mm
OPGW
-KEMA witness report TIC 3171-12 for ZTT 17.3mm OPGW
-SECRI Type Test Report 12-2009-2 for ZTT 17.3mm
OPGW
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated June 18, 2009.

Page 75 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
LS CABLES

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-02583-03032301 dated
19/09/2010, it is pre-qualified for OPGW as confirming to
SEC specification # 10-TMSS-04,Rev.0, with the following
conditions:

All type/design; routine/sample and special tests per


SEC material specification # 10-TMSS-04, Rev.0 of first
batch of each types of OPGW to be supplied to SEC shall
be conducted in an independent testing laboratory in the
presence of three (3) SEC engineers & one (1) SEC
approved independent inspection agency Inspector and all
cost pertaining to the tests shall be borne by Manufacturer.
This was confirmed in writing by the manufacturer through
letter #Nil dated 24th December 2009.

Ten (10) years extended warranty for each types of


OPGW from the date of PAC of the turnkey project in case
of contract award or date of delivery in case of direct
material supply order. This was confirmed in writing by the
manufacturer through letter #Nil dated 24th December
2009.

PHILLIPS FITEL

CANADA

Yes

PIRELLI

ITALY

Yes

PRYSMIAN TELECOM

SPAIN

Yes

PREVIOUSLY "PIRELLI"

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Based on TS&SD letter# 09-F00730/03-03032301 dated


24th August 2009, Taihan Electric Wire Co. Ltd. from
South Korea-Anyang for OPGW as confirming to SEC
specification # 10-TMSS-04, rev.0 with the following
conditions:

All type, design, special & routine tests as per SEC


specifications/standards shall be carried out on the first
batch to be supplied to SEC in securing an order in the
manufacturer's laboratory in the presence of three (3) SEC
engineers & one (1) approved independent inspection
agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.
Total =

12 . 6

HEAT RESISTANT ALUMINUM ALLOY CONDUCTOR

12. 6. 1

HEAT RESISTANT ALUMINUM ALLOY CONDUCTOR

Applicable Standards:

13

10-TMSS-06

Page 76 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FUJIKURA VISCAS CORP

JAPAN

Yes

IT IS A CONSORTIUM OF FUJIKURA & FURUKAWA. ONLY


INVAR CONDUCTORS PER CLAUSE 1.3 & 1.4 OF
10-TMSS-06. FIRST LOT TO BE TYPE TESTED IN THE
PRESENCE OF 3 SEC ENGRS AND IIA INSPECTOR;
EXTENDED WARRANTY FOR 10 YEARS.

J-POWER SYSTEM CORP.

JAPAN

Yes

Based on TS&SD letter# 09-00649-1-03032301 dated 28


March 2009 it is pre-qualified for GTACSR & GZTACSR.

LS CABLES

KOREA, Republic of

Yes

Based on TS&SD letter # 10-02584-03032301 dated


19/09/2010, it is pre-qualified for Heat Resistance
Aluminum Alloy Conductors, Gap& Non Gap type as
confirming to SEC specification # 10-TMSS-06,Rev.0, with
the following conditions:

All type/design; routine/sample and special tests per


SEC material specification # 10-TMSS-06, Rev.0 of first
batch of each types of Heat Resistance Aluminum Alloy
Conductors to be supplied to SEC shall be conducted in an
independent testing laboratory in the presence of three (3)
SEC engineers & one (1) SEC approved independent
inspection agency Inspector and all cost pertaining to the
tests shall be borne by Manufacturer. This was confirmed
in writing by the manufacturer through letter #Nil dated
08th January 2010.

Ten (10) years extended warranty for each types of


Heat Resistance Aluminum Alloy Conductors from the date
of PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order. This
was confirmed in writing by the manufacturer through
letter #Nil dated 08th January 2010.

Full time presence of LS-Korea expert during


execution of first order with Gap type conductor for
guidance and training of SEC/Contractor staff about
installation of this type of conductor as confirmed through
LS letter # LS/LHJ-100526/00 dated 26th May 2010.

Full technical support will be provided to SEC during


operation of Gap Conductors for minimum five (5) years
period from first project as confirmed through LS letter #
LS/LHJ-100526/00 dated 26th May 2010.
Total =

13
13 . 1

INSULATED CONDUCTOR CABLE (XLPE)

13.8 KV

Page 77 of 238

SER
13. 1. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

XLPE CABLE 13.8 KV


ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

REMARKS

11-TMSS-04
Based on S&SD Letter 13-05014-2-3050440 dated
September 08, 2013, it is pre-qualified for Insulated
Conductor Cable (XLPE) as conforming to National Grid SA
Specification # 11-TMSS-04, Rev.0 with the following
conditions:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery (in case of direct material supply
order), as confirmed through ALFANAR Electrical Systems,
Riyadh letter # nil dated March 10, 2013.
Type Tests have been successfully conducted in
KINETRIC-Canada in the presence of National Grid SA
Engineers on 1x630mm2 CU/XLPE/ATA/PVC 20/35 KV MV
Cable during 9th to 22nd April 2013. However, any MV
Power Cable beyond cable size of 630 mm2 to be supplied
to SEC/National Grid SA shall fully type tested at an
accredited laboratory in the presence of National Grid SA
Engineers & third party inspector.

DUBAI CABLE CO.

United Arab Emirates-DUBAI

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Ref# is 08-02531/01-0303230 dated 08/11/2008


no accessories are pre-qualified

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13 . 2

33 & 34.5 KV

13. 2. 1

XLPE CABLE 33 & 34.5 KV

Applicable Standards:

11-TMSS-04

Page 78 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALFANAR ELECTRICAL SYSTEMS

FACTORY LOCATION
Saudi Arabia-RIYADH

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-05014-2-30504401 dated
September 08, 2013, it is pre-qualified for Insulated
Conductor Cable (XLPE) as conforming to National Grid SA
Specification # 11-TMSS-04, Rev.0 with the following
conditions:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery (in case of direct material supply
order), as confirmed through ALFANAR Electrical Systems,
Riyadh letter # nil dated March 10, 2013.
Type Tests have been successfully conducted in
KINETRIC-Canada in the presence of National Grid SA
Engineers on 1x630mm2 CU/XLPE/ATA/PVC 20/35 KV MV
Cable during 9th to 22 April 2013. However, any MV Power
Cable beyond cable size of 630 mm2 to be supplied to
National Grid SA shall be fully type tested at an accredited
laboratory in the presence of National Grid SA Engineers &
third party inspector.

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DUBAI CABLE CO.

United Arab Emirates-DUBAI

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

Including Joints & Terminations

FUJIKURA CABLES

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

MKM

HUNGARY

Yes

Including Joints & Terminations

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Ref# is 08-02531/01-0303230 dated 08/11/2008


no accessories are pre-qualified

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13 . 3

15

XLPE CABLES 69 KV

Page 79 of 238

SER
13. 3. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

XLPE CABLES 69 KV

REMARKS

11-TMSS-01

ALCATEL

FRANCE

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DRAKA NK

FINLAND

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE


TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY
INSPECTION AGENCY & THREE ENGINEERS OF SEC FOR
FIRST CONTRACT; 10 YEARS OF EXTENDED
GUARANTEE/WARRANTY; FOR JOINTS & TERMINATIONS
ALSO;

FUJIKURA CABLES

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Based on TS&SD letter # 10-02784-01-03032301 dated


24/10/2010, it is pre-qualified for 69kV, 1x630mm XLPE
Power Cable as confirming to SEC specification #
11-TMSS-01, Rev.0, with the following condition:

Ten (10) years extended warranty for the proposed


69kV, 1x630mm XLPE Power Cable from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed in writing by Jeddah Cable Co. through letter
#Nil dated 26th June 2006.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

MKM

HUNGARY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations


Total =

13 . 4

110KV TO 132 KV

13. 4. 1

XLPE CABLES 110 TO 132 KV

Applicable Standards:

14

11-TMSS-02

Page 80 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

DRAKA NK

FINLAND

Yes

Including Joints & Terminations

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

TO CARRY OUT ALL TYPE/DESIGN AND ROUTINE/SAMPLE


TESTS AT SEC APPROVED INDEPENDENT LABORATORY IN
PRESENCE OF A REPRESENTATIVE OF 3RD PARTY
INSPECTION AGENCY & THREE ENGINEERS OF SEC FOR
FIRST CONTRACT; 10 YEARS OF EXTENDED
GUARANTEE/WARRANTY; FOR JOINTS & TERMINATIONS
ALSO;

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

Based on TS&SD letter # 10-02784-01-03032301 dated


October 10,2014 and S&SD letter#
14-04876-01-30504401 dated July 16, 2014. it is
pre-qualified for 132kV, 1x2500mm
CU/XLPE/CWS/LAT/HDPE Power Cable as confirming to
National Grid specification # 11-TMSS-02, Rev.1, with the
following condition:
Ten (10) years extended warranty for XLPE Power Cable
from the date of PAC of the turnkey project in case of
contract award or date of delivery in case of direct material
supply order. This was confirmed in writing by Jeddah
Cable Co. through letter #Nil dated 26th June 2006.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on S&SD letter # 15-00585-01-30504401 dated


February 10, 2015, the manufacturer is prequalified for
110/115/132KV, 1X1200mm CU/XLPE Power Cable as
conforming to National Grid SA specification #
11-TMSS-02, Rev.01.
Not approved to supply the power cable 110/115KV,
132KV with conductor cross section of 1X2500 mm,XLPE,
as per 11-TMSS-02, Rev.01 for any SEC/ National Grid SA
projects based on S&SD letter# 13-02128-02-30504401
dated November 25, 2013.

Page 81 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

13 . 5

230 K V

13. 5. 1

XLPE CABLE 230 K V

Applicable Standards:

15

11-TMSS-02

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations; COMPLETE TYPE,


SPECIAL & ROUTINE TESTS FOR THE FIRST ORDER ,
ALSO 10 YEARS WARRANTY FROM THE DATE OF PAC ARE
REQUIRED

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

based on TS&SD letter# 09-01366-03032301 dated 10th.


May 2009, it is pre-qualified as conforming to SEC
specifications # 11-TMSS-02, rev.0 with the following
conditions:

All type/design and routine/sample tests shall be


carried out on the first batch of 230kV XLPE power cable to
be supplied to SEC in securing an order in an independent
testing laboratory as per IEC/AEIC and SEC standards in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

Page 82 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TAIHAN ELECTRIC WIRE COMPANY

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.
Total =

13 . 6

380 KV

13. 6. 1

XLPE CABLE -380 KV

Applicable Standards:

11

11-TMSS-02

BRUGG

SWITZERLAND

Yes

Including Joints & Terminations; COMPLETE TYPE,


SPECIAL & ROUTINE TESTS FOR THE FIRST ORDER ,
ALSO 10 YEARS WARRANTY FROM THE DATE OF PAC ARE
REQUIRED

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

No

Based on TS&SD letter 11-01374-03032301 dated April 27,


2011. It is DISQUALIFIED for 380KV XLPE Cable.

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

LS

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.

NEXANS

BELGIUM-Charleroi

Yes

Based on S&SD letter # 14-07330-030504401, dated


22/10/2014 , it is prequalified for 380kV XLPE Cables as
confirming to National Grid SA Material Specification
11-TMSS-02, Rev.01 with the following conditions: Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order, as
confirmed by the manufacturer through letter # Nil dated
12/02/2013.

NKT

GERMANY

Yes

Including Joints & Terminations

PIRELLI

GERMANY-BERLIN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

Page 83 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TAIHAN ELECTRIC WIRE COMPANY

FACTORY LOCATION
KOREA, Republic of

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-08139-01-30504401 dated
January 07, 2015, the manufacturer is prequilified to
supply power cables rated 380 kV with conductor cross
section of 1X2500 mm, XLPE, with copper wires metallic
shield as per 11-TMSS-02, Rev.01 along with the cable
accessories with the following drawings numbers:
- Power cable: TXCCD-3802500-130501.
- Outdoor termination: CVC-APS-3804605N-BD (Rev. A).
- GIS termination fluid filled type: CVC-GWO-380-BD
(Rev. A).
- GIS termination dry type: CVC-GWBS-380-BD (Rev. A).
- Cable joint type: CVC-MIP-380-BD (Rev. A).
- Cable joint (A type) with screen interruption type
CVC-MIP-380-R1-BD (Rev. A).
- Straight joint type CVC-MNP-380-BD (Rev. A).
- Coffin Box (1 hole) CV-C1-380N-BD (Rev. A).
- Coffin Box (1 hole) CV-C1-380N-BD (Rev. A).
In addition to the following condition:
- Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) or from the date of first delivery in case of
direct material supply order shall be provided as confirmed
by the manufacturer through their letter # Nill dated
September 02, 2014.

VISCAS FUJIKURA

JAPAN

Yes

Including Joints & Terminations


Total =

14

11

LOW-PRESSURE OIL FILLED (LPOF) CABLE

14 . 1

110 TO 132 KV

14. 1. 1

LPOF CABLE 110 KV TO 132 KV

Applicable Standards:

11-TMSS-03

ALCATEL CABLE

FRANCE

Yes

Including Joints & Terminations

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

DATWYLER

United Kingdom

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

Page 84 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

KABEL WERK BRUGG AG

SWITZERLAND

Yes

Including Joints & Terminations

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG; Including Joints & Terminations

NEXAN(CORTALLIOD)

SWITZERLAND

Yes

Including Joints & Terminations

PIRELLI

ITALY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations


Total =

14 . 2

230 KV

14. 2. 1

LPOF CABLE 230 KV

Applicable Standards:

16

11-TMSS-03

ALCATEL

FRANCE

Yes

Including Joints & Terminations

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SUDKABEL

GERMANY-GERMANY

Yes

PREVIOUSLY ABB. Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations.


Complete Type, Routine / Sample tests for first order.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.
Total =

10

Page 85 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

14 . 3

380 KV

14. 3. 1

LPOF CABLE 380 KV

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

REMARKS

11-TMSS-03

ALCATEL

FRANCE

Yes

Including Joints & Terminations

CANADA WIRE

CANADA

Yes

Including Joints & Terminations

DAINICHI-NIPPON CABLES (MITSUBISHI)

JAPAN

Yes

Including Joints & Terminations

FUJIKURA

JAPAN

Yes

Including Joints & Terminations

FURUKAWA ELECTRIC CO. LTD.

JAPAN

Yes

Including Joints & Terminations

HITACHI CABLE LTD.

JAPAN

Yes

Including Joints & Terminations

J-POWER SYSTEM CORP.

JAPAN

Yes

Including Joints & Terminations

KABEL RHEYDT (AEG)

GERMANY

Yes

Including Joints & Terminations

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG;
Including Joints & Terminations.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.

MITSUBISHI CABLE INDUSTRIES LTD

JAPAN

Yes

Including Joints & Terminations

PIRELLI

ITALY

Yes

Including Joints & Terminations

PIRELLI GENERAL

United Kingdom

Yes

Including Joints & Terminations

PIRELLI KABEL AND SYSTEM GMBH

GERMANY-BERLIN

Yes

Including Joints & Terminations

SHOWA CABLE

JAPAN

Yes

Including Joints & Terminations

SIEMENS

GERMANY

Yes

Including Joints & Terminations

STANDARD TELEFON OG KABELFABRIK A/S

NORWAY

Yes

Including Joints & Terminations

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Including Joints & Terminations.


Complete Type, Routine / Sample tests for first order.
Ten (10) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order.
Total =

14 . 4

17

LINK BOX FOR U/G POWER

Page 86 of 238

SER
14. 4. 1

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

LINK BOX FOR U/G POWER

REMARKS

12-TMSS-11

---

Yes

LINK BOX SUPPLIED / MANUFACTURED BY APPROVED


POWER CABLE MANUFACTURERS ARE ACCEPTABLE

AARTCO

Saudi Arabia-Al-Khobar

Yes

UP TO 230KV.

ABB

SWEDEN

Yes

AK POWER SOLUTONS PTY LTD

AUSTRALIA-Huntingwood, NSW

Yes

AL SHAHRANI EST.

Saudi Arabia-RIYADH

Yes

DEMIRER KABLO/SAUDI CABLE CO.

TURKEY--

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG

MOHAMMAD AL OJAIMI FACTORY

Saudi Arabia-RIYADH

Yes

PAD MOUNTED STAINLESS STEEL BOXES AND UNDER


GROUND FIBER GLASS BOXES UP TO 132KV ACCEPTABLE.
EXTENDED GUARANTEE FOR 10 YEARS FOR THE FIRST
SUPPLY AND IT WILL BE REDUCED YEARLY IN CASE OF
FUTURE PROJECT AWARDS.

PIRELLI

GERMANY-BERLIN

Yes

Power and Telecommunication Equipments


Factory (P.T.E. Co.) (CEPCO)

Saudi Arabia-Jeddah

Yes

STEINER

GERMANY

Yes

Previously HAYCOLEC SWITCHGEAR PTY Australia-NSW


[The name has been changed to AK POWER SOLUTONS
PTY LTD- Australia-Huntingwood, NSW based on
S&SD/P&SFD letter # 13-07444-30504401 dated
December 11, 2013 and based on AK POWER SOLUTONS
PTY LTD- Australia-NSW-Huntingwood Letter # NG251113
dated November 25, 2013].

Based on TS&SD fax ref# 09-00396-1-03032301 dated


17/02/2009 P.T.E is prequalified for Link Boxes rated up to
380kV.
* (10) years extended warranty.

Total =

14 . 5

SHEATH VOLTAGE LIMITERS (SVL)

14. 5. 0

SHEATH VOLTAGE LIMITERS (SVL)

13

Applicable Standards:
ABB

SWEDEN

Yes

Page 87 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
AK POWER SOLUTONS PTY LTD

14 . 6

EARTHING BONDING CABLE

14. 6. 0

EARTHING BONDING CABLE

15

FACTORY LOCATION
AUSTRALIA-Huntingwood, NSW

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Previously HAYCOLEC SWITCHGEAR PTY Australia-NSW
[The name has been changed to AK POWER SOLUTONS
PTY LTD- Australia- Huntingwood, NSW based on
S&SD/P&SFD letter # 13-07444-30504401 dated
December 11, 2013 and based on AK POWER SOLUTONS
PTY LTD- Australia-NSW-Huntingwood Letter # NG251113
dated November 25, 2013].
Total =

Total =

Applicable Standards:
FUJIKURA VISCAS CORP

JAPAN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

PIRELLI

GERMANY-BERLIN

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SAUDI MODERN CO. (RIYADH CABLES)

Saudi Arabia- RIYADH

Yes

PREVIOUSLY LG

FIBER OPTIC CABLE

15 . 1

NON-METALLIC FIBER OPTIC (F/O) CABLE & ACCESSORIES

15. 1. 0

NON-METALLIC FIBER OPTIC (F/O) CABLE & ACCESSORIES

Applicable Standards:

AFL TELECOMMUNICATIONS EUROPE LTD

United Kingdom--

Yes

ALCATEL

SWEDEN

Yes

B.V.TWENTSCHE KABELFABRIEK

NETHERLANDS- NAAKSBERGEN

Yes

BICC

United Kingdom

Yes

BRUGG TELECOM AG

SWITZERLAND

Yes

CORNING CABLES

United Kingdom-PRESCOT

Yes

DRAKA NK

FINLAND

Yes

ERICSON

SWEDEN

Yes

FUJIKURA LTD.

JAPAN

Yes

48-TMSS-02
PREVIOUSLY ALCOA FUJIKURA LTD. (AFL)

ACCESSORIES ONLY

Page 88 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

FURUKAWA

JAPAN

Yes

HITACHI

JAPAN

Yes

INDUSTRIAS ARRUTI

SPAIN

Yes

ONLY ACCESSORIES

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

MIDDLE EAST OPTIC FIBER & CABLE


MANUFACTURING CO. (MEFC)

Saudi Arabia-RIYADH

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

NKF KABEL B.V.

NETHERLANDS

Yes

NOKIA

FINLAND

Yes

ACCESSORIES ONLY

Oman Fiber Optic Cable Company

Oman-Rusayl

Yes

Based on TS&SD letter# 10-00909-2-03032300 dated April


06, 2010. It is pre-qualified for Non Metallic Fiber Optic
Cable per SEC Specification 48-TMSS-02, Rev.0 with the
following conditions:
Type Test: The first batch of each type of Non Metallic
Fiber Optic Cable to be supplied to SEC shall be type tested
per relevant International and SEC Specifications in
presence of three (3) SEC Engineers and one (1) SEC
approved IIA Inspector and all cost pertaining to the test
shall be borne by the Manufacturer as confirmed through
Letter# Nil dated September 12, 2009.
Extended Warranty: Ten (10) year Extended Warranty
shall be applicable for all supplies made by Oman Fiber
Optic Cable Company to SEC as confirmed through Letter#
EU.SEC.PQ.01 dated June17, 2009.

OPTOKON

CZECH REPUBLIC-Jihlava

Yes

PIRELLI

ITALY

Yes

PRYSMIAN TELECOM

SPAIN

Yes

ONLY FOR THE FOLLOWING ACCESSORIES


1 Standard 19 rack (ROV Series) and 23" rack
2 Standard 19" rack Mount Fiber Optic Patch Panel type
MCNP & MFDC consisting of 12/24/36/48 Ports
3 Fiber Optic Wall Mount Box type MPIC consisting of
12/24/36/48 Ports
4 Fiber Storage Shelf type MFSS
5 Optical Pig Tails/Patch Chords equipped with FC/PC &
E2000 Connectors

PREVIOUSLY "PIRELLI"

Page 89 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
R & M Reichle & De-Massari AG

FACTORY LOCATION
SWITZERLAND-Wetzikon

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-02127-030504401 dated May 19,
2013, R & M Reichle & De-Massari AG, Wetzikon,
Switzerland is pre-qualified for "Accessories only" fiber
optic and copper passive components (Structure Cabling)
as conforming to National Grid SA specification #
01-TMSS-01, Rev.01, with the following conditions:
Five (5) years extended warranty from the date of PAC of
the first turnkey project (in case of contract award) or from
the date of first delivery of direct material supply order as
confirmed by R & M Reichle & De-Massari AG, Wetzikon,
Switzerland through their letter #Nill dated June 10, 2013.

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

RIYADH TELEPHONE CABLES CO.

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on S&SD Letter 12-03896-30504401 dated


November 10, 2012, SAUDI CABLE Co. - Saudi
Arabia-Jeddah is pre-qualified for Non-Metallic Fiber Optic
Cable (F/O) Cable & Accessories as conforming to SEC
Specification # 48-TMSS-02, Rev.0, with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated June 12, 2011.

SIEMENS

GERMANY

Yes

SUMITOMO

JAPAN-YOKOHAMA

Yes

TE Connectivity Ltd.

United States--

Yes

Based on S&SD Letter 12-03688-01-30504401 dated


January 03, 2012. The name of the manufacturer has been
changed from ADC- United States to TE Connectivity Ltd.
-United States.

TELECT

Poland-Wroclaw

Yes

based on TS&SD letter# 09-01095-03032301 dated 18th.


April 2009 for the following accessories:
- Management Rack E-9000 series
- Distribution & Termination Unit LCX.
- Wall mounted unit LanLinxs.
Total =

16

29

PILOT WIRE CABLES & ACCESSORIES

16 . 0

Page 90 of 238

SER
16. 0. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

PILOT WIRE CABLES & ACCESSORIES

REMARKS

48-TMSS-01,48-TMSS-03,48-TMSS-04,48-TMSS-05

DEMIRER KABLO

TURKEY

Yes

CABLE & ACCESSORIES

GOLDSTAR CABLE

KOREA, Republic of

Yes

UP TO 100 PAIRS

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

KERPENWORK

GERMANY

Yes

CABLE & ACCESSORIES

LS CABLES

KOREA, Republic of

Yes

PREVIOUSLY LG

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

SIEMENS

GERMANY

Yes

STEINER

GERMANY

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

CABLE & ACCESSORIES

Total =

17

11

SHIELDED CABLE FOR INSTRUMENTATION

17 . 0
17. 0. 0

Applicable Standards:

SHIELDED CABLE FOR INSTRUMENTATION


ALPHA

United States

Yes

AT & T

United States-NEW YORK

Yes

BELDEN

United States

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

Based on TS&SD fax ref.#08-02969-3-03032301 dated


07/01/2009. Pre-Qualified for Shielded Instrumentation &
Thermocouple Cables with this conditions:
-First batch shall be type, designe, special, acceptance &
routine tests in the factory test laboratory in presence of
(3) SEC engineers & (1) independent inspector.
-(10) years warranty

TEKAB Co. Ltd.

United Arab Emirates-Sharjah

Yes

APPROVED FOR CABLES WITHOUT METALLIC SHEATH;


TYPE TEST CERTIFICATE FROM INDEPENDENT LAB TO BE
SUBMITTED FOR 1ST ORDER; EXTENDED QUARANTEE
FOR 10 YEARS.

Page 91 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

18

POWER /OR CONTROL CABLE (0.6/1KV)

18 . 0
18. 0. 0

Applicable Standards:

POWER /OR CONTROL CABLE (0.6/1KV)

11-TMSS-10

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

BELDEN

United States

Yes

ELSEWEDY EGYTECH CABLE CO.

EGYPT--

Yes

JEDDAH CABLE CO.

Saudi Arabia-JEDDAH

Yes

MIDDLE EAST SPECIALIZED CABLE (MESC)

Saudi Arabia-Riyadh

Yes

Middle East Specialized Cable Co. MESC

Jordan--

Yes

Previously JORDAN NEW CABLE COMPANYJORDAN-AMMAN [The name has been changed based on
S&SD/P&SFD letter # 14-01869-30504401 dated March
24, 2014].

OMAN CABLE INDUSTRIES

MUSCAT--

Yes

Based on TS&SD letters # 10-02435-03032301 dated


06/09/2010 & 10-02611-03032301 dated 02/10/2010, it is
pre-qualified for LV Power& Control Cables (0.6/1kV) rating
as confirming to SEC specification # 11-TMSS-10,Rev.0,
with the following condition:

Based on TS&SD letter# 09-01432-03032301 dated 16th.


May 2009 is pre-qualified for Low Voltage Power & Control
Cables 0.6/1kV as conforming to SEC specifications #
11-TMSS-10, rev.0 with the following conditions:

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

based on TS&SD fax ref# 09-00303/01-03032301 dated


18/02/2009.

Ten (10) years extended warranty for the proposed


LV Power& Control Cables from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by Oman Cables Industry through letter # Nil
dated 21/08/2010.
RIYADH CABLES

Saudi Arabia-RIYADH

Yes

SAUDI CABLE

Saudi Arabia-JEDDAH

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

Page 92 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TEKAB Co. Ltd.

FACTORY LOCATION
United Arab Emirates-Sharjah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07588-30504401 dated
December 11, 2013, it is pre-qualified for Power and/or
Control Cable Copper 600/1000 V Rating as conforming to
National Grid SA specification # 11-TMSS-10, Rev.01, with
the following conditions:
It is pre-qualified for All LV power & control cables with
copper conductor except clause 4.3.5 point a.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer TEKAB
Co. Ltd, UAE through their letter # 0580/SO/13 dated
November 17, 2013.
Total =

19

11

CONDUCTOR FITTINGS/CABLE ACCESSORIES

19 . 1

CABLE SPLICE & TERMINATION KITS UP TO 132 KV

19. 1. 1

CABLE SPLICE & TERMINATION KITS UP TO 132 KV

Applicable Standards:

---

Yes

ABB

SWITZERLAND

Yes

BRUGG CABLE

SWITZERLAND

Yes

DAITWEILER

United Kingdom

Yes

ELASTIMOLD

United States

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

G&W

United States

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS CABLES

KOREA, Republic of

Yes

NEXAN

SWITZERLAND

Yes

PFISTERER IXOSIL

SWITZERLAND

Yes

PIRELLI

GERMANY-BERLIN

Yes

RAYCHEM

GERMANY

Yes

12-TMSS-10
APPROVED POWER CABLE MANUFACTURERS UP TO
132KV ARE ACCEPTABLE SUPPLIERS FOR SPLICE AND
TERMINATION KITS OF THE SAME RATING

SUSPENDED FOR ALL ONGOING & FUTURE PROJECTS


DUE TO FREQUENT FAILURE & VERY POOR FOLLOWUP
RESPONSE FROM THE MANUFACTURER.

PREVIOUSLY LG

PREVIOUSLY SEFAG IXOSIL

Page 93 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

RAYCHEM

Saudi Arabia-DAMMAM

Yes

TAIHAN ELECTRIC WIRE COMPANY

KOREA, Republic of

Yes

REMARKS
LIMITED TO 69KV ONLY. UNDER THE GROUP OF TYCO

Total =

19 . 2

CABLE SPLICE & TERMINATION KITS UP TO 230 KV

19. 2. 1

CABLE SPLICE & TERMINATION KITS UP TO 230 KV

Applicable Standards:

---

Yes

ABB

GERMANY

Yes

12-TMSS-10
APPROVED 230 KV POWER CABLE MANUFACTURERS ARE
ALSO ACCEPTABLE SUPPLIERS FOR SPLICE AND
TERMINATION KITS OF THE SAME RATING

Total =

19 . 3

CABLE SPLICE & TERMINATION KITS UP TO 380 KV

19. 3. 0

CABLE SPLICE & TERMINATION KITS UP TO 380 KV

Applicable Standards:

15

12-TMSS-10

---

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

NEXANS

SWITZERLAND-Cossonnay

Yes

Based on S&SD letter # 14-07330-030504401, dated


22/10/2014, it is prequalified 380kV XLPE Cable
Accessories as confirming to National Grid SA Material
Specification 12-TMSS-10, Rev.0 with the following
conditions:-

APPROVED 380 KV POWER CABLE MANUFACTURERS ARE


ALSO ACCEPTABLE SUPPLIERS FOR SPLICE AND
TERMINATION KITS OF THE SAME RATING

Only the following Type/Model of accessories are


approved for 380kV: DTF 1.380 (380kV Dry type GIS
Sealing End), SOA 1.380 (380kV Outdoor Sealing End),
SFY 1.380 (380kV Transformer Sealing End), SMP 1.380
(380kV Cross-bonding joint).
Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order, as
confirmed by the manufacturer through letter #Nil dated
12/02/2013.
Total =

Page 94 of 238

SER

20

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

CONNECTORS, OVERHEAD LINE COMPRESSION TYPE

20 . 0
20. 0. 0

Applicable Standards:

CONNECTORS, OVERHEAD LINE COMPRESSION TYPE


A SALVI & C SPA

ITALY-MILANO

Yes

ALCOA

United States

Yes

BURNDY

United States

Yes

CAROBENI

ITALY

Yes

DALEKOVOD PROIZVODNJA

Croatia/Hrvatska-Zagreb

Yes

12-TMSS-02

Based on TS&SD fax # 10-01179-03032301 dated April 20,


2010, this manufacturer is pre-qualified for Compression
Type Connectors for O/H T/L per 12-TMSS-02, Rev.0 with
the following conditions:
Each new design of Compression Type Connectors for
O/H T/L which has NOT been type tested/supplied to SEC
before, shall be type tested as per 12-TMSS-02.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
Previously DALEKOVOD Croatia.[The name has been
changed based on S&SD/P&SFD letter #
12-01292-30504401 dated April 10, 2012]

ELASTIMOLD

United States

Yes

HOMAC

United States

Yes

INDUSTRIAS ARRUTI

SPAIN

Yes

ISELFA

ITALY

Yes

On Hold

Page 95 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Lorunser Austria GmbH

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

SLOVAKIA-ML Production Myjava Yes

REMARKS
Based on S&SD letter# 13-062982-2-30504401 dated
December 04, 2013, it is pre-qualified for Substation
Connectors as conforming to National Grid SA specification
# 12-TMSS-02 Rev. 01, with the following conditions:
Fresh type tests shall be conducted on any new type of
connectors (other than the six 6 types listed below) in the
presence of three (03) SEC/National Grid SA engineers and
one (01) SEC/National Grid SA approved independent
inspection agency (IIA) Inspector in an accredited
laboratory and all cost pertaining to these tests shall be
borne by the manufacturer. This was confirmed in writing
by the manufacturer through their letter # Nil dated
November 02, 2009.
a. AL-T-Connector: 1AB012-002-031.
b. AL-Straight- Duplex Connector: 1FA017-012-008.
c. AL-Straight- Bundle Connector: 1FA080-033-001.
d. AL-T-Type Connector: 1FB101-002-002.
e. AL-Bus-Support: 1JB008-160-004.
f. AL-Welded-Flat Terminal: 1CB082-010-002.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated November 02, 2009.

MOSDORFER

AUSTRIA

Yes

PFISTERER

SWEDEN

Yes

PREVIOUSLY SEFAG

PFISTERER

SWITZERLAND

Yes

PREVIOUSLY SEFAG AG

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Ankara (Polatli Plant) &

Yes

Based on TS&SD fax ref.#09-00087-03032301 dated


11/01/2009. Pre-Qualified for TL & S/S Lattice Steel
Structure, Line Hardware and Compression Type Connector
for T/L O/H upto 380kV except Space Damper upto 230kV
with the following conditions: -All tests shall be carried out
in presence of (3) SEC engineers. -(10) years warranty

SICAMEX

FRANCE-FEUGEROLLE &

Yes

SM-CI

FRANCE--

Yes

PREVIOUSLY AS FCI(SAAE), FRANCE.


Total =

16

Page 96 of 238

SER

21

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

INSULATORS

21 . 1

PORCELAIN INSULATORS

21. 1. 1

STATION POST INSULATOR PORCELAIN, UP TO 132 KV, 230 KV and 380 KV

Applicable Standards:

15-TMSS-01

DIELVE

ITALY

Yes

LAPP

GERMANY-ROSENTHAL

Yes

LAPP

United States

Yes

NGK

JAPAN

Yes

PPC INSULATORS

AUSTRIA

Yes

Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC


Insulators (Austria) Letter # Nil dated 4th July 2010, it is
pre-qualified for Station Post Insulator Porcelain, up to
132kV, 230kV&380kV as confirming to SEC specification #
15-TMSS-01, Rev.0 with the following conditions:

Approved Only Up To 132 KV Only

A) Type tests conducted in presence of SEC Engineers on


132kV-10.9KN (Drawing # 124-11740-132-101), 230kV10.3KN (Drawing # 124-11850-132-101) and 380kV-12KN
(Drawing # 124-11860-132-101 & 124-11870-132-801)
Insulators.
B) Any new type of Insulators (other than the types
which are mentioned in A) offered by PPC shall Type
Tested in presence of three (3) SEC Engineers and one (1)
Approved Independent Agency Inspector.
C) Ten (10) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order.
SIEMENS

GERMANY

Yes

W.S.I

INDIA

Yes

(On HOLD)
Approved Only Up To 132 KV Only
Total =

21. 1. 2

Applicable Standards:

OHL PORCELAIN INSULATOR UP TO 380 KV


CERAMTEC

GERMANY-N/A

Yes

DIELVE

ITALY

Yes

15-TMSS-02,15-TMSS-03

Page 97 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

LAPP

GERMANY-ROSENTHAL

Yes

NGK

JAPAN

Yes

SIEMENS

GERMANY

Yes

REMARKS

Total =
21. 1. 3

Applicable Standards:

LONG ROD PORCELAIN INSULATORS UP TO 380 KV


LAPP

GERMANY-ROSENTHAL

Yes

NGK

JAPAN

Yes

PPC INSULATORS (ELEKTROKERAMIK


SONNEBERG)

GERMANY

Yes

15-TMSS-04

Based on TS&SD/ESD e-mail dated 07/07/2010 and PPC


Insulators (ELEKTROKERAMIK SONNEBERG, Germany)
Letter # Nil dated 4th July 2010, it is pre-qualified for Long
Rod Porcelain Insulators up to 380kV as confirming to SEC
specification # 15-TMSS-04, Rev.01 with the following
conditions:
A) Type tests conducted in presence of SEC Engineers on
160KN:LG75/18+17/1450 (Drawing # 11134-339900-B)
and 330KN: LG105/18+17/1545 (Drawing # 11134621400-A) Insulators.
B) Any new type of Insulators (other than the types
which are mentioned in A) offered by PPC shall Type
Tested in presence of three (3) SEC Engineers and one (1)
Approved Independent Agency Inspector.
C) Ten (10) years warranty from the date of PAC of the
first turnkey project in case of contract award or date of
first delivery in case of direct material supply order.

SIEMENS

GERMANY

Yes
Total =

21 . 2

OHL GLASS INSULATOR UP TO 380KV

21. 2. 0

OHL GLASS INSULATOR UP TO 380KV

Applicable Standards:

15-TMSS-02

SEDIVER

BRAZIL--

Yes

COMPLETE SAMPLE, TYPE & ROUTINE TESTS FOR THE


FIRST ORDER IS REQUIRED.

SEDIVER

ITALY

Yes

Complete Sample, Type & Routine Tests for the first order
is required.

Page 98 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SGD LA GRANJA VIDRIERIA, S.L.

FACTORY LOCATION
SPAIN-Segovia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07206-01-30504401 dated
November 09, 2013, it is pre-qualified for Glass Insulator
as conforming to National Grid SA specification #
15-TMSS-02 , Rev.01, with the following conditions:
Fresh type tests shall be conducted on each type of
Insulators per clause 5.1 of 15-TMSS-02 Rve.01 and
relevant international standards in the presence of three
(03) SEC/National Grid SA engineers and one (01)
SEC/National Grid SA approved independent inspection
agency (IIA) Inspector in an Independent laboratory and
all cost pertaining to these tests shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated November
08, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated November 08, 2012.
Total =

21 . 3

OHL COMPOSITE INSULATORS

21. 3. 1

OHL COMPOSITE INSULATORS UP TO 230KV

Applicable Standards:

E.B.REBOSIO S.r.L

ITALY

Yes

FCI (FURUKAWA COMPOSITE INSULATORS


LTD)

HUNGARY-BUDAPEST

Yes

LAPP

GERMANY-ROSENTHAL

Yes

MACLEAN POWER SYSTEM

United States-ILLINOIS

Yes

NGK LOCKE INC.

United States

Yes

15-TMSS-05
Up To 132 kV only. Complete Type, Routine / Sample tests
for first order & 10 Years Warranty from the date of PAC is
required.

Page 99 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
PFISTERER SEFAG AG

FACTORY LOCATION
SWITZERLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
It is pre-qualified for Composite Suspension & Tension
insulators up to 380 kV, Composite Line Post insulators up
to 132 kV per SEC Specification 15-TMSS-05, Rev.0 with
the following conditions based on TS&SD letter#
10-02374-03032301 dated August 18, 2010:
A) Type Tests have been conducted in presence of SEC
Engineers on:
110KV, 120KN (Drawing # 138 206 -393A) and 160KN
(Drawing # 138 206 -667A) at 40 kA.
380KV, 160KN (Drawing # 138 206 -588BC) at 50kA.
However, the manufacturer shall perform the Power Arc
Test only at 63kA.
B) Any new type of Insulators (other than the types which
are mentioned in A) offered by PFISTERRER SEFAG AG
Switzerland shall be Type Tested in presence of three (3)
SEC Engineers and one (1) Approved Independent Agency
Inspector.
C) Ten (10) years warranty from the date of PAC.

XIANGFAN GUOWANG

CHINA--

Yes

MOLDED DESIGN ONLY; UPTO 132KV ONLY; ALL THE


TYPE/SPECIAL / ROUTINE TESTS TO BE CARRIED OUT
FOR FIRST CONTRACT/PROJECT AT SEC APPROVED
INDEPENDENT LAB IN PRESENCE OF 3 SEC ENGRS & A
THIRD PARTY INSPECTOR APPROVED BY SEC; 10 YEARS
EXTENDED WARRANTY
Total =

21. 3. 2

OHL COMPOSITE INSULATORS UP TO 380KV

Applicable Standards:

15-TMSS-05

LAPP

GERMANY-ROSENTHAL

Yes

FIRST BATCH OF EVERY NEW TYPE OF 380KV INSULATOR


TO BE TYPE TESTED IN PRESENCE OF 3 SEC ENGINEERS
AND ONE SEC APPROVED INDEPENDENT INSPECTOR;
EXTENDED WARRANTY OF 10 YEARS

MACLEAN POWER SYSTEM

United States-ILLINOIS

Yes

*All type/design & special tests were performed for first


batch at Independent lab. in presence of SEC/IIA
Inspectorbased on TS&SD fax#09-F00306-030323001
dated 17/02/2009.
-Extended 10(ten) year guarantee/warranty is required.

Page 100 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
NGK LOCKE

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 10-F02356/02-03032301 dated
22/11/2010, it is pre-qualified for 380kV Composite
Insulators with the following conditions:

Manufacturer shall conduct/repeat the following tests


on the 380kV Composite Insulators 160kN, Cat.# 402
-SL1370-SK-95 using test series X (Note: Type tests using
test series Y on the 380kV Composite Insulators,160kN ,
Cat.# 402-SL1370-SK-95 have already been conducted
satisfactory by the manufacturer in the presence of SEC
engineers).
1. Power Arc Test (by using test series X) as per IEC
61467.
2. High Pressure Water Withstand Test followed by
Electrical Test and Verification of the Specified Mechanical
Load (SML) as per IEC 61109

Any new type of composite insulator (other than type


Cat. # 402-SL1370-SK-95) offered by NGK Locke Polymer
Insulators Inc.(USA) shall be subjected to all type, special
,sample and routine tests as per SEC standards
specifications in the presence of three (03) SEC engineers
& one (01) SEC approved independent inspection
agency(IIA) Inspector.

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.

PFISTERER SEFAG AG

SWITZERLAND

Yes

It is pre-qualified for Composite Suspension & Tension


insulators up to 380 kV, Composite Line Post insulators up
to 132 kV per SEC Specification 15-TMSS-05, Rev.0 with
the following conditions based on TS&SD letter#
10-02374-03032301 dated August 18, 2010:
A) Type Tests have been conducted in presence of SEC
Engineers on:
110KV, 120KN (Drawing # 138 206 -393A) and 160KN
(Drawing # 138 206 -667A) at 40 kA.
380KV, 160KN (Drawing # 138 206 -588BC) at 50kA.
However, the manufacturer shall perform the Power Arc
Test only at 63kA.
B) Any new type of Insulators (other than the types which
are mentioned in A) offered by PFISTERRER SEFAG AG
Switzerland shall be Type Tested in presence of three (3)
SEC Engineers and one (1) Approved Independent Agency
Inspector.
C) Ten (10) years warranty from the date of PAC.

Page 101 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

21 . 4
21. 4

RTV Silicone Rubber Insulator Coating


Applicable Standards:

RTV Silicone Rubber Insulator Coating


Dow Corning Corporation

United States-Auburn

Yes

15-TMSS-07
Based on S&SD letter # 14-04590-02-30504401, dated
16th September 2014, it is prequalified for RTV Silicone
Rubber Insulator Coating Material Xiameter ECE Sylgard
HVIC as conforming to National Grid SA Material
Specification 15-TMSS-07,Rev.0 with the following
conditions:
All Fresh type/design & special tests shall be conducted
as per National Grid SA Specification 15-TMSS-07, Rev.0 &
relevant International Standards on the first batch to be
supplied to National Grid SA in the presence of three (3)
National Grid SA engineers & one (1) approved
Independent Inspection Agency (IIA) inspector, as
confirmed by the manufacturer through letter # Nil dated
20-07-2014.
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award and date
of delivery in case of direct material supply order, as
confirmed by the manufacturer through letter # Nil dated
March 2014.
Total =

22

LINE INSULATOR HARDWARE FITTINGS

22 . 1

HARDWARE FITTINGS

22. 1. 0

HARDWARE FITTINGS

Applicable Standards:
A SALVI & C SPA

ITALY-MILANO

Yes

ALCOA

United States

Yes

CAROBENI

ITALY

Yes

12-TMSS-01

Page 102 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
DALEKOVOD PROIZVODNJA

FACTORY LOCATION
Croatia/Hrvatska-Zagreb

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD fax # 10-01179-03032301 dated April 20,
2010, this manufacturer is pre-qualified for Line Hardware
except Spacer Dampers per 12-TMSS-01, Rev.0 with the
following conditions:
Each new design of hardware which has NOT been type
tested/supplied to SEC before, shall be type tested as per
12-TMSS-01.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
Previously DALEKOVOD Croatia.[The name has been
changed based on S&SD/P&SFD letter #
12-01292-30504401 dated April 10, 2012]

DAMP

ITALY

Yes

DERVAUX

FRANCE

Yes

Previously "SM-CI-France", the name has been change to


DERVAUX-France based on DERVAUX-France letter # Nil
dated 13/10/2009.

Hubbell Power Systems, Inc.

United States-Columbia

Yes

Previously A B CHANCE [The name has been changed


based on S&SD/P&SFD letter# 14-010193-30504401 dated
January 06, 2015 and based on Hubbell Power System Grid
Letter # Nil dated December 18, 2014]

INDUSTRIAS ARRUTI

SPAIN

Yes

ISELFA

ITALY

Yes

JOSLYN

United States

Yes

MOSDORFER GMBH

AUSTRIA-WEIZ

Yes

PFISTERER

SWEDEN

Yes

PREVIOUSLY SEFAG

PFISTERER

SWITZERLAND

Yes

PREVIOUSLY SEFAG AG

PREFORMED LINE PRODUCTS (PLP)

United States

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Ankara (Polatli Plant) &

Yes

SICAMEX

FRANCE-FEUGEROLLE &

Yes

On Hold

Based on TS&SD fax ref.#09-00087-03032301 dated


11/01/2009. Pre-Qualified for TL & S/S Lattice Steel
Structure, Line Hardware and Compression Type Connector
for T/L O/H upto 380kV except Space Damper upto 230kV
with the following conditions: -All tests shall be carried out
in presence of (3) SEC engineers. -(10) years warranty

Total =

22 . 2

16

OBSTRUCTION MARKERS AND CONDUCTOR LIGHTING

Page 103 of 238

SER
22. 2. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

OBSTRUCTION MARKERS AND CONDUCTOR LIGHTING


BP SOLAR ARABIA LTD

Saudi Arabia

Yes

DERVAUX

FRANCE

Yes

OBSTA

FRANCE

Yes

P&R TECHNOLOGIES

United States

Yes

PFISTERER SEFAG

SWITZERLAND

Yes

SHIN SEONG IND CORP.

KOREA, Republic of

Yes

SM-CI

FRANCE--

Yes

TANA WIRE MARKER

United States

Yes

REMARKS

12-TMSS-03

PREVIOUSLY SEFAG AG

PREVIOUSLY AS FCI(SAAE), FRANCE.

Total =

23

LINE SUPPORT STRUCTURE

23 . 1

SUBSTATION STEEL STRUCTURE (LATTICED)

23. 1. 0

SUBSTATION STEEL STRUCTURE (LATTICED)


AL BABTAIN

Applicable Standards:
Saudi Arabia-RIYADH

20-TMSS-01

Yes

Page 104 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Al Yamamah Electric Powers Factory

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-03472-03032301 dated
09/01/2011, it is pre-qualified for Substation Steel
Structure (Latticed) up to 132kV as confirming to SEC
specification # 20-TMSS-01, Rev.0 with the following
conditions:

Any Substation Steel Structure (Latticed) of new


design proposed by Al-Yamamah Electric Power Towers
Factory, Jeddah (except for the pervious approved design
and drawings provided by SEC to the manufacturer) shall
be subjected to full-scale loading tests and other type,
routine and special tests as per SEC standards
specifications and relevant International Standards in the
presence of three (03) SEC engineers & one (01) SEC
approved independent inspection agency (IIA) Inspector
and all cost pertaining to the tests shall be borne by the
manufacturer.

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order. This
was confirmed in writing by Al-Yamamah Electric Power
Towers Factory, Jeddah through letter # Nil dated 21st
October 2009.

AL ZAMIL STEEL

Saudi Arabia-DAMMAM

Yes

AL-BABTAIN POWER&TELECOM CO.

EGYPT-N/A

Yes

FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE


TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.

Alfanar Steel

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter# 08-1058/1-03032301 dated 25th


May 2009 it is pre-qualified for Transmission Towers for
projects up to 132kV, Substation & Gantry Steel Structures
up to 380kV and Communications Tower for transmission
sector as confirming to SEC specification # 20-TMSS-01,
rev.0 with the following conditions:

All type, routine & special tests including the load test
shall be carried out on the first batch to be supplied to SEC
in securing an order in the manufacturer's testing
laboratory in the presence of three (3) SEC engineers &
one (1) approved independent inspection agency
Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

Page 105 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Energya Steel Solution (Hesham Helal El
Sewedy & Partners for Steel Industries Co.)

FACTORY LOCATION
Saudi Arabia-Rabigh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter# 09-2179/07-03032301 dated
November 11, 2009, approval of Executive Directive for
TS&SD letter# 09-02179/06-03032301 dated November
11, 2009 & based on S&SD letter# 13-01978/01-30504401
dated June 10, 2013, it is pre-qualified for Substation Steel
Structures up to 380kV as conforming to National Grid SA
specification # 20-TMSS-01, Rev.01 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order.

GEYARD FOR COMMERCE AND IMPORT CO.

Saudi Arabia-AL KHOBAR

Yes

HIDADA

Saudi Arabia-JEDDAH

Yes

KEC INTERNATIONAL LTD.

INDIA--

Yes

LARSEN & TOUBRO LTD.

INDIA-CHENNAI

Yes

NAJEM

Saudi Arabia

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Ankara (Polatli Plant) &

Yes

NAGPUR-BUTIPORI, JABALPUR, JAIPUR PLANTS ARE


ACCEPTABLE; ALL THE TESTS SHALL BE CARRIED OUT
FOR FIRST CONTRACT/PROJECT IN PRESENCE OF THREE
(3) SEC ENGINEERS; 10 YEARS OF EXTENDED
WARRANTY.

Based on TS&SD fax ref.#09-00087-03032301 dated


11/01/2009. Pre-Qualified for TL & S/S Lattice Steel
Structure, Line Hardware and Compression Type Connector
for T/L O/H upto 380kV except Space Damper upto 230kV
with the following conditions: -All tests shall be carried out
in presence of (3) SEC engineers. -(10) years warranty
Total =

23 . 2

T/L STEEL STRUCTURE (LATTICED) UP TO 380 KV

23. 2. 0

T/L STEEL STRUCTURE (LATTICED) UP TO 380 KV


AL BABTAIN

Applicable Standards:
Saudi Arabia-RIYADH

13

20-TMSS-01

Yes

Page 106 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Al Yamamah Electric Powers Factory

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 13-05834-30504401-01 dated
September 29, 2013 and letter # 12-0054-30504401 dated
January 10, 2012 Al-Yamamah Electric Power Towers
Factory, Jeddah is prequalified for Transmission Line
Structures up to 380 kV as conforming to National Grid SA
Specification # 20-TMSS-01, Rev.0 with the following
conditions:
Any new transmission Line Structure (Latticed) designed
by Al-Yamamah Electric Power Towers Factory, Jeddah
(except other than previous approved design and drawings
provided by SEC/National Grid SA to the manufacturer)
shall be subjected to full scale loading tests and other type,
routine & special tests as per SEC/National Grid SA
Standards Specifications and relevant International
Standards in the presence of three (03) SEC/National Grid
SA engineers and one (01) SEC/National Grid SA approved
independent inspection agency (IIA) Inspector and all cost
pertaining to these tests shall be borne by the
manufacturer. This was confirmed in writing by the
manufacturer through their letter # Nil dated January 07,
2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated October 21, 2009 and letter # Nil
dated January 07, 2012.

AL ZAMIL STEEL

Saudi Arabia-DAMMAM

Yes

AL-BABTAIN POWER&TELECOM CO.

EGYPT-N/A

Yes

FIRST LOT OF EACH TYPE OF STRUCTURE SHALL BE TYPE


TESTED IN AN INDEPENDENT LAB IN PRESENCE OF SEC
ENGINEERS; 10 YEARS EXTENDED WARRANTY.

Alfanar Steel

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter# 08-1058/1-03032301 dated 25th


May 2009 it is pre-qualified for Transmission Towers for
projects up to 132kV, Substation & Gantry Steel Structures
up to 380kV and Communications Tower for transmission
sector as confirming to SEC specification # 20-TMSS-01,
rev.0 with the following conditions:

All type, routine & special tests including the load test
shall be carried out on the first batch to be supplied to SEC
in securing an order in the manufacturer's testing
laboratory in the presence of three (3) SEC engineers &
one (1) approved independent inspection agency
Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

Page 107 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

AL-SALAM INSDUTRIES AND TRADING


EST./ADVANCE TECHNOLOGIES.

Saudi Arabia-JEDDAH

Yes

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

Energya Steel Solution (Hesham Helal El


Sewedy & Partners for Steel Industries Co.)

Saudi Arabia-Rabigh

Yes

REMARKS
ONE TRIAL PROJECT FOR 110/132 KV SHORT LINE.

Based on TS&SD letter# 09-2179/07-03032301 dated


November 11, 2009 & based on S&SD letter#
13-01978/01-30504401 dated June 10, 2013, it is
pre-qualified for Transmission Line Steel Structures and
Communication Towers as conforming to National Grid SA
specification # 20-TMSS-01, Rev.01 with the following
conditions:
The approval will be initially restricted to the following
items only:
1. Transmission Towers for projects up to 132kV
2. Communication Towers for Transmission Sector
Any Transmission Line Structure (Latticed) of new design
proposed by ENERGYA Steel Solutions, Rabigh (except for
the pervious approved design and drawings provided by
SEC/ National Grid SA to the manufacturer) shall be
subjected to full-scale loading tests and other type, routine
and special tests as per National Grid SA standards
specifications and relevant International Standards in the
presence of three (3) SEC/National Grid SA engineers &
one (1) National Grid SA approved independent inspection
agency (IIA) Inspector and all cost pertaining to the tests
shall be borne by the manufacturer.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order.

HIDADA

Saudi Arabia-JEDDAH

Yes

KALPATARU Power Transmission Ltd.

INDIA-Gujarat

Yes

Based on TS&SD letter 09-00665/1-03032301 dated 16th.


March 2009 for Galvanised Transmission line Lattice Steel
Tower up to 380kV as conforming to SEC specifications #
20-TMSS-01, rev.0; with the following conditions:

Ten (10) years extended warranty.

Improvement needs indicated in the plant survey


report.

All the tests shall be carried out for first


contract/project in presence of three (3) sec engineers &
independent Inspector.

Page 108 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
KEC INTERNATIONAL LTD.

FACTORY LOCATION
INDIA--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Only NAGPUR-BUTIPORI, JABALPUR & JAIPUR Plants are
acceptable.
Any new transmission line structure designed by KEC,
India shall be subjected to full-scale loading tests and
other type/routine/sample tests per SEC specifications in
the presence of three (3) SEC engineers and one (1) SEC
approved Independent Inspection Agency (IIA) inspector
and all costs pertaining to tests shall be borne by the
manufacturer.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of delivery in case of first direct material supply order.

LARSEN & TOUBRO LTD.

INDIA-CHENNAI

Yes

SA_RA Energy, Construction, Trade and


Industry Co. Inc.

TURKEY-Ankara (Polatli Plant) &

Yes

Based on TS&SD fax ref.#09-00087-03032301 dated


11/01/2009. Pre-Qualified for TL & S/S Lattice Steel
Structure, Line Hardware and Compression Type Connector
for T/L O/H upto 380kV except Space Damper upto 230kV
with the following conditions: -All tests shall be carried out
in presence of (3) SEC engineers. -(10) years warranty
Total =

23 . 3

STEEL POLES, TUBULAR UP TO 230 KV

23. 3. 0

STEEL POLES, TUBULAR UP TO 230 KV


AL BABTAIN

Applicable Standards:
Saudi Arabia-RIYADH

13

20-TMSS-02

Yes

Page 109 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Energya Steel Solution (Hesham Helal El
Sewedy & Partners for Steel Industries Co.)

FACTORY LOCATION
Saudi Arabia-Rabigh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-0331/06-03032301 dated
28/06/2010, it is pre-qualified for Steel Poles, Tubular up
to 230kV as confirming to SEC specification # 20-TMSS-02.
Rev.0 with the following conditions:

All Type, Routine and Special Tests including the load


test per SEC specification # 20-TMSS-02 and all relevant
International Standards shall be conducted on the first
batch in presence of three (3) SEC Engineers and one (1)
SEC approved independent inspection agency (IIA)
Inspector and related cost pertaining to the test shall be
borne by Hesham Helal EL Sewedy & Partners for Steel
Industries Co.(Energya Steel Solutions) as confirmed by
manufacturer through letter # SEC/WK/100524 dated 24th
May 2010.

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order as
confirmed by Hesham Helal EL Sewedy & Partners for Steel
Industries Co.(Energya Steel Solutions) letter #
SEC/WK/100524 dated 24th May 2010 .

HIDADA

Saudi Arabia-JEDDAH

Yes

PETIT JEAN

FRANCE

Yes

SUMMIT MANUFACTURING

United States-PA

Yes

TECHNOPALI

ITALY

Yes

VALMONT

United States

Yes
Total =

23 . 5

WOOD POLES

23. 5. 1

WOOD POLES, ANSI CLASS HI H 3

Applicable Standards:

ATLANTIC WOOD IND.

United States-GEORGIA

Yes

CAHABA PRESSURE TREATED FOREST


PRODUCT (NORTH PACIFIC GROUP)

United States-ALABAMA

Yes

COLFAX CREOSOTING CO

United States-LOUISIANA

Yes

KOPPERS INDUSTRIES

United States-PA

Yes

STALLWORTH TIMBER

United States-ALABAMA

Yes

STELLA JONES INC.

CANADA-NEW WESTMINSTER

Yes

Page 110 of 238

METERIAL / EQUIPMENT
DESCRIPTION

SER

MANUFACTURER
TAYLOR LUMBER (NORTH PACIFIC GROUP)

23. 5. 2

24

United States-OREGON

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

Total =

Total =

Applicable Standards:

WOOD POLES, ANSI CLASS I - 4


ATLANTIC WOOD IND.

United States-GEORGIA

Yes

CAHABA PRESSURE TREATED FOREST


PRODUCT (NORTH PACIFIC GROUP)

United States-ALABAMA

Yes

COLFAX CREOSOTING CO

United States-LOUISIANA

Yes

KOPPERS INDUSTRIES

United States-PA

Yes

STALLWORTH TIMBER

United States-ALABAMA

Yes

STELLA JONES INC.

CANADA-NEW WESTMINSTER

Yes

TAYLOR LUMBER (NORTH PACIFIC GROUP)

United States-OREGON

Yes

GALVANIZED GUY WIRE (GROUNDING)

24 . 0

24. 0. 0

GALVANIZED GUY WIRE (GROUNDING)

25

FACTORY LOCATION

Applicable Standards:

FLORIDA WIRE & CABLE

United States

Yes

JOSLYN

United States

Yes

SOUTHWIRE

United States

Yes

TREFILEUROPE

FRANCE

Yes

10-TMSS-02

RACEWAYS

25 . 1

METAL ENCLOSED BUS DUCT, 4.16 13.8 KV OR 34.5 KV

25. 1. 0

METAL ENCLOSED BUS DUCT, 4.16 13.8 KV OR 34.5 KV

Applicable Standards:

ABB ( T& D)

United States-N/A

Yes

UNIBUS

United States

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

Page 111 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

25 . 2

CABLE TRAY SYSTEMS

25. 2. 0

CABLE TRAY SYSTEMS

Applicable Standards:

24-TMSS-01

3M

United States-Minnesota

Yes

AB WIRE

SWEDEN-sweden

Yes

ABAHSAIN-COPE

Saudi Arabia- DHAHRAN

Yes

AL-AMAL CO.

Saudi Arabia-RIYADH

Yes

FOR LADDERS & ACCESSORIES ALSO; 10 YEARS OF


EXTENDED WARRANTY;

ALASHHOURY INDUSTRY

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter # 11-0036/04-03032301 dated


06/06/2011, it's prequalified for Cable Trays & Cable
Ladders as conforming to SEC Specification # 24-TMSS-01,
Rev.0 with the following conditions:

Ten (10) years extended warranty from the date of


PAC of the first turnkey project in case of contract award
or date of first delivery in case of direct material supply
order. This was confirmed by Al-Ashouri Industries
through letter # 2010/4-03/0003 dated 01/08/2010.

For any new design of Cable Trays or Cable Ladders


proposed by Al-Ashouri Industries (other than the test
proven SEC designs), Type, Special, routine and Sample
test as per the SEC standards/Specification shall be
conduct on the first batch to be supplied to SEC in
presence of three (03) SEC Engineers in an SEC approved
independent test laboratory.

AL-MISBAH House for Steel Works

Saudi Arabia-Riyadh

Yes

ARABIAN INTERNATIONAL CO.

Saudi Arabia-JEDDAH

Yes

EFCOR

United States

Yes

Based on TS&SD letter 09-00509/1-03032301 dated 16th.


March 2009 for Metallic Cable Tray Systems as conforming
to SEC specifications # 24-TMSS-01, rev.0; with the
following conditions:

Ten (10) years extended warranty.

Improvement needs indicated in the plant survey


report

Page 112 of 238

SER

26

METERIAL / EQUIPMENT
DESCRIPTION

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ELECTROLINK Co. Ltd.

Saudi Arabia-Riyadh

Yes

HIDADA

Saudi Arabia-JEDDAH

Yes

MECSS - MID EAST CABLE SUPPORT


SOLUTIONS

Saudi Arabia- AL-KHOBAR

Yes

O-Z GEDNEY

United States

Yes

SAUDI ELECTRIC INDUSTRIES CO. LTD.

Saudi Arabia-JEDDAH

Yes

TOLARTOIS

FRANCE

Yes

WESCOSA

Saudi Arabia-DAMMAM

Yes

REMARKS
based on TS&SD letter 09-00524/1-03032301 dated 16th.
March 2009 for Metallic Cable Tray Systems as conforming
to SEC specifications # 24-TMSS-01, rev.0; with the
following conditions:

Eight (8) years extended warranty.

Improvement needs indicated in the plant survey


report.

Total =

15

Total =

CONDUIT FITTINGS

26 . 1

DUCT SEALING UNITS

26. 1. 0

DUCT SEALING UNITS

27

MANUFACTURER

Applicable Standards:
AMIANTIT RUBBER IND. (ARIL)

Saudi Arabia-DAMMAM

Yes

UM- AL QUWAIN RUBBER INDUSTRIES

United Arab Emirates

Yes

23-TMSS-02

SWITCHES

27 . 1

DISCONNECT SWITCH, AIR BREAK, UP TO 380 KV

27. 1. 0

DISCONNECT SWITCH, AIR BREAK, UP TO 380 KV

Applicable Standards:

ABB ( T& D)

United States-N/A

Yes

ALPHA NIDAU

SWITZERLAND

Yes

30-TMSS-01

Page 113 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid S. p .A

FACTORY LOCATION
ITALY-Venice - Noventa di Piave

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-04035-02-30504401 dated July
22, 2013, it is pre-qualified for Disconnect Switches 420kV,
4000A (S3CD, S3CDT & S3CD2T) only and Standalone
Grounding Switches (STB) 420kV, 63kA only as conforming
to National Grid SA specification # 30-TMSS-01, Rev.0,
with the following conditions:
All type/special and routine tests for Disconnect Switches
420kV, 4000A (S3CD, S3CDT & S3CD2T) only and
Standalone Grounding Switches (STB) 420kV, 63kA only
shall be conducted at in an Independent testing laboratory
on one switch before supplied to SEC system in the
presence of three (3) SEC/National Grid SA engineers &
one (1) National Grid SA approved independent inspection
agency Inspector, all the related costs for witnessing the
tests will be borne by the manufacturer. This was
confirmed by Alstom Grid S. p .A, ITALY through their
letter # 323/11/C/RP.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by Alstom Grid S. p .A,
ITALY through their letter # 136/11/CO/RP.

AREVA

FRANCE

Yes

EFACEC

PORTUGAL

Yes

HAPAM

NETHERLANDS

Yes

SUSPENDED based on TS&SD letter 10-00402-03032301


dated February 08, 2010

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

MG/EGIC

FRANCE

Yes

S&C

United States

Yes

SDCEM

FRANCE

Yes

SIEMENS

GERMANY

Yes

SOUTHERN STATES

United States

Yes

SOUTHERN STATES/ USA HAS ACQUIRED SIEMENS


SWITCH FACTORY
Total =

27 . 2

12

LV AUTO-TRANSFER SWITCH

Page 114 of 238

SER
27. 2. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

Pre-Qualified
Manufacturers
By SEC

REMARKS

Applicable Standards:

LV AUTO-TRANSFER SWITCH
ALSTOM

FRANCE

Yes

ASCO

United Arab Emirates

Yes

WESTINGHOUSE

United States

Yes

27 . 3

PAD MOUNTED SF6/OIL SWITCH, 34.5 KV

27. 3. 0

PAD MOUNTED SF6/OIL SWITCH, 34.5 KV


FRITZ DRIESHER KG

28

FACTORY LOCATION

Total =

Total =

Applicable Standards:
GERMANY

Yes

LV PANELS & ENCLOSURES

28 . 1

RELAY & CONTROL PANEL

28. 1. 0

RELAY & CONTROL PANEL

Applicable Standards:
ABB

SWEDEN

Yes

ABB/AEIL

Saudi Arabia

Yes

ACRASTYLE

United Kingdom

Yes

AEL -SIEMENS

Saudi Arabia-JEDDAH

Yes

ALFANAR ELECTRICAL SYSTEMS

Saudi Arabia-RIYADH

Yes

31-TMSS-01

Based on TS&SD letter# 09-01251-03032301 dated 03rd.


May 2009 UP TO 380KV as confirming to SEC specification
# 31-TMSS-01, rev.0 with Ten (10) years warranty from
the date of PAC of the Turnkey project in case of contract
award or date of delivery in case of direct material supply
order.

Page 115 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid Integration & Testing Facility

FACTORY LOCATION
Saudi Arabia-Alkhobar

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-04579-2-030504401, dated
30/06/2014, it is prequalified for Integration & Testing of
Relay & Control Panels confirming to National Grid SA
Material Specification 31-TMSS-01, Rev.0, with the
following conditions: Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order,
as confirmed through Alstom Grid letter No. nil, dated
03/10/2013.

AREVA

United Kingdom

Yes

CRUINKSHANK & PARTNERS LTD.

United Kingdom

Yes

EPS LTD. (GROUPE SCHNEIDER)

Saudi Arabia-RIYADH

Yes

ETA-PCS

United Arab Emirates-DUBAI

Yes

It is pre-qualified for Relay & Control Panels as conforming


to SEC specification # 31-TMSS-01, Rev.0 with the
following condition:

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

Up to 132kV only.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of delivery in case of first direct material supply order.

Koncar Elektricni Uredaji d.d

CROATIA-Dicmo

Yes

Based on S&SD letter# 14-1456-03-30504401 dated April


15, 2014, it is pre-qualified for Relay & Control Panel up to
380 kV as conforming to National Grid SA specification #
31-TMSS-01, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # nil dated March 09, 2012.

LS

KOREA, Republic of

Yes

PREVIOUSLY LG

Page 116 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
MEMF-ETA Switchgear Manufacturing Company

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-03789-03-30504401 dated
January 28, 2013. It is prequalified for Relay & Control
Panel up to 132kV as conforming to National Grid SA
specification # 31-TMSS-01, Rev.0, with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # META/12/AM dated March 23, 2011.

MOHD. AL-OJAIMI LTD.

Saudi Arabia-Riyadh

Yes

Extended warranty for 10 years.

PROTEA/AREVA T&D

FRANCE--

Yes

10 YEAR EXTENDED WARRANTY

REYROLLE LTD.

United Kingdom

Yes

SCHNEIDER H.V FACTORY

FRANCE-GRENOBLE

Yes

SIEMENS

GERMANY

Yes

System House Factory for Electric Panels (SEP)

Saudi Arabia-Riyadh

Yes

TIEPCO

Saudi Arabia-DAMMAM

Yes

VA TECH

Saudi Arabia-RIYADH

Yes

Based on TS&SD letter# 09-01500-03032301 dated May


25, 2009, 10-01055/02-03032301 dated May 03, 2010 &
S&SD Letter 12-03596-02-30504401 dated April 29, 2012.
It is prequalified for Relay & Control Panel up to 380kV as
conforming to SEC specification # 31-TMSS-01, Rev.0 with
the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated December 11, 2011.

ASSEMBLING UP TO 132KV ONLY, ENCLOSURES SHALL BE


PROCURED FROM MESCO (RIYADH)

Page 117 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
WESCOSA

FACTORY LOCATION
Saudi Arabia-DAMMAM

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD letter # 11-F02715-03032301 dated
17/09/2011, it is prequalified for Relay & Control Panels,
230kV and above as confirming to SEC specification #
31-TMSS-01, Rev.0 with the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards shall be carried out on the first
batch of Relay & Control Panels to be supplied to SEC, in
case of securing an order, in the presence of three (3) SEC
Engineers & one (1) approved Independent Inspection
Agency Inspector in an Independent Testing Laboratory.
All the related costs for witnessing the tests will be borne
by the manufacturer. This was confirmed by
WESCOSA-Dammam through letter # Nil dated
16/06/2010.
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by WESCOSA-Dammam through letter # Nil
dated 05/10/2010.
Total =

28 . 2

ANNUNCIATOR SYSTEM

28. 2. 0

ANNUNCIATOR SYSTEM

Applicable Standards:
ABB SUBSTATION AUTOMATION OY

FINLAND

Yes

AMETEK POWER INSTRUMENTS

United States

Yes

FUJIKURA VISCAS CORP

JAPAN

Yes

J-POWER SYSTEM CORP.

JAPAN

Yes

LS

KOREA, Republic of

Yes

NEXANS

SWITZERLAND

Yes

PAN ALARM

United States

Yes

PIRELLI

GERMANY-BERLIN

Yes

RONAN ENGINEERING

United Kingdom

Yes

RTK ENGINEERING LTD.

United Kingdom

Yes

SIEMENS

GERMANY

Yes

STEINER

JAPAN

Yes

23

38-TMSS-05
SACO 16D3

PREVIOUSLY LG

Page 118 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

28 . 3
28. 3

12

PARTIAL DISCHARGE MONITORING SYSTEM


Applicable Standards:

PARTIAL DISCHARGE MONITORING SYSTEM


APM TECHNOLOGIES INC

KOREA, Republic of-Seoul

Yes

Based on S&SD letter # 14-08866-2-30504401 dated


December 11, 2014, it is pre-qualified for Partial Discharge
Monitoring System (PDMS) APM5000 & APM2000
(Portable) as conforming to National Grid SA specification
# 38-TMSS-07, Rev.0, with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil, dated May 12, 2014.
Total =

29

ARRESTER, SURGE OR LIGHTNING

29 . 1

SURGE ARRESTERS, STATION CLASS UP TO 380 KV

29. 1. 0

SURGE ARRESTERS, STATION CLASS UP TO 380 KV

Applicable Standards:

35-TMSS-01

ABB

SWEDEN

Yes

ABB HV TECHNOLOGIES

SWITZERLAND

Yes

AREVA

FRANCE

Yes

BOWTHORPE

United Kingdom

Yes

COOPER (MCGRAW-ED)

United States

Yes

ELPRO INTL. LTD

INDIA

Yes

Upto 132 kV Only - Complete Type, Routine / Acceptance


tests for first order & 10 Years Warranty from the date of
PAC is required.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 119 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Hubbell Power Systems, Inc.

United States-Columbia

Yes

JAPAN AE POWER SYSTEMS CORP.

JAPAN

Yes

MITSUBISHI

JAPAN--

Yes

SIEMENS

GERMANY

Yes

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

TRIDELTA

GERMANY

Yes

REMARKS
Previously OHIO BRASS [The name has been changed
based on S&SD/P&SFD letter# 14-07802-30504401 dated
October 22, 2014 and based on Hubbell Power System
Grid Letter # Nil dated October 06, 2014]

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Total =

30

14

CIRCUIT BREAKER

30 . 1

DEADTANK SF6 BREAKER

30. 1. 1

DEADTANK SF6 BREAKERS, 69 KV

Applicable Standards:

37-TMSS-01

ABB ( T& D)

United States-N/A

Yes

AREVA

United States-CHARLEROI

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

GE-HITACHI HVB

United States-GEORGIA

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Page 120 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-2202-01-30504401 dated July
24, 2012, it is pre-qualified for Dead Tank Circuit Breaker
type 3AP1 DT 72.5KV & 145KV as conforming to National
Grid SA Specification # 37-TMSS-01, Rev.0 with the
following conditions:
CB type 3AP1 DT 72.5KV & 145KV is not capable for
Reactor and Capacitor bank back to back switching as
confirmed by Siemens through their letter# E T HP CB B
SL/MTH dated April 27, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed by Siemens through their letter# E T HP CB B
SL/MTH, dated December 18, 2012.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

30. 1. 2

Applicable Standards:

DEADTANK SF6 BREAKERS,110 - 132 KV


ABB

SWITZERLAND

Yes

ABB ( T& D)

United States-N/A

Yes

AREVA T&D Inc.-USA

United States-Charleroi

Yes

37-TMSS-01

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
The old remark before suspension was:
Based on TS&SD letter # 10-02708-02-03032301 dated
25/10/2010, it is pre-qualified for 145kV Dead Tank Circuit
Breaker type DT1-145FK, 40KA, 2000A as confirming to
SEC specification # 37-TMSS-01, Rev.0, with the following
condition:
Ten (10) years extended warranty for the proposed
145kV Dead Tank Circuit Breaker type DT1-145FK from the
date of PAC of the turnkey project in case of contract
award or date of delivery in case of direct material supply
order. This was confirmed in writing by AREVA T&D,
Inc-USA through letter #Nil dated 6th March 2009.

FUJI Electric Co.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Page 121 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

GE-HITACHI HVB

United States-GEORGIA

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

SIEMENS

GERMANY-Berlin

Yes

Based on S&SD Letter 12-2202-01-30504401 dated July


24, 2012, it is pre-qualified for Dead Tank Circuit Breaker
type 3AP1 DT 72.5KV & 145KV as conforming to National
Grid SA Specification # 37-TMSS-01, Rev.0 with the
following conditions:
CB type 3AP1 DT 72.5KV & 145KV is not capable for
Reactor and Capacitor bank back to back switching as
confirmed by Siemens through their letter# E T HP CB B
SL/MTH dated April 27, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed by Siemens through their letter# E T HP CB B
SL/MTH dated December 18, 2012.

SIEMENS

United States

Yes

CB type 3AP1 DT 72.5KV & 145KV is not capable for


Reactor and Capacitor bank back to back switching as
confirmed by Siemens through their letter# E T HP CB B
SL/MTH dated April 27, 2012.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.
Total =

30. 1. 3

Applicable Standards:

DEADTANK SF6 BREAKERS, 230 KV


ABB ( T& D)

United States-N/A

Yes

AREVA

United States-CHARLEROI

Yes

10

37-TMSS-01

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
13-01705-30504401 dated March 23, 2013.
The old remark before suspension was:
Type DT1-245 F3; 10 years of extended warranty;
di-electric test, riv test, continuous current temperature
rise test @ 2500 A, 60Hz is to be carried out in the first
batch in the presence of 3 SEC engineers and 1 IIA
inspector.

Page 122 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

30 . 2

SF6, LIVE TANK

30. 2. 1

LIVE TANK, 69 KV SF6 BREAKER

30. 2. 2

30. 2. 3

MANUFACTURER

FACTORY LOCATION

REMARKS

FUJI Electric Co.

JAPAN--

Yes

GE-HITACHI HVB

United States-GEORGIA

Yes

HITACHI Ltd.

JAPAN--

Yes

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

MITSUBISHI

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

TOSHIBA CORPORATION, T&D

JAPAN--

Yes

ORIGINALLY TMT&D CORP. & DISSOLVED DURING APRIL


2005.

Applicable Standards:
ABB

SWEDEN

Yes

ABB

SWITZERLAND

Yes

ABB SWITCHGEAR AB

SWEDEN-LUDUVIKA

Yes

AREVA

SWITZERLAND-OBERENTFELDEN Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

SIEMENS

GERMANY

Yes

Applicable Standards:

LIVE TANK, 110 - 132 KV SF6 BREAKER

LIVE TANK, 230 KV SF6 BREAKER

Pre-Qualified
Manufacturers
By SEC

ABB

SWEDEN

Yes

AREVA

GERMANY

Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

SIEMENS

GERMANY

Yes

Applicable Standards:

Originally JAPAN AE POWER SYSTEM CORP and


subsequent change affected as per HITACHI letter #
XAE-VR-121213, dated 13-12-2012 and FUJI letter #
AT-LTR-121115-1, dated 18-12-2012.

Total =

Total =

Total =

37-TMSS-02

37-TMSS-02

37-TMSS-02

Page 123 of 238

SER

30. 2. 4

31

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ABB

SWEDEN

Yes

AREVA_FRANCE,VILLEUR BANNE

FRANCE-,VILLEUR BANNE

Yes

SIEMENS

GERMANY

Yes

REMARKS

Total =

Total =

Total =

Total =

Applicable Standards:

CIRCUIT SWITCHER, 69 230 KV


S&C

CANADA

Yes

S&C

United States

Yes

SIEMENS

GERMANY

Yes

SUPERVISING EQUIPMENT, TELEMETERING EQUIPMENT

31 . 1

LINE TRAP

31. 1. 0

LINE TRAP

31 . 2

LINE TUNER

31. 2. 0

LINE TUNER

Applicable Standards:
HAEFELY-TRENCH ELECTRIC

CANADA

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

Applicable Standards:
ABB HV TECHNOLOGIES

31 . 3

CCVT AND/OR COUPLING CAPACITOR CARRIER

31. 3. 1

CCPD/CCVT, 69KV UP TO 380 KV

SWITZERLAND

38-TMSS-01

38-TMSS-02

Yes

Applicable Standards:
ABB

SWEDEN

Yes

ABB HV TECHNOLOGIES

SWITZERLAND

Yes

38-TMSS-08,50-TMSS-02

Page 124 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated
February 19, 2012, it is pre-qualified for CVT Capacitor
Voltage Transformer up to 132 kV only as confirming to
SEC Specification # 50-TMSS-02 Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of CVT Capacitor Voltage Transformer up
to 132 kV only in an Independent Testing Laboratory in the
presence of three (3) SEC Engineers & one (1) SEC
approved Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the manufacturer. This
was confirmed by the manufacturer through their letter #
Nil dated April 28, 2011G and October 07, 2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

CANADA

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

PASSONI & VILLA

ITALY

Yes

PFIFFNER

SWITZERLAND

Yes

Limited up to 132kV only. All Type, Special, Routine tests


per SEC Standards and IEC to be performed at
KONCAR-Electrical Institute Inc. as independent and
accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

Based on TS&SD letter# 09-01105-03032301 dated 24th


June 2009, it is pre-qualified for CT & CVT rated up to
380kV as confirming to SEC specification # 50-TMSS-01,
rev.0 & # 50-TMSS-02, rev.0 respectively with the
following conditions:

All type, routine & special tests including the load test
shall be carried out on the first batch to be supplied to SEC
in securing an order in an independent testing laboratory in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.
Page 125 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

RITZ

United States

Yes

TYPE TEST REQUIRED IN FIRST SUPPLY

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO)


Total =

31 . 4

REMOTE TERMINAL UNIT (RTU)

31. 4. 0

REMOTE TERMINAL UNIT (RTU)

Applicable Standards:
ABB

GERMANY

Yes

AREVA

FRANCE

Yes

EFACEC Sistemas de Elctronica, S.A

PORTUGAL-Maia

Yes

13

38-TMSS-03
RTU-560, SPIDER 200,232 & 233

Based on TS&SD letter# 09-01819-03032301 dated 23rd


June 2009, it is prequalified for for RTU type CLP500 as
confirming to SEC specification # 38-TMSS-03, rev.0 with
the following condition:
Ten (10) years warranty from the date of PAC of the first
turnkey project in case of contract award or date of first
delivery in case of direct material supply order.

FOXBORO

AUSTRALIA

Yes

GE HARRIS

CANADA

Yes

HARRIS D20

Global Energy Technologies Ltd.

United Arab Emirates-Dubai

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications
Dept. Manager letter # 14-02646-02-30504401 dated July
17, 2014.
Earlier Condition was:
Ten (10) years extended warranty. Microsol XCell SCADA
RTU System.

HARRIS CORPORATION

United States-MELBOURNE,

Yes

HARRIS MICROPLEX 5000

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

ASSEMBLING ONLY

LSIS

KOREA, Republic of--

Yes

SEVEN (7) YEARS EXTENDED WARRANTY.

MICROSOL LTD.

Ireland-DUBLIN

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications
Dept. Manager letter # 14-02646-02-30504401 dated July
17, 2014.

SAT

AUSTRIA

Yes

SIEMENS

GERMANY

Yes

SIEMENS (LANDYS) - TELEGYR

United States-SAN JOSE, CA

Yes

VA TECH

AUSTRIA

Yes

TELEGYR 5700

Page 126 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

31 . 5

SEQUENCE OF EVENTS RECORDER

31. 5. 0

SEQUENCE OF EVENTS RECORDER

Applicable Standards:

14

38-TMSS-04

ABB

GERMANY

Yes

RTU 560

GE HARRIS

CANADA

Yes

HARRIS D20

Global Energy Technologies Ltd.

United Arab Emirates-Dubai

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications
Dept. Manager letter # 14-02646-02-30504401 dated July
17, 2014.
Earlier Condition was:
Ten (10) years extended warranty. Microsol XCell SCADA
RTU System

JAL INTERNATIONAL

Saudi Arabia-KHOBAR

Yes

SOE RECORDING SYSTEM AND INTERFACE & CONTROL


CABINET/MARSHALING PANELS

LSIS

KOREA, Republic of--

Yes

SEVEN (7) YEARS EXTENDED WARRANTY.

MICROSOL LTD.

Ireland-DUBLIN

Yes

SUSPENDED for all SEC/National Grid SA ongoing and


forthcoming projects based on Standards & Specifications
Dept. Manager letter # 14-02646-02-30504401 dated July
17, 2014.

RONAN ENGINEERING

United States-LOS ANGELES, CA

Yes

X500E/1000
Total =

31 . 6

TRANSDUCERS

31. 6. 1

FREQUENCY TRANSDUCERS

Applicable Standards:
ALSTOM

United States

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.
Total =

31. 6. 2

Applicable Standards:

TAP POSITION TRANSDUCERS


AREVA

United Kingdom

Yes

Page 127 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

31. 6. 3

Applicable Standards:

TRANSDUCERS
CEWE INSTRUMENTS AB

SWEDEN

Yes

ENERDIS

FRANCE

Yes

LSIS

KOREA, Republic of--

Yes

TILLQUIST

SWEDEN

Yes

TYCO ELECTRONICS (UK) Ltd - CROMPTON


INSTRUMENTS

United Kingdom--

Yes

SEVEN (7) YEARS EXTENDED WARRANTY.

Based on TS&SD Letters (08-F00975/01-03032301 dated


June 04, 2008), (10-F00230/01-03032301 dated February
03, 2010) & (11-F03017/01-03032301 dated October 16,
2011). Integra 1560 is prequalified for Transducers as
confirming to SEC Specification # 40-TMSS-02, Rev.0 with
the following condition:
Five (05) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order. This was confirmed by TYCO Electronic UK through
their letter # INT-SEC-06 dated January 03, 2008 and its
Amendment dated November 21, 2011.
Total =

31. 6. 4

Applicable Standards:

WATTHOURS/VARHOURS TRANSDUCERS
ISKRA MIS

SLOVENIA-KRANJ

Yes

MITSUBISHI ELECTRIC

JAPAN

Yes

SCIENTIFIC COLUMBUS

United States

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.

Total =
31. 6. 5

Applicable Standards:

VOLTAGE TRANSDUCERS
ABB (ASEA INC.)

CANADA-MONTREAL

Yes

AREVA

United Kingdom

Yes

Page 128 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ISKRA MIS

SLOVENIA-KRANJ

Yes

TRANSDATA

United States

Yes

REMARKS
ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT
EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.

Total =
31. 6. 6

Applicable Standards:

WATTS/VARS TRANSDUCERS
ABB (ASEA INC.)

CANADA-MONTREAL

Yes

AREVA

United Kingdom

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

TRANSDATA

United States

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.

Total =

31 . 7

PROTECTIVE RELAYS

31. 7. 1

TRANSMISSION LINE PROTECTIVE RELAYS 380/132/115/110kV

Applicable Standards:

Page 129 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X
0-D1A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIs+12BOs
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6X
0-D1A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Page 130 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware:
4CT+4VT+12BIs+12BOs
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B
6-D1A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P01-B1X-CB-KB-B-B6B
6-D1A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
Page 131 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 132 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom

FACTORY LOCATION
United Kingdom---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P546
Ordering Code:
P54631NH7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIs+12BOs
8CT+4VT+16BIs+16BOs
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
MiCOM P546
Ordering Code:
P54631NK7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Page 133 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware:
4CT+4VT+12BIs+12BOs
8CT+4VT+16BIs+16BOs
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 134 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE

FACTORY LOCATION
CANADA---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIS+12BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W73(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
Page 135 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
4CT+4VT+12BIS+12BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-U67-W73(*) (*) CH2
to be attenuated to fit SDH
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
Page 136 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 137 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P546 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Enclosure Protection per IEC 60259
2001) for MiCOM P546 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Codes, Built in Functions & Hardware shall be as
the following:
Ordering Code: P54631NA7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking,
Under / over Frequency 81,open conductor protection,
Second harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2
CB) controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/
67N ,49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital
Outputs, Protection data interface-1 850, Protection data
interface-2 850, IEC61850, 2 x port(PRP)
Ordering Code: P54631NL7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking,
Under / over Frequency 81,open conductor protection,
Second harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2
CB) controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/
67N ,49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT
Page 138 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital
Outputs, Protection data interface-1 1300, Protection data
interface-2 850, IEC61850, 2 x port(PRP)
Ordering Code: P54631NR7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking,
Under / over Frequency 81,open conductor protection,
Second harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2
CB) controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/
67N ,49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 32 Digital Inputs, 24Digital
Outputs, Protection data interface-1 1550, Protection data
interface-2 850, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P543 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P54331NL7M0D08M
Built in Functions: 87L(Dual Combined Slope), 21P&G
(5Zones,Quad+Mho+Bi), 67DEF with comm. Scheme,
79(2CBs OR 1CB controlled)+25, 50/51PH&GR / SEF/46,
67P/ 67N, 49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator,
Hardware: 4CT+4VT+ 12BI's+12BO's, CH-1 1300nm, CH-2
850nm, IEC61850, 2 x port(PRP)

Page 139 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Ordering Code: P54331NR7M0D08M
Built in Functions: 87L, Under current 37,Inrush Blocking,
Under / over Frequency 81,open conductor protection,
Second harmonic detection, 21P&G, 67DEF, 79 (1 CB or 2
CB) controlled + 25, SEF, 50/51PH&GR / SEF/46, 67P/
67N ,49 Thermal Overload, 27/59/59N, 50BF, 74 DC
supply supervision, 74 Trip circuit supervision, CT
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 4CT+4VT+ 12BI's+12BO's, CH-1 1550nm, CH-2
850nm, IEC61850, 2 x port(PRP)
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J
Built in Functions: 87L High Impedance, 95 CT bus wire
supervision, 50/51PH&GR / SEF/46, 67P/ 67N , SEF,49
Thermal Overload, 27/59/59N, 50BF, 74 DC supply
supervision, 74 Trip circuit supervision, CT Supervision, 60
VT Supervision, DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7Digital
Outputs, IEC61850, 2 x port(PRP)
Page 140 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Ordering Code: P14231NC7M0468J
Built in Functions: 50/51PH&GR / SEF/46, 67P/ 67N ,
SEF,49 Thermal Overload, 27/59/59N, 50BF, 74 DC supply
supervision, 74 Trip circuit supervision, CT Supervision, 60
VT Supervision, DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7Digital
Outputs, IEC61850, 2 x port(PRP)
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P841 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P84133NC7M0D08M
Built in Functions: 79 (1 CB or 2 CB) controlled + 25,
50/51PH&GR / SEF/46, 67P/ 67N , SEF,49 Thermal
Overload, 27/59/59N, 50BF, 74 DC supply supervision, 74
Trip circuit supervision, CT Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 8xCT(Ph) + 5xVT, 24 Digital Inputs, 32Digital
Outputs, IEC61850, 2 x port(PRP)

Page 141 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL 411L
Ordering code:
0411L1X6X1C7CDXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
SEL 411L
Ordering code:
0411L1X6X1C7CEXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BIS+16BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS

Page 142 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SD522
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0H+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BIS+12BOS
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
7SD522
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0J+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
Page 143 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
4CT+4VT+12BIS+12BOS
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Total =

31. 7. 2

POWER TRANSFORMER PROTECTION RELAYS 380/132/115/110kV

Applicable Standards:

Page 144 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
RED 670
Ordering code:
RET670*1.2-B30X00-A02D03E01P01-B1X-C-B-KB-B-B3B3D1A-XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
14xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Relay Type:
RET 670
Ordering code:
RET670*1.2-B40X00-A01A02D04E01P01-B1X-C-B-KB-B-B3
B3-D1A-XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
Page 145 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
14xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 146 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P 643
Ordering code:
P64332NA6M0040K
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT (Ph) + 4xCT (Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Relay Type:
MiCOM P 643
Ordering code:
P64532NA6M0040K
Built in Functions:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Page 147 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 148 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE Multilin

FACTORY LOCATION
CANADA-Markham

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
T 60
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-PXX-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
15xCT(Ph)+5xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING:
IEC 61850 2-ports
Relay Type:
T 60
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-P6T-U8N-WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Page 149 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+5xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 150 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P643 + MiCOM
P849 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Thermal Withstand per IEC
60255-1 2009, Change of Temperature per IEC
60068-2-14 2009 & Damp Heat Steady State per IEC
60068-2-78 2002) for MiCOM P643 shall be conducted in
the accredited testing laboratory witnessing by one (1)
Independent Inspection Agency (IIA) inspector and type
test report shall be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P64332QA6M0B08M + P8490NA6M0A08K
Built in Functions: 87T ( Dual Combined Slope), 87REF
(low Impedance), 87REF (High Impedance), 87/50
Instantaneous Diff, 50/51PH&GR All Windings, 67P/67N
(All Windings), 27/59/25, 81U/O, 50BF, 49T, 24, 74 DC
supply supervision, 74 Trip circuit supervision, CT Super.
(All Windings), 60 VT Supervision, DFR/SOE,
Hardware: 15xCT(Ph) + 3xCT(Gnd) + 4xVT, 32+16 Digital
Inputs, 16+16 Digital Outputs, IEC61850, 2 x port (PRP)
Ordering Code: P64332QA6M0B08M + P84930NE6M0A08K
Built in Functions: 87T ( Dual Combined Slope),
50/51PH&GR/SEF/46, 67P/67N, 49Therma l overload,
27/59/81/59N, 50BF74 DC supply supervision, CT
Supervision, 60 VT Supervision, DFR/SOE
Hardware: 9xCT(Ph) + 3xCT(G) + 4xVT , 16+64 Digital
Inputs, 16+16 Digital Outputs, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated
Page 151 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P642 + MiCOM
P849 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013..
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Functions: P64232QD6M0B08L +
P8490NA6M0A08K
Built in Functions: 87T ( Dual Combined Slope), 87REF
(low Impedance), 87REF (High Impedance), 87/50
Instantaneous Diff, 50/51PH&GR All Windings, 67P/67N
(All Windings), 27/59/25, 81U/O, 50BF, 49T, 24, 74 DC
supply supervision, 74 Trip circuit supervision, CT Super.
(All Windings), 60 VT Supervision, DFR/SOE,
Hardware: 9xCT(Ph) + 3xCT(Gnd) + 4xVT, 32+12 Digital
Inputs, 16+12 Digital Outputs, IEC61850, 2 x port (PRP)
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM 142 + MiCOM
P849 as per the following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
Page 152 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J + P84930NE6M0A08K
Built in Functions: 87 High Impedance Diff Protection, SEF,
50/51+50N/51N / 46, 49 Thermal Overload, 27/59/59N,
Breaker Failure (50BF) 74DC DC SUPPLY SUPERVISION,
CT Supervision, 67P/67N, Under / Over Frequency 81,
Under current 37, 60VT Supervision, DFR/SOE/F Locator
Hardware: 5xCT(Ph) + 3xVT 16+64 Digital Inputs, 7+16
Digital Outputs, IEC61850, 2 x port (PRP)
Ordering Code: P14231NC7M0468J
Built in Functions: 87 High Impedance Diff Protection, SEF,
50/51+50N/51N / 46, 49 Thermal Overload, 27/59/59N,
Breaker Failure (50BF) 74DC DC SUPPLY SUPERVISION,
CT Supervision, 67P/67N, Under / Over Frequency 81,
Under current 37, 60VT Supervision, DFR/SOE/F Locator
Hardware: 5xCT(Ph) + 3xVT , 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 x port (PRP)

Page 153 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL487E
Ordering code:
0487E3X648XXC2X4H624XXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
60
DFR/SOE
Hardware:
2-WINDING:
8xcontact inputs
4xcontact outputs
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
IEC 61850 2 ports

Page 154 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7UT6
Ordering code:
7UT6331-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Relay Type:
7UT6
Ordering code:
7UT6351-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
Page 155 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
12xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports

Page 156 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ZIV

FACTORY LOCATION
SPAIN-Madrid

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
IDV
Ordering code:
8IDVK4F22Z104SKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
9xCT(Ph)+2xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING
IEC 61850 2 ports
Relay Type:
IDV
Ordering code:
8IDVD4F22Z904VKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
50 BF
49T
74 DC supply supervision.
74 Lockout Coil Supervision.
CT Super (All windings)
DFR/SOE

Page 157 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware:
3-WINDING:
12xCT(Ph)+2xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Total =

31. 7. 3

Double BUS-BAR Single CB 132/115/110 kV Relays

Applicable Standards:

Page 158 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REB500 CU
Ordering code:
REB500-CU03-V76-S30-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 CU
Ordering code:
REB500-CU03-V76-S50-P0-B0-CA3-CB3
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
48 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
REB500 PU
Ordering code:
REB500-BU03-C2-A40-P0-F1-BB2-IO0-R0-OC0-BFP1-EFP1PD0-DR0-L0-T0+1MRB150073R0052
Built in Function:
50BF: stage1
50BF: stage2
Page 159 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
End fault protection with Interntrip or Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BIS+12BOS

Alstom

United Kingdom---

Yes

Relay Type:
MICOM P740 PU
Ordering code:
P74137NA6M0510K
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
50BF: stage2
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIS+8BOS
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
MICOM P740
Ordering code:
P74331NA6M0510K
Built in Function:
50BF: stage1
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BIs+12BOS
IEC 61850, 2-PORTS

Page 160 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SS52x CU
Ordering code:
7SS5220-4AB92-1CA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
24 PU connected to CU
IEC 61850, 2-PORTS
Relay Type:
7SS52x CU
Ordering code:
7SS5220-4AB92-1FA0+L0R
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BIs+8BOs
48 PU connected to CU
IEC 61850, 2-PORTS

Page 161 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Relay Type:
7SS52x PU
Ordering code:
7SS5231-5CA01-1AA1
*BO=6 with double contact
Built in Function:
87BB: Biased Current Differential high speed BBP with built
in check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
PU: 4CT+16BIs+12BOS
Total =

31. 7. 4

33kV Plain OH Feeder + UG + Incomer Relays

Applicable Standards:

Page 162 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REL 670
Ordering code:
REL670*1.2-A31X00-H07P01-B1X-AX-KB-B-B6X0-D1A-XX-X
E
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 163 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P543 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Enclosure Protection per IEC 60259
2001) for MiCOM P543 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P54331NE7M0D08M
Built in Functions: 21 P&GD / 87 L, 50/51PH&GR, 67P/
67N, 49 Thermal Overload, Phase Unbalance 46, Under
current 37, 27/59, Auto Re-closure 79, 50BF, 74 Trip
circuit supervision, In rush blocking, Under/over Frequency
81, CT Supervision, 60 VT Supervision, Open conductor
protection, second harmonic detection, sensitive earth fault
protection, DFR/SOE / Fault Locator.
Hardware: 5CT + 4VT, 16BI+14BO, IEC61850, 2 x optical
port (PRP)

Page 164 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL421
Ordering code:
04214611XC2X43224XXXX
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
15BI+23 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 165 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY-Berlin

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SA6x
Ordering code:
7SA6311-5BB92-2DM4+L0S
*with 20BI+09BO
**ONLY 67N
Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67N
49 Thermal Overload
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total =

31. 7. 5

13.8kV Plain OH Feeder + UG + Incomer Relays

Applicable Standards:

Page 166 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
FINLAND

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REF615
Ordering code:
HBFJAEAGNEA1BAA1XE
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 167 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE Multilin

FACTORY LOCATION
SPAIN--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
F650
Ordering code:
F650-NFD-F2G1-HI-6E
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 168 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
NR Electric Co. Ltd

FACTORY LOCATION
CHINA-Nanjing

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 13-07186-1-30504401 dated
December 23, 2013, it is pre-qualified for 13.8 kV Plain OH
Feeder + UG + Incomer Relays, with the following
condition:
Ten (10) years extended warranty from the date of PAC of
the first turnkey project in case of contract award and
subsequently reduced yearly in case of future project
award . This was confirmed in writing by the manufacturer
through their letter # NR-SEC-20110829-CL2 dated August
29, 2011.
Relay Type:
PCS 9611
Ordering code:
PCS-9611-A1C-1B1B3A3A2A
Built in Function:
Control & Mimic
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase unbalance 46
Under Current 37
27/59
Auto reclosure 79
50BF
Trip Circuit Supervision 74TC
Inrush Blocking
Under / over frequency 81
CT Supervision
60 (VT Fuse Supervision )
Sensitive earth element function
Second harmonic detection
DFR / SOE
Hardware:
16 BI+ 07 BO
3CT(Ph) + 1CT(GD)+3VT
IEC 61850, 2-Optical Ports PRP

Page 169 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SCHNEIDER ELECTRIC (Telemecanique)

FACTORY LOCATION
FRANCE--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
Sepam-80
Ordering code:
SEP888S84J33TNTLA
Along with Ordering Code, following optional modules
needs to be ordered..
1. MES120 (59715) #2 nos.
2. ACE850F0 interface module (59659) # 2 no.
3. ACE850 communication cable (CCA614) # 2 no.
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
14BI+6 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 170 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL-451
Ordering code:
04515611XC2X4H244XXXX
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC

Page 171 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SJ64
Ordering code:
7SJ6411-5EB92-1FG1+L0S
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
15BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total =

31. 7. 6

13.8kV and 33kV Capacitor Bank Relays

Applicable Standards:

Page 172 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REC670
Ordering code:
1MRK 002 814-AC
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BIs+24BOs
IEC 61850,2-PORTS

GE Multilin

CANADA-Markham

Yes

Relay Type:
C70
Ordering code:
C70-K03-HKH-F8N-H6D-M8V-P67-U6D-W67
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BIs+20BOs
IEC 61850,2-PORTS

Page 173 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL487V
Ordering code:
0487V0X6111XC2X4H424XXX
Built in Function:
27P
50/51 P&G
Undercurrent
50_2
59B&59N
59_2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67_2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+15BIs+23BOs
IEC 61850,2-PORTS
Total =

31. 7. 7

Tripping and Lockout Relay

Applicable Standards:

Page 174 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom

FACTORY LOCATION
United Kingdom---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MVAJ
Ordering code:
MVAJ101RA0802A
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case
Relay Type:
MVAJ
Ordering code:
MVAJ105RA0802A
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case

Page 175 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ELECTRO-SWITCH

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
LOR
Ordering code:
LOR/HR-7810F
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Relay Type:
LOR
Ordering code:
LOR/SR-7868FD
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)

Page 176 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10095-030504401 dated 31
December 2014, the manufacturer is prequalified for
Latched Tripping and lockout Relay type BI-16R HB,
Ordering Code: BI-16R HB 125 VDC Standard Specification:
High burden, flag indication, electrical reset, 16 Contacts
make and carry (3 sec) AC/DC 7500VA/w with max 30A,
300V. Breaking capacity DC 125w resistive, 60w inductive
(L/R = 40ms).
Latched Tripping and lockout Relay type BI-16RP HB,
ordering code: BI-16RP HB 125 VDC, Standard
Specification: High burden, flag indication, electrical and
hand reset, 16 Contacts make and carry (3 sec) AC/DC
7500VA/w with max 30A, 300V. Breaking capacity DC
125w resistive, 60w inductive (L/R = 40ms).
Unlatched Tripping Relay type RI-16R HB, ordering code:
BI-16RP HB 125 VDC op: 01000, Standard Specification:
High burden, LED indication, Self-reset, 16 Contacts make
and carry (3 sec) AC/DC 7500VA/w with max 30A, 300V.
make and carry continuous AC/DC 1250 VA/w with max of
5A, 300V. DC 80w resistive, 40w inductive (L/R = 40ms).
with the following condition:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award and
subsequently reduced yearly (in case of future project
award) . and from the date of first delivery in case of direct
material supply order. This was confirmed in writing by the
manufacturer through their letter SEC030214_Annex
dated February 03, 2014.

Page 177 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
TR
Ordering code:
TR241-7PG1524-1JC60-1AF0
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case

Relay Type:
TR
Ordering code:
TR212-7PG1521-2JC60-1AF0
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC: 7500VA/W with Max of
30A,300V
(Make & Carry (continuous))AC/DC: 1250VA/W with Max
of 5A,300V
(Break) AC/DC: 1250VA/W with MAX of 5A,300V,DC 80w
Resistive,40w Inductive (L/R=0.04sec)
Note-Withdrawable from Case
Page 178 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Total =

31. 7. 8

Applicable Standards:

Short Cable - all voltage levels


ABB

SWEDEN

Yes

Relay Type:
RED670
Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-KB-B-B6X0-D1AX-A
AXXXX
-XE
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT+6VT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 850nm, CH-2 850nm (up to 3km)
IEC 61850 -2 Ports
Relay Type:
RED670
Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-KB-B-B6X0-D1AX-B
BXXXX
-XE
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT+6VT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1310nm, CH-2 1310nm (up to 80km)
IEC 61850 -2 Ports

Page 179 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MiCOM P543
Ordering code:
P54331NA7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs 16 Inputs
Binary Outputs 14
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
MiCOM P543
Ordering code:
P54331NC7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs 16 Inputs
Binary Outputs 14
CH-1 1300nm, CH-2 1300nm (up to 50km)
IEC 61850 -2 Ports

Page 180 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
GE

FACTORY LOCATION
CANADA---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W77
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
L90
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-W2B
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports

Page 181 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P543 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Enclosure Protection per IEC 60259
2001) for MiCOM P543 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P54331NA7M0C08M
Built in Functions: Cable Diff. Protection, Breaker Failure
(50BF), DC supply supervision, 50/51 + 50N/51N, Current
Circuit Supervision,.
Hardware: 5 Analog Inputs CT, 4 Analog input VT, 16
Binary Inputs-14 outputs, CH-1 820nm, CH-2 820nm (up
to 1KM), IEC61850, 2 x port (PRP),
Ordering Code: P54331NC7M0C08M
Built in Functions: Cable Diff. Protection, Breaker Failure
(50BF), DC supply supervision, 50/51 + 50N/51N, Current
Circuit Supervision.
Hardware: 5 Analog Inputs CT, 4 Analog input VT, 16
Binary inputs-14 outputs, CH-1 1300nm ,CH-2 1300nm (up
to 50KM), IEC61850, 2 x port (PRP),
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
Page 182 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J
Built in Functions: High Impedance Diff Protection, Internal
CT Bus-wire Supervision (95) , Breaker Failure (50BF), DC
Supply Supervision, 50/51+50N/51N, Current Circuit
Supervision
Hardware: 5CT + 3 VT, 16 BI, 7 BO, IEC61850, (? 300m
and GIB), 2 x port IEC61850 (PRP)

Page 183 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL

FACTORY LOCATION
United States

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
SEL411L
Ordering code:
0411L1X6X1C7CCXH5C424XX (2KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Relay Type:
SEL411L
Ordering code:
0411L1X6X1C7DDXH5C424XX (24KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports

Page 184 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens

FACTORY LOCATION
GERMANY---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SD52
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0A+N0A
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1.5km)
IEC 61850 -2 Ports
Relay Type:
7SD52
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0G+N0G
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to 24km)
IEC 61850 -2 Ports
Total =

31. 7. 9

High Impedance BBP for all levels

Applicable Standards:

Page 185 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB

FACTORY LOCATION
SWEDEN---

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
REC670
Ordering code:
REC670*1.2-A30X00-A02C31P02-B1-AA-KB-B-B6X0-D1A-X
XX-XE
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+6U
24BO
16BI
IEC 61850,2-Optical Ports (PRP)
Relay Type:
REB650
Ordering code:
1MRK006520-AD
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+4U
27BO
18BI
IEC 61850,2-Optical Ports (PRP)

Page 186 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alstom Grid

FACTORY LOCATION
United Kingdom-Stafford

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
MCAG
Ordering code:
MCAG34VCD*****A
Built in Function:
87 3-Phase High Z Differential (Current Base)
External CT Bus Wire Supervision
External stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
3 CT Inputs
2 Output Contacts
Relay Type:
MCAG
Ordering code:
MCAG14SSD**** *A
Built in Function:
87 3-Phase High Z Differential
(Current Base)
External CT Bus Wire Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 CT Phase Inputs
2 Output Contacts
Relay Type:
MFAC
Ordering code:
MFAC34V1B*0001A
Built in Function:
87 3-Phase High Z Differential
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Page 187 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
Hardware:
3 elements / phases voltage based
2 Output Contacts
Relay Type:
MFAC
Ordering code:
MFACI4S1B*0001A
Built in Function:
87 3-Phase High Z Differential.
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 elements / phases voltage based
4 Output Contacts

Page 188 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NH7M0468J
Built in Functions: 87 3-Phase High Z Differential, 50/51N,
CT Bus-wire Supervision (95), TCS : Trip Circuit
Supervision, 74 DC supply supervision, External stabilizing
resistor, External Metrosil Resistor, External CT shorting
Hardware: 5CT + 3 VT, 16 BI, 5CT Input+3 VT input, 8 BI,
11 BO, IEC61850, 2 optical ports (PRP)

Page 189 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
7SJ64
Ordering code:
7SJ6411-5EB92-1FE0+L0S
Built in Function:
87 3-Phase High Z Differential
(based on current)50/51N
Internal CT Bus Wire Supervision
(based on current )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
4 CT Inputs
13BO
15BI
IEC 61850, 2-Optical Ports (PRP)
Total =

31. 7. 10

Applicable Standards:

Auxiliary Relays
ABB

SWEDEN---

Yes

Relay Type:
RXMVB2
Ordering code:
RK 251 204-AP (125V DC)
RK 251 204-AN (110v DC)
Built in Function:
CT Shorting
Hardware:

Alstom

United Kingdom---

Yes

Relay Type:
MVTP31
Ordering code:
MVTP31V1CB0751E
Built in Function:
CT Supervision
Hardware:

Page 190 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-10095-030504401 dated 31
December 2014, the manufacturer is prequalified for
Relay type VDF- 10, ordering code VDF- 10 125 VDC,
built-in function: Trip circuit supervision - single phase, LED
indication and two contacts.
Relay type VDJ- 30, ordering code VDJ- 30 125 VDC,
built-in functions: Trip circuit supervision - three phase,
LED indication and two contacts.
Relay type RTU-4, ordering code RTU-4 125 VDC, built-in
functions: Auxiliary supply supervision, Self-Reset, LED
indication and (4) contacts.
Relay type RJ-8, ordering code RJ-8 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (8)
contacts.
Relay type RF-4, ordering code RF-4 125 VDC Op: 01101,
built-in functions: Auxiliary Control, Self-Reset and (4)
contacts.
Relay type BJ-8 RP, ordering code BJ-8 RP 125 VDC,
built-in functions: CT shorting application, flag indication,
electrical and hand reset and (8) contacts.
Relay type BF-4 RP, ordering code BF-4 RP 125 VDC,
built-in functions: CT shorting application, flag indication,
electrical and hand reset and (4) contacts.
Relay type TDJ-8, ordering code TDJ-8 125 VDC, built-in
functions: time-lag, LED indication, (8) timed contacts (10
functions,16 timing ranges from 30ms to 99 hours).
Relay type TDF-4, ordering code TDF-4 125 VDC, built-in
functions: time-lag, LED indication, (4) timed contacts (10
functions,16 timing ranges from 30ms to 99 hours).
with the following condition:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award and
subsequently reduced yearly (in case of future project
award) . and from the date of first delivery in case of direct
material supply order. This was confirmed in writing by the
manufacturer through their letter SEC030214_Annex
dated February 03, 2014.

Page 191 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIEMENS

FACTORY LOCATION
GERMANY

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Relay Type:
AR 901
Ordering code:
7PG1110-7AE10-0AF0
Built in Function:
CT Shorting
Hardware:
Total =

31. 7. 11

Bus Coupler and Bus Section 110 kV to 380 KV

Applicable Standards:

Page 192 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J
Built in Functions: 67P/67N, 50 N / 51PH&GR, SEF, 49
Thermal Overload, 27/59/59N, 50BF, 74DC DC\ circuit
supervision, 74 Trip circuit supervision, CT Supervision, VT
Supervision, Stub protection, DFR/SOE / Fault Locator
Hardware: 5CT + 3 VT, 16 BI, 7 BO, IEC61850, 2 x port
(PRP)
Total =

31. 7. 12

Line 380kV CBF

Applicable Standards:

Page 193 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J
Built in Functions: 2 CB breaker Failure, CBF reset by
Under current, CBF reset by CB status, Pole discrepancy,
50BF, 74 Trip circuit supervision,
50/51/67+50N/51N/67N+46, 27/59/59N, Fuse Fail
supervision, DFT/SOE
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 portx (PRP)
Total =

31. 7. 13

380 KV LINE REACTOR

Applicable Standards:

Page 194 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P142 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Damp Heat Cycle per IEC 60068-2-78
2002) for MiCOM P142 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P14231NC7M0468J
Built in Functions: 87 High Impedance, 50/51PH&GR /
SEF/46, 67P/ 67N, 49 Thermal Overload, 27/59/59N,
50BF, 74 DC supply supervision, 74 Trip circuit supervision,
CT Supervision, 60 VT Supervision, DFR/SOE / Fault
Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital Inputs, 7 Digital
Outputs, IEC61850, 2 x (PRP)
Total =

31. 7. 14

132-115-110 KV REACTOR BANK AND CAPACITOR BANK

Applicable Standards:

Page 195 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P643 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Thermal Withstand per IEC
60255-1 2009, Change of Temperature per IEC
60068-2-14 2009 & Damp Heat Steady State per IEC
60068-2-78 2002) for MiCOM P643 shall be conducted in
the accredited testing laboratory witnessing by one (1)
Independent Inspection Agency (IIA) inspector and type
test report shall be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P64332QA6M0B08M
Built in Functions: 87T ( Dual Combined Slope), 87REF
(low Impedance), 87REF (High Impedance), 87REF , 87/50
Instantaneous Diff, 67P/67N (All Windings), 50/51PH&GR
All Windings, , 27/59, 81U/O, 50BF, 49T, 24, 74 DC
supply supervision, 74 Trip circuit supervision, CT Super.
(All Windings), 60 VT Supervision, DFR/SOE,
Hardware: 9xCT(Ph) + 3xCT(Gnd) + 4xVT, 16 Digital
Inputs, 16 Digital Outputs, IEC61850, 2 x port (PRP)
Total =

31. 7. 15

13.8 KV CONSUMER FEEDER

Applicable Standards:

Page 196 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric

FACTORY LOCATION
United Kingdom-Stone

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-040883-2-30504401 dated
June 12, 2014, M/s Schneider Electric from United
Kingdom stone is prequalified for MiCOM P543 as per the
following conditions:
Type tests shall be carried out on the MiCOM P40 relays
as per new IEC 61850-10 (2012-12) edition 2 in the
approved Independent Testing laboratory witnessing by
three (3) National Grid SA engineers and one (1) approved
Independent Agency Inspector (IIA). All costs of
witnessing the tests shall be borne by the manufacturer as
per their confirmation through letter # Nil dated October
23, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed by the manufacturer through
their letter # Nil dated June 25, 2013.
The following type tests (Change of Temperature per IEC
60068-2-14 2009, Damp Heat Steady State per IEC
60068-2-78 2002 & Enclosure Protection per IEC 60259
2001) for MiCOM P543 shall be conducted in the accredited
testing laboratory witnessing by one (1) Independent
Inspection Agency (IIA) inspector and type test report shall
be submitted within July 2014.
Ordering Code, Built in Functions & Hardware shall be as
the following:
Ordering Code: P54331NE7M0C08M
Built in Functions: Open Conductor , Protection for primary
cables, Second harmonic detection, under/ over frequency,
In rush blocking, Under & Over Frequency 81, 87L, 21
P&G, 67DEF, 79 + 25 (1CB), ,50/51 P&G + 46, SEF,
67P/67N, 49 Thermal Overload, 27/59/59N, 50 BF, 74 Trip
circuit supervision, 74DC DC circuit supervision, CT
Supervision, 60 VT Supervision, DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 4xVT, 16 Digital Inputs, 14
Digital Outputs, Protection data interface-1 1300,
Protection data interface-2 1300, IEC61850, 2 x optical
port(fiber) (PRP)
Total =

31 . 8

TERMINAL BLOCK

Page 197 of 238

SER
31. 8. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

TERMINAL BLOCK
Connectwell industries Pvt. Ltd.

INDIA-Dombivli

Yes

REMARKS

31-TMSS-06
Based on S&SD letter# 13-07512-030504401 dated
December 09, 2013, it is pre-qualified for terminal blocks
as conforming to National Grid SA specification #
31-TMSS-06, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer
Connectwell industries Pvt. Ltd., India through their letter
# Nil dated November 27, 2012.

ENTRELEC

FRANCE

Yes

PHOENIX

GERMANY

Yes

WEIDMULLER

GERMANY

Yes

Wieland Electric GmbH

GERMANY-Bamberg

Yes

Based on S&SD letter# 13-05908-30504401 dated


December 04, 2013, it is pre-qualified for terminal blocks
as conforming to National Grid SA specification #
31-TMSS-06, Rev.0 with the following condition:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer Wieland
Electric GmbH, Germany-Bamberg through their letter #
Bamberg dated July 20, 2012.

31 . 9

FAULT RECORDERS

31. 9. 0

FAULT RECORDERS

Total =

Total =

Applicable Standards:
AMETEK (ROCHESTER)

United States

Yes

QUALITROL HATHAWAY

NORTHERN IRELAND

Yes

31 . 10

DYNAMIC SYSTEM MONITORING EQUIPMENTS

31. 10. 0

DYNAMIC SYSTEM MONITORING EQUIPMENTS

Applicable Standards:

38-TMSS-06

Page 198 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

DIgSILENT GmbH

GERMANY

Yes

POWER TECHNOLOGY INC. (PTI)

United States

Yes

QUALITROL HATHAWAY

NORTHERN IRELAND

Yes

REMARKS

Based on S&SD Letter 12-03055-01-30504401 dated


August 26, 2012, it is pre-qualified for Dynamic System
Monitoring (DSM) as conforming to SEC Specification #
38-TMSS-06, Rev.0 with the following conditions:
All Factory tests shall be carried out on the first batch of
Dynamic System Monitoring (DSM) as per 38-TMSS-06,
Rev.0 in the presence of three (3) SEC Engineers. All costs
related to the tests shall be borne by the manufacturer.
This prequalification requirement was confirmed by
Qualitrol-Hathaway, Belfast North Ireland U.K in writing
through their letter # Nil dated July 27, 2012.
Ten (10) years extended warranty in respect of defects
due to design , manufacturing, installation and
workmanship from the date of PAC of the first turnkey
project (in case of contract award) or from the date of first
delivery of direct material supply order as confirmed by
Qualitrol-Hathaway, Belfast North Ireland U.K through
their letter # Nil dated May 18, 2010.
Total =

31 . 11

SUBSTATION AUTOMATION SYSTEM

31. 11. 0

SUBSTATION AUTOMATION SYSTEM

Applicable Standards:

Page 199 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Automation Co. Ltd.

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00953-1-30504401 dated
February 27, 2014, ABB Automation Co. Ltd., Riyadh is
pre-qualified for integration and testing of SAS systems for
substations rated up to 230kV against specification #
TES-P-107.01, Rev.00 with the following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850
Edition2, and latest amendments of IEC in an accredited
laboratory in presence of three (03) SEC/National Grid SA
engineers and one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer by ABB-Riyadh
through their letter # PSN/SAS/0709/08/2013 dated July
09, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by ABB Automation Co. Ltd.,
Riyadh through their letter # PSN/SAS/0110 dated January
28, 2012.
Bay Controller Unit (BCU) shall be type
REC670*1.2-B30X00-P02-B1X-BE-KB-B-B6X0-D1AD1D1D1XXX-XE.
All the protection IEDs shall be as per section 31.7
National Grid SA list of technically acceptable
manufacturers.
Station Computer, Gateway, EWS and OWS shall be from
Advantech Taiwan.
SAS network shall be provided with SAS oriented
Industrial type Ethernet Switches per SEC/National Grid SA
approved list.
Software shall be Micro SCADA.

Page 200 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ABB Switzerland Ltd.( Global SAS Center)

FACTORY LOCATION
SWITZERLAND-Baden

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00953-1-30504401 dated
February 27, 2014, ABB Switzerland Ltd.( Global SAS
Center), Baden, Switzerland is pre-qualified for
Engineering, integration and testing of SAS systems for
substations up to 380 kV against specification #
TES-P-107.01, Rev.00 with the following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850
Edition2, and latest amendments of IEC in an accredited
laboratory in presence of three (03) SEC/National Grid SA
engineers and one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by ABB Switzerland Ltd. (
Global SAS Center), through their letter # Nil dated April
29, 2012.
Bay Controller Unit (BCU) shall be type
REC670*1.2-B30X00-P02-B1X-BE-KB-B-B6X0-D1AD1D1D1XXX-XE.
All the protection IEDs shall be as per section 31.7
National Grid SA list of technically acceptable
manufacturers.
Station Computer, Gateway, EWS and OWS shall be from
Advantech Taiwan.
SAS network shall be provided with SAS oriented
Industrial Ethernet Switches per SEC/National Grid SA
approved list.
Software shall be Micro SCADA.

Page 201 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid AG

FACTORY LOCATION
Saudi Arabia-Al-Khobar

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter# 14-00832-2-30504401 dated
February 27, 2014, ALSTOM Grid AG France Montpelier/
U.K Stafford with integration and testing facility in
Al-Khobar, KSA is pre-qualified for substations rated up to
380 kV against specification # TES-P-107.01, Rev.00 with
the following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC61850
Edition2, and latest amendments of IEC in an accredited
laboratory in presence of three (03) SEC/National Grid SA
engineers and one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This was
confirmed in writing by the manufacturer by ALSTOM Grid
AG France, U.K through their letter
SAS/TSSD/2014/WR1201-1 dated January 12, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by ALSTOM Grid AG France
Montpelier & U.K Stafford for Substation Automation
System through their letter # RN-2012-03-11SAS dated
March 4, 2012 for SAS and from ALSTOM integration
facility through their letter # SAS/
TSSD/2014/2012/WR0202-2 dated March 5, 2012.
Bay Controller Unit (BCU) type MICOM C264 from
ALSTOM U.K Stafford is with ordering code
AGC264MB116910012X-Y-Z-PRP.
All the protection IEDs shall be as per section 31.7
National Grid SA list of technically acceptable
manufacturers.
SAS software - DS Agile,
SAS network shall be provided with SAS oriented
Industrial type Ethernet Switches per SEC/National Grid SA
approved list.
SAS OI Server is provided with Advantech IPC (Taiwan),
SCADA gateway and IEC/IEC GTW is provided with
Advantech IPC(Taiwan), Workstation OI Viewer is provided
with Advantech IPC(Taiwan), EW is provided with
Advantech IPC(Taiwan).

Page 202 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Schneider Electric- France/Lattes

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on the S & SD letter# 14-00571-1-30504401 dated
April 20, 2014, Schneider Electric, Lattes, France is
prequalified for Substation Automation System (SAS) for
substations up to 380 kV with Integration and Testing of
SAS (to be performed only by Schneider Electric), at EPS
factory Riyadh K.S.A subject to the following conditions:
Type test shall be conducted on The SAS System as per
National Grid SA Specifications/Standards, IEC 61850
Edition 2, and latest amendments of IEC in an accredited
laboratory in presence of three (03) SEC/National Grid SA
engineers and one (01) National Grid SA approved
Independent Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed in writing by Schneider Electric,
through their letter # Nil dated January 05, 2013.
SAS Equipment:
Bay Controller Unit (BCU)
Type MiCOM C264 with ordering codes as follows:
1- For all bays except for Transformers (HV side):
MiCOM C264M11I69100126030000U1111N10 {96 DI + 30
DO, 4 CT (Ph) + 5 VT}
2- For Transformer Bays (HV side):
MiCOM C264M11I691001260300A0U1111N10 {96 DI + 30
DO, 4CT (Ph) + 5 VT + 8 AI}( 8 Analog Current Inputs
selectable 4-20 mA, 0-1 mA, 0-5 mA, 0-10 mA, 0-20 mA )
3- For Common BCU:
MiCOM C264L11I6910002D010000U1111N10 { 208 DI +
10 DO}
4- For ABTS/ ACCS:
MiCOM C264L11I691000250300A0U1111N10 {80 DI + 30
DO + 8 AI}
( 8 Analog Current Inputs selectable 4-20 mA, 0-1 mA, 0-5
mA, 0-10 mA, 0-20 mA )
Station Computers: Advantech (Taiwan).
Gateway: Advantech (Taiwan).
EWS: Advantech (Taiwan).
Page 203 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
OWS: Advantech (Taiwan).
Ruggedized Ethernet Switches: SAS network shall be
provided with ruggedized SAS oriented Industrial type
Ethernet Switches per SEC/National Grid SA approved list
Software: Latest version of PACiS.
Protection IEDS: From Manufacturers listed in section
31.7 of the data base of Approved Manufacturers.

Page 204 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SEL U.S.A

FACTORY LOCATION
Saudi Arabia-S.E.P - Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on the S & SD letter# 14-01257-30504401 dated 23
March 2014, Schweitzer Engineering Laboratory (SEL)
-U.S.A is prequalified for Substation Automation System
(SAS) with Integration and Testing of SAS to be performed
only by (SEL), at System House Factory for Electric Panels
(SEP) Riyadh K.S.A up to 380KV subject to the following:
1. Type Tests: The manufacturer has confirmed to perform
the required type tests in Independent Testing
laboratories- KEMA as per SEC/National Grid SA
requirements , IEC 81650 Edition 2 standards in the
presence of three (3) SEC/National Grid SA Engineers and
one (1) Independent Inspector through reference letter #
SEL/SAS/08/2013.
2. Guarantee/Warranty: The manufacturer has agreed to
give guarantee/ warranty to SEC/National Grid SA for the
proposed Substation Automation System (SAS) from SEL
U.S.A with Integration & Testing facility at SEP Riyadh
K.S.A in respect of the defects due to design,
manufacturing, installation and workmanship for a period
of ten (10) years , This was confirmed in writing by the
manufacturer through their letter ref: nil dated February
18, 2013.
3. Bay Controller Unit (BCU) type SEL 451 from SEL U.S.A
is with ordering code 04515611XC2X4H64444X1.
4. All the protection IEDs shall be as per section 31.7
National Grid SA list of technically acceptable
manufacturers.
5. Station Computer (FESC) SEL-3355, Gateway SEL -3355,
EWS: SEL-3355, OWS: SEL-3355.
6. Software: Survalent Technology EMEA from U.S.A - the
software shall comprise of Survalent packages (Scada
Manager, Scada Explorer, and Worldview Professional).
7. SAS network shall be provided with SAS oriented
Industrial type Ethernet Switches per SEC/National Grid SA
approved list.

Page 205 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Siemens - Germany/Nurnberg

FACTORY LOCATION
Saudi Arabia-Jeddah

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on the S&SD letter# 14-03345-02-30504401 dated
May 20, 2014, SIEMENS -Germany is prequalified for
Substation Automation System (SAS) with Integration and
Testing at SIEMENSJeddah K.S.A up to 380kV projects
subject to the following conditions:
Type tests shall be carried out for SAS components as
per National Grid SA requirements latest revision of IEC
61850 (edition 2) on the approved Independent Testing
laboratory witnessing by three (3) National Grid SA
engineers and one (1) approved Independent Agency
Inspector (IIA). All costs of witnessing the tests shall be
borne by the Siemens Jeddah K.S.A as per their
confirmation through letter # Nil dated April 21, 2014.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery in case of direct material
supply order as confirmed from SIEMENS -Germany & for
Integration & Testing facility at SIEMENS Jeddah K.S.A
the Siemens-Germany & Siemens Jeddah K.S.A through
their letter # Nil dated November 12, 2012.
SAS Equipment:
Bay Controller Unit (BCU) : type 6MD6 from SIEMENS
Germany is with ordering code
(6MD6631-4EB90-0AA4+L0S) shall be used.
Station Computers: Advantech (Taiwan).
Gateway: Advantech (Taiwan).
EWS: Advantech (Taiwan).
OWS: Advantech (Taiwan).
Ruggedized Ethernet Switches: SAS network shall be
provided with ruggedized SAS oriented Industrial type
Ethernet Switches per National Grid SA approved list
Software: Latest version of SICAM PAS/PAS CC/SCC.
Protection IEDS: From Manufacturers listed in section
31.7 of the data base of Approved Manufacturers.
Total =

32

METERS

32 . 1

KILOWATT HOUR METER (ENERGY METER)

32. 1. 0

KILOWATT HOUR METER (ENERGY METER)

Applicable Standards:

40-TMSS-02

Page 206 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ADVANCE ELECTRONICS CO., LTD.

Saudi Arabia-Riyadh

Yes

Based on the approval of Executive Director through


TS&SD Letter # 08-1105-03032301 dated 20/10/2008, this
Manufacturer is pre-qualified for Energy Meters Type
(ADDAD-4).

ELSTER

United States

Yes

PREVIOUSLY ABB (T &D)


Based on S&SD Letter 12-00932-1-30504401 dated March
25, 2012, it is pre-qualified for A3RAQ, A1860RALC and
A1860RAL meters as confirming to SEC Specification #
40-TMSS-02, Rev.0 with the following condition:
A3RAQ meters with configuration ZD3D44F00LD-16,
ZD3E44F00LD-16, ZD3D46000LD-16.
A1860RALC meters with configuration ZE3KM4CF5LK-EL.
A1860RAL meters with configuration ZE3KM4CF0LH-EL.
Free Supply of Meter Type A3RAQ: Five (5) Revenue
Meters Type A3RAQ shall be supplied free of cost to SEC
as confirmed through ELSTER letter # L1-ST12-001 dated
January 21, 2012.
Five (5) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through ELSTER letter # NIL dated
12-01-2012.

GEC MEASUREMENT

United Kingdom

Yes

ISKRA MIS

SLOVENIA-KRANJ

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.

Landis + Gyr AG-Zug

SWITZERLAND-Zug

Yes

Based on S&SD Letter 14-04075-30504401 dated July 01,


2014, it is pre-qualified for Revenue Meters Type E650
(ZXD) & E850 (ZXQ) conforming to National Grid SA
specifications # 40-TMSS-03, Rev.1 and 40-TMSS-02 Rev.0
with the following conditions:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed by the manufacturer through their
letter # Nil, dated January 30, 2014.
Software for both meters [(E650 (ZXD) & E850 (ZXQ)]
shall be MAP120 and MAP110 .

SIEMENS

GERMANY

Yes

Page 207 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TYCO ELECTRONICS (UK) Ltd - CROMPTON
INSTRUMENTS

FACTORY LOCATION
United Kingdom--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letters (08-F00975/01-03032301 dated
June 04, 2008), (10-F00230/01-03032301 dated February
03, 2010) & (11-F03017/01-03032301 dated October 16,
2011). Integra (1530, 1540, &1630) are prequalified for
Digital Metering Devices (NOT FOR BULK ENERGY
METERS) as confirming to SEC Specification #
40-TMSS-02, Rev.0 with the following condition:
Five (05) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order. This was confirmed by TYCO Electronic UK through
their letter # INT-SEC-06 dated January 03, 2008 and its
Amendment dated November 21, 2011.
Total =

32 . 2

AMMETER, VOLTMETER, MW, MVAR

32. 2. 0

AMMETER, VOLTMETER, MW, MVAR

Applicable Standards:
AREVA

FRANCE

Yes

CELSA

ITALY

Yes

CEWE

SWEDEN--

Yes

ENTES

TURKEY-ISTANBUL

Yes

40-TMSS-02

Based on TS&SD letter # 10-F2298/03-03032301 dated


02/10/2010, it is pre-qualified for Digital Ammeter type
(EPM-34) and Digital Voltmeter type (EVM-35) as
conforming to SEC specification # 40-TMSS-02, Rev.0 with
the following condition:

ENTES (Turkey) has agreed to give SEC a


Guarantee/Warranty on the proposed digital meters for a
period of two (02) years and eight (08) years (for
maintenance) for total of ten (10) years from the date of
PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.

ISKRA MIS

SLOVENIA-KRANJ

Yes

ACCEPTANCE SUBJECTED TO SUCCESSFUL PRODUCT


EVALUATION / ACCEPTANCE BY SEC CONCERNED END
USER DEPARTMENT FOR EACH PURCHASE ORDER /
PROJECT DURING TENDER/BIDDING STAGE.

SCHNEIDER ELECTRIC

CANADA--

Yes

DIGITAL POWER METERS TYPE ION 6200 (0.5%


ACCURACY CLASS); 10 YEARS EXTENDED WARRANTY

Page 208 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
TYCO ELECTRONICS (UK) Ltd - CROMPTON
INSTRUMENTS

FACTORY LOCATION
United Kingdom--

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letters (08-F00975/01-03032301 dated
June 04, 2008), (10-F00230/01-03032301 dated February
03, 2010) & (11-F03017/01-03032301 dated October 16,
2011). Integra (1530, 1540, &1630) are prequalified for
Digital Metering Devices as confirming to SEC Specification
# 40-TMSS-02, Rev.0 with the following condition:
Five (05) years extended warranty from the date of PAC
of the First turnkey project in case of contract award or
date of the First delivery in case of direct material supply
order. This was confirmed by TYCO Electronic UK through
their letter # INT-SEC-06 dated January 03, 2008 and its
Amendment dated November 21, 2011.
Total =

32 . 3
32. 3

AUTOMATIC METER READING (AMR) SYSTEM


AUTOMATIC METER READING (AMR) SYSTEM

Applicable Standards:

40-TMSS-03

ADVANCE ELECTRONICS CO., LTD.

Saudi Arabia-Riyadh

Yes

Based on approval of Executive Directive for TS&SD Letter


# 08-1105-03032301 dated 20/10/2008, it is pre-qualified
for Energy Meters Type (ADDAD-4) & Quality Meters Type
(SEL-734).

ALps Technologies

FRANCE-ANNECY-LE-VIEUX

Yes

Based on TS&SD letter# 09-F00181/03-03032301 dated


06th. April 2009 with (5) years warranty from the date of
PAC

Page 209 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electro Industries / GaugeTech

FACTORY LOCATION
United States-New York

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 13-00862/03-030504401 dated April
20, 2013, Electro Industries/ GaugeTech, New York, USA is
pre-qualified for Power Quality Meters type NEXUS 1500
as conforming to National Grid SA specification #
40-TMSS-03, Rev.0, with the following conditions:
Product Support: Continuous supply and product support
of Power Quality Meters type NEXUS 1500 to all
SEC/National Grid SA approved AMR Manufacturers for a
minimum period of ten (10) years shall be ensured as
confirmed through their letter # Nil dated January 01,
2012.
Product Demo: EIG Tech USA in coordination with their
Local Agent (Ideal Technical Solutions, Riyadh) shall
demonstrate the hardware and software capability and the
features of NEXUS 1500 Power Quality Meters during the
proposed Live Demo of the AMR system to be conducted
on the first order in presence of SEC/National Grid SA
Engineers as already confirmed through item # 8 of ITS
letter # L1-NG01-J13-006 dated February06, 2013.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
from the date of first delivery of direct material supply
order as confirmed by Electro Industries /Gauge Tech
-New York, USA through their letter # L1-NG01-J13-004
dated January 29, 2013.

ELSTER

United States

Yes

Based on S&SD Letter 12-00932-1-30504401 dated March


25, 2012, it is pre-qualified for A1884RALNC meters as
confirming to SEC Specification # 40-TMSS-03, Rev.0 with
the following conditions:
A1884RALNC meters with configuration
ZE3KM4C4FLP-01
[ This Meter is approved for
Revenue Meter Application only ].
Five (5) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through ELSTER letter # NIL dated
12-01-2012.

Page 210 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Ideal Technical Solutions (ITS)

FACTORY LOCATION
Saudi Arabia-Riyadh

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
AMI
Based on S&SD Letter 14-00090-1-30504401 dated
January 09, 2014, it is pre-qualified for Advance Metering
Infrastructure (AMI) systems as conforming to National
Grid SA Specification # 40-TMSS-03, Rev. 01 with the
following conditions:
- Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award) or
date of first delivery in case of direct material supply order
as confirmed through Ideal Technical Solutions (ITS), KSA,
Riyadh letter #W1-NG01-J14-001 dated January 01,2014
and Letter#L1-NG01-J14-001 dated December 03, 2013.
- System Demo: Live Demo of the AMI System will be
conducted in presence of SEC/National Grid SA Engineers
on the first system to be manufactured in SEP factory
already confirmed through Ideal Technical Solutions (ITS),
KSA, Riyadh letter #L1-NG01-J14-002, dated January
06,2014.
AMR
Based on S&SD Letter 13-00971-1-30504401 dated May
15, 2013, it is pre-qualified for AMR system as conforming
to National Grid SA Specification # 40-TMSS-03, Rev.0 with
the following conditions:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project (in case of contract award)or
date of first delivery in case of direct material supply order
as confirmed through Ideal Technical Solutions (ITS), KSA,
Riyadh letter # W1-NG01-J13-001 dated January 08, 2013
and L1-ST12-020 dated December 03, 2012.
System Demo: Live Demo of the AMR System will be
conducted in presence of SEC/National Grid SA Engineers
on the first system to be manufactured in SEP factory
already confirmed through item # 8 of letter #
L1-NG01-J13-006, dated February 06, 2013.
ITS Integration & Test Facility: as per item# 3.a of ITS
letter# L1-NG01-J13-003 dated January 26, 2013.

Page 211 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Landis + Gyr AG-Zug

FACTORY LOCATION
SWITZERLAND-Zug

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 14-04075-30504401 dated July 01,
2014, it is pre-qualified for Revenue Meters Type E650
(ZXD) & E850 (ZXQ) conforming to National Grid SA
specifications # 40-TMSS-03, Rev.1 and 40-TMSS-02 Rev.0
with the following conditions:
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order.
This was confirmed by the manufacturer through their
letter # Nil, dated January 30, 2014.
E650 (ZXD) & E850 (ZXQ) [This meters are approved for
Revenue Meter application only].
Software for both meters [(E650 (ZXD) & E850 (ZXQ)]
shall be MAP120 and MAP110 .
Total =

33

CAPACITOR

33 . 1

SHUNT CAPACITOR

33. 1. 0

SHUNT CAPACITOR

Applicable Standards:
ABB

SWEDEN

Yes

43-TMSS-01
Based on TS&SD Letter # 10-00269-03032301 dated
24/01/2010, it is pre-qualified for Shunt Capacitor Banks as
confirming to SEC specification # 43-TMSS-01, rev.0 with
the following condition:
Seven (7) years warranty from the date of PAC of the
turnkey project in case of contract award or date of
delivery in case of direct material supply order.

ALSTOM Grid Ltd.

FINLAND-Tampere

Yes

COOPER (MCGRAW-ED)

United States

Yes

Previously " Nokian Capacitors Ltd. Finland", the name


has been changed to Areva T&D Ltd. Finland based on
TS&SD/ESD Letter # 10-00145-03032301 dated January
16, 2010 and Areva T&D Ltd.-Finland Letter # Nil dated
January 04, 2010, then the name has been changed again
to ALSTOM Grid Ltd. Finland based on Dept Mgr, S&SD
E-mail dated February 26, 2012 and ALSTOM Grid Ltd.
letter # RN-2012-02-18 dated February 18, 2012.

Page 212 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

General Electric Energy-CPQP

United States-New York

Yes

Based on TS&SD fax ref.#08-F0623/01-03032301 dated


02/12/2008.
Pre-Qualified for Capacitor Bank (13.8kV through 380kV)
with this conditions:
-First batch shall be type test in an independent laboratory
in presence of (3) SEC engineers & (1) independent
inspector.
-(10) years warranty

SAMWAH CAPACITOR CO. Ltd

KOREA, Republic of-Yongin-Si,

Yes

Based on TS&SD Letter # 11-02016/01-03032301 dated


06/07/2011, it is pre-qualified for Substation Type 13.8kV
to 36kV Only Shunt Capacitor Banks as confirming to SEC
specification # 43-TMSS-01, Rev.0 with the following
condition:
Ten (10) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by SAMWAHA through letter # Nil dated
12/03/2010.

VISHAY ELECTRONICS

34

Yes

Suspended for all SEC/National Grid SA ongoing and


forthcoming projects based on VP, Engineering letter #
14-06522-30504401 dated September 03, 2014.
Total =

Total =

ELECTRONIC COMPONENTS

34 . 1

MODULAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS

34. 1. 0

MODULAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS


NEST OY/NAPS

35

CZECH REPUBLIC-BLATNA

Applicable Standards:
FINLAND

Yes

INSTRUMENT TRANFORMERS

35 . 1

33 & 34.5 KV CTS

35. 1. 0

33 & 34.5 KV CTS

Applicable Standards:
ABB ( T& D)

United States-N/A

Yes

ABB EJF

CZECH REPUBLIC

Yes

50-TMSS-01

Page 213 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated
February 19, 2012, it is pre-qualified for 33 kV & 34.5 kV
Current Transformers (CTs) as confirming to SEC
Specification # 50-TMSS-01 Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of 33 kV & 34.5 kV Current Transformers
(CTs) kV in an Independent Testing Laboratory in the
presence of three (3) SEC Engineers & one (1) SEC
approved Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the manufacturer. This
was confirmed by the manufacturer through their letter #
Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

GE

United States

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

MEMF

Saudi Arabia-RIYADH

Yes

TS&SD letter# 09-00918-03032301 dated 29 March 2009


it is prequalified for CT up to 36kV with the following
conditions:
TYPE TEST SHALL BE DONE AT AN INTL. TESTING LAB IN
PRESENCE OF 3RD PARTY INSPECTOR;
EXTENDED GUARANTEE/ WARRANTY FOR 10 YEARS
FROM PAC.

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE & BLOCK TYPE CTs UP TO 36kV.

SIEMENS

United States

Yes

STE

ITALY

Yes

RING/SPLIT CORE TYPE


Total =

35 . 2

12

69KV CTS

Page 214 of 238

SER
35. 2. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

69KV CTS
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

REMARKS

50-TMSS-01

Type test required in first supply; 10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated


February 19, 2012, it is pre-qualified for 69 kV Current
Transformers (CTs) as confirming to SEC Specification #
50-TMSS-01 Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of 69 kV Current Transformers (CTs) in
an Independent Testing Laboratory in the presence of
three (3) SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector. All costs
of which shall be borne by the manufacturer. This was
confirmed by the manufacturer through their letter # Nil
dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

Page 215 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

SIEMENS

United States

Yes

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO);


OIL TYPE
Total =

35 . 3

110 - 132 KV CTS

35. 3. 0

110 - 132 KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

19

50-TMSS-01

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

Page 216 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated
February 19, 2012, it is pre-qualified for 110 132 kV
Current Transformers (CTs) as confirming to SEC
Specification # 50-TMSS-01 Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out
on the first batch of 110 132 kV Current Transformers
(CTs) in an Independent Testing Laboratory in the
presence of three (3) SEC Engineers & one (1) SEC
approved Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the manufacturer. This
was confirmed by the manufacturer through their letter #
Nil dated April 28, 2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO);


OIL TYPE
Total =

35 . 4

230KV CTS

35. 4. 0

230KV CTS

Applicable Standards:

16

50-TMSS-01

Page 217 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

REMARKS

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

RING/SPLIT CORE TYPE

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO);


OIL TYPE
Total =

35 . 5

380KV CTS

35. 5. 0

380KV CTS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

14

50-TMSS-01

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

Page 218 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

KUHLMAN ELECTRIC CORPORATION

United States

Yes

RING/SPLIT CORE TYPE

KWK MESWANDLER

GERMANY

Yes

RING TYPE

NISSIN

JAPAN

Yes

PFIFFNER

SWITZERLAND

Yes

Based on TS&SD letter# 09-01105-03032301 dated 24th


June 2009, it is pre-qualified for CT & CVT rated up to
380kV as confirming to SEC specification # 50-TMSS-01,
rev.0 & # 50-TMSS-02, rev.0 respectively with the
following conditions:

All type, routine & special tests including the load test
shall be carried out on the first batch to be supplied to SEC
in securing an order in an independent testing laboratory in
the presence of three (3) SEC engineers & one (1)
approved independent inspection agency Inspector.

Ten (10) years warranty from the date of PAC of the


turnkey project in case of contract award or date of
delivery in case of direct material supply order.

SADTEM

FRANCE

Yes

RING/SPLIT CORE TYPE

STE

ITALY

Yes

RING/SPLIT CORE TYPE

TRENCH ITALIA

ITALY-N/A

Yes

PREVIOUSLY AS VA TECH (NOUVA MAGRINI GALILEO);


OIL TYPE
Total =

36

14

POTENTIAL TRANSFORMER

36 . 1

33 & 34.5 KV POTENTIAL TRANSFORMERS

36. 1. 0

33 & 34.5 KV POTENTIAL TRANSFORMERS

Applicable Standards:

ABB ( T& D)

United States-N/A

Yes

ABB EJF

CZECH REPUBLIC

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

50-TMSS-03

Page 219 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Electrotecnica Arteche

FACTORY LOCATION
SPAIN-Mungia

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-03192-02-30504001 dated
February 19, 2012, it is pre-qualified for 33 kV & 34.5 kV
Potential Transformers (PT) as confirming to SEC
Specification #50-TMSS-03 Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out
the complete tests in one (1) sample of the first batch of
33 kV & 34.5 kV Potential Transformers (PT) in an
Independent Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed by the
manufacturer through their letter # Nil dated April 28,
2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

GE

United States

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

MEMF

Saudi Arabia-RIYADH

Yes

Based on S&SD Letter 12-00694-030504401 dated March


03, 2012. It is prequalified for Medium Voltage Resin Cast
Indoor, Potential Transformers with the following
conditions:
This approval is restricted to Resin Cast, Indoor Potential
Transformers with accuracy class including 0.5/3P (0.5%)
rated up to 36kV. Any other accuracy class including
0.2/3P (0.2%) will be considered only after submitting
Type Test Reports (acceptable to the Company) from
Independent Laboratory as confirmed by MEMF through
Letter # NIL dated February 13, 2012.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or the
date of first delivery in case of direct material supply order.
This was confirmed in writing by the manufacturer through
their letter # Nil dated October 24, 2011.

NISSIN

JAPAN

Yes

Page 220 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

SADTEM

FRANCE

Yes

SIEMENS

GERMANY

Yes

REMARKS
BLOCK TYPE PTs UP TO 36kV.

Total =

36 . 2

69 KV POTENTIAL TRANSFORMERS

36. 2. 0

69 KV POTENTIAL TRANSFORMERS

Applicable Standards:
ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

14

50-TMSS-03

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

E. PFIFFNER

SWITZERLAND

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated


February 19, 2012, it is pre-qualified for 69 kV Potential
Transformers (PT) as confirming to SEC Specification
#50-TMSS-03 Rev.0 with the following conditions:
All Type, Routine and Special testes shall be carried out
the complete tests in one (1) sample of the first batch of
69 kV Potential Transformers (PT) in an Independent
Testing Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent Inspection
Agency (IIA) Inspector. All costs of which shall be borne
by the manufacturer. This was confirmed by the
manufacturer through their letter # Nil dated April 28,
2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

Page 221 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

REMARKS
All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

Total =

36 . 3

110 - 132 KV POTENTIAL TRANSFORMERS

36. 3. 0

110 - 132 KV POTENTIAL TRANSFORMERS

Applicable Standards:

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

11

50-TMSS-02,50-TMSS-03

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

Electrotecnica Arteche

SPAIN-Mungia

Yes

Based on S&SD Letter 12-03192-02-30504001 dated


February 19, 2012, it is pre-qualified for 110 132 kV
Potential Transformers (PT) as confirming to SEC
Specification # 50-TMSS-03 Rev.0 with the following
conditions:
All Type, Routine and Special testes shall be carried out
the complete tests in one (1) sample of the first batch of
110 132 kV Potential Transformers (PT) in an
Independent Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed by the
manufacturer through their letter # Nil dated April 28,
2011G.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Electrotecnica Arteche letter # NIL
dated January 11, 2010 G.

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

Page 222 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

KONCAR INSTRUMENT TRANSFORMERS INC.

Croatia/Hrvatska--

Yes

NISSIN

JAPAN

Yes

PFIFFNER Instrument Transformers Ltd

SWITZERLAND-Hirschthal

Yes

REMARKS

All Type, Special, Routine tests per SEC Standards and IEC
to be performed at KONCAR-Electrical Institute Inc. as
independent and accredited testing laboratory. Extended
guarantee/warrenty for 10 years.

Based on TS&SD letter # 11-01326-02-03032301 dated


04/12/2011, it is pre-qualified for Inductive Voltage
Transformers from 110kV up to 230kV as confirming to
SEC specification # 50-TMSS-03, Rev.0 with the following
conditions:

All type, special, routine and sample tests as per SEC


specifications/standards shall be carried out on the first
unit of Inductive Voltage Transformers to be supplied to
SEC in case of securing an order in the presence of three
(3) SEC Engineers & one (1) approved independent
inspection agency Inspector in an independent testing
laboratory or at the manufacturers testing laboratory. All
the related costs for witnessing the tests will be borne by
the manufacturer. This was confirmed by PFIFFNER
Instrument Transformers Ltd through letter # P/90017052011 dated 17 May 2011.

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.
This was confirmed by PFIFFNER Instrument Transformers
Ltd through letter # P/900-25112010 dated 22 March
2011.
Total =

36 . 4

230 KV POTENTIAL TRANSFORMERS

36. 4. 0

230 KV POTENTIAL TRANSFORMERS

Applicable Standards:

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

11

50-TMSS-02,50-TMSS-03

Page 223 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
ALSTOM Grid

FACTORY LOCATION
United States-Waynesboro

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Type test required in first supply;10 Years Warranty from
the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

MESWANDLER

GERMANY

Yes

NISSIN

JAPAN

Yes

PFIFFNER Instrument Transformers Ltd

SWITZERLAND-Hirschthal

Yes

Based on TS&SD letter # 11-01326-02-03032301 dated


04/12/2011, it is pre-qualified for Inductive Voltage
Transformers from 110kV up to 230kV as confirming to
SEC specification # 50-TMSS-03, Rev.0 with the following
conditions:

All type, special, routine and sample tests as per SEC


specifications/standards shall be carried out on the first
unit of Inductive Voltage Transformers to be supplied to
SEC in case of securing an order in the presence of three
(3) SEC Engineers & one (1) approved independent
inspection agency Inspector in an independent testing
laboratory or at the manufacturers testing laboratory. All
the related costs for witnessing the tests will be borne by
the manufacturer. This was confirmed by PFIFFNER
Instrument Transformers Ltd through letter # P/90017052011 dated 17 May 2011.

Ten (10) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.
This was confirmed by PFIFFNER Instrument Transformers
Ltd through letter # P/900-25112010 dated 22 March
2011.
Total =

36 . 5

380 KV POTENTIAL TRANSFORMERS

36. 5. 0

380 KV POTENTIAL TRANSFORMERS

Applicable Standards:

ABB

SWEDEN

Yes

ABB ( T& D)

United States-N/A

Yes

10

50-TMSS-02,50-TMSS-03

Page 224 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

ALSTOM (T & D) BALTEAU SA (NV)

BELGIUM

Yes

ALSTOM Grid

United States-Waynesboro

Yes

REMARKS

Type test required in first supply;10 Years Warranty from


the date of PAC is required.
Previously RITZ- United States [The name has been
changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].

AREVA

United Kingdom

Yes

HAEFELY-TRENCH ELECTRIC

SWITZERLAND

Yes

HAEFELY-TRENCH ELECTRIC

FRANCE

Yes

NISSIN

JAPAN

Yes
Total =

37

INSULATING OIL

37 . 1

MINERAL OIL FOR ELECTRICAL APPARATUS

37. 1. 1

MINERAL OIL FOR ELECTRICAL APPARATUS

Applicable Standards:

54-TMSS-01

---

Yes

CT, PT, POWER TRANSFORMER MANUFACTURERS CAN


PROCURE OIL MEETING ALL THE REQUIREMENTS OF
APPLICABLE STANDARD FROM ANY REPUTED OIL
MANUFACTURERS.

APAR INDUSTRIES LTD

INDIA-RABLE-NEW MUMBAI

Yes

Based on TS&SD letter # 11-00152-1-03032301 dated


22/01/2011, it is pre-qualified for Uninhibited Naphthenic
Mineral Insulating Oil type POWEROIL TO 1020 (60U) as
conforming to SEC specification # 54-TMSS-01, Rev.01
with the following condition:

Five (5) years extended warranty from the date of


PAC of the turnkey project in case of contract award or
date of delivery in case of direct material supply order.

CHEMTRADE/MOBIL OIL CO. LTD.

Saudi Arabia-YANBU

Yes

NYNAS

SWEDEN

Yes

PETROMIN CORPORATION (Petrolube)

Saudi Arabia-Jeddah

Yes

SAVITA

INDIA

Yes

Previously "PETROLUBE", the name has been change to


PETROMIN CORPORATION (Petrolube) - Saudi Arabia
based on PETROMIN CORPORATION letter # Nil dated
30/06/2010.

Page 225 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SHELL

FACTORY LOCATION
GERMANY-Hamburg

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
- previously Shell (France), The location has been changed
to Hamburg, Germany Based on the manufacturer email
dated 19/08/2013.
- The acceptable mineral oil type is Shell Diala Type
S2-ZU-I.

37 . 2

INSULATING OIL FOR LOW PRESSURE OIL FILLED (LPOF) CABLES

37. 2. 0

INSULATING OIL FOR LOW PRESSURE OIL FILLED (LPOF) CABLES

39

Total =

Total =

Applicable Standards:

ATOFINA CHEMICALS

United States

Yes

DIELECTRIC SYSTEM INC.

United States

Yes

FURAKAWA CABLES

JAPAN-FUJIKURA

Yes

INDOPOL

FRANCE-LAVERA

Yes

SIEMENS

GERMANY

Yes

TELECOMMUNICATION EQUIPMENT

39 . 1

FIBER OPTIC COMMUNICATION SYSTEM

39. 1. 1

SYSTEM INTEGRATION AND TESTING OF COMMUNICATION/SCADA EQUIPMENT


SIEMENS

Applicable Standards:

Saudi Arabia-JEDDAH

Yes

48-TMSS-06
Based on S&SD letter # 14-08957-02-30504401 dated 17
December 2014, the manufacturer is prequalified for
Integration (Assembly) and Testing of Communication
Equipment from Original Equipment Manufacturer (OEM)
type tested and approved by National Grid SA as
conforming to National Grid SA specification #
48-TMSS-06, Rev.0 with the following condition:
Ten (10) years extended warranty in respect of the
defects due to design, manufacturing, installation and
workmanship from the date of the Provisional Acceptance
Certificate (PAC) of the first turnkey project (in case of
contract award) and from the date of first delivery in case
of direct material supply order shall be provided as
confirmed by the manufacturer through their letter
Fe/08/14 dated October 10, 2012.
Total =

Page 226 of 238

SER
39. 1. 2

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

FIBER OPTIC COMMUNICATION TERMINAL EQUIPMENT


ABB

SWEDEN

Yes

ABB

SWITZERLAND

Yes

ALCATEL

FRANCE

Yes

REMARKS

48-TMSS-06

Based on TADD letter# 09-0576-030225, SCADA letter#


SOCW/DIV/97 and Telecomunication Dep. letter#
09-136-03040001.

Page 227 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Alcatel-Lucent-ShangHai Bell Alcatel Co.Ltd(ASB)

FACTORY LOCATION
CHINA-ShangHai

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD letter # 14-07395-30504401, dated
23/10/2014, the test facility of Alcatel Lucent in
(Bydgoszcz, Poland) is allowed to conduct Factory Routine
test and Integration testing of communication equipment
manufactured in Alcatel-Lucent Factory in Shanghai China
confirming to National Grid SA requirements.
Based on TS&SD letter #10-03519/03-03032301 dated
17/04/2011, it is pre-qualified for Fiber Optic
Communication Terminal type Optenix1660SM with the
following conditions:

The first batch of each type of Optenix 1660SM to be


supplied to SEC shall be Type/Special & Routine/Sample
tested in an independent testing laboratory in the presence
of three (3) SEC engineers & one (1) SEC approved
independent inspection agency Inspector and all cost
pertaining to the tests shall be borne by Manufacturer. This
was confirmed in writing by the Alcatel-Lucent (ASB)-China
through letter # ALU/172/SI/2010 dated 12/12/2010.

Ten (10) years extended warranty for the offered


Optenix 1660SM from the date of PAC of the first turnkey
project in case of contract award or date of first delivery in
case of direct material supply order. This was confirmed in
writing by A by the Alcatel-Lucent (ASB)-China through
letter # ALU/170/SI/2010 dated 12/12/2010.

Alcatel-lucent (ASB)-China has confirmed that after


the successful resolution of the prequalification process,
configuration as well as the drawings and details of the
Trial Link to be installed in SEC Network shall be submitted
for SEC review and approval. The places and dates of Trail
Link installation will be sent to the manufacturer.
----------------------------------------------------------------------Based on TS&SD letter # 11-03458/02-03032301 dated
03/12/2011, it's prequalified for Fiber Optics Terminal
Equipment 1511MAX Series conforming to SEC
Specification # 48-TMSS-06 Rev.0 with the following
conditions:

Type, Special, sample & routine tests shall be


conducted on the first batch of 1511MAX Series to be
supplied to SEC, in the presence of three (3) SEC
Engineers & one (1) SEC approved independent inspection
agency Inspector in an independent testing laboratory. All
the related costs for witnessing the tests will be borne by
the manufacturer. This was confirmed by Alcatel Lucent
Page 228 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS
(ASB) Shanghai China through response letter #
ALU/25/SI/2011 dated 30/01/2011 and letter # Nil dated
27/04/2011.

Ten (10) years extended warranty from the date of


PAC of the first turnkey project in case of contract award
or date of first delivery in case of direct material supply
order. This was confirmed by Alcatel Lucent (ASB)
Shanghai China through
letter # Nil dated
30/01/2011.

Alcatel-lucent (ASB)-China has confirmed that after


the successful resolution of the prequalification process,
configuration as well as the drawings and details of the
Trial Link to be installed in SEC Network shall be submitted
for SEC review and approval. The places and dates of Trail
Link installation will be sent to the manufacturer.

Amwaj Telecommunication Manufacturing Co.

Saudi Arabia-Riyadh

Yes

Based on TS&SD letter # 11-F01302/03-03032301 dated


28/05/2011, it is prequalified for Telecommunication &
Fiber Optic Passive Products (Frame, Box, Rack, etc.) with
the following conditions:
All type, special, routine and sample tests as per SEC
specifications/standards
for Telecommunication & Fiber Optic Passive Products
(Frame, Box, Rack, etc.), shall be carried out in case of
contract award or SEC direct purchase order at SEC
approved independent laboratory in presence of three (3)
SEC Engineers and one (1) SEC approved independent
inspection agency. All the related costs for witnessing of
the tests will be borne by the manufacturer. This was
confirmed by Amwaj Telecom MFG. Co. letter dated
09/06/2010.
Seven (7) years extended warranty from the date of PAC
of the turnkey project in case of contract award or date of
delivery in case of direct material supply order. This was
confirmed by Amwaj Telecom MFG. Co. letter dated
09/06/2010.

AT & T (LUCENT TECHNOLOGIES)

United States

Yes

FUJITSU

JAPAN

Yes

GE Industrial System

CANADA-Ontario

Yes

Based on TADD letter# 09-0297-030225 dated 28th March


2009; (Note: GE Industrial System, Canada has bought
only the Lentronics business from Nortel, Canada that
manufactures TN1U SHD Fiber Optic Terminal Equipment
and MUX)

Page 229 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
HUAWEI TECHNOLOGIES CO.LTD.

FACTORY LOCATION
CHINA-Shenzhen

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on TS&SD Letter # 10-F01736/02-03032301 dated
18/08/2010 & S&SD Letter # 14-06894-01-30504401
dated 22/10/2014, it is prequalified for (OSN
Series:1500,2500,3500,7500,9500 and iManager
T2000NMS) with the following conditions:
Ten (10) years extended warranty for the proposed
Communication Transmission Equipment (OSN Series
1500,2500,3500,7500,9500 and iManager T2000NMS)
from the date of PAC of the turnkey project in case of
contract award or from date of delivery in case of direct
material supply order, as already confirmed by the
manufacturer Huawei vide letter # 70917174/MRK/SEC
dated19/02/2008G.

39. 1. 3

NIPPON ELECTRIC CO. LTD.

JAPAN-TOKYO

Yes

NOKIA

FINLAND

Yes

NORTEL

CANADA

Yes

PHILIPS

HOLLAND

Yes

SIEMENS

GERMANY

Yes

TELETTRA

FRANCE

Yes

Applicable Standards:

FIBER OPTIC LOW DENSITY EQUIPMENT

39 . 8

DC POWER SYSTEMS

39. 8. 0

DC POWER SYSTEMS

ABB INFOCOM LTD.

FRANCE-TURGI

Yes

LICOM

United States

Yes

PRISM

CANADA

Yes

SIEMENS

GERMANY

Yes

Total =

15

Total =

48-TMSS-06

Applicable Standards:
EXIDE CORP.

United States-PA

Yes

HARMER & SIMMONS

United Kingdom-ESSEX

Yes

LORAIN PRODUCTS INTERNATIONAL SALES

United States-LOARIN

Yes

SAFT POWER SYSTEMS SAS

FRANCE

Yes

Previously SAFT-NIFE

Page 230 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

39 . 9

TELEPHONE EXCHANGE

39. 9. 1

PAX (TELEPHONE EXCHANGE)

39. 9. 2

MANUFACTURER

ALCATEL

FRANCE

Yes

NORTEL

CANADA

Yes

SIEMENS

GERMANY

Yes

39. 9. 5

SWEDEN

Total =

Total =

Total =

Total =

Total =

Total =

Yes

Applicable Standards:

PABXS TELEPHONE SETS, KEY SYSTEMS


CANADA

Yes

Applicable Standards:

PABXS TELEPHONE SETS, COMMUNICATION CABLES AND ACCESSORIES


ALCATEL NV

FRANCE-PARIS

Yes

AT & T

United States-NEW YORK

Yes

NORTHERN TELECOM

CANADA

Yes

PHILIPS

HOLLAND

Yes

SIEMENS

GERMANY

Yes

Applicable Standards:

CABLING ACCESSORIES
RAYCHEM

39 . 10

REMARKS

Applicable Standards:

TELEPHONE EQUIPMENT PABXS AND ACCESSORIES

MITEL CORP.

39. 9. 4

Pre-Qualified
Manufacturers
By SEC

Applicable Standards:

ERICSON

39. 9. 3

FACTORY LOCATION

United States-CA

Yes

POWER LINE CARRIER EQPT.

Page 231 of 238

SER
39. 10. 0

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Applicable Standards:

POWER LINE CARRIER EQPT.


ABB

SWEDEN

Yes

ABB INFOCOM LTD.

FRANCE-TURGI

Yes

AREVA

FRANCE

Yes

GENERAL ELECTRIC CO.

United States-LYNCHBURG,

Yes

NERA

NORWAY

Yes

SIEMENS

GERMANY

Yes
Total =

39 . 11

TELE-PROTECTION SYSTEM

39. 11. 1

TELEPROTECTION SYSTEM

39. 11. 2

Applicable Standards:
ABB

SWEDEN

Yes

AREVA

FRANCE

Yes

DIMAT

SPAIN-Barcelona

Yes

SIEMENS

GERMANY

Yes

POSITRON INDUSTRIES

VF INTERFACE EQUIPMENT

39. 12. 0

VF INTERFACE EQUIPMENT

Based on TS&SD Letters# 09-01439-2-03032301 dated 7th


July 2009 & 10-00845-1-03032301 dated April 04, 2010. It
is pre- qualified for Tele-protection Equipment type TPU-1
with the following conditions:
Five (5) years Extended Warranty.

Total =

Total =

Total =

Applicable Standards:

CABLE ISOLATION EQUIPMENT

39 . 12

CANADA-MONTREAL

Yes

Applicable Standards:
ABB INFOCOM LTD.

SWITZERLAND-TURGI

Yes

TELLABS INC.

United States-N/A

Yes

Page 232 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

39 . 13

RADIO/PAGING EQUIPMENT (MOBILE FIXED)

39. 13. 0

RADIO/PAGING EQUIPMENT (MOBILE FIXED)

39 . 14

TEST EQUIPMENT

39. 14. 0

TEST EQUIPMENT

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

Applicable Standards:

ELECTRONIA

Saudi Arabia-AL-KHOBAR

Yes

GE/ERICSON

United States-N/A

Yes

GLENAYRE

CANADA- BC

Yes

KENWOOD

United States-CALIFORNIA

Yes

MOTOROLA

United States-SCHAMBURG IL

Yes

NEC

United States

Yes

NOKIA

FINLAND

Yes

PHILIPS

United Kingdom-CAMBRIDGE

Yes
Total =

Total =

Total =

Applicable Standards:
ACTERNA

United States

Yes

ANDO ELECTRIC CO. LTD

JAPAN-TOKYO

Yes

HEWLETT PACKARD CO.

United States

Yes

IFR

United States-N/A

Yes

PHILIPS

United Kingdom-CAMBRIDGE

Yes

ROHDE & SCHWARZ

GERMANY-N/A

Yes

TREND

SPAIN

Yes

WANDEL & GOLTERMAN GMBH CO.

WEST GERMANY

Yes

39 . 15

TEST EQUIPMENT (FIBER OPTIC RELATED)

39. 15. 0

TEST EQUIPMENT (FIBER OPTIC RELATED)


ANRITSU CORPORATION

Applicable Standards:
JAPAN-TOKYO

Yes

Page 233 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

39 . 16

TEST EQUIPMENT (RADIO RELATED)

39. 16. 0

TEST EQUIPMENT (RADIO RELATED)

Yes

MARCONI

United Kingdom-N/A

Yes

39. 17. 0

TEST EQUIPMENT (RADIO/PAGING RELATED)


NEC

39 . 18

RADIO/PAGING EQUIPMENT (ACCESSORIES)

39. 18. 0

RADIO/PAGING EQUIPMENT (ACCESSORIES)

39. 19. 0

UHF RADIO

REMARKS

Applicable Standards:
United States-SOLON

TEST EQUIPMENT (RADIO/PAGING RELATED)

UHF RADIO

Pre-Qualified
Manufacturers
By SEC

BIRD

39 . 17

39 . 19

FACTORY LOCATION

Total =

Total =

Total =

Applicable Standards:
United States

Yes

Applicable Standards:

ALLEN

United States-DALLAS TEXAS

Yes

ANDREW

United States- IL

Yes

ANTENNA SPECIALIST (AS)

United States- DALLAS TEXAS

Yes

CELWAVE

United States

Yes

DECIBEL

United States-DALLAS TEXAS

Yes

FLEXWELL

United States-N/A

Yes

JAYBEAM

United Kingdom- NORTHAMPTON Yes

RADIO SPARES (RS)

United Kingdom-NORTHANTS

Yes

Applicable Standards:
ALCATEL

FRANCE

Yes

ASCOM

United Kingdom

Yes

Page 234 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
SIMOCO

39 . 20

HIGH DIGITAL SUBSCRIBER LINE (HDSL)

39. 20. 0

HIGH DIGITAL SUBSCRIBER LINE (HDSL)

40

United Kingdom

Pre-Qualified
Manufacturers
By SEC

REMARKS

Yes
Total =

Total =

Total =

Applicable Standards:

ABB

SWEDEN

Yes

NOKIA

FINLAND

Yes

NORTEL

CANADA

Yes

FIRE PROTECTION SYSTEM

40 . 1

FM 200 SYSTEM

40. 1. 1

GAS CYLINDERS & ACCCESSORIES

40. 1. 2

FACTORY LOCATION

Applicable Standards:
DUEPOINT

United States

Yes

GREAT LAKES

United States

Yes

Applicable Standards:

EQUIPMENT

Yes

Based on TS&SD Letter # 10-2425/02-03032301 dated


31/08/2010, it is pre-qualified for HFC227ea system (FM
200) as confirming to SEC specification # TES-B-106.05.

ANSUL

United States

Yes

LOCAL AGENT AL-BILAD

CHEMETRON

United States

Yes

LOCAL AGENT HEBA

FENWAL

United States

Yes

LOCAL AGENT ENERGY HOUSE

FIGGIE

United States

Yes

FIKE

United States

Yes

FIREATER

United States

Yes

HYGOOD

United States

Yes

KIDDE

United States

Yes

Page 235 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER
Minimax

FACTORY LOCATION
GERMANY-Bad Oldesloe

Pre-Qualified
Manufacturers
By SEC
Yes

REMARKS
Based on S&SD Letter 12-02704-02-30504001 dated
February 19, 2012. It is pre-qualified for Fire Protective
Signaling Panel as conforming to SEC Specification #
90-TMSS-01 Rev.0 with the following condition:
All Type, Routine and Special testes shall be carried out
on the first batch of Fire Protective Signaling Panel in an
Independent Testing Laboratory in the presence of three
(3) SEC Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of which shall
be borne by the manufacturer. This was confirmed in
writing by the manufacturer through their letter # Nil dated
January 09, 2011.
Ten (10) years extended warranty from the date of PAC
of the first turnkey project in case of contract award or
date of first delivery in case of direct material supply order
as confirmed through Minimax-Germany letter # NIL dated
January 09, 2011.

Siemens Building Technologies

40 . 2

WATER SPRAY SYSTEM

40. 2. 1

DELUGE VALVE, SPRAY NOZZLE, ALARM VALVE AND SPRINKLERS

United States-Buffalo Grove

Yes

United States

Yes

RELIABLE

United States

Yes

SPRAYSAFE

United States

Yes

VIKING

United States

Yes

WATTS

United States

Yes

CARBON DIOXIDE (CO2) SYSTEM

40. 3. 1

GAS CYLINDERS & ACCCESSORIES

Total =

11

Total =

Applicable Standards:

GRINNEL

40 . 3

Based on TS&SD Letter # 10-2425/02-03032301 dated


31/08/2010, it is pre-qualified for HFC227ea system (FM
200) as confirming to SEC specification # TES-B-106.05,
Rev.0

LOCAL AGENT AL-BILAD

LOCAL AGENT AL-BILAD

Applicable Standards:
CARDOX

United States

Yes

LOCAL AGENT HEBA

CHEMETRON

United States

Yes

LOCAL AGENT HEBA

Page 236 of 238

SER

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

United States

Yes

HYGOOD

United States

Yes

KIDDE

United States

Yes

FIRE FIGHTING WATER PUMPS

40. 4. 1

FIRE WATER PUMPS & ACCESSORIES

FOAM SYSTEM

40. 5. 1

FOAM SYSTEM & ACCESSORIES

40 . 6

FIRE EXTINGUISHER

40. 6. 1

PORTABLE / MOBILE

Pre-Qualified
Manufacturers
By SEC

FIKE

40 . 4

40 . 5

FACTORY LOCATION

REMARKS
...

LOCAL AGENT ENERGY HOUSE


Total =

Total =

Total =

Applicable Standards:

AURORA

United States

Yes

LOCAL AGENT SAUDI PUMP >= 500 GPM

FAIRBANK MORSE

United States

Yes

LOCAL AGENT SAUDI PUMP >=500GPM

FLOWAY

United States

Yes

ITT

United States

Yes

PEERLESS

United States

Yes

PETTERSON

United States

Yes

REDDY BUFFALOU

United States

Yes

WORTHINGTON

United States

Yes

LOCAL AGENT SAUDI PUMP >=500GPM

LOCAL AGENT SAUDI PUMP >=500GPM

Applicable Standards:
ANGUS

United Kingdom

Yes

CHEMGUARD

United States

Yes

LOCAL AGENT NAFISCO

NATIONAL FOAM

United States

Yes

LOCAL AGENT HEBA

Applicable Standards:
HEBA

Saudi Arabia

Yes

SFFECO

Saudi Arabia

Yes

Page 237 of 238

SER

40. 6. 2

40. 6. 3

40. 6. 4

METERIAL / EQUIPMENT
DESCRIPTION

MANUFACTURER

FACTORY LOCATION

Pre-Qualified
Manufacturers
By SEC

REMARKS

ANSUL

United States

Yes

LOCAL AGENT AL-BILAD >=5 LBS

KIDDE

United States

Yes

>=5 LBS

SENTRY

United States

Yes

LOCAL AGENT AL-BILAD >=5 LBS

ANSUL

United States

Yes

LOCAL AGENT AL-BILAD >=2 LBS

SENTRY

United States

Yes

LOCAL AGENT AL-BILAD >=2 LBS

40. 7. 1

EQUIPMENT & ACCESSORIES

Total =

Total =

Applicable Standards:

PORTABLE FIRE EXTINGUISHER, WATER TYPE

FIRE DETECTION AND ALARM SYSTEM

Total =

Applicable Standards:

PORTABLE FIRE EXTINGUISHER, DRY CHEMICAL TYPE

40 . 7

Applicable Standards:

PORTABLE FIRE EXTINGUISHER, CO2 TYPE

SENTRY

Total =

United States

Yes

LOCAL AGENT AL-BILAD >=2.5 LBS

Applicable Standards:
AUTOCALL (GRINNEL)

United States

Yes

EDWARDS

CANADA

Yes

MIRETONE

United States

Yes

NOTIFIRE

United States

Yes

LOCAL AGENT -NAFISCO

Siemens Building Technologies Fire Safety

United States-New Jersey

Yes

Originaly was PYROTRONICS from USA.


Local Agents are: Siemens Building Technologies (SBT) &
SASEEQ

SIMPLEX

United States

Yes

LOCAL AGENT NAFISCO

THORN

United Kingdom

Yes

LOCAL AGENT AL-BILAD

Total =

Page 238 of 238

You might also like