Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC00
Page 1 of 1
INDEX

SECTION WSC01: GENERAL


INTRODUCTION ......................................................................... Page 1
RULING SPAN CALCULATOR .................................................. Page 1
SAG CHARTS ............................................................................. Page 1
SAGGING CONDUCTOR ........................................................... Page 2
HORIZONTAL BLOWOUT CALCULATIONS ........................... Page 2
METHODS OF SAGGING

Page 3

SECTION WSC02: DISTRIBUTION CHARTS-STANDARD CONDUCTOR


SECTION WSC03: DISTRIBUTION CHARTS-NON-STANDARD CONDUCTOR
SECTION WSC04: UNDERBUILD CHARTS (Not issued at This Time)
SECTION WSC05: SECONDARY CHARTS - INITIAL SAG
SECTION WSC06: SECONDARY CHARTS - DESIGN AND FINAL SAG
SECTION WSC07: SERVICE CHARTS STANDARD CONTRACTOR
SECTION WSC08: SAG TEMPLATES
SAG CRITERIA ..................................................................Page 1
RULING SPAN INCREMENTS .............................................Page 1
SAG TEMPLATE SCALE .....................................................Page 1
CLEARANCE REFERENCE CURVE ....................................Page 1
MARGIN OF ERROR FOR DETERMINING CLEARANCE ......Page 1
AVAILABLE SAG CHARTS ..................................................Page 1
SECTION WSC09: PROJECT SAG DATA RECORDING WORK SHEET

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC01
Page 1 of 5
GENERAL

1. INTRODUCTION
The sag charts shown on the following pages cover the conductor sizes and ruling spans that are
normally used.
2. RULING SPAN CALCULATOR
When one span, or a series of equal spans are to be sagged, the ruling span is equal to the span
length. For a series of unequal spans, the ruling span is defined as:

RS =

S13 + S 23 + S 33 + ...S n3
S1 + S 2 + S 3 + ...S n

Where S1, S2, etc. are the individual span lengths. When these span lengths are within 10 percent
of each other, their average can be used for the ruling span.

Figure 01-1 - Ruling Span Calculations


3.

SAG CHARTS
Each of the following pages consist of an initial and final sag chart for a given conductor size
and ruling span. The purpose of these two charts is as follows:

Section WSC01
Page 2 of 5

E.C.S.
INFORMATION SECTION

GENERAL

Issued 11-01-14

SAG AND TENSION

a. Initial Sag Chart


The initial sag charts are to be used for stringing new conductors. If a conductor has been
previously used, these curves do not apply
b. Design/Final Sag Chart
The final sag charts are to be used to determine proper clearance of existing lines. It represents
the sag of a conductor at some point in time and at a specific temperature.
The design sag charts are used to determine the expected maximum sag at various loading
conditions. It is primarily used during the design stage of a line.
For each conductor size, the sag chart ruling spans are in 25 foot increments. If a particular
ruling span is between these values, the chart with the closest ruling span should be used.
Example - Actual ruling span - 210 ft., use 200 ft. chart.
4. SAGGING CONDUCTOR
When stringing conductor, it is important to sag it correctly. A conductor that is strung too loose (too
much sag) may cause clearance problems. A conductor that is strung too tight (not enough sag)
may exceed its allowable tension limits under heavy loading conditions and possibly overstressing it
and other line components, which could result in a catastrophic line failure.
5. HORIZONTAL BLOWOUT CALCULATIONS
The horizontal blowout of a conductor can be calculated using the following values:
a. The resultant of the vertical sag and the horizontal wind.
b. The angle between the resultant and the vertical sag without wind.
In each of the relevant design sag charts is a row with a 60 degree temperature with a six pound
wind. The sag values in this row are the resultant of the sag and wind forces. The value for the
blowout angle, is the angle between the vertical and the resultant for a six pound wind.

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC01
Page 3 of 5
GENERAL

6. METHODS OF SAGGING
The two most common methods for sagging conductor are sighting and time. Each of these is
described below:
a. Sighting
This method uses targets which are sighted down to determine when the conductor is sagged
properly. The targets should be attached at the conductor support points of an average length
span. This span should be near the center of the line section to be sagged. The targets should
be set so that the distance between the top of them and the top of the conductor support point is
equal to the sag given for the length of span and temperature in the proper initial sag chart. With
the conductor resting on the support point, sight across from the top of one target to the top of
the other target. Adjust the sag until the lowest point of the conductor is in line with the tops of
the targets. If the section of line to be sagged is long, ten or more spans, the sag on one of the
end spans, preferably at the pulling end, should be checked in the same manner.
b. Stop Watch Method for Sagging Conductor
In this method, a traveling wave is generated in the span by striking the conductor at one
support and the time required for the wave to make a certain number of reflected returns is
measured. This measure is best applicable to light conductors supported on pin insulators,
however, satisfactory results are obtained for conductors supported on suspension insulators.
This method proves unsatisfactory on deadend spans or spans with splices because the
reflected wave is garbled when it strikes the insulator string or splice. Also, as span length or
conductor size increases, this method becomes less accurate. A strong wind will also tend to
modify the wave and make it difficult to determine the exact time of its return.
The wire should be given an impulse close to one support (| 3 ft.) either by striking a blow or by
jerking with a rope or heavy cord and the stop watch started simultaneously. The impulse will
cause a wave to travel to the far support. At the far support, this wave will be reflected back to
the near support where it will again be reflected and so on until it dies out. At the third return of
the wave to the near support, the watch should be stopped and the time read. The sag in feet,
for the time read, can then be obtained from the following table.
Actually, it does not make any difference whether the first three returns of the wave or any other
three consecutive returns are timed. The time for three complete cycles is the same throughout
the period the conductor is in wave. The person checking the sag may therefore use any three
consecutive returns that he wishes.
To eliminate errors which occasionally occur, the checking procedure should be repeated at
least three times to obtain the final result. If, in checking the result obtained against the stringing
sag tables used on the project, there appears to be an unwarranted difference, a further check
should be made by actually measuring the span to make certain that the span length given on
the staking sheet is correct.

E.C.S.
INFORMATION SECTION

Section WCS01
Page 4 of 5
GENERAL

Issued 11-01-14

SAG AND TENSION

It is recommended that the time for the third return of the wave be used in sag measurements
and the values of sag taken directly from the table on the preceding pages. Where this is not
possible, the following formula may be used to compute the sag for any number of return
waves:

T
D = 4.025

2N

Where D = sag in feet


T = time in seconds
N = number of return waves counted

E.C.S.
INFORMATION SECTION

Issued 11-01-14

Section WSC01
Page 5 of 5

SAG AND TENSION

SAG
FT

IN

0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3

1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6

TIME
SEC

GENERAL

SAG
FT

IN

3
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
6
6
6
6
6
7

7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0

3rd wave

0.86
1.22
1.50
1.73
1.93
2.11
2.28
2.44
2.59
2.73
2.86
2.99
3.11
3.23
3.34
3.45
3.56
3.66
3.76
3.86
3.96
4.05
4.14
4.23
4.32
4.40
4.49
4.57
4.65
4.73
4.81
4.88
4.96
5.03
5.11
5.18
5.25
5.32
5.39
5.46
5.53
5.60

TIME
SEC

SAG
FT

IN

7
7
7
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
8
8
8
8
9
9
9
9
9
9
9
9
9
9
9
9
10
10
10
10
10
10
10

1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6
7
8
9
10
11
0
1
2
3
4
5
6

3rd wave

(END)

5.66
5.73
5.79
5.86
5.92
5.98
6.04
6.10
6.17
6.23
6.29
6.34
6.40
6.46
6.52
6.58
6.63
6.69
6.74
6.80
6.85
6.91
6.96
7.01
7.07
7.12
7.17
7.22
7.27
7.33
7.38
7.43
7.48
7.53
7.58
7.62
7.67
7.72
7.77
7.82
7.87
7.91

TIME
SEC
3rd wave

7.96
8.01
8.05
8.10
8.14
8.19
8.24
8.28
8.33
8.37
8.41
8.46
8.50
8.55
8.59
8.63
8.68
8.72
8.76
8.80
8.85
8.89
8.93
8.97
9.01
9.05
9.10
9.14
9.18
9.22
9.26
9.30
9.34
9.38
9.42
9.46
9.50
9.54
9.57
9.61
9.65
9.69

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 1 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


Sag and Tension Design Charts
* limiting condition

Conductor

Blowout
Angle 6 lb.
wind

Ruling
Span

degrees
1/0 ACSR

266 ACSR

477 ACSR

53.9

46.5

38.2

Maximum Design Tension @ 0 deg F,


1/2" ice, 4 lb. wind, Initial
% of Ultimate Strength

Pounds
1194
1310

100

27.2%

125

29.9%

150
175
200

32.5%
34.9%
37.2%

225

39.4%

250
275
300

41.6%
43.7%
45.7%

325

47.6%

350
100
125

49.5%
26.0%
28.3%

150

30.4%

175
200
225

32.5%
34.3%
36.1%

250

37.9%

275
300
325

39.6%
41.3%
42.8%

350

44.3%

1421
1528
1630
1728
1822
1913
2000
2085
2167
1785
1945
2094
2232
2362
2486
2609
2726
2838
2945
3047

0 deg F
No Ice, No Wind, Final
(Aeolian Vibration Limit)
% of Ultimate Strength
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%
18%

Pounds
788*
788*
788*
788*
788*
788*
788*
788*
788*
788*
788*
1238*
1238*
1238*
1238*
1238*
1238*
1238*
1238*
1238*
1238*
1238*

100
125
150

2500*
2500*
2500*

175

2500*

18%
14.4%
11.8%
9.9%
8.7%

200
225
250
275

3580
3742
3894
4000*

18%
18%
18%
17.6%

2124*
2124*
2124*
2077

300
325
350

4000*
4000*
4000*

16.3%
15.2%
14.3%

1918
1789
1687

1698
1395
1169
1028

E.C.S.
INFORMATION SECTION

Section WSC02
Page 2 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

Sag and Tension Design Charts


* limiting condition
Conductor

T2-1/0

Blowout
Angle 6 lb.
wind
degrees
48.3

Ruling
Span

38.4

0 deg F
No Ice, No Wind, Final (Aeolian
Vibration Limit)
% of Ultimate Strength Pounds
-----------

% of Ultimate Strength
26.5%

Pounds
------

------

------

150

28.1%
26.5%

2320

18%

1577*

175

28.1%

2463

18%

1577*

200

2593
2726

18%
18%

1577*

225

29.7%
31.2%

250

33%

2855

18%

1577*

275

2978
3098

18%
18%

1577*

300

34%
35%

325

37%

3213

18%

1577*

350

------

------

------

------

100

------

------

------

------

125

------

------

------

------

150

2500*

------

1134

175

15.0%
15.0%

2500*

------

1015

200

24.0%

4000*

------

2688

225

4000*

------

2435

250

24.0%
24.0%

4000*

------

2208

275

24.0%

4000*

------

2020

300

4000*

------

1870

325

24.0%
24.0%

4000*

------

1755

350

24.0%

4000*

------

1666

100
125

T2-4/0

Maximum Design Tension @ 0 deg F,


1/2" ice, 4 lb. wind. Initial

375
400
425
450
475
500
525
550
575
600

------

1577*

1577*

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 3 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 100.0 Feet

INITIAL SAG CHART


H Tens
(LBS)
Temp F F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

897

816

735

652

570

488

410

388

278

230

194

0
Ft-IN
0-2
0-2
0-3
0-3
0-4
0-5
0-5
0-6

10
Ft-IN
0-2
0-3
0-3
0-4
0-4
0-5
0-6
0-6

20
Ft-IN
0-2
0-3
0-3
0-4
0-5
0-6
0-6
0-7

30
Ft-IN
0-3
0-3
0-4
0-5
0-5
0-6
0-7
0-8

40
Ft-IN
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-9

50
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-11

60
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-9
0-11
1-0

70
Ft-IN
0-5
0-6
0-7
0-8
0-10
0-11
1-1
1-3

80
Ft-IN
0-6
0-7
0-8
0-10
1-0
1-2
1-4
1-6

90
Ft-IN
0-7
0-8
0-10
1-0
1-2
1-4
1-7
1-10

100
Ft-IN
0-8
0-10
1-0
1-2
1-5
1-7
1-10
2-2

DESIGN SAG CHART


NESC Heavy Load Zone
H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

Max Tension = 1194

1014

1193

777

331

144

99

-20
.145
Ft-IN
0-2
0-2
0-3
0-3
0-4
0-4
0-5
0-5

0
1 144
Ft-IN
0-10
1-0
1-3
1-6
1-9
2-1
2-5
2-9

32
.703
Ft-IN
0-9
0-11
1-2
1-5
1-8
1-11
2-3
2-7

60
.246
Ft-IN
0-8
0-10
1-0
1-2
1-5
1-7
1-10
2-2

120
.145
Ft-IN
0-10
1-1
1-4
1-7
1-10
2-2
2-6
2-10

212
.145
Ft-IN
1-3
1-6
1-10
2-3
2-8
3-2
3-8
4-2

FINAL SAG CHART


H Tens
(LBS)
Temp F F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

788

678

571

470

378

301

243

201

183

171

161

0
Ft-IN
0-2
0-3
0-3
0-4
0-4
0-5
0-6
0-7

10
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-6
0-7
0-8

20
Ft-IN
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-9

30
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-10
0-11

40
Ft-IN
0-4
0-5
0-6
0-7
0-9
0-10
0-0
0-1

50
Ft-IN
0-5
0-6
0-8
0-9
0-11
1-1
1-3
1-5

60
Ft-IN
0-6
0-8
0-9
0-11
1-1
1-4
1-6
1-9

70
Ft-IN
0-7
0-9
0-11
1-2
1-4
1-7
1-10
2-1

80
Ft-IN
0-8
0-10
1-0
1-3
1-6
1-9
2-0
2-3

90
Ft-IN
0-9
0-11
1-1
1-4
1-7
1-10
2-1
2-5

100
Ft-IN
0-9
0-11
1-2
1-5
1-8
1-11
2-3
2-7

E.C.S.
INFORMATION SECTION

Section WSC02
Page 4 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN


Ruling Span: 125.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0

932

853

773

692

612

533

457

387

327

277

239

0
Ft-IN
0-2
0-2
0-3
0-3
0-4
0-4
0-5
0-6
0-6
0-7
0-8

10
Ft-IN
0-2
0-3
0-3
0-4
0-4
0-5
0-5
0-6
0-7
0-8
0-9

20
Ft-IN
0-2
0-3
0-3
0-4
0-5
0-5
0-6
0-7
0-8
0-9
0-10

30
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11

40
Ft-IN
0-3
0-3
0-4
0-5
0-6
0-7
0-7
0-9
0-10
0-11
1-0

50
Ft-IN
0-3
0-4
0-5
0-5
0-6
0-7
0-9
0-10
0-11
1-0
1-2

60
Ft-IN
0-4
0-4
0-5
0-6
0-7
0-9
0-10
0-11
1-1
1-2
1-4

70
Ft-IN
0-4
0-5
0-6
0-7
0-9
0-10
1-0
1-1
1-3
1-5
1-7

80
Ft-IN
0-5
0-6
0-7
0-9
0-10
1-0
1-2
1-3
1-6
1-8
1-10

90
Ft-IN
0-6
0-7
0-8
1-10
1-0
1-2
1-4
1-6
1-9
1-11
2-2

100
Ft-IN
0-6
0-8
1-10
1-0
1-2
1-4
1-6
1-9
2-0
2-3
2-6

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 1194

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0

1010

1309

866

376

172

122

-20
.145
Ft-IN
0-2
0-2
0-3
0-3
0-4
0-4
0-5
0-5
0-6
0-7
0-7

0
1 144
Ft-IN
0-9
1-11
1-2
1-4
1-7
1-11
2-2
2-6
2-10
3-2
3-7

32
.703
Ft-IN
0-8
0-10
1-1
1-3
1-6
1-9
2-0
2-4
2-8
3-0
3-4

60
.246
Ft-IN
0-7
0-8
1-10
1-0
1-3
1-5
1-8
1-11
2-2
2-5
2-8

120
.145
Ft-IN
0-9
1-11
1-1
1-4
1-7
1-10
2-1
2-5
2-9
3-1
3-5

212
.145
Ft-IN
1-0
1-3
1-6
1-10
2-2
2-7
3-0
3-5
3-10
4-4
4-10

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0

788

681

578

482

397

327

273

233

211

200

190

0
Ft-IN
0-2
0-3
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-8
0-9

10
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11

20
Ft-IN
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1

30
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-11
1-0
1-2
1-3

40
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-10
0-11
1-1
1-3
1-4
1-6

50
Ft-IN
0-5
0-6
0-7
0-9
0-10
1-0
1-2
1-3
1-6
1-8
1-10

60
Ft-IN
0-6
0-7
0-8
0-10
1-0
1-2
1-4
1-6
1-9
2-0
2-2

70
Ft-IN
0-6
0-8
0-10
1-0
1-2
1-4
1-7
1-10
2-0
2-4
2-7

80
Ft-IN
0-7
0-9
0-11
1-1
1-3
1-6
1-9
2-0
2-3
2-6
2-10

90
Ft-IN
0-7
0-9
0-11
1-2
1-4
1-7
1-10
2-1
2-4
2-8
3-0

100
Ft-IN
0-8
0-10
1-0
1-2
1-5
1-8
1-11
2-2
2-6
2-10
3-2

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 5 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 150.0 Feet
INITIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0
190.0
200.0

967

889

811

732

653

576

502

434

374

323

282

0
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-6
0-6
0-7
0-8
0-9
0-9

10
Ft-IN
0-3
0-3
0-4
0-5
0-5
0-6
0-7
0-8
0-8
0-9
0-10

20
Ft-IN
0-3
0-4
0-4
0-5
0-6
0-7
0-7
0-8
0-9
0-10
0-11

30
Ft-IN
0-3
0-4
0-5
0-6
0-6
0-7
0-8
0-9
0-10
0-11
1-0

40
Ft-IN
0-4
0-5
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1
1-2

50
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1
1-2
1-4

60
Ft-IN
0-5
0-6
0-7
0-8
0-9
0-10
1-0
1-1
1-3
1-4
1-6

70
Ft-IN
0-6
0-7
0-8
0-9
0-10
1-0
1-1
1-3
1-5
1-7
1-9

80
Ft-IN
0-6
0-8
0-9
0-10
1-0
1-2
1-3
1-5
1-7
1-9
2-0

90
Ft-IN
0-7
0-9
0-10
1-0
1-2
1-4
1-6
1-8
1-10
2-1
2-3

100
Ft-IN
0-8
0-10
1-0
1-2
1-4
1-6
1-8
1-11
2-1
2-4
2-7

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 1421

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0
190.0
200.0

1006

1421

949

418

198

144

-20
.145
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-5
0-6
0-7
0-8
0-8
0-9

0
1 144
Ft-IN
1-1
1-3
1-6
1-9
2-0
2-4
2-7
2-11
3-4
3-8
4-1

32
.703
Ft-IN
1-0
1-2
1-5
1-7
1-10
2-2
2-5
2-9
3-1
3-5
3-9

60
.246
Ft-IN
0-9
0-11
1-1
1-3
1-6
1-8
1-11
2-2
2-5
2-8
3-0

120
.145
Ft-IN
1-11
1-2
1-4
1-7
1-10
2-1
2-5
2-8
3-0
3-4
3-8

212
.145
Ft-IN
1-4
1-7
1-10
2-2
2-6
2-10
3-3
3-8
4-1
4-7
5-1

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0
190.0
200.0

788

684

585

495

416

351

300

261

238

227

217

0
Ft-IN
0-3
0-4
0-4
0-5
0-6
0-7
0-8
0-8
0-9
0-10
1-0

10
Ft-IN
0-4
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-1

20
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1
1-2
1-3

30
Ft-IN
0-5
0-6
0-7
0-8
0-9
0-10
1-0
1-1
1-3
1-4
1-6

40
Ft-IN
0-6
0-7
0-8
0-9
0-11
1-0
1-2
1-4
1-5
1-7
1-9

50
Ft-IN
0-7
0-8
0-9
0-11
1-1
1-2
1-4
1-6
1-9
1-11
2-1

60
Ft-IN
0-8
0-9
0-11
1-1
1-3
1-5
1-7
1-9
2-0
2-3
2-6

70
Ft-IN
0-9
0-11
1-0
1-3
1-5
1-7
1-10
2-1
2-3
2-7
2-10

80
Ft-IN
0-10
1-0
1-2
1-4
1-6
1-9
2-0
2-3
2-6
2-9
3-1

90
Ft-IN
0-10
1-0
1-2
1-5
1-7
1-10
2-1
2-4
2-8
2-11
3-3

100
Ft-IN
0-11
1-1
1-3
1-5
1-8
1-11
2-2
2-6
2-9
3-1
3-5

E.C.S.
INFORMATION SECTION

Section WSC02
Page 6 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN


Ruling Span: 175.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
120.0
130.0
140.0
150.0
160.0
170.0
180.0
190.0
200.0
210.0
220.0
230.0

1002

926

848

771

694

619

547

480

419

368

324

0
Ft-IN
0-4
0-4
0-5
0-5
0-6
0-7
0-8
0-8
0-9
0-10
0-11
1-0

10
Ft-IN
0-4
0-4
0-5
0-6
0-7
0-7
0-8
0-9
0-10
0-11
1-0
1-1

20
Ft-IN
0-4
0-5
0-6
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2

30
Ft-IN
0-5
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-3

40
Ft-IN
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-4
1-5

50
Ft-IN
0-6
0-6
0-7
0-8
0-9
0-11
1-0
1-1
1-3
1-4
1-6
1-7

60
Ft-IN
0-6
0-7
0-8
0-9
0-11
1-0
1-1
1-3
1-4
1-6
1-8
1-10

70
Ft-IN
0-7
0-8
0-9
0-11
1-0
1-2
1-3
1-5
1-7
1-9
1-10
2-0

80
Ft-IN
0-8
0-9
0-11
1-0
1-2
1-3
1-5
1-7
1-9
1-11
2-2
2-4

90
Ft-IN
0-9
0-11
1-0
1-2
1-4
1-6
1-8
1-10
2-0
2-3
2-5
2-8

100
Ft-IN
0-10
1-0
1-2
1-4
1-6
1-8
1-10
2-1
2-3
2-6
2-9
3-0

DESIGN SAG CHART


NESC Heavy Load Zone
Max Tension = 1528
Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final
H Tens
1002
1527
1027
456
223
166
(LBS)
Temp -> F> -20
0
32
60
120
212
Wt lb/f>
.145
1 144
.703
.246
.145
.145
SAG SPAN Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
120.0
0-4
1-5
1-3
1-0
1-3
1-7
130.0
0-4
1-7
1-6
1-2
1-5
1-11
140.0
0-5
1-11
1-9
1-4
1-8
2-2
150.0
0-5
2-2
2-0
1-7
1-10
2-6
160.0
0-6
2-5
2-3
1-9
2-1
2-10
170.0
0-7
2-9
2-6
2-0
2-5
3-2
180.0
0-8
3-1
2-10
2-3
2-8
3-7
190.0
0-8
3-5
3-2
2-6
3-0
4-0
200.0
0-9
3-9
3-6
2-9
3-3
4-5
210.0
0-10
4-2
3-10
3-0
3-7
4-10
220.0
0-11
4-7
4-2
3-4
4-0
5-4
230.0
1-0
5-0
4-7
3-7
4-4
5-10
FINAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
120.0
130.0
140.0
150.0
160.0
170.0
180.0
190.0
200.0
210.0
220.0
230.0

788

688

593

508

434

374

325

288

264

253

242

0
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-8
0-9
0-10
1-0
1-1
1-2
1-3

10
Ft-IN
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-4
1-5

20
Ft-IN
0-6
0-7
0-8
0-9
0-10
0-11
1-0
1-2
1-3
1-5
1-6
1-8

30
Ft-IN
0-7
0-8
0-9
0-10
0-11
1-1
1-2
1-4
1-6
1-7
1-9
1-11

40
Ft-IN
0-8
0-9
0-10
1-0
1-1
1-3
1-5
1-7
1-9
1-11
2-1
2-3

50
Ft-IN
0-9
0-10
1-0
1-2
1-3
1-5
1-7
1-10
2-0
2-2
2-5
2-7

60
Ft-IN
0-10
1-0
1-2
1-4
1-6
1-8
1-10
2-1
2-3
2-6
2-9
3-0

70
Ft-IN
0-11
1-1
1-3
1-6
1-8
1-10
2-1
2-4
2-7
2-10
3-1
3-5

80
Ft-IN
1-0
1-2
1-5
1-7
1-10
2-0
2-3
2-6
2-6
3-1
3-4
3-8

90
Ft-IN
1-1
1-3
1-5
1-8
1-11
2-1
2-4
2-8
2-11
3-2
3-6
3-10

100
Ft-IN
1-1
1-4
1-6
1-9
1-11
2-2
2-6
2-9
3-0
3-4
3-8
4-0

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 7 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 200.0 Feet
INITIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
150.0
160.0
170.0
180.0
190.0
200.0
210.0
220.0
230.0
240.0
250.0

1037

961

886

810

734

66

590

523

463

411

366

0
Ft-IN
0-5
0-6
0-7
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2

10
Ft-IN
0-6
0-6
0-7
0-8
0-9
0-10
0-10
0-10
1-0
1-2
1-3

20
Ft-IN
0-6
0-7
0-8
0-8
0-9
0-10
0-11
1-0
1-1
1-3
1-4

30
Ft-IN
0-7
0-7
0-8
0-9
0-10
0-11
1-0
1-2
1-3
1-4
1-5

40
Ft-IN
0-7
0-8
0-9
0-10
0-11
1-0
1-2
1-3
1-4
1-6
1-7

50
Ft-IN
0-8
0-9
0-10
0-11
1-0
1-2
1-3
1-4
1-6
1-7
1-9

60
Ft-IN
0-9
0-10
0-11
1-0
1-2
1-3
1-5
1-6
1-8
1-10
2-0

70
Ft-IN
0-10
0-11
1-1
1-2
1-4
1-5
1-7
1-9
1-10
2-0
2-2

80
Ft-IN
0-11
1-1
1-2
1-4
1-5
1-7
1-9
1-11
2-1
2-4
2-6

90
Ft-IN
1-0
1-2
1-4
1-6
1-8
1-10
2-0
2-2
2-5
2-7
2-10

100
Ft-IN
1-2
1-4
1-6
1-8
1-10
2-0
2-3
2-5
2-8
2-11
3-2

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 1630

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
150.0
160.0
170.0
180.0
190.0
200.0
210.0
220.0
230.0
240.0
250.0

997

1629

1102

492

247

187

-20
.145
Ft-IN
0-5
0-6
0-7
0-8
0-8
0-9
0-10
0-11
1-0
1-1
1-2

0
1 144
Ft-IN
2-0
2-3
2-7
2-11
3-3
3-7
3-11
4-4
4-8
5-1
5-6

32
.703
Ft-IN
1-10
2-1
2-4
2-8
2-11
3-3
3-7
3-11
4-3
4-8
5-0

60
.246
Ft-IN
1-5
1-8
1-10
2-1
2-4
2-7
2-10
3-1
3-4
3-8
3-11

120
.145
Ft-IN
1-8
1-11
2-2
2-5
2-8
3-0
3-3
3-7
3-11
4-3
4-7

212
.145
Ft-IN
2-3
2-6
2-10
3-2
3-7
3-11
4-4
4-9
5-2
5-8
6-1

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
150.0
160.0
170.0
180.0
190.0
200.0
210.0
220.0
230.0
240.0
250.0

788

691

601

521

452

395

349

312

288

277

267

0
Ft-IN
0-7
0-8
0-8
0-9
0-10
1-0
1-1
1-2
1-3
1-4
1-6

10
Ft-IN
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-4
1-5
1-7
1-8

20
Ft-IN
0-9
0-10
0-11
1-0
1-2
1-3
1-5
1-6
1-8
1-9
1-11

30
Ft-IN
0-10
0-11
1-1
1-2
1-4
1-5
1-7
1-9
1-11
2-1
2-3

40
Ft-IN
0-11
1-1
1-2
1-4
1-6
1-8
1-10
2-0
2-2
2-4
2-7

50
Ft-IN
1-1
1-3
1-4
1-6
1-8
1-11
2-1
2-3
2-6
2-8
2-11

60
Ft-IN
1-3
1-4
1-7
1-9
1-11
2-1
2-4
2-7
2-9
3-0
3-3

70
Ft-IN
1-4
1-6
1-9
1-11
2-2
2-4
2-7
2-10
3-1
3-5
3-8

80
Ft-IN
1-5
1-8
1-10
2-1
2-4
2-7
2-10
3-1
3-4
3-8
4-0

90
Ft-IN
1-6
1-9
1-11
2-2
2-5
2-8
2-11
3-2
3-6
3-10
4-2

100
Ft-IN
1-7
1-9
2-0
2-3
2-6
2-9
3-0
3-4
3-8
4-0
4-4

E.C.S.
INFORMATION SECTION

Section WSC02
Page 8 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN


Ruling Span: 225.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
170.0
180.0
190.0
200.0
210.0
220.0
230.0
240.0
250.0
260.0
270.0
280.0

1071

997

922

847

774

701

631

566

506

452

406

0
Ft-IN
0-6
0-7
0-8
0-9
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-4

10
Ft-IN
0-7
0-8
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-4
1-6

20
Ft-IN
0-7
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-4
1-6
1-7

30
Ft-IN
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-5
1-6
1-7
1-9

40
Ft-IN
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-5
1-6
1-8
1-9
1-11

50
Ft-IN
0-9
0-11
1-0
1-1
1-2
1-4
1-5
1-6
1-8
1-9
1-11
2-1

60
Ft-IN
0-10
1-0
1-1
1-2
1-4
1-5
1-7
1-8
1-10
2-0
2-2
2-4

70
Ft-IN
1-0
1-1
1-2
1-4
1-5
1-7
1-9
1-11
2-1
2-2
2-5
2-7

80
Ft-IN
1-1
1-2
1-4
1-6
1-7
1-9
1-11
2-1
2-3
2-6
2-8
2-10

90
Ft-IN
1-2
1-4
1-6
1-8
1-10
2-0
2-4
3-10
2-7
2-9
3-0
3-2

100
Ft-IN
1-4
1-6
1-8
1-10
2-0
2-2
2-5
2-7
2-10
3-1
3-4
3-6

DESIGN SAG CHART


NESC Heavy Load Zone
Max Tension = 1728
Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final
H Tens
991
1726
1173
525
271
207
(LBS)
Temp -> F> -20
0
32
60
120
212
Wt lb/f>
.145
1 144
.703
.246
.145
.145
SAG SPAN Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
170.0
0-7
2-5
2-3
1-9
2-0
2-7
180.0
0-8
2-9
2-6
1-11
2-3
2-11
190.0
0-8
3-0
2-9
2-2
2-6
3-2
200.0
0-9
3-4
3-0
2-5
2-9
3-6
210.0
0-10
3-8
3-4
2-8
3-0
3-11
220.0
0-11
4-1
3-8
2-11
3-3
4-3
230.0
1-0
4-5
4-0
3-2
3-7
4-8
240.0
1-1
4-10
4-4
3-5
3-11
5-1
250.0
1-2
5-3
4-9
3-8
4-3
5-6
260.0
1-3
5-8
5-1
4-0
4-7
5-11
270.0
1-5
6-1
5-6
4-4
4-11
6-5
280.0
1-6
6-6
5-11
4-8
5-4
6-11
FINAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
170.0
180.0
190.0
200.0
210.0
220.0
230.0
240.0
250.0
260.0
270.0
280.0

788

695

610

534

469

415

371

335

312

301

290

0
Ft-IN
0-8
0-9
0-10
1-0
1-1
1-2
1-3
1-4
1-6
1-7
1-9
1-10

10
Ft-IN
0-10
0-11
1-0
1-1
1-2
1-4
1-5
1-7
1-8
1-10
1-11
2-1

20
Ft-IN
0-11
1-0
1-1
1-3
1-4
1-6
1-7
1-9
1-11
2-1
2-3
2-4

30
Ft-IN
1-0
1-2
1-3
1-5
1-6
1-8
1-10
2-0
2-2
2-4
2-6
2-8

40
Ft-IN
1-2
1-4
1-5
1-7
1-9
1-11
2-1
2-3
2-5
2-8
2-10
3-1

50
Ft-IN
1-4
1-5
1-7
1-9
2-0
2-2
2-4
2-7
2-9
3-0
3-3
3-6

60
Ft-IN
1-5
1-8
1-10
2-0
2-2
2-5
2-8
2-10
3-1
3-4
3-7
3-11

70
Ft-IN
1-7
1-10
2-0
2-2
2-5
2-8
2-11
3-2
3-5
3-8
4-0
4-3

80
Ft-IN
1-9
1-11
2-2
2-4
2-7
2-10
3-1
3-5
3-8
4-0
4-3
4-7

90
Ft-IN
1-9
2-0
2-3
2-5
2-8
3-0
3-3
3-6
3-10
4-1
4-5
4-9

100
Ft-IN
1-10
2-1
2-4
2-7
2-10
3-1
3-4
3-8
3-11
4-3
4-7
4-11

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 9 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 250.0 Feet
INITIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
200.0
210.0
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
300.0

1105

1032

958

885

812

741

672

607

547

493

446

0
Ft-IN
0-8
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-4
1-5
1-6

10
Ft-IN
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-4
1-5
1-6
1-7

20
Ft-IN
0-10
0-11
0-11
1-1
1-2
1-3
1-4
1-5
1-6
1-8
1-9

30
Ft-IN
0-10
0-11
1-0
1-2
1-3
1-4
1-5
1-6
1-8
1-9
1-11

40
Ft-IN
0-11
1-0
1-1
1-3
1-4
1-5
1-7
1-8
1-10
1-11
2-1

50
Ft-IN
1-0
1-1
1-3
1-4
1-5
1-7
1-8
1-10
2-0
2-1
2-3

60
Ft-IN
1-1
1-3
1-4
1-6
1-7
1-9
1-10
2-0
2-2
2-4
2-6

70
Ft-IN
1-3
1-4
1-6
1-7
1-9
1-11
2-1
2-3
2-5
2-7
2-9

80
Ft-IN
1-4
1-6
1-8
1-10
1-11
2-1
2-3
2-5
2-8
2-10
3-0

90
Ft-IN
1-6
1-8
1-10
2-0
2-2
2-4
2-6
2-9
2-11
3-2
3-4

100
Ft-IN
1-8
1-10
2-0
2-2
2-5
2-7
2-9
3-0
3-3
3-6
3-8

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 1822

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
200.0
210.0
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
300.0

985

1820

1240

557

293

227

-20
.145
Ft-IN
0-9
0-10
0-11
1-0
1-1
1-2
1-3
1-5
1-6
1-7
1-8

0
1 144
Ft-IN
3-2
3-6
3-10
4-2
4-7
4-11
5-4
5-9
6-2
6-8
7-1

32
.703
Ft-IN
2-11
3-2
3-6
3-10
4-2
4-6
4-10
5-3
5-7
6-0
6-5

60
.246
Ft-IN
2-3
2-6
2-9
3-0
3-3
3-6
3-9
4-1
4-5
4-8
5-0

120
.145
Ft-IN
2-6
2-9
3-0
3-4
3-7
3-11
4-3
4-7
4-11
5-3
5-7

212
.145
Ft-IN
3-3
3-7
3-11
4-3
4-8
5-0
5-5
5-10
6-4
6-9
7-3

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
200.0
210.0
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
300.0

788

699

618

546

485

433

9371

356

334

323

312

0
Ft-IN
1-0
1-1
1-2
1-3
1-4
1-6
1-7
1-9
1-10
2-0
2-1

10
Ft-IN
1-1
1-2
1-4
1-5
1-6
1-8
1-10
1-11
2-1
2-3
2-5

20
Ft-IN
1-3
1-4
1-6
1-7
1-9
1-11
2-0
2-2
2-4
2-6
2-8

30
Ft-IN
1-4
1-6
1-8
1-10
1-11
2-1
2-3
2-6
2-8
2-10
3-0

40
Ft-IN
1-6
1-8
1-10
2-0
2-2
2-5
2-7
2-9
3-0
3-2
3-5

50
Ft-IN
1-9
1-11
2-1
2-3
2-5
2-8
2-10
3-1
3-4
3-7
3-10

60
Ft-IN
1-11
2-1
2-3
2-6
2-9
2-11
3-2
3-5
3-8
3-11
4-3

70
Ft-IN
2-1
2-3
2-6
2-9
3-0
3-3
3-6
3-9
4-0
4-4
4-7

80
Ft-IN
2-3
2-5
2-8
2-11
3-2
3-5
3-8
4-0
4-4
4-7
4-11

90
Ft-IN
2-3
2-6
2-9
3-0
3-3
3-7
3-10
4-2
4-5
4-9
5-1

100
Ft-IN
2-4
2-7
2-10
3-1
3-5
3-8
4-0
4-3
4-7
4-11
5-3

E.C.S.
INFORMATION SECTION

Section WSC02
Page 10 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN


Ruling Span: 275.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
300.0
310.0
320.0
330.0

1138

1066

993

921

850

779

712

647

588

533

485

0
Ft-IN
0-10
0-11
1-0
1-0
1-1
1-2
1-3
1-5
1-6
1-7
1-8
1-9

10
Ft-IN
0-10
0-11
1-0
1-1
1-2
1-3
1-5
1-6
1-7
1-8
1-9
1-11

20
Ft-IN
0-11
1-0
1-1
1-2
1-3
1-4
1-6
1-7
1-8
1-10
1-11
2-0

30
Ft-IN
1-0
1-1
1-2
1-3
1-4
1-6
1-7
1-8
1-10
1-11
2-1
2-2

40
Ft-IN
1-1
1-2
1-3
1-5
1-6
1-7
1-9
1-10
2-0
2-1
2-3
2-4

50
Ft-IN
1-2
1-3
1-5
1-6
1-7
1-9
1-10
2-0
2-2
2-3
2-5
2-7

60
Ft-IN
1-3
1-5
1-6
1-8
1-9
1-11
2-0
2-2
2-4
2-6
2-8
2-10

70
Ft-IN
1-5
1-6
1-8
1-10
1-11
2-1
2-3
2-5
2-7
2-9
2-11
3-1

80
Ft-IN
1-6
1-8
1-10
2-0
2-2
2-3
2-6
2-8
2-10
3-0
3-2
3-5

90
Ft-IN
1-8
1-10
2-0
2-2
2-4
2-6
2-8
2-11
3-1
3-4
3-6
3-11

100
Ft-IN
1-10
2-0
2-2
2-5
2-7
2-9
3-0
3-2
3-5
3-8
3-10
4-1

DESIGN SAG CHART


NESC Heavy Load Zone
Max Tension = 1913
Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final
H Tens
979
1910
1305
587
314
247
(LBS)
Temp -> F> -20
0
32
60
120
212
Wt lb/f>
.145
1 144
.703
.246
.145
.145
SAG SPAN Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
Ft-IN
220.0
0-11
3-8
3-4
2-7
2-10
3-7
230.0
1-0
4-0
3-7
2-10
3-1
3-11
240.0
1-1
4-4
3-11
3-1
3-4
4-3
250.0
1-2
4-9
4-3
3-4
3-8
4-8
260.0
1-4
5-1
4-7
3-7
3-11
5-0
270.0
1-5
5-6
4-11
3-10
4-3
5-5
280.0
1-6
5-11
5-4
4-2
4-7
5-10
290.0
1-7
6-4
5-9
4-5
4-11
6-3
300.0
1-9
6-9
6-1
4-9
5-3
6-8
310.0
1-10
7-3
6-6
5-1
5-7
7-1
320.0
1-11
7-9
6-11
5-5
5-11
7-7
330.0
2-1
8-2
7-5
5-9
6-4
8-1
FINAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
300.0
310.0
320.0
330.0

788

703

626

558

500

451

410

376

356

345

334

0
Ft-IN
1-2
1-3
1-4
1-6
1-7
1-9
1-10
2-0
2-1
2-3
2-5
2-7

10
Ft-IN
1-3
1-5
1-6
1-8
1-9
1-11
2-1
2-3
2-4
2-6
2-8
2-10

20
Ft-IN
1-5
1-7
1-9
1-10
2-0
2-2
2-4
2-6
2-8
2-10
3-0
3-2

30
Ft-IN
1-7
1-9
1-11
2-1
2-3
2-5
2-7
2-9
3-0
3-2
3-4
3-7

40
Ft-IN
1-10
2-0
2-2
2-4
2-6
2-8
2-11
3-1
3-4
3-6
3-9
4-0

50
Ft-IN
2-0
2-2
2-4
2-7
2-9
3-0
3-2
3-5
3-8
3-11
4-2
4-5

60
Ft-IN
2-2
2-5
2-7
2-10
3-0
3-3
3-6
3-9
4-0
4-3
4-7
4-10

70
Ft-IN
2-4
2-7
2-10
3-1
3-4
3-7
3-10
4-1
4-5
4-8
5-0
5-4

80
Ft-IN
2-6
2-9
3-0
3-3
3-6
3-9
4-0
4-4
4-7
4-11
5-3
5-7

90
Ft-IN
2-7
2-10
3-1
3-4
3-7
3-10
4-2
4-6
4-9
5-1
5-5
5-9

100
Ft-IN
2-8
2-11
3-2
3-5
3-9
4-0
4-4
4-7
4-11
5-3
5-7
5-11

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 11 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 300.0 Feet
INITIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
250.0
260.0
270.0
280.0
290.0
300.0
310.0
320.0
330.0
340.0
350.0

1170

1099

1028

957

886

871

750

686

627

572

523

0
Ft-IN
1-0
1-1
1-2
1-3
1-4
1-5
1-6
1-8
1-9
1-10
1-11

10
Ft-IN
1-1
1-2
1-3
1-4
1-5
1-6
1-8
1-9
1-10
1-11
2-1

20
Ft-IN
1-2
1-3
1-4
1-5
1-6
1-8
1-9
1-10
2-0
2-1
2-2

30
Ft-IN
1-3
1-4
1-5
1-6
1-8
1-9
1-10
2-0
2-1
2-3
2-4

40
Ft-IN
1-4
1-5
1-6
1-8
1-9
1-11
2-0
2-2
2-3
2-5
2-7

50
Ft-IN
1-5
1-6
1-8
1-9
1-11
2-0
2-2
2-4
2-5
2-7
2-9

60
Ft-IN
1-7
1-8
1-10
1-11
2-1
2-3
2-4
2-6
2-8
2-10
3-0

70
Ft-IN
1-8
1-10
2-0
2-1
2-3
2-5
2-7
2-9
2-11
3-1
3-3

80
Ft-IN
1-10
2-0
2-2
2-4
2-6
2-8
2-10
3-0
3-2
3-5
3-7

90
Ft-IN
2-0
2-2
2-4
2-6
2-8
2-11
3-1
3-3
3-6
3-8
3-11

100
Ft-IN
2-2
2-5
2-7
2-9
2-11
3-2
3-4
3-7
3-10
4-1
4-3

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 2000

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
250.0
260.0
270.0
280.0
290.0
300.0
310.0
320.0
330.0
340.0
350.0

972

1998

1368

615

335

266

-20
.145
Ft-IN
1-2
1-4
1-5
1-6
1-7
1-9
1-10
1-11
2-1
2-2
2-4

0
1 144
Ft-IN
4-6
4-11
5-3
5-8
6-1
6-6
6-11
7-5
7-10
8-4
8-10

32
.703
Ft-IN
4-1
4-5
4-9
5-1
5-5
5-10
6-3
6-8
7-1
7-6
7-11

60
.246
Ft-IN
3-2
3-5
3-8
4-0
4-3
4-7
4-10
5-2
5-6
5-10
6-2

120
.145
Ft-IN
3-5
3-8
4-0
4-3
4-7
4-11
5-3
5-7
5-11
6-4
6-8

212
.145
Ft-IN
4-4
4-8
5-0
5-5
5-9
6-2
6-7
7-0
7-6
7-11
8-5

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
250.0
260.0
270.0
280.0
290.0
300.0
310.0
320.0
330.0
340.0
350.0

788

707

633

569

514

467

428

395

377

366

355

0
Ft-IN
1-6
1-7
1-9
1-10
2-0
2-1
2-3
2-5
2-7
2-8
2-10

10
Ft-IN
1-8
1-9
1-11
2-1
2-2
2-4
2-6
2-8
2-10
3-0
3-2

20
Ft-IN
1-10
2-0
2-2
2-3
2-5
2-7
2-10
3-0
3-2
3-4
3-7

30
Ft-IN
2-0
2-2
2-4
2-6
2-9
2-11
3-1
3-4
3-6
3-9
3-11

40
Ft-IN
2-3
2-5
2-7
2-10
3-0
3-3
3-5
3-8
3-11
4-1
4-4

50
Ft-IN
2-6
2-8
2-10
3-1
3-4
3-6
3-9
4-0
4-3
4-6
4-10

60
Ft-IN
2-8
2-11
3-2
3-4
3-7
3-10
4-1
4-5
4-8
4-11
5-3

70
Ft-IN
2-11
3-2
3-5
3-8
3-11
4-2
4-5
4-9
5-1
5-4
5-8

80
Ft-IN
3-1
3-3
3-7
3-10
4-1
4-4
4-8
5-0
5-3
5-7
5-11

90
Ft-IN
3-2
3-5
3-8
3-11
4-3
4-6
4-10
5-1
5-5
5-9
6-1

100
Ft-IN
3-3
3-6
3-9
4-1
4-4
4-8
4-11
5-3
5-7
5-11
6-4

E.C.S.
INFORMATION SECTION

Section WSC02
Page 12 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN


Ruling Span: 325.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
290.0
300.0
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0

1202

1132

1062

992

922

854

788

725

665

610

560

0
Ft-IN
1-4
1-5
1-6
1-7
1-8
1-9
1-11
2-0
2-1
2-3

10
Ft-IN
1-5
1-6
1-7
1-8
1-9
1-11
2-0
2-1
2-3
2-4

20
Ft-IN
1-6
1-7
1-8
1-9
1-11
2-0
2-2
2-3
2-5
2-6

30
Ft-IN
1-7
1-8
1-10
1-11
2-0
2-2
2-3
2-5
2-7
2-8

40
Ft-IN
1-8
1-10
1-11
2-1
2-2
2-4
2-5
2-7
2-9
2-11

50
Ft-IN
1-10
1-11
2-1
2-3
2-4
2-6
2-8
2-10
2-11
3-1

60
Ft-IN
2-0
2-1
2-3
2-5
2-7
2-8
2-10
3-0
3-2
3-4

70
Ft-IN
2-2
2-4
2-5
2-7
2-9
2-11
3-1
3-3
3-6
3-8

80
Ft-IN
2-4
2-6
2-8
2-10
3-0
3-2
3-5
3-7
3-9
4-0

90
Ft-IN
2-6
2-9
2-11
3-1
3-3
3-6
3-8
3-11
4-1
4-4

100
Ft-IN
2-9
2-11
3-2
3-4
3-7
3-9
4-0
4-3
4-6
4-9

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 2085

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
290.0
300.0
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0

965

2082

1427

642

355

285

-20
.145
Ft-IN
1-7
1-9
1-10
2-0
2-1
2-3
2-4
2-6
2-7
2-9

0
1 144
Ft-IN
5-10
6-3
6-8
7-1
7-6
8-0
8-6
8-11
9-5
10-0

32
.703
Ft-IN
5-3
5-7
6-0
6-4
6-9
7-2
7-7
8-0
8-6
8-11

60
.246
Ft-IN
4-1
4-4
4-8
4-11
5-3
5-7
5-11
6-3
6-7
7-0

120
.145
Ft-IN
4-4
4-8
4-11
5-3
5-7
5-11
6-4
6-8
7-0
7-5

212
.145
Ft-IN
5-5
5-9
6-2
6-7
7-0
7-5
7-10
8-4
8-9
9-3

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN

788

710

641

580

527

483

445

412

397

386

375

0
Ft-IN

10
Ft-IN

20
Ft-IN

30
Ft-IN

40
Ft-IN

50
Ft-IN

60
Ft-IN

70
Ft-IN

80
Ft-IN

90
Ft-IN

100
Ft-IN

290.0
300.0
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0

2-0
2-1
2-3
2-5
2-7
2-8
2-10
3-0
3-2
3-4

2-2
2-4
2-6
2-8
2-10
3-0
3-2
3-4
3-6
3-9

2-5
2-7
2-9
2-11
3-1
3-4
3-6
3-8
3-11
4-2

2-8
2-10
3-1
3-3
3-5
3-8
3-10
4-1
4-4
4-7

2-11
3-2
3-4
3-7
3-9
4-0
4-3
4-6
4-9
5-0

3-2
3-5
3-8
3-11
4-2
4-5
4-8
4-11
5-2
5-6

3-6
3-9
4-0
4-3
4-6
4-9
5-0
5-4
5-7
5-11

3-9
4-0
4-3
4-7
4-10
5-1
5-5
5-9
6-1
6-5

3-11
4-2
4-5
4-9
5-0
5-4
5-8
5-11
6-3
6-8

4-0
4-3
4-7
4-10
5-2
5-6
5-10
6-2
6-6
6-10

4-1
4-5
4-8
5-0
5-4
5-8
6-0
6-4
6-8
7-0

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 13 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


#1/0 AWG 6/ 1 Stranding ACSR Conductor RAVEN
Ruling Span: 350.0 Feet
INITIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0
390.0
400.0

1234

1165

1096

1026

958

890

825

762

703

648

597

0
Ft-IN
1-5
1-7
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-5

10
Ft-IN
1-6
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-5
2-6

20
Ft-IN
1-8
1-9
1-10
1-11
2-1
2-2
2-4
2-5
2-7
2-8

30
Ft-IN
1-9
1-10
2-0
2-1
2-2
2-4
2-6
2-7
2-9
2-10

40
Ft-IN
1-10
2-0
2-1
2-3
2-4
2-6
2-8
2-9
2-11
3-1

50
Ft-IN
2-0
2-2
2-3
2-5
2-6
2-8
2-10
3-0
3-2
3-4

60
Ft-IN
2-2
2-4
2-5
2-7
2-9
2-11
3-1
3-3
3-5
3-7

70
Ft-IN
2-4
2-6
2-8
2-9
2-11
3-1
3-4
3-6
3-8
3-10

80
Ft-IN
2-6
2-8
2-10
3-0
3-2
3-5
3-7
3-9
4-0
4-2

90
Ft-IN
2-9
2-11
3-1
3-3
3-6
3-8
3-10
4-1
4-4
4-6

100
Ft-IN
3-0
3-2
3-4
3-7
3-9
4-0
4-2
4-5
4-8
4-11

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 2167

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0
390.0
400.0

958

2163

1485

667

375

303

-20
.145
Ft-IN
1-10
2-0
2-1
2-3
2-4
2-6
2-8
2-9
2-11
3-1

0
1 144
Ft-IN
6-5
6-10
7-3
8-2
8-6
8-7
9-1
9-7
10-1
10-7

32
.703
Ft-IN
5-9
6-1
6-6
6-11
7-4
7-9
8-2
8-7
9-1
9-6

60
.246
Ft-IN
4-6
4-9
5-1
5-4
5-8
6-0
6-4
6-8
7-1
7-5

120
.145
Ft-IN
4-8
5-0
5-4
5-8
6-0
6-4
6-8
7-0
7-5
7-9

212
.145
Ft-IN
5-10
6-2
6-7
7-0
7-4
7-10
8-3
8-8
9-2
9-7

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
310.0
320.0
330.0
340.0
350.0
360.0
370.0
380.0
390.0
400.0

788

714

648

590

540

497

460

429

417

406

395

0
Ft-IN
2-3
2-5
2-7
2-8
2-10
3-0
3-2
3-4
3-6
3-9

10
Ft-IN
2-6
2-8
2-10
3-0
3-2
3-4
3-6
3-9
3-11
4-1

20
Ft-IN
2-9
2-11
3-1
3-3
3-6
3-8
3-10
4-1
4-4
4-6

30
Ft-IN
3-0
3-2
3-5
3-7
3-10
4-0
4-3
4-6
4-9
4-11

40
Ft-IN
3-3
3-6
3-8
3-11
4-2
4-5
4-8
4-11
5-2
5-5

50
Ft-IN
3-7
3-9
4-0
4-3
4-6
4-9
5-0
5-4
5-7
5-11

60
Ft-IN
3-10
4-1
4-4
4-7
4-10
5-2
5-5
5-9
6-0
6-4

70
Ft-IN
4-1
4-4
4-8
4-11
5-3
5-6
5-10
6-2
6-6
6-10

80
Ft-IN
4-3
4-6
4-9
5-1
5-4
5-8
6-0
6-4
6-8
7-0

90
Ft-IN
4-4
4-7
4-11
5-2
5-6
5-10
6-2
6-6
6-10
7-2

100
Ft-IN
4-5
4-9
5-0
5-4
5-8
6-0
6-4
6-8
7-0
7-5

E.C.S.
INFORMATION SECTION

Section WSC02
Page 14 of 50

Issued 11-01-14

DISTRIBUTION CHARTS STANDARD CONDUCTOR

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 100.0 Feet
INITIAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

1366

1165

966

777

612

484

394

333

291

260

236

0
Ft-IN
0-3
0-3
0-4
0-4
0-5
0-6
0-7
0-8

10
Ft-IN
0-3
0-4
0-4
0-5
06
0-7
0-8
0-9

20
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-11

30
Ft-IN
0-4
0-5
0-6
0-7
0-9
0-10
0-11
1-1

40
Ft-IN
0-5
0-6
0-8
0-9
0-11
1-1
1-2
1-5

50
Ft-IN
0-6
0-8
0-9
0-11
1-1
1-4
1-6
1-9

60
Ft-IN
0-8
0-9
1-0
1-2
1-4
1-7
1-10
2-1

70
Ft-IN
0-9
0-11
1-2
1-4
1-7
1-11
2-2
2-6

80
Ft-IN
1-10
1-1
1-3
1-7
1-10
2-2
2-6
2-10

90
Ft-IN
0-11
1-2
1-5
1-9
2-1
2-5
2-9
3-2

100
Ft-IN
1-0
1-3
1-7
1-11
2-3
2-8
3-1
3-6

DESIGN SAG CHART


NESC Heavy Load Zone

Max Tension = 1785

Design: 18.0% Ult.@ 0.Deg - .00 in Ice,.00 psf wind, Final


H Tens
(LBS)
Temp -> F>
Wt lb/f>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

1732

1771

1092

446

192

156

-20
.145
Ft-IN
0-2
0-3
0-3
0-4
0-4
0-5
0-5
0-6

0
1 144
Ft-IN
0-8
0-10
1-0
1-3
1-6
1-9
2-0
2-4

32
.703
Ft-IN
0-9
0-11
1-2
1-5
1-8
1-11
2-3
2-7

60
.246
Ft-IN
0-10
1-0
1-3
1-6
1-9
2-0
2-4
2-8

120
.145
Ft-IN
1-3
1-7
1-11
2-4
2-9
3-3
3-9
4-4

212
.145
Ft-IN
1-6
1-11
2-4
2-10
3-5
4-0
4-7
5-3

FINAL SAG CHART


H Tens
(LBS)
Temp F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0

1238

1005

792

614

482

392

331

298

259

236

218

0
Ft-IN
0-3
0-5
0-4
0-5
0-6
0-6
0-7
0-8

10
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-10

20
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-10
0-11
1-1

30
Ft-IN
0-5
0-6
0-8
0-9
0-11
1-0
1-2
1-4

40
Ft-IN
0-6
0-8
0-10
0-11
1-1
1-4
1-6
1-9

50
Ft-IN
0-8
0-9
1-0
1-2
1-4
1-7
1-10
2-1

60
Ft-IN
0-9
0-11
1-2
1-4
1-7
1-11
2-2
2-6

70
Ft-IN
0-10
1-1
1-4
1-7
1-10
2-2
2-6
2-10

80
Ft-IN
0-11
1-2
1-5
1-9
2-1
2-5
2-9
3-2

90
Ft-IN
1-0
1-3
1-7
1-11
2-3
2-8
3-1
3-6

100
Ft-IN
1-1
1-5
1-9
2-1
2-5
2-10
3-4
3-10

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC02
Page 15 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING
Ruling Span: 125.0 Feet
INTIAL SAG CHART

H Tens
(LBS)
Temp F>
SAG SPAN
80.0
90.0
100.0
110.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0

1046

1212

1012

842

686

561

470

404

356

320

292

0
Ft-IN
0-2
0-3
0-4
0-4
0-5
0-6
0-7
0-7
0-8
0-9
0-11

10
Ft-IN
0-3
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-10
1-1
1-2

20
Ft-IN
0-3
0-4
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1
1-2

30
Ft-IN
0-4
0-5
0-6
0-7
0-8
0-9
0-11
1-0
1-2
1-3
1-5

40
Ft-IN
0-5
0-6
0-7
0-8
0-10
0-11
1-1
1-3
1-5
1-7
1-9

50
Ft-IN
0-5
0-7
0-8
0-10
1-0
1-2
1-4
1-6
1-8
1-11
2-2

60
Ft-IN
0-6
0-8
0-10
1-0
1-2
1-4
1-7
1-9
2-0
2-3
2-7

70
Ft-IN
0-7
0-9
0-11
1-2
1-4
1-7
1-10
2-1
2-4
2-8
2-11

80
Ft-IN
0-8
0-10
1-1
1-3
1-6
1-9
2-0
2-4
2-8
3-0
3-4

90
Ft-IN
0-9
1-0
1-2
1-5
1-8
1-11
2-3
2-7
2-11
3-4
3-9

100
Ft-IN
0-10
1-1
1-3
1-7
1-10
2-2
2-6
2-10
3-3
3-8
4-1

DESIGN SAG CHART


NESC Heavy Load Zone
Max Tension =
1945 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1719. 1928. 1232.
524.
234.
189.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----80.0
0- 2
0- 8
0- 8
0- 8
1- 0
1- 3
90.0
0- 3
0- 9
0-10
0-10
1- 4
1- 7
100.0
0- 3
1- 0
1- 0
1- 1
1- 7
1-11
110.0
0- 4
1- 2
1- 3
1- 3
1-11
2- 4
120.0
0- 4
1- 4
1- 6
1- 6
2- 3
2-10
130.0
0- 5
1- 7
1- 9
1- 9
2- 8
3- 3
140.0
0- 5
1-10
2- 0
2- 0
3- 1
3-10
150.0
0- 6
2- 1
2- 3
2- 4
3- 6
4- 4
160.0
0- 7
2- 5
2- 7
2- 7
4- 0
4-11
170.0
0- 8
2- 8
2-11
2-11
4- 6
5- 7
180.0
0- 9
3- 0
3- 3
3- 4
5- 1
6- 3
FINAL SAG CHART
H Tens
(LBS)
Temp F>
SAG SPAN
100.0
100.0
120.0
130.0
140.0
150.0
160.0
170.0
180.0

1238

1017

820

659

538

452

391

346

313

287

266

0
Ft-IN
0-4
0-5
0-6
0-6
0-7
0-8
0-9
0-11
1-0

10
Ft-IN
0-5
0-6
0-7
0-8
0-9
0-10
0-11
1-1
1-2

20
Ft-IN
0-6
0-7
0-8
0-9
0-11
1-0
1-2
1-4
1-6

30
Ft-IN
0-7
0-8
0-10
1-0
1-1
1-3
1-5
1-8
1-10

40
Ft-IN
0-9
0-10
1-0
1-2
1-4
1-7
1-9
2-0
2-3

50
Ft-IN
0-10
1-0
1-2
1-5
1-7
1-10
2-1
2-4
2-8

60
Ft-IN
1-0
1-2
1-5
1-7
1-10
2-2
2-5
2-9
3-1

70
Ft-IN
1-1
1-4
1-7
1-10
2-1
2-5
2-9
3-1
3-5

80
Ft-IN
1-2
1-5
1-9
2-0
2-4
2-8
3-0
3-5
3-10

90
Ft-IN
1-4
1-7
1-10
2-2
2-6
2-11
3-3
3-8
4-2

100
Ft-IN
1-5
1-8
2-0
2-4
2-9
3-1
3-6
4-0
4-6

Section WSC02
Page 16 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 150.0 Feet
INITIAL SAG CHART
H Tens
1440. 1252. 1069.
898.
750.
630.
538.
469.
418.
378.
347.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
0- 4
0- 4
0- 5
0- 5
0- 6
0- 7
0- 9
0-10
0-11
1- 0
1- 1
110.0
0- 4
0- 5
0- 5
0- 6
0- 8
0- 9
0-10
1- 0
1- 1
1- 2
1- 4
120.0
0- 5
0- 6
0- 6
0- 7
0- 9
0-10
1- 0
1- 2
1- 4
1- 5
1- 7
130.0
0- 6
0- 6
0- 7
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-10
140.0
0- 6
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 7
1- 9
1-11
2- 1
150.0
0- 7
0- 8
0-10
0-11
1- 2
1- 4
1- 7
1- 9
2- 0
2- 2
2- 5
160.0
0- 8
0- 9
0-11
1- 1
1- 3
1- 6
1- 9
2- 0
2- 3
2- 6
2- 9
170.0
0- 9
0-11
1- 0
1- 2
1- 5
1- 8
2- 0
2- 3
2- 7
2-10
3- 1
180.0
0-10
1- 0
1- 2
1- 4
1- 7
1-11
2- 3
2- 7
2-10
3- 2
3- 5
190.0
0-11
1- 1
1- 3
1- 6
1- 9
2- 1
2- 6
2-10
3- 2
3- 6
3-10
200.0
1- 1
1- 2
1- 5
1- 8
2- 0
2- 4
2- 9
3- 2
3- 6
3-11
4- 3
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2094 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1704. 2078. 1360.
595.
276.
221.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----100.0
0- 3
0-11
0-11
0-11
1- 4
1- 8
110.0
0- 4
1- 1
1- 2
1- 1
1- 8
2- 0
120.0
0- 4
1- 3
1- 4
1- 4
1-11
2- 5
130.0
0- 5
1- 6
1- 7
1- 6
2- 3
2-10
140.0
0- 6
1- 9
1-10
1- 9
2- 7
3- 3
150.0
0- 6
2- 0
2- 1
2- 0
3- 0
3- 9
160.0
0- 7
2- 3
2- 4
2- 4
3- 5
4- 3
170.0
0- 8
2- 6
2- 8
2- 7
3-10
4-10
180.0
0- 9
2-10
3- 0
2-11
4- 4
5- 4
190.0
0-10
3- 1
3- 4
3- 3
4- 9
6- 0
200.0
0-11
3- 5
3- 8
3- 7
5- 4
6- 7
FINAL SAG CHART
H Tens
1238. 1029.
848.
700.
588.
505.
444.
398.
363.
335.
312.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
0-11
1- 0
1- 2
1- 2
110.0
0- 5
0- 6
0- 7
0- 8
0- 9
0-11
1- 0
1- 2
1- 3
1- 4
1- 5
120.0
0- 6
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 4
1- 6
1- 7
1- 9
130.0
0- 6
0- 8
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
1-10
2- 0
140.0
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 0
2- 2
2- 4
150.0
0- 8
0-10
1- 0
1- 2
1- 5
1- 8
1-11
2- 1
2- 3
2- 6
2- 8
160.0
0- 9
0-11
1- 2
1- 4
1- 7
1-11
2- 2
2- 4
2- 7
2-10
3- 0
170.0
0-11
1- 1
1- 3
1- 6
1-10
2- 1
2- 5
2- 8
2-11
3- 2
3- 5
180.0
1- 0
1- 2
1- 5
1- 9
2- 0
2- 4
2- 8
3- 0
3- 3
3- 7
3-10
190.0
1- 1
1- 4
1- 7
1-11
2- 3
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
200.0
1- 3
1- 5
1- 9
2- 1
2- 6
2-11
3- 4
3- 8
4- 0
4- 5
4- 8

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 17 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING
Ruling Span: 175.0 Feet

INITIAL SAG CHART


H Tens
1468. 1286. 1110.
948.
807.
691.
600.
529.
475.
432.
398.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
0- 6
0- 6
0- 7
0- 8
0-10
0-11
1- 1
1- 2
1- 4
1- 6
1- 7
140.0
0- 6
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 5
1- 6
1- 8
1-10
150.0
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
2- 1
160.0
0- 8
0- 9
0-11
1- 0
1- 2
1- 5
1- 7
1-10
2- 0
2- 2
2- 4
170.0
0- 9
0-10
1- 0
1- 2
1- 4
1- 7
1- 9
2- 0
2- 3
2- 6
2- 8
180.0
0-10
0-11
1- 1
1- 3
1- 6
1- 9
2- 0
2- 3
2- 6
2- 9
3- 0
190.0
0-11
1- 1
1- 3
1- 5
1- 8
1-11
2- 3
2- 6
2-10
3- 1
3- 4
200.0
1- 0
1- 2
1- 4
1- 7
1-10
2- 2
2- 6
2- 9
3- 1
3- 5
3- 8
210.0
1- 2
1- 3
1- 6
1- 9
2- 0
2- 4
2- 9
3- 1
3- 5
3- 9
4- 1
220.0
1- 3
1- 5
1- 7
1-11
2- 3
2- 7
3- 0
3- 4
3- 9
4- 1
4- 5
230.0
1- 4
1- 6
1- 9
2- 1
2- 5
2-10
3- 3
3- 8
4- 1
4- 6
4-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2232 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1686. 2221. 1479.
661.
317.
250.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----130.0
0- 5
1- 5
1- 5
1- 5
2- 0
2- 6
140.0
0- 6
1- 7
1- 8
1- 7
2- 3
2-11
150.0
0- 6
1-10
1-11
1-10
2- 7
3- 4
160.0
0- 7
2- 1
2- 2
2- 1
3- 0
3- 9
170.0
0- 8
2- 4
2- 5
2- 4
3- 4
4- 3
180.0
0- 9
2- 8
2- 9
2- 7
3- 9
4- 9
190.0
0-10
2-11
3- 0
2-11
4- 2
5- 3
200.0
0-11
3- 3
3- 4
3- 3
4- 7
5-10
210.0
1- 0
3- 7
3- 8
3- 7
5- 1
6- 5
220.0
1- 1
3-11
4- 1
3-11
5- 7
7- 1
230.0
1- 2
4- 3
4- 5
4- 3
6- 1
7- 9
FINAL SAG CHART
H Tens
1238. 1042.
874.
738.
634.
554.
494.
447.
410.
380.
355.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
0- 6
0- 8
0- 9
0-10
1- 0
1- 2
1- 3
1- 5
1- 6
1- 8
1- 9
140.0
0- 7
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1- 9
1-11
2- 1
150.0
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
2- 4
160.0
0- 9
0-11
1- 1
1- 4
1- 6
1- 9
1-11
2- 1
2- 4
2- 6
2- 8
170.0
0-11
1- 1
1- 3
1- 6
1- 8
1-11
2- 2
2- 5
2- 7
2-10
3- 0
180.0
1- 0
1- 2
1- 5
1- 8
1-11
2- 2
2- 5
2- 8
2-11
3- 2
3- 4
190.0
1- 1
1- 4
1- 6
1-10
2- 1
2- 5
2- 8
3- 0
3- 3
3- 6
3- 9
200.0
1- 3
1- 5
1- 8
2- 0
2- 4
2- 8
3- 0
3- 3
3- 7
3-10
4- 2
210.0
1- 4
1- 7
1-10
2- 2
2- 7
2-11
3- 3
3- 7
3-11
4- 3
4- 7
220.0
1- 6
1- 9
2- 1
2- 5
2-10
3- 3
3- 7
4- 0
4- 4
4- 8
5- 0
230.0
1- 7
1-11
2- 3
2- 8
3- 1
3- 6
3-11
4- 4
4- 9
5- 1
5- 5

Section WSC02
Page 18 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 200.0 Feet
INITIAL SAG CHART
H Tens
1490. 1314. 1145.
991.
857.
745.
655.
584.
528.
484.
447.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----150.0
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 3
1- 5
1- 7
1- 9
1-10
160.0
0- 8
0- 9
0-10
1- 0
1- 2
1- 3
1- 5
1- 8
1-10
2- 0
2- 1
170.0
0- 9
0-10
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 0
2- 2
2- 5
180.0
0-10
0-11
1- 1
1- 3
1- 5
1- 7
1-10
2- 1
2- 3
2- 6
2- 8
190.0
0-11
1- 0
1- 2
1- 4
1- 7
1-10
2- 0
2- 3
2- 6
2- 9
3- 0
200.0
1- 0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 3
2- 6
2- 9
3- 0
3- 3
210.0
1- 1
1- 3
1- 5
1- 8
1-11
2- 2
2- 6
2- 9
3- 1
3- 4
3- 7
220.0
1- 3
1- 5
1- 7
1-10
2- 1
2- 5
2- 9
3- 1
3- 4
3- 8
4- 0
230.0
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
3- 0
3- 4
3- 8
4- 0
4- 4
240.0
1- 5
1- 8
1-10
2- 2
2- 6
2-10
3- 3
3- 7
4- 0
4- 4
4- 9
250.0
1- 7
1- 9
2- 0
2- 4
2- 8
3- 1
3- 6
3-11
4- 4
4- 9
5- 1
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2362 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1667. 2356. 1591.
722.
356.
279.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----150.0
0- 6
1- 9
1- 9
1- 8
2- 4
3- 0
160.0
0- 7
2- 0
2- 0
1-11
2- 8
3- 4
170.0
0- 8
2- 3
2- 3
2- 2
3- 0
3-10
180.0
0- 9
2- 6
2- 6
2- 5
3- 4
4- 3
190.0
0-10
2- 9
2-10
2- 8
3- 9
4- 9
200.0
0-11
3- 1
3- 1
2-11
4- 1
5- 3
210.0
1- 0
3- 4
3- 5
3- 3
4- 6
5- 9
220.0
1- 1
3- 8
3- 9
3- 7
5- 0
6- 4
230.0
1- 2
4- 0
4- 1
3-11
5- 5
6-11
240.0
1- 4
4- 4
4- 6
4- 3
5-11
7- 6
250.0
1- 5
4- 9
4-10
4- 7
6- 5
8- 2
FINAL SAG CHART
H Tens
1238. 1055.
899.
773.
675.
599.
539.
492.
454.
423.
397.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----150.0
0- 8
0-10
0-11
1- 1
1- 3
1- 5
1- 7
1- 8
1-10
2- 0
2- 1
160.0
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
2- 1
2- 3
2- 5
170.0
0-11
1- 0
1- 2
1- 5
1- 7
1-10
2- 0
2- 2
2- 4
2- 6
2- 8
180.0
1- 0
1- 2
1- 4
1- 7
1- 9
2- 0
2- 3
2- 5
2- 8
2-10
3- 0
190.0
1- 1
1- 3
1- 6
1- 9
2- 0
2- 3
2- 6
2- 8
2-11
3- 2
3- 4
200.0
1- 3
1- 5
1- 8
1-11
2- 2
2- 6
2- 9
3- 0
3- 3
3- 6
3- 8
210.0
1- 4
1- 7
1-10
2- 1
2- 5
2- 9
3- 0
3- 4
3- 7
3-10
4- 1
220.0
1- 6
1- 8
2- 0
2- 4
2- 8
3- 0
3- 4
3- 7
3-11
4- 2
4- 6
230.0
1- 7
1-10
2- 2
2- 6
2-11
3- 3
3- 7
3-11
4- 3
4- 7
4-11
240.0
1- 9
2- 0
2- 4
2- 9
3- 2
3- 6
3-11
4- 3
4- 8
5- 0
5- 4
250.0
1-10
2- 2
2- 7
3- 0
3- 5
3-10
4- 3
4- 8
5- 0
5- 5
5- 9

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 19 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING
Ruling Span: 225.0 Feet

INITIAL SAG CHART


H Tens
1511. 1341. 1179. 1032.
903.
795.
707.
636.
579.
533.
494.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----190.0
0-11
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 1
2- 4
2- 6
2- 8
200.0
1- 0
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 4
2- 7
2- 9
3- 0
210.0
1- 1
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 3
220.0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
3- 7
230.0
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 9
3- 1
3- 4
3- 8
3-11
240.0
1- 5
1- 7
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
4- 0
4- 3
250.0
1- 6
1- 9
2- 0
2- 3
2- 7
2-11
3- 3
3- 7
3-11
4- 4
4- 8
260.0
1- 8
1-10
2- 1
2- 5
2- 9
3- 1
3- 6
3-11
4- 3
4- 8
5- 0
270.0
1- 9
2- 0
2- 3
2- 7
3- 0
3- 4
3- 9
4- 2
4- 7
5- 0
5- 5
280.0
1-11
2- 2
2- 5
2-10
3- 2
3- 7
4- 1
4- 6
4-11
5- 5
5-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2486 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1647. 2485. 1696.
778.
393.
308.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----190.0
0-10
2- 7
2- 8
2- 6
3- 5
4- 4
200.0
0-11
2-11
2-11
2- 9
3- 9
4- 9
210.0
1- 0
3- 2
3- 3
3- 0
4- 1
5- 3
220.0
1- 1
3- 6
3- 6
3- 4
4- 6
5- 9
230.0
1- 2
3-10
3-10
3- 7
4-11
6- 3
240.0
1- 4
4- 2
4- 2
3-11
5- 4
6-10
250.0
1- 5
4- 6
4- 7
4- 3
5-10
7- 5
260.0
1- 6
4-10
4-11
4- 7
6- 3
8- 0
270.0
1- 8
5- 3
5- 4
5- 0
6- 9
8- 8
280.0
1- 9
5- 8
5- 8
5- 4
7- 3
9- 4
FINAL SAG CHART
H Tens
1238. 1067.
923.
806.
713.
639.
581.
534.
495.
463.
436.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----190.0
1- 1
1- 3
1- 6
1- 8
1-11
2- 1
2- 4
2- 6
2- 8
2-10
3- 1
200.0
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 6
2- 9
3- 0
3- 2
3- 4
210.0
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-10
3- 0
3- 3
3- 6
3- 9
220.0
1- 6
1- 8
1-11
2- 3
2- 6
2- 9
3- 1
3- 4
3- 7
3-10
4- 1
230.0
1- 7
1-10
2- 1
2- 5
2- 9
3- 1
3- 4
3- 8
3-11
4- 2
4- 5
240.0
1- 9
2- 0
2- 4
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
4- 7
4-10
250.0
1-10
2- 2
2- 6
2-10
3- 3
3- 7
3-11
4- 3
4- 7
4-11
5- 3
260.0
2- 0
2- 4
2- 8
3- 1
3- 6
3-11
4- 3
4- 8
5- 0
5- 4
5- 8
270.0
2- 2
2- 6
2-11
3- 4
3- 9
4- 2
4- 7
5- 0
5- 5
5- 9
6- 1
280.0
2- 4
2- 8
3- 1
3- 7
4- 0
4- 6
4-11
5- 4
5- 9
6- 2
6- 7

Section WSC02
Page 20 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 250.0 Feet
INITIAL SAG CHART
H Tens
1539. 1374. 1218. 1076.
952.
847.
759.
688.
630.
581.
541.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----200.0
1- 0
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
2- 2
2- 4
2- 6
2- 9
210.0
1- 1
1- 2
1- 4
1- 6
1- 9
1-11
2- 2
2- 4
2- 7
2- 9
3- 0
220.0
1- 2
1- 4
1- 6
1- 8
1-11
2- 1
2- 4
2- 7
2-10
3- 1
3- 3
230.0
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 4
3- 7
240.0
1- 5
1- 7
1- 9
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
3- 8
3-11
250.0
1- 6
1- 8
1-11
2- 2
2- 5
2- 9
3- 0
3- 4
3- 8
3-11
4- 3
260.0
1- 8
1-10
2- 1
2- 4
2- 7
2-11
3- 3
3- 7
3-11
4- 3
4- 7
270.0
1- 9
2- 0
2- 3
2- 6
2-10
3- 2
3- 6
3-11
4- 3
4- 7
4-11
280.0
1-11
2- 1
2- 4
2- 8
3- 0
3- 5
3- 9
4- 2
4- 7
4-11
5- 4
290.0
2- 0
2- 3
2- 7
2-10
3- 3
3- 8
4- 1
4- 6
4-11
5- 3
5- 8
300.0
2- 2
2- 5
2- 9
3- 1
3- 6
3-11
4- 4
4- 9
5- 3
5- 8
6- 1
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2609 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1625. 2607. 1794.
831.
428.
334.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----200.0
0-11
2- 9
2- 9
2- 7
3- 5
4- 5
210.0
1- 0
3- 0
3- 1
2-10
3- 9
4-10
220.0
1- 1
3- 4
3- 4
3- 1
4- 2
5- 4
230.0
1- 3
3- 8
3- 8
3- 5
4- 6
5- 9
240.0
1- 4
3-11
4- 0
3- 8
4-11
6- 4
250.0
1- 5
4- 3
4- 4
4- 0
5- 4
6-10
260.0
1- 7
4- 8
4- 8
4- 4
5- 9
7- 5
270.0
1- 8
5- 0
5- 0
4- 8
6- 3
8- 0
280.0
1- 9
5- 4
5- 5
5- 0
6- 8
8- 7
290.0
1-11
5- 9
5- 9
5- 4
7- 2
9- 2
300.0
2- 1
6- 2
6- 2
5- 9
7- 8
9-10
FINAL SAG CHART
H Tens
1238. 1078.
944.
835.
747.
677.
619.
573.
534.
501.
473.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----200.0
1- 3
1- 5
1- 7
1- 9
2- 0
2- 2
2- 5
2- 7
2- 9
2-11
3- 1
210.0
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 7
2-10
3- 0
3- 3
3- 5
220.0
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
2-10
3- 1
3- 4
3- 7
3- 9
230.0
1- 7
1-10
2- 1
2- 4
2- 7
2-11
3- 2
3- 5
3- 8
3-10
4- 1
240.0
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 5
3- 8
3-11
4- 3
4- 5
250.0
1-10
2- 2
2- 5
2- 9
3- 1
3- 5
3- 8
4- 0
4- 3
4- 7
4-10
260.0
2- 0
2- 4
2- 8
3- 0
3- 4
3- 8
4- 0
4- 4
4- 8
4-11
5- 3
270.0
2- 2
2- 6
2-10
3- 2
3- 7
3-11
4- 4
4- 8
5- 0
5- 4
5- 8
280.0
2- 4
2- 8
3- 1
3- 5
3-10
4- 3
4- 8
5- 0
5- 4
5- 9
6- 1
290.0
2- 6
2-10
3- 3
3- 8
4- 1
4- 7
5- 0
5- 4
5- 9
6- 2
6- 6
300.0
2- 8
3- 1
3- 6
3-11
4- 5
4-10
5- 4
5- 9
6- 2
6- 7
6-11

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 21 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING
Ruling Span: 275.0 Feet

INITIAL SAG CHART


H Tens
1564. 1405. 1254. 1118.
997.
894.
808.
737.
678.
628.
587.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----240.0
1- 5
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
2-11
3- 1
3- 4
3- 7
250.0
1- 6
1- 8
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 5
3- 8
3-11
260.0
1- 7
1- 9
2- 0
2- 3
2- 6
2- 9
3- 1
3- 4
3- 8
3-11
4- 3
270.0
1- 9
1-11
2- 2
2- 5
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
4- 7
280.0
1-10
2- 1
2- 4
2- 7
2-11
3- 3
3- 7
3-11
4- 3
4- 7
4-11
290.0
2- 0
2- 3
2- 6
2- 9
3- 1
3- 5
3-10
4- 2
4- 7
4-11
5- 3
300.0
2- 2
2- 4
2- 8
3- 0
3- 4
3- 8
4- 1
4- 6
4-10
5- 3
5- 7
310.0
2- 3
2- 6
2-10
3- 2
3- 6
3-11
4- 4
4- 9
5- 2
5- 7
6- 0
320.0
2- 5
2- 8
3- 0
3- 4
3- 9
4- 2
4- 8
5- 1
5- 6
5-11
6- 4
330.0
2- 7
2-10
3- 2
3- 7
4- 0
4- 5
4-11
5- 5
5-10
6- 4
6- 9
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2726 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1604. 2724. 1887.
880.
462.
360.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----240.0
1- 4
3- 9
3- 9
3- 6
4- 7
5-10
250.0
1- 5
4- 1
4- 1
3- 9
4-11
6- 4
260.0
1- 7
4- 5
4- 5
4- 1
5- 4
6-10
270.0
1- 8
4- 9
4- 9
4- 5
5- 9
7- 5
280.0
1-10
5- 2
5- 2
4- 9
6- 2
7-11
290.0
1-11
5- 6
5- 6
5- 1
6- 8
8- 6
300.0
2- 1
5-11
5-11
5- 5
7- 1
9- 1
310.0
2- 3
6- 4
6- 3
5- 9
7- 7
9- 9
320.0
2- 4
6- 8
6- 8
6- 2
8- 1 10- 4
330.0
2- 6
7- 2
7- 1
6- 7
8- 7 11- 0
FINAL SAG CHART
H Tens
1238. 1089.
965.
862.
779.
711.
655.
609.
570.
537.
509.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----240.0
1- 9
2- 0
2- 2
2- 6
2- 9
3- 0
3- 3
3- 6
3- 8
3-11
4- 2
250.0
1-10
2- 1
2- 5
2- 8
2-11
3- 3
3- 6
3- 9
4- 0
4- 3
4- 6
260.0
2- 0
2- 3
2- 7
2-11
3- 2
3- 6
3- 9
4- 1
4- 4
4- 7
4-10
270.0
2- 2
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 8
5- 0
5- 3
280.0
2- 4
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 0
5- 4
5- 8
290.0
2- 6
2-10
3- 2
3- 7
3-11
4- 4
4- 8
5- 1
5- 5
5- 9
6- 0
300.0
2- 8
3- 0
3- 5
3-10
4- 3
4- 8
5- 0
5- 5
5- 9
6- 1
6- 5
310.0
2-10
3- 3
3- 8
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 6
6-11
320.0
3- 0
3- 5
3-11
4- 4
4-10
5- 3
5- 9
6- 2
6- 7
6-11
7- 4
330.0
3- 3
3- 8
4- 2
4- 7
5- 1
5- 7
6- 1
6- 6
7- 0
7- 5
7-10

Section WSC02
Page 22 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 300.0 Feet
INITIAL SAG CHART
H Tens
1587. 1433. 1288. 1156. 1039.
939.
854.
783.
723.
673.
630.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
1- 7
1- 9
1-11
2- 2
2- 5
2- 8
2-11
3- 2
3- 5
3- 8
3-11
270.0
1- 8
1-11
2- 1
2- 4
2- 7
2-10
3- 2
3- 5
3- 8
4- 0
4- 3
280.0
1-10
2- 0
2- 3
2- 6
2- 9
3- 1
3- 4
3- 8
4- 0
4- 3
4- 7
290.0
2- 0
2- 2
2- 5
2- 8
3- 0
3- 3
3- 7
3-11
4- 3
4- 7
4-11
300.0
2- 1
2- 4
2- 7
2-10
3- 2
3- 6
3-10
4- 3
4- 7
4-11
5- 3
310.0
2- 3
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 6
4-10
5- 3
5- 7
320.0
2- 5
2- 8
2-11
3- 3
3- 7
4- 0
4- 5
4- 9
5- 2
5- 7
5-11
330.0
2- 6
2-10
3- 1
3- 5
3-10
4- 3
4- 8
5- 1
5- 6
5-11
6- 4
340.0
2- 8
3- 0
3- 4
3- 8
4- 1
4- 6
4-11
5- 5
5-10
6- 3
6- 8
350.0
2-10
3- 2
3- 6
3-11
4- 4
4- 9
5- 3
5- 9
6- 2
6- 8
7- 1
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2838 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1582. 2835. 1975.
926.
495.
385.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----260.0
1- 7
4- 3
4- 3
3-11
5- 0
6- 5
270.0
1- 9
4- 7
4- 7
4- 2
5- 5
6-11
280.0
1-10
4-11
4-11
4- 6
5- 9
7- 5
290.0
2- 0
5- 4
5- 3
4-10
6- 2
8- 0
300.0
2- 1
5- 8
5- 7
5- 2
6- 8
8- 6
310.0
2- 3
6- 1
6- 0
5- 6
7- 1
9- 1
320.0
2- 5
6- 5
6- 5
5-10
7- 7
9- 8
330.0
2- 6
6-10
6-10
6- 3
8- 0 10- 4
340.0
2- 8
7- 3
7- 3
6- 7
8- 6 10-11
350.0
2-10
7- 8
7- 8
7- 0
9- 0 11- 7
FINAL SAG CHART
H Tens
1238. 1099.
983.
887.
808.
743.
689.
643.
604.
571.
542.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
3- 7
3-10
4- 1
4- 4
4- 7
270.0
2- 2
2- 5
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 5
4- 8
4-11
280.0
2- 4
2- 8
2-11
3- 3
3- 7
3-10
4- 2
4- 6
4- 9
5- 0
5- 3
290.0
2- 6
2-10
3- 2
3- 6
3-10
4- 2
4- 6
4- 9
5- 1
5- 5
5- 8
300.0
2- 8
3- 0
3- 4
3- 9
4- 1
4- 5
4- 9
5- 1
5- 5
5- 9
6- 1
310.0
2-10
3- 3
3- 7
4- 0
4- 4
4- 9
5- 1
5- 6
5-10
6- 2
6- 6
320.0
3- 0
3- 5
3-10
4- 3
4- 8
5- 0
5- 5
5-10
6- 2
6- 7
6-11
330.0
3- 3
3- 8
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 7
6-11
7- 4
340.0
3- 5
3-10
4- 4
4- 9
5- 3
5- 8
6- 2
6- 7
7- 0
7- 5
7- 9
350.0
3- 8
4- 1
4- 7
5- 1
5- 6
6- 0
6- 6
6-11
7- 5
7-10
8- 3

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 23 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING
Ruling Span: 325.0 Feet

INITIAL SAG CHART


H Tens
1608. 1458. 1318. 1191. 1078.
980.
897.
826.
766.
715.
671.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
1-11
2- 2
2- 4
2- 7
2-10
3- 2
3- 5
3- 9
4- 0
4- 4
4- 7
300.0
2- 1
2- 3
2- 6
2- 9
3- 1
3- 4
3- 8
4- 0
4- 4
4- 7
4-11
310.0
2- 3
2- 5
2- 8
3- 0
3- 3
3- 7
3-11
4- 3
4- 7
4-11
5- 3
320.0
2- 4
2- 7
2-10
3- 2
3- 6
3-10
4- 2
4- 6
4-11
5- 3
5- 7
330.0
2- 6
2- 9
3- 0
3- 4
3- 8
4- 1
4- 5
4-10
5- 2
5- 7
5-11
340.0
2- 8
2-11
3- 3
3- 7
3-11
4- 4
4- 9
5- 1
5- 6
5-11
6- 3
350.0
2-10
3- 1
3- 5
3- 9
4- 2
4- 7
5- 0
5- 5
5-10
6- 3
6- 8
360.0
3- 0
3- 3
3- 7
4- 0
4- 5
4-10
5- 3
5- 9
6- 2
6- 7
7- 1
370.0
3- 2
3- 5
3-10
4- 3
4- 8
5- 1
5- 7
6- 1
6- 6
7- 0
7- 5
380.0
3- 4
3- 8
4- 0
4- 5
4-11
5- 5
5-11
6- 5
6-11
7- 4
7-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2945 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1561. 2942. 2059.
969.
526.
409.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----290.0
2- 0
5- 1
5- 1
4- 7
5-10
7- 6
300.0
2- 2
5- 6
5- 5
4-11
6- 3
8- 0
310.0
2- 3
5-10
5- 9
5- 3
6- 8
8- 7
320.0
2- 5
6- 3
6- 2
5- 7
7- 1
9- 2
330.0
2- 7
6- 7
6- 6
5-11
7- 7
9- 9
340.0
2- 9
7- 0
6-11
6- 4
8- 0 10- 4
350.0
2-11
7- 5
7- 4
6- 8
8- 6 10-11
360.0
3- 1
7-10
7- 9
7- 1
9- 0 11- 7
370.0
3- 3
8- 3
8- 2
7- 6
9- 6 12- 2
380.0
3- 5
8- 9
8- 8
7-11 10- 0 12-10
FINAL SAG CHART
H Tens
1238. 1109. 1000.
910.
835.
772.
719.
675.
636.
603.
574.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
2- 6
2- 9
3- 1
3- 5
3- 8
4- 0
4- 3
4- 7
4-10
5- 1
5- 4
300.0
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
4- 7
4-11
5- 2
5- 5
5- 9
310.0
2-10
3- 2
3- 6
3-10
4- 3
4- 7
4-11
5- 2
5- 6
5-10
6- 1
320.0
3- 0
3- 5
3- 9
4- 1
4- 6
4-10
5- 2
5- 7
5-11
6- 2
6- 6
330.0
3- 3
3- 7
4- 0
4- 5
4- 9
5- 2
5- 6
5-11
6- 3
6- 7
6-11
340.0
3- 5
3-10
4- 3
4- 8
5- 1
5- 6
5-10
6- 3
6- 8
7- 0
7- 4
350.0
3- 8
4- 1
4- 6
4-11
5- 4
5-10
6- 3
6- 8
7- 0
7- 5
7- 9
360.0
3-10
4- 3
4- 9
5- 2
5- 8
6- 2
6- 7
7- 0
7- 5
7-10
8- 3
370.0
4- 1
4- 6
5- 0
5- 6
6- 0
6- 6
6-11
7- 5
7-10
8- 3
8- 8
380.0
4- 3
4- 9
5- 3
5-10
6- 4
6-10
7- 4
7-10
8- 3
8- 9
9- 2

Section WSC02
Page 24 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

266.8 Kcmil 18/ 1 Stranding ACSR Conductor WAXWING


Ruling Span: 350.0 Feet
INITIAL SAG CHART
H Tens
1626. 1481. 1346. 1223. 1114. 1019.
937.
867.
807.
755.
711.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----320.0
2- 4
2- 7
2-10
3- 1
3- 4
3- 8
4- 0
4- 4
4- 8
4-11
5- 3
330.0
2- 6
2- 8
3- 0
3- 3
3- 7
3-11
4- 3
4- 7
4-11
5- 3
5- 7
340.0
2- 7
2-10
3- 2
3- 6
3-10
4- 2
4- 6
4-11
5- 3
5- 7
5-11
350.0
2- 9
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 2
5- 7
5-11
6- 3
360.0
2-11
3- 3
3- 6
3-11
4- 3
4- 8
5- 1
5- 6
5-10
6- 3
6- 8
370.0
3- 1
3- 5
3- 9
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 7
7- 0
380.0
3- 3
3- 7
3-11
4- 4
4- 9
5- 2
5- 8
6- 1
6- 6
7- 0
7- 5
390.0
3- 5
3- 9
4- 2
4- 7
5- 0
5- 5
5-11
6- 5
6-11
7- 4
7-10
400.0
3- 7
3-11
4- 4
4- 9
5- 3
5- 9
6- 3
6- 9
7- 3
7- 9
8- 2
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3047 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
1540. 3043. 2138. 1009.
556.
432.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .290 1.417
.980
.421
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----320.0
2- 5
6- 0
5-11
5- 5
6- 9
8- 8
330.0
2- 7
6- 5
6- 3
5- 9
7- 2
9- 2
340.0
2- 9
6- 9
6- 8
6- 1
7- 7
9- 9
350.0
2-11
7- 2
7- 1
6- 5
8- 0 10- 4
360.0
3- 1
7- 7
7- 6
6-10
8- 6 10-11
370.0
3- 3
8- 0
7-11
7- 2
9- 0 11- 6
380.0
3- 5
8- 5
8- 4
7- 7
9- 6 12- 2
390.0
3- 7
8-11
8- 9
8- 0 10- 0 12-10
400.0
3-10
9- 4
9- 3
8- 5 10- 6 13- 6
FINAL SAG CHART
H Tens
1238. 1118. 1016.
931.
860.
799.
748.
704.
666.
633.
604.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----320.0
3- 0
3- 4
3- 8
4- 0
4- 4
4- 8
5- 0
5- 4
5- 7
5-11
6- 2
330.0
3- 3
3- 7
3-11
4- 3
4- 8
5- 0
5- 4
5- 8
6- 0
6- 3
6- 7
340.0
3- 5
3- 9
4- 2
4- 7
4-11
5- 3
5- 8
6- 0
6- 4
6- 8
7- 0
350.0
3- 8
4- 0
4- 5
4-10
5- 3
5- 7
6- 0
6- 4
6- 8
7- 1
7- 5
360.0
3-10
4- 3
4- 8
5- 1
5- 6
5-11
6- 4
6- 9
7- 1
7- 6
7-10
370.0
4- 1
4- 6
4-11
5- 4
5-10
6- 3
6- 8
7- 1
7- 6
7-11
8- 3
380.0
4- 3
4- 9
5- 2
5- 8
6- 2
6- 7
7- 0
7- 6
7-11
8- 4
8- 8
390.0
4- 6
5- 0
5- 6
6- 0
6- 6
6-11
7- 5
7-10
8- 4
8- 9
9- 2
400.0
4- 9
5- 3
5- 9
6- 3
6-10
7- 4
7-10
8- 3
8- 9
9- 2
9- 8

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 25 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN
Ruling Span: 100.0 Feet

INITIAL SAG CHART


H Tens
1922. 1573. 1251.
983.
786.
651.
559.
493.
444.
407.
377.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----80.0
0- 3
0- 4
0- 4
0- 6
0- 7
0- 8
0- 9
0-11
1- 0
1- 1
1- 2
90.0
0- 4
0- 5
0- 6
0- 7
0- 9
0-10
1- 0
1- 1
1- 3
1- 4
1- 5
100.0
0- 5
0- 5
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1- 9
110.0
0- 5
0- 6
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
1-10
2- 0
2- 1
120.0
0- 6
0- 8
0- 9
1- 0
1- 3
1- 6
1- 9
1-11
2- 2
2- 4
2- 6
130.0
0- 7
0- 9
0-11
1- 2
1- 5
1- 9
2- 0
2- 3
2- 6
2- 9
2-11
140.0
0- 8
0-10
1- 1
1- 4
1- 8
2- 0
2- 4
2- 7
2-11
3- 2
3- 5
150.0
0-10
1- 0
1- 2
1- 6
1-11
2- 3
2- 8
3- 0
3- 4
3- 8
3-11
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2634 lb
----------------------------------------------------------------------------Design: 2500. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
2541. 2416. 1448.
618.
321.
266.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----80.0
0- 2
0- 8
0- 9
0-11
1- 4
1- 7
90.0
0- 3
0- 9
1- 0
1- 1
1- 8
2- 0
100.0
0- 4
0-11
1- 2
1- 4
2- 1
2- 6
110.0
0- 4
1- 2
1- 5
1- 8
2- 6
3- 0
120.0
0- 5
1- 4
1- 8
2- 0
2-11
3- 7
130.0
0- 6
1- 7
2- 0
2- 4
3- 5
4- 2
140.0
0- 6
1-10
2- 4
2- 8
4- 0
4-10
150.0
0- 7
2- 1
2- 8
3- 1
4- 7
5- 6
FINAL SAG CHART
H Tens
1697. 1329. 1030.
814.
669.
571.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----80.0
0- 3
0- 4
0- 5
0- 7
0- 8
0- 9
90.0
0- 4
0- 5
0- 7
0- 8
0-10
1- 0
100.0
0- 5
0- 6
0- 8
0-10
1- 0
1- 2
110.0
0- 6
0- 8
0-10
1- 0
1- 3
1- 5
120.0
0- 7
0- 9
0-11
1- 2
1- 5
1- 8
130.0
0- 8
0-10
1- 1
1- 5
1- 8
2- 0
140.0
0- 9
1- 0
1- 3
1- 7
1-11
2- 3
150.0
0-11
1- 2
1- 5
1-10
2- 3
2- 7

502.
451.
412.
381.
356.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----0-10
1- 0
1- 1
1- 2
1- 2
1- 1
1- 2
1- 4
1- 5
1- 6
1- 4
1- 6
1- 7
1- 9
1-10
1- 7
1- 9
1-11
2- 1
2- 3
1-11
2- 1
2- 4
2- 6
2- 8
2- 3
2- 6
2- 8
2-11
3- 1
2- 7
2-10
3- 1
3- 4
3- 7
2-11
3- 3
3- 7
3-10
4- 2

Section WSC02
Page 26 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 125.0 Feet
INITIAL SAG CHART
H Tens
1643. 1345. 1097.
908.
771.
672.
599.
544.
500.
465.
436.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----80.0
0- 4
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
0-10
0-11
1- 0
90.0
0- 4
0- 5
0- 6
0- 7
0- 9
0-10
0-11
1- 0
1- 1
1- 2
1- 3
100.0
0- 5
0- 6
0- 8
0- 9
0-11
1- 0
1- 1
1- 3
1- 4
1- 5
1- 6
110.0
0- 6
0- 7
0- 9
0-11
1- 1
1- 2
1- 4
1- 6
1- 7
1- 9
1-10
120.0
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
2- 1
2- 2
130.0
0- 8
0-10
1- 0
1- 3
1- 6
1- 8
1-10
2- 1
2- 3
2- 5
2- 7
140.0
0-10
1- 0
1- 2
1- 5
1- 8
1-11
2- 2
2- 5
2- 7
2- 9
2-11
150.0
0-11
1- 2
1- 4
1- 8
1-11
2- 3
2- 6
2- 9
2-11
3- 2
3- 5
160.0
1- 1
1- 3
1- 7
1-10
2- 2
2- 6
2-10
3- 1
3- 4
3- 7
3-10
170.0
1- 2
1- 5
1- 9
2- 1
2- 6
2-10
3- 2
3- 6
3- 9
4- 1
4- 4
180.0
1- 4
1- 7
1-11
2- 4
2- 9
3- 2
3- 7
3-11
4- 3
4- 7
4-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2500 lb
----------------------------------------------------------------------------Design: 2500. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
2122. 2410. 1521.
677.
374.
313.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----80.0
0- 3
0- 8
0- 9
0-10
1- 2
1- 4
90.0
0- 3
0- 9
0-11
1- 0
1- 5
1- 9
100.0
0- 4
0-11
1- 2
1- 3
1- 9
2- 1
110.0
0- 5
1- 2
1- 4
1- 6
2- 2
2- 7
120.0
0- 6
1- 4
1- 7
1-10
2- 6
3- 0
130.0
0- 7
1- 7
1-11
2- 1
3- 0
3- 6
140.0
0- 8
1-10
2- 2
2- 5
3- 5
4- 1
150.0
0- 9
2- 1
2- 6
2- 9
3-11
4- 8
160.0
0-10
2- 5
2-10
3- 2
4- 6
5- 4
170.0
0-11
2- 8
3- 3
3- 7
5- 1
6- 0
180.0
1- 0
3- 0
3- 7
4- 0
5- 8
6- 9
FINAL SAG CHART
H Tens
1394. 1122.
921.
779.
677.
603.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----80.0
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
90.0
0- 5
0- 6
0- 7
0- 9
0-10
0-11
100.0
0- 6
0- 7
0- 9
0-10
1- 0
1- 1
110.0
0- 7
0- 9
0-11
1- 1
1- 2
1- 4
120.0
0- 9
0-10
1- 1
1- 3
1- 5
1- 7
130.0
0-10
1- 0
1- 3
1- 5
1- 8
1-10
140.0
0-11
1- 2
1- 5
1- 8
1-11
2- 2
150.0
1- 1
1- 4
1- 7
1-11
2- 2
2- 5
160.0
1- 3
1- 6
1-10
2- 2
2- 6
2- 9
170.0
1- 5
1- 9
2- 1
2- 5
2-10
3- 2
180.0
1- 7
1-11
2- 4
2- 9
3- 2
3- 6

547.
503.
467.
438.
413.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----0-10
0-10
0-11
1- 0
1- 1
1- 0
1- 1
1- 2
1- 3
1- 4
1- 3
1- 4
1- 5
1- 6
1- 7
1- 6
1- 7
1- 9
1-10
1-11
1- 9
1-11
2- 0
2- 2
2- 4
2- 1
2- 3
2- 5
2- 7
2- 8
2- 4
2- 7
2- 9
2-11
3- 1
2- 8
2-11
3- 2
3- 4
3- 7
3- 1
3- 4
3- 7
3-10
4- 1
3- 6
3- 9
4- 1
4- 4
4- 7
3-11
4- 3
4- 6
4-10
5- 2

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 27 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 150.0 Feet
INITIAL SAG CHART
H Tens
1381. 1159.
987.
858.
761.
687.
628.
582.
543.
511.
484.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
0- 6
0- 7
0- 8
0-10
0-11
1- 0
1- 1
1- 2
1- 3
1- 4
1- 5
110.0
0- 7
0- 9
0-10
0-11
1- 1
1- 2
1- 3
1- 5
1- 6
1- 7
1- 8
120.0
0- 9
0-10
1- 0
1- 2
1- 3
1- 5
1- 6
1- 8
1- 9
1-10
2- 0
130.0
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1- 9
1-11
2- 1
2- 2
2- 4
140.0
1- 0
1- 2
1- 4
1- 6
1- 9
1-11
2- 1
2- 3
2- 5
2- 6
2- 8
150.0
1- 1
1- 4
1- 6
1- 9
1-11
2- 2
2- 4
2- 7
2- 9
2-11
3- 1
160.0
1- 3
1- 6
1- 9
2- 0
2- 3
2- 5
2- 8
2-11
3- 1
3- 3
3- 6
170.0
1- 5
1- 8
1-11
2- 3
2- 6
2- 9
3- 0
3- 3
3- 6
3- 8
3-11
180.0
1- 7
1-10
2- 2
2- 6
2-10
3- 1
3- 5
3- 8
3-11
4- 2
4- 5
190.0
1- 9
2- 1
2- 5
2- 9
3- 1
3- 5
3- 9
4- 1
4- 4
4- 7
4-11
200.0
1-11
2- 3
2- 8
3- 1
3- 5
3-10
4- 2
4- 6
4-10
5- 1
5- 5
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2500 lb
----------------------------------------------------------------------------Design: 2500. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
1712. 2413. 1581.
722.
422.
355.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----100.0
0- 5
0-11
1- 1
1- 2
1- 7
1-10
110.0
0- 6
1- 2
1- 4
1- 5
1-11
2- 3
120.0
0- 7
1- 4
1- 7
1- 8
2- 3
2- 8
130.0
0- 8
1- 7
1-10
2- 0
2- 8
3- 1
140.0
0- 9
1-10
2- 1
2- 3
3- 1
3- 7
150.0
0-11
2- 1
2- 5
2- 7
3- 6
4- 2
160.0
1- 0
2- 5
2- 9
3- 0
4- 0
4- 9
170.0
1- 2
2- 8
3- 1
3- 4
4- 6
5- 4
180.0
1- 3
3- 0
3- 6
3- 9
5- 0
5-11
190.0
1- 5
3- 4
3-10
4- 2
5- 7
6- 8
200.0
1- 7
3- 8
4- 3
4- 7
6- 2
7- 4
FINAL SAG CHART
H Tens
1168.
989.
858.
760.
686.
628.
581.
543.
511.
484.
460.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
0- 7
0- 8
0-10
0-11
1- 0
1- 1
1- 2
1- 3
1- 4
1- 5
1- 5
110.0
0- 9
0-10
0-11
1- 1
1- 2
1- 3
1- 5
1- 6
1- 7
1- 8
1- 9
120.0
0-10
1- 0
1- 2
1- 3
1- 5
1- 6
1- 8
1- 9
1-10
2- 0
2- 1
130.0
1- 0
1- 2
1- 4
1- 6
1- 8
1- 9
1-11
2- 1
2- 2
2- 4
2- 5
140.0
1- 2
1- 4
1- 6
1- 9
1-11
2- 1
2- 3
2- 5
2- 6
2- 8
2-10
150.0
1- 3
1- 6
1- 9
2- 0
2- 2
2- 4
2- 7
2- 9
2-11
3- 1
3- 3
160.0
1- 6
1- 9
2- 0
2- 3
2- 6
2- 8
2-11
3- 1
3- 3
3- 6
3- 8
170.0
1- 8
1-11
2- 3
2- 6
2- 9
3- 0
3- 3
3- 6
3- 8
3-11
4- 1
180.0
1-10
2- 2
2- 6
2-10
3- 1
3- 5
3- 8
3-11
4- 2
4- 5
4- 7
190.0
2- 1
2- 5
2- 9
3- 1
3- 5
3- 9
4- 1
4- 4
4- 7
4-11
5- 2
200.0
2- 3
2- 8
3- 1
3- 5
3-10
4- 2
4- 6
4-10
5- 1
5- 5
5- 8

Section WSC02
Page 28 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 175.0 Feet
INITIAL SAG CHART
H Tens
1183. 1032.
916.
826.
754.
697.
649.
610.
576.
547.
522.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
1- 0
1- 1
1- 3
1- 4
1- 6
1- 7
1- 9
1-10
1-11
2- 0
2- 2
140.0
1- 1
1- 3
1- 5
1- 7
1- 9
1-10
2- 0
2- 1
2- 3
2- 4
2- 6
150.0
1- 3
1- 5
1- 8
1-10
2- 0
2- 2
2- 3
2- 5
2- 7
2- 8
2-10
160.0
1- 5
1- 8
1-10
2- 1
2- 3
2- 5
2- 7
2- 9
2-11
3- 1
3- 3
170.0
1- 7
1-10
2- 1
2- 4
2- 6
2- 9
2-11
3- 1
3- 3
3- 6
3- 8
180.0
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 3
3- 6
3- 8
3-11
4- 1
190.0
2- 0
2- 4
2- 7
2-10
3- 2
3- 5
3- 8
3-11
4- 1
4- 4
4- 6
200.0
2- 3
2- 7
2-10
3- 2
3- 6
3- 9
4- 0
4- 3
4- 6
4- 9
5- 0
210.0
2- 5
2-10
3- 2
3- 6
3-10
4- 2
4- 5
4- 9
5- 0
5- 3
5- 6
220.0
2- 8
3- 1
3- 6
3-10
4- 2
4- 7
4-10
5- 2
5- 6
5- 9
6- 1
230.0
2-11
3- 4
3- 9
4- 2
4- 7
5- 0
5- 4
5- 8
6- 0
6- 4
6- 7
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2500 lb
----------------------------------------------------------------------------Design: 2500. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
1385. 2419. 1629.
757.
463.
392.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----130.0
0-10
1- 7
1- 9
1-11
2- 5
2-10
140.0
0-11
1-10
2- 1
2- 2
2- 9
3- 3
150.0
1- 1
2- 1
2- 4
2- 6
3- 2
3- 9
160.0
1- 3
2- 5
2- 8
2-10
3- 8
4- 3
170.0
1- 5
2- 8
3- 0
3- 2
4- 1
4-10
180.0
1- 7
3- 0
3- 4
3- 7
4- 7
5- 5
190.0
1- 9
3- 4
3- 9
4- 0
5- 1
6- 0
200.0
1-11
3- 8
4- 2
4- 5
5- 8
6- 8
210.0
2- 1
4- 1
4- 7
4-10
6- 3
7- 4
220.0
2- 4
4- 6
5- 0
5- 4
6-10
8- 1
230.0
2- 6
4-10
5- 6
5-10
7- 5
8-10
FINAL SAG CHART
H Tens
1027.
910.
820.
750.
693.
646.
607.
574.
546.
521.
499.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
1- 1
1- 3
1- 5
1- 6
1- 7
1- 9
1-10
1-11
2- 1
2- 2
2- 3
140.0
1- 3
1- 5
1- 7
1- 9
1-10
2- 0
2- 2
2- 3
2- 4
2- 6
2- 7
150.0
1- 6
1- 8
1-10
2- 0
2- 2
2- 4
2- 5
2- 7
2- 9
2-10
3- 0
160.0
1- 8
1-10
2- 1
2- 3
2- 5
2- 7
2- 9
2-11
3- 1
3- 3
3- 4
170.0
1-10
2- 1
2- 4
2- 6
2- 9
2-11
3- 1
3- 4
3- 6
3- 8
3-10
180.0
2- 1
2- 4
2- 7
2-10
3- 1
3- 3
3- 6
3- 8
3-11
4- 1
4- 3
190.0
2- 4
2- 7
2-11
3- 2
3- 5
3- 8
3-11
4- 1
4- 4
4- 6
4- 9
200.0
2- 7
2-11
3- 2
3- 6
3- 9
4- 1
4- 4
4- 7
4- 9
5- 0
5- 3
210.0
2-10
3- 2
3- 6
3-10
4- 2
4- 6
4- 9
5- 0
5- 3
5- 6
5- 9
220.0
3- 1
3- 6
3-10
4- 3
4- 7
4-11
5- 2
5- 6
5- 9
6- 1
6- 4
230.0
3- 5
3-10
4- 3
4- 7
5- 0
5- 4
5- 8
6- 0
6- 4
6- 7
6-11

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 29 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN
Ruling Span: 200.0 Feet

INITIAL SAG CHART


H Tens
2563. 2251. 1957. 1691. 1463. 1276. 1127. 1010.
917.
842.
781.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----170.0
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 1
2- 3
2- 5
180.0
0-10
1- 0
1- 1
1- 3
1- 6
1- 8
1-11
2- 1
2- 4
2- 6
2- 9
190.0
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 4
2- 7
2-10
3- 0
200.0
1- 1
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 4
210.0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 5
3- 8
220.0
1- 3
1- 5
1- 8
1-11
2- 2
2- 6
2-10
3- 2
3- 6
3- 9
4- 1
230.0
1- 5
1- 7
1-10
2- 1
2- 5
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
240.0
1- 6
1- 8
1-11
2- 3
2- 7
3- 0
3- 4
3- 9
4- 1
4- 6
4-10
250.0
1- 7
1-10
2- 1
2- 5
2-10
3- 3
3- 8
4- 1
4- 5
4-10
5- 3
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3580 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
2875. 3447. 2353. 1138.
627.
494.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----170.0
0- 8
1-11
2- 1
2- 2
3- 0
3-10
180.0
0- 9
2- 1
2- 4
2- 5
3- 5
4- 3
190.0
0-10
2- 4
2- 7
2- 8
3- 9
4- 9
200.0
0-11
2- 7
2-11
2-11
4- 2
5- 3
210.0
1- 0
2-10
3- 2
3- 3
4- 7
5-10
220.0
1- 2
3- 2
3- 6
3- 7
5- 1
6- 5
230.0
1- 3
3- 5
3-10
3-10
5- 6
7- 0
240.0
1- 4
3- 9
4- 2
4- 3
6- 0
7- 7
250.0
1- 5
4- 1
4- 6
4- 7
6- 6
8- 3
FINAL SAG CHART
H Tens
2124. 1808. 1543. 1332. 1167. 1039.
939.
860.
795.
742.
698.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----170.0
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 0
2- 3
2- 5
2- 7
2- 9
180.0
1- 0
1- 2
1- 5
1- 7
1-10
2- 1
2- 3
2- 6
2- 8
2-10
3- 1
190.0
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 6
2- 9
3- 0
3- 2
3- 5
200.0
1- 3
1- 6
1- 9
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
3- 6
3- 9
210.0
1- 5
1- 7
1-11
2- 2
2- 6
2- 9
3- 1
3- 4
3- 8
3-11
4- 2
220.0
1- 6
1- 9
2- 1
2- 5
2- 9
3- 1
3- 5
3- 8
4- 0
4- 3
4- 6
230.0
1- 8
1-11
2- 3
2- 7
3- 0
3- 4
3- 8
4- 0
4- 4
4- 8
4-11
240.0
1-10
2- 1
2- 6
2-10
3- 3
3- 8
4- 0
4- 5
4- 9
5- 1
5- 5
250.0
1-11
2- 3
2- 8
3- 1
3- 6
3-11
4- 4
4- 9
5- 2
5- 6
5-10

Section WSC02
Page 30 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 225.0 Feet
INITIAL SAG CHART
H Tens
2591. 2291. 2010. 1757. 1540. 1360. 1215. 1098. 1003.
926.
862.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----190.0
0-11
1- 1
1- 2
1- 4
1- 7
1- 9
2- 0
2- 2
2- 4
2- 7
2- 9
200.0
1- 0
1- 2
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 7
2-10
3- 1
210.0
1- 2
1- 3
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
2-11
3- 2
3- 4
220.0
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-11
3- 2
3- 5
3- 8
230.0
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 5
3- 9
4- 0
240.0
1- 6
1- 8
1-11
2- 2
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 4
250.0
1- 7
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 9
4- 1
4- 5
4- 9
260.0
1- 9
1-11
2- 3
2- 6
2-11
3- 3
3- 8
4- 0
4- 5
4- 9
5- 1
270.0
1-10
2- 1
2- 5
2- 9
3- 1
3- 6
3-11
4- 4
4- 9
5- 2
5- 6
280.0
2- 0
2- 3
2- 7
2-11
3- 4
3- 9
4- 3
4- 8
5- 1
5- 6
5-11
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3742 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
2836. 3608. 2501. 1228.
692.
542.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----190.0
0-10
2- 3
2- 5
2- 6
3- 5
4- 4
200.0
0-11
2- 6
2- 9
2- 9
3- 9
4-10
210.0
1- 1
2- 9
3- 0
3- 0
4- 2
5- 4
220.0
1- 2
3- 0
3- 3
3- 3
4- 7
5-10
230.0
1- 3
3- 3
3- 7
3- 7
5- 0
6- 4
240.0
1- 4
3- 7
3-11
3-11
5- 5
6-11
250.0
1- 6
3-10
4- 3
4- 3
5-11
7- 6
260.0
1- 7
4- 2
4- 7
4- 7
6- 4
8- 1
270.0
1- 8
4- 6
4-11
4-11
6-10
8- 9
280.0
1-10
4-10
5- 3
5- 4
7- 5
9- 5
FINAL SAG CHART
H Tens
2124. 1830. 1586. 1389. 1234. 1111.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----190.0
1- 2
1- 4
1- 6
1- 9
1-11
2- 2
200.0
1- 3
1- 5
1- 8
1-11
2- 2
2- 4
210.0
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
220.0
1- 6
1- 9
2- 0
2- 4
2- 7
2-10
230.0
1- 8
1-11
2- 2
2- 6
2-10
3- 2
240.0
1-10
2- 1
2- 5
2- 9
3- 1
3- 5
250.0
1-11
2- 3
2- 7
2-11
3- 4
3- 8
260.0
2- 1
2- 5
2-10
3- 2
3- 7
4- 0
270.0
2- 3
2- 7
3- 0
3- 5
3-10
4- 4
280.0
2- 5
2-10
3- 3
3- 8
4- 2
4- 7

1012.
933.
867.
813.
767.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----2- 4
2- 7
2- 9
2-11
3- 1
2- 7
2-10
3- 0
3- 3
3- 5
2-10
3- 1
3- 4
3- 7
3- 9
3- 2
3- 5
3- 8
3-11
4- 2
3- 5
3- 9
4- 0
4- 3
4- 6
3- 9
4- 0
4- 4
4- 8
4-11
4- 0
4- 5
4- 9
5- 0
5- 4
4- 4
4- 9
5- 1
5- 5
5- 9
4- 8
5- 1
5- 6
5-10
6- 2
5- 1
5- 6
5-11
6- 3
6- 8

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 31 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN
Ruling Span: 250.0 Feet

INITIAL SAG CHART


H Tens
2610. 2322. 2055. 1815. 1608. 1436. 1294. 1178. 1082. 1004.
938.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
1- 2
1- 3
1- 5
1- 7
1-10
2- 0
2- 3
2- 6
2- 8
2-11
3- 1
220.0
1- 3
1- 5
1- 7
1- 9
2- 0
2- 3
2- 6
2- 8
2-11
3- 2
3- 5
230.0
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 8
2-11
3- 2
3- 5
3- 8
240.0
1- 6
1- 8
1-10
2- 1
2- 4
2- 8
2-11
3- 3
3- 6
3- 9
4- 0
250.0
1- 7
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 6
3- 9
4- 1
4- 4
260.0
1- 9
1-11
2- 2
2- 5
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
270.0
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
4- 1
4- 5
4- 9
5- 1
280.0
2- 0
2- 3
2- 6
2-10
3- 2
3- 7
4- 0
4- 4
4- 9
5- 1
5- 5
290.0
2- 2
2- 5
2- 8
3- 1
3- 5
3-10
4- 3
4- 8
5- 1
5- 6
5-10
300.0
2- 3
2- 7
2-11
3- 3
3- 8
4- 1
4- 7
5- 0
5- 5
5-10
6- 3
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3894 lb
----------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
----------------------------------------------------------------------------H Tens
2795. 3762. 2640. 1311.
755.
588.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----210.0
1- 1
2- 8
2-10
2-10
3-10
4-11
220.0
1- 2
2-11
3- 1
3- 1
4- 2
5- 4
230.0
1- 3
3- 2
3- 5
3- 4
4- 7
5-10
240.0
1- 5
3- 5
3- 8
3- 8
5- 0
6- 5
250.0
1- 6
3- 9
4- 0
4- 0
5- 5
6-11
260.0
1- 7
4- 0
4- 4
4- 3
5-10
7- 6
270.0
1- 9
4- 4
4- 8
4- 7
6- 4
8- 1
280.0
1-10
4- 8
5- 0
5- 0
6- 9
8- 8
290.0
2- 0
5- 0
5- 4
5- 4
7- 3
9- 4
300.0
2- 2
5- 4
5- 9
5- 8
7- 9 10- 0
FINAL SAG CHART
H Tens
2124. 1851. 1625. 1442. 1294. 1176.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----210.0
1- 5
1- 7
1-10
2- 0
2- 3
2- 6
220.0
1- 6
1- 9
2- 0
2- 3
2- 6
2- 8
230.0
1- 8
1-11
2- 2
2- 5
2- 8
2-11
240.0
1-10
2- 1
2- 4
2- 8
2-11
3- 3
250.0
1-11
2- 3
2- 6
2-10
3- 2
3- 6
260.0
2- 1
2- 5
2- 9
3- 1
3- 5
3- 9
270.0
2- 3
2- 7
2-11
3- 4
3- 8
4- 1
280.0
2- 5
2- 9
3- 2
3- 7
4- 0
4- 4
290.0
2- 7
3- 0
3- 5
3-10
4- 3
4- 8
300.0
2- 9
3- 2
3- 8
4- 1
4- 7
5- 0

1080. 1001.
935.
880.
832.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----2- 8
2-11
3- 1
3- 3
3- 6
2-11
3- 2
3- 5
3- 7
3-10
3- 3
3- 6
3- 8
3-11
4- 2
3- 6
3- 9
4- 0
4- 3
4- 6
3- 9
4- 1
4- 4
4- 8
4-11
4- 1
4- 5
4- 9
5- 0
5- 4
4- 5
4- 9
5- 1
5- 5
5- 9
4- 9
5- 1
5- 6
5-10
6- 2
5- 1
5- 6
5-10
6- 3
6- 7
5- 5
5-10
6- 3
6- 8
7- 1

Section WSC02
Page 32 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 275.0 Feet
INITIAL SAG CHART
H Tens
2563. 2291. 2042. 1821. 1631. 1472. 1339. 1229. 1138. 1061.
996.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 5
1- 6
1- 9
1-11
2- 2
2- 4
2- 7
2-10
3- 1
3- 3
3- 6
240.0
1- 6
1- 8
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 4
3- 7
3- 9
250.0
1- 7
1-10
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
3- 7
3-10
4- 1
260.0
1- 9
1-11
2- 2
2- 5
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 5
270.0
1-11
2- 1
2- 4
2- 8
2-11
3- 3
3- 7
3-11
4- 2
4- 6
4- 9
280.0
2- 0
2- 3
2- 6
2-10
3- 2
3- 6
3-10
4- 2
4- 6
4-10
5- 2
290.0
2- 2
2- 5
2- 9
3- 0
3- 5
3- 9
4- 1
4- 6
4-10
5- 2
5- 6
300.0
2- 4
2- 7
2-11
3- 3
3- 7
4- 0
4- 5
4- 9
5- 2
5- 6
5-11
310.0
2- 6
2- 9
3- 1
3- 6
3-10
4- 3
4- 8
5- 1
5- 6
5-11
6- 3
320.0
2- 8
2-11
3- 3
3- 8
4- 1
4- 7
5- 0
5- 5
5-10
6- 4
6- 8
330.0
2-10
3- 1
3- 6
3-11
4- 4
4-10
5- 4
5- 9
6- 3
6- 8
7- 1
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
----------------------------------------------------------------------------Design: 4000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
2693. 3872. 2744. 1372.
809.
630.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----230.0
1- 4
3- 1
3- 3
3- 3
4- 3
5- 6
240.0
1- 5
3- 4
3- 7
3- 6
4- 8
6- 0
250.0
1- 7
3- 7
3-10
3-10
5- 1
6- 6
260.0
1- 8
3-11
4- 2
4- 1
5- 5
7- 0
270.0
1-10
4- 2
4- 6
4- 5
5-11
7- 7
280.0
1-11
4- 6
4-10
4- 9
6- 4
8- 1
290.0
2- 1
4-10
5- 2
5- 1
6- 9
8- 8
300.0
2- 2
5- 2
5- 6
5- 5
7- 3
9- 4
310.0
2- 4
5- 6
5-11
5-10
7- 9
9-11
320.0
2- 6
5-11
6- 3
6- 2
8- 3 10- 7
330.0
2- 8
6- 3
6- 8
6- 7
8- 9 11- 3
FINAL SAG CHART
H Tens
2075. 1831. 1628. 1463. 1328. 1218.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----230.0
1- 8
1-11
2- 2
2- 5
2- 7
2-10
240.0
1-10
2- 1
2- 4
2- 7
2-10
3- 1
250.0
2- 0
2- 3
2- 6
2-10
3- 1
3- 4
260.0
2- 2
2- 5
2- 9
3- 0
3- 4
3- 8
270.0
2- 4
2- 7
2-11
3- 3
3- 7
3-11
280.0
2- 6
2-10
3- 2
3- 6
3-10
4- 3
290.0
2- 8
3- 0
3- 5
3- 9
4- 2
4- 6
300.0
2-10
3- 3
3- 7
4- 0
4- 5
4-10
310.0
3- 0
3- 5
3-10
4- 4
4- 9
5- 2
320.0
3- 3
3- 8
4- 1
4- 7
5- 0
5- 6
330.0
3- 5
3-11
4- 4
4-10
5- 4
5-10

1128. 1052.
988.
933.
886.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----3- 1
3- 4
3- 6
3- 9
3-11
3- 4
3- 7
3-10
4- 0
4- 3
3- 8
3-11
4- 2
4- 5
4- 7
3-11
4- 2
4- 6
4- 9
5- 0
4- 3
4- 6
4-10
5- 1
5- 4
4- 7
4-10
5- 2
5- 6
5- 9
4-10
5- 3
5- 7
5-11
6- 2
5- 3
5- 7
5-11
6- 3
6- 7
5- 7
6- 0
6- 4
6- 9
7- 1
5-11
6- 4
6- 9
7- 2
7- 6
6- 4
6- 9
7- 2
7- 7
8- 0

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 33 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN
Ruling Span: 300.0 Feet

INITIAL SAG CHART


H Tens
2356. 2116. 1902. 1716. 1559. 1426. 1315. 1221. 1142. 1075. 1016.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----270.0
2- 1
2- 3
2- 6
2-10
3- 1
3- 4
3- 8
3-11
4- 2
4- 5
4- 8
280.0
2- 2
2- 5
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 6
4- 9
5- 0
290.0
2- 4
2- 7
2-11
3- 3
3- 6
3-10
4- 2
4- 6
4-10
5- 1
5- 5
300.0
2- 6
2-10
3- 1
3- 5
3- 9
4- 2
4- 6
4-10
5- 2
5- 6
5- 9
310.0
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 2
5- 6
5-10
6- 2
320.0
2-10
3- 2
3- 6
3-11
4- 4
4- 8
5- 1
5- 6
5-10
6- 3
6- 7
330.0
3- 0
3- 4
3- 9
4- 2
4- 7
5- 0
5- 5
5-10
6- 3
6- 7
7- 0
340.0
3- 3
3- 7
4- 0
4- 5
4-10
5- 4
5- 9
6- 2
6- 7
7- 0
7- 5
350.0
3- 5
3- 9
4- 3
4- 8
5- 2
5- 7
6- 1
6- 6
7- 0
7- 5
7-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
----------------------------------------------------------------------------Design: 4000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
2437. 3882. 2770. 1385.
842.
661.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----270.0
2- 0
4- 2
4- 5
4- 5
5- 8
7- 2
280.0
2- 2
4- 6
4- 9
4- 8
6- 1
7- 9
290.0
2- 3
4-10
5- 1
5- 1
6- 6
8- 3
300.0
2- 5
5- 2
5- 6
5- 5
7- 0
8-10
310.0
2- 7
5- 6
5-10
5- 9
7- 5
9- 6
320.0
2- 9
5-10
6- 3
6- 2
7-11 10- 1
330.0
2-11
6- 3
6- 7
6- 6
8- 5 10- 9
340.0
3- 1
6- 7
7- 0
6-11
8-11 11- 5
350.0
3- 4
7- 0
7- 5
7- 4
9- 6 12- 1
FINAL SAG CHART
H Tens
1916. 1716. 1552. 1416. 1304. 1211.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----270.0
2- 6
2-10
3- 1
3- 5
3- 8
3-11
280.0
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
290.0
2-11
3- 3
3- 7
3-11
4- 3
4- 6
300.0
3- 1
3- 5
3-10
4- 2
4- 6
4-10
310.0
3- 3
3- 8
4- 1
4- 5
4-10
5- 2
320.0
3- 6
3-11
4- 4
4- 9
5- 2
5- 6
330.0
3- 9
4- 2
4- 7
5- 0
5- 5
5-10
340.0
3-11
4- 5
4-10
5- 4
5- 9
6- 3
350.0
4- 2
4- 8
5- 2
5- 8
6- 2
6- 7

1132. 1066. 1008.


958.
915.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----4- 3
4- 6
4- 9
5- 0
5- 2
4- 6
4-10
5- 1
5- 4
5- 7
4-10
5- 2
5- 5
5- 9
6- 0
5- 2
5- 6
5-10
6- 2
6- 5
5- 6
5-11
6- 3
6- 6
6-10
5-11
6- 3
6- 7
7- 0
7- 4
6- 3
6- 8
7- 0
7- 5
7- 9
6- 8
7- 1
7- 6
7-10
8- 3
7- 1
7- 6
7-11
8- 4
8- 9

Section WSC02
Page 34 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477.0 Kcmil 18/ 1 Stranding ACSR Conductor PELICAN


Ruling Span: 325.0 Feet
INITIAL SAG CHART
H Tens
2169. 1963. 1784. 1630. 1500. 1389. 1295. 1215. 1146. 1086. 1033.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
2- 7
2-10
3- 1
3- 5
3- 8
4- 0
4- 3
4- 6
4-10
5- 1
5- 4
300.0
2- 9
3- 0
3- 4
3- 7
3-11
4- 3
4- 7
4-10
5- 2
5- 5
5- 8
310.0
2-11
3- 3
3- 6
3-10
4- 2
4- 6
4-10
5- 2
5- 6
5- 9
6- 1
320.0
3- 1
3- 5
3- 9
4- 1
4- 6
4-10
5- 2
5- 6
5-10
6- 2
6- 6
330.0
3- 4
3- 8
4- 0
4- 4
4- 9
5- 1
5- 6
5-10
6- 2
6- 6
6-10
340.0
3- 6
3-10
4- 3
4- 8
5- 0
5- 5
5-10
6- 2
6- 7
6-11
7- 3
350.0
3- 8
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 7
7- 0
7- 4
7- 9
360.0
3-11
4- 4
4- 9
5- 2
5- 8
6- 1
6- 6
6-11
7- 4
7- 9
8- 2
370.0
4- 2
4- 7
5- 0
5- 6
5-11
6- 5
6-11
7- 4
7- 9
8- 3
8- 8
380.0
4- 4
4-10
5- 3
5- 9
6- 3
6- 9
7- 3
7- 9
8- 2
8- 8
9- 1
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
----------------------------------------------------------------------------Design: 4000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
----------------------------------------------------------------------------H Tens
2214. 3890. 2793. 1396.
871.
690.
(LBS)
----- ----- ----- ----- ----- ----Temp >
-20.
0.
32.
60.
120.
212.
Wt lb/f> .518 1.766 1.335
.659
.518
.518
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----290.0
2- 6
4-10
5- 1
5- 0
6- 4
7-11
300.0
2- 8
5- 2
5- 5
5- 4
6- 9
8- 6
310.0
2-10
5- 6
5- 9
5- 9
7- 2
9- 1
320.0
3- 0
5-10
6- 2
6- 1
7- 8
9- 8
330.0
3- 3
6- 3
6- 7
6- 6
8- 2 10- 3
340.0
3- 5
6- 7
6-11
6-10
8- 8 10-11
350.0
3- 8
7- 0
7- 4
7- 3
9- 2 11- 7
360.0
3-10
7- 5
7- 9
7- 8
9- 8 12- 3
370.0
4- 1
7-10
8- 3
8- 1 10- 3 12-11
380.0
4- 3
8- 3
8- 8
8- 7 10- 9 13- 7
FINAL SAG CHART
H Tens
1787. 1625. 1491. 1379. 1285. 1205.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----290.0
3- 1
3- 5
3- 8
4- 0
4- 3
4- 7
300.0
3- 4
3- 8
3-11
4- 3
4- 7
4-11
310.0
3- 6
3-10
4- 3
4- 7
4-11
5- 2
320.0
3- 9
4- 1
4- 6
4-10
5- 2
5- 7
330.0
4- 0
4- 5
4- 9
5- 2
5- 6
5-11
340.0
4- 3
4- 8
5- 1
5- 6
5-10
6- 3
350.0
4- 6
4-11
5- 4
5-10
6- 3
6- 8
360.0
4- 9
5- 2
5- 8
6- 2
6- 7
7- 0
370.0
5- 0
5- 6
6- 0
6- 6
6-11
7- 5
380.0
5- 3
5-10
6- 4
6-10
7- 4
7-10

1136. 1077. 1026.


980.
----- ----- ----- ----60.
70.
80.
90.
Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----4-10
5- 1
5- 4
5- 7
5- 2
5- 5
5- 9
6- 0
5- 6
5-10
6- 1
6- 5
5-11
6- 2
6- 6
6-10
6- 3
6- 7
6-11
7- 3
6- 8
7- 0
7- 4
7- 8
7- 0
7- 5
7- 9
8- 2
7- 5
7-10
8- 3
8- 7
7-10
8- 3
8- 8
9- 1
8- 3
8- 9
9- 2
9- 7

940.
----100.
Ft-In
----5-10
6- 3
6- 8
7- 1
7- 7
8- 0
8- 6
9- 0
9- 6
10- 0

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 35 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN
Ruling Span: 150.0 Feet

INITIAL SAG CHART


H Tens
1767. 1611. 1453. 1297. 1144.
998.
863.
743.
643.
561.
497.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----110.0
0- 3
0- 4
0- 4
0- 5
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
0-11
120.0
0- 4
0- 4
0- 5
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 1
130.0
0- 5
0- 5
0- 6
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 3
140.0
0- 5
0- 6
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
150.0
0- 6
0- 7
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
160.0
0- 7
0- 7
0- 8
0- 9
0-10
1- 0
1- 1
1- 3
1- 6
1- 8
1-11
170.0
0- 8
0- 8
0- 9
0-10
0-11
1- 1
1- 3
1- 5
1- 8
1-11
2- 2
180.0
0- 8
0- 9
0-10
0-11
1- 1
1- 3
1- 5
1- 7
1-10
2- 2
2- 5
190.0
0- 9
0-10
0-11
1- 1
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 8
200.0
0-10
0-11
1- 0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 4
2- 7
3- 0
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2319 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
2013. 2319. 1577.
990. 1599.
774.
600.
427.
375.
317.
278.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----110.0
0- 3
1- 0
0- 4
0- 6
1- 0
0-11
0- 9
1- 1
1- 3
1- 5
1- 7
120.0
0- 4
1- 2
0- 4
0- 7
1- 2
1- 1
0-11
1- 3
1- 5
1- 8
1-11
130.0
0- 4
1- 4
0- 5
0- 8
1- 5
1- 3
1- 1
1- 6
1- 8
2- 0
2- 3
140.0
0- 5
1- 7
0- 6
0- 9
1- 7
1- 5
1- 3
1- 8
1-11
2- 3
2- 7
150.0
0- 5
1-10
0- 7
0-10
1-10
1- 8
1- 5
1-11
2- 3
2- 7
3- 0
160.0
0- 6
2- 1
0- 8
1- 0
2- 1
1-10
1- 7
2- 3
2- 6
3- 0
3- 5
170.0
0- 7
2- 4
0- 8
1- 1
2- 4
2- 1
1- 9
2- 6
2-10
3- 4
3-10
180.0
0- 8
2- 7
0- 9
1- 3
2- 7
2- 4
2- 0
2-10
3- 2
3- 9
4- 3
190.0
0- 8
2-11
0-10
1- 4
2-11
2- 7
2- 3
3- 1
3- 6
4- 2
4- 9
200.0
0- 9
3- 2
1- 0
1- 6
3- 3
2-10
2- 6
3- 5
3-11
4- 7
5- 3
FINAL SAG CHART
H Tens
1577. 1368. 1171.
990.
832.
702.
600.
522.
463.
427.
408.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----110.0
0- 4
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-11
1- 0
1- 1
1- 1
120.0
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-11
1- 0
1- 2
1- 3
1- 4
130.0
0- 5
0- 6
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 4
1- 6
1- 7
140.0
0- 6
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1- 8
1- 9
150.0
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 5
1- 7
1-10
1-11
2- 0
160.0
0- 8
0- 9
0-10
1- 0
1- 2
1- 4
1- 7
1-10
2- 1
2- 3
2- 4
170.0
0- 8
0-10
0-11
1- 1
1- 4
1- 6
1- 9
2- 1
2- 4
2- 6
2- 7
180.0
0- 9
0-11
1- 1
1- 3
1- 5
1- 9
2- 0
2- 3
2- 7
2-10
2-11
190.0
0-10
1- 0
1- 2
1- 4
1- 7
1-11
2- 3
2- 7
2-10
3- 1
3- 3
200.0
1- 0
1- 1
1- 3
1- 6
1- 9
2- 1
2- 6
2-10
3- 2
3- 5
3- 7

Section WSC02
Page 36 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN


Ruling Span: 175.0 Feet
INITIAL SAG CHART
H Tens
1806. 1652. 1498. 1346. 1198. 1056.
926.
810.
711.
630.
563.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
0- 5
0- 5
0- 5
0- 6
0- 7
0- 7
0- 8
0-10
0-11
1- 0
1- 2
140.0
0- 5
0- 6
0- 6
0- 7
0- 8
0- 9
0-10
0-11
1- 0
1- 2
1- 4
150.0
0- 6
0- 6
0- 7
0- 8
0- 9
0-10
0-11
1- 1
1- 2
1- 4
1- 6
160.0
0- 7
0- 7
0- 8
0- 9
0-10
0-11
1- 1
1- 2
1- 4
1- 6
1- 8
170.0
0- 7
0- 8
0- 9
0-10
0-11
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
180.0
0- 8
0- 9
0-10
0-11
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 2
190.0
0- 9
0-10
0-11
1- 0
1- 2
1- 3
1- 5
1- 8
1-11
2- 1
2- 4
200.0
0-10
0-11
1- 0
1- 1
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
210.0
0-11
1- 0
1- 1
1- 3
1- 5
1- 7
1- 9
2- 0
2- 3
2- 7
2-11
220.0
1- 0
1- 1
1- 3
1- 4
1- 6
1- 8
1-11
2- 2
2- 6
2-10
3- 2
230.0
1- 1
1- 2
1- 4
1- 6
1- 8
1-10
2- 1
2- 5
2- 9
3- 1
3- 5
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2463 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
2003. 2462. 1577. 1016. 1720.
843.
651.
472.
421.
360.
318.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
0- 4
1- 3
0- 5
0- 8
1- 3
1- 2
1- 0
1- 4
1- 6
1- 9
2- 0
140.0
0- 5
1- 6
0- 6
0- 9
1- 6
1- 4
1- 2
1- 7
1- 9
2- 0
2- 3
150.0
0- 5
1- 8
0- 7
0-10
1- 8
1- 6
1- 4
1- 9
2- 0
2- 4
2- 7
160.0
0- 6
1-11
0- 8
0-11
1-11
1- 8
1- 6
2- 0
2- 3
2- 7
3- 0
170.0
0- 7
2- 2
0- 8
1- 1
2- 2
1-11
1- 8
2- 3
2- 6
2-11
3- 4
180.0
0- 8
2- 5
0- 9
1- 2
2- 5
2- 2
1-10
2- 6
2-10
3- 4
3- 9
190.0
0- 8
2- 9
0-10
1- 4
2- 9
2- 5
2- 1
2-10
3- 2
3- 8
4- 2
200.0
0- 9
3- 0
1- 0
1- 6
3- 0
2- 8
2- 3
3- 1
3- 6
4- 1
4- 7
210.0
0-10
3- 4
1- 1
1- 7
3- 4
2-11
2- 6
3- 5
3-10
4- 6
5- 1
220.0
0-11
3- 7
1- 2
1- 9
3- 7
3- 2
2- 9
3- 9
4- 3
4-11
5- 7
230.0
1- 0
3-11
1- 3
1-11
3-11
3- 6
3- 0
4- 1
4- 7
5- 5
6- 1
FINAL SAG CHART
H Tens
1577. 1375. 1187. 1016.
869.
747.
651.
575.
516.
472.
454.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 1
1- 3
1- 4
1- 5
140.0
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 3
1- 5
1- 7
1- 7
150.0
0- 7
0- 8
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 7
1- 9
1-10
160.0
0- 8
0- 9
0-10
0-11
1- 1
1- 3
1- 6
1- 8
1-10
2- 0
2- 1
170.0
0- 8
0-10
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 3
2- 4
180.0
0- 9
0-11
1- 0
1- 2
1- 5
1- 7
1-10
2- 1
2- 4
2- 6
2- 8
190.0
0-10
1- 0
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 7
2-10
2-11
200.0
1- 0
1- 1
1- 3
1- 6
1- 9
2- 0
2- 3
2- 7
2-10
3- 1
3- 3
210.0
1- 1
1- 2
1- 5
1- 7
1-11
2- 2
2- 6
2-10
3- 2
3- 5
3- 7
220.0
1- 2
1- 4
1- 6
1- 9
2- 1
2- 5
2- 9
3- 1
3- 5
3- 9
3-11
230.0
1- 3
1- 5
1- 8
1-11
2- 3
2- 7
3- 0
3- 5
3- 9
4- 1
4- 3

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 37 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN
Ruling Span: 200.0 Feet

INITIAL SAG CHART


H Tens
1843. 1692. 1542. 1393. 1249. 1113.
986.
874.
776.
694.
627.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----160.0
0- 7
0- 7
0- 8
0- 8
0- 9
0-11
1- 0
1- 1
1- 3
1- 5
1- 6
170.0
0- 7
0- 8
0- 9
0-10
0-11
1- 0
1- 1
1- 3
1- 5
1- 7
1- 9
180.0
0- 8
0- 9
0-10
0-11
1- 0
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
190.0
0- 9
0-10
0-11
1- 0
1- 1
1- 3
1- 4
1- 6
1- 9
1-11
2- 2
200.0
0-10
0-11
1- 0
1- 1
1- 2
1- 4
1- 6
1- 8
1-11
2- 2
2- 4
210.0
0-11
1- 0
1- 1
1- 2
1- 4
1- 6
1- 8
1-10
2- 1
2- 4
2- 7
220.0
1- 0
1- 1
1- 2
1- 4
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-10
230.0
1- 1
1- 2
1- 3
1- 5
1- 7
1- 9
2- 0
2- 3
2- 6
2-10
3- 1
240.0
1- 2
1- 3
1- 5
1- 6
1- 9
1-11
2- 2
2- 5
2- 9
3- 1
3- 4
250.0
1- 3
1- 5
1- 6
1- 8
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2601 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1993. 2600. 1577. 1042. 1835.
909.
698.
518.
463.
401.
356.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----160.0
0- 6
1-10
0- 8
0-11
1-10
1- 7
1- 4
1-10
2- 1
2- 4
2- 8
170.0
0- 7
2- 1
0- 8
1- 1
2- 1
1- 9
1- 7
2- 1
2- 4
2- 8
3- 0
180.0
0- 8
2- 4
0- 9
1- 2
2- 3
2- 0
1- 9
2- 4
2- 7
3- 0
3- 4
190.0
0- 8
2- 7
0-10
1- 4
2- 6
2- 2
1-11
2- 7
2-10
3- 4
3- 9
200.0
0- 9
2-10
1- 0
1- 5
2-10
2- 5
2- 1
2-10
3- 2
3- 8
4- 1
210.0
0-10
3- 2
1- 1
1- 7
3- 1
2- 8
2- 4
3- 2
3- 6
4- 0
4- 6
220.0
0-11
3- 5
1- 2
1- 9
3- 5
2-11
2- 7
3- 5
3-10
4- 5
5- 0
230.0
1- 0
3- 9
1- 3
1-11
3- 8
3- 3
2- 9
3- 9
4- 2
4-10
5- 5
240.0
1- 1
4- 1
1- 4
2- 1
4- 0
3- 6
3- 0
4- 1
4- 7
5- 3
5-11
250.0
1- 2
4- 5
1- 6
2- 3
4- 4
3-10
3- 3
4- 5
4-11
5- 8
6- 5
FINAL SAG CHART
H Tens
1577. 1383. 1203. 1042.
904.
790.
698.
624.
565.
518.
497.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----160.0
0- 8
0- 9
0-10
0-11
1- 1
1- 3
1- 4
1- 6
1- 8
1-10
1-11
170.0
0- 8
0-10
0-11
1- 1
1- 2
1- 4
1- 7
1- 9
1-11
2- 1
2- 2
180.0
0- 9
0-11
1- 0
1- 2
1- 4
1- 6
1- 9
1-11
2- 1
2- 4
2- 5
190.0
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 2
2- 4
2- 7
2- 8
200.0
1- 0
1- 1
1- 3
1- 5
1- 8
1-11
2- 1
2- 4
2- 7
2-10
3- 0
210.0
1- 1
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 7
2-10
3- 2
3- 3
220.0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 5
3- 7
230.0
1- 3
1- 5
1- 8
1-11
2- 2
2- 6
2- 9
3- 1
3- 5
3- 9
3-11
240.0
1- 4
1- 7
1- 9
2- 1
2- 4
2- 8
3- 0
3- 5
3- 9
4- 1
4- 3
250.0
1- 6
1- 8
1-11
2- 3
2- 7
2-11
3- 3
3- 8
4- 1
4- 5
4- 7

Section WSC02
Page 38 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN


Ruling Span: 225.0 Feet
INITIAL SAG CHART
H Tens
1879. 1731. 1584. 1439. 1299. 1166. 1044.
934.
838.
756.
687.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----180.0
0- 8
0- 9
0- 9
0-10
0-11
1- 1
1- 2
1- 4
1- 5
1- 7
1- 9
190.0
0- 9
0-10
0-10
0-11
1- 1
1- 2
1- 4
1- 5
1- 7
1- 9
1-11
200.0
0-10
0-11
0-11
1- 1
1- 2
1- 3
1- 5
1- 7
1- 9
2- 0
2- 2
210.0
0-11
1- 0
1- 1
1- 2
1- 3
1- 5
1- 7
1- 9
1-11
2- 2
2- 4
220.0
1- 0
1- 1
1- 2
1- 3
1- 5
1- 7
1- 9
1-11
2- 2
2- 4
2- 7
230.0
1- 1
1- 2
1- 3
1- 4
1- 6
1- 8
1-11
2- 1
2- 4
2- 7
2-10
240.0
1- 2
1- 3
1- 4
1- 6
1- 8
1-10
2- 1
2- 3
2- 6
2-10
3- 1
250.0
1- 3
1- 4
1- 6
1- 7
1- 9
2- 0
2- 3
2- 6
2- 9
3- 0
3- 4
260.0
1- 4
1- 5
1- 7
1- 9
1-11
2- 2
2- 5
2- 8
3- 0
3- 3
3- 7
270.0
1- 5
1- 7
1- 9
1-11
2- 1
2- 4
2- 7
2-10
3- 2
3- 6
3-11
280.0
1- 7
1- 8
1-10
2- 0
2- 3
2- 6
2- 9
3- 1
3- 5
3-10
4- 2
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2735 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1982. 2733. 1577. 1068. 1945.
970.
741.
564.
504.
440.
394.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----180.0
0- 8
2- 2
0- 9
1- 2
2- 2
1-10
1- 8
2- 1
2- 4
2- 9
3- 0
190.0
0- 8
2- 5
0-10
1- 3
2- 5
2- 1
1-10
2- 4
2- 8
3- 0
3- 4
200.0
0- 9
2- 8
1- 0
1- 5
2- 8
2- 3
2- 0
2- 7
2-11
3- 4
3- 9
210.0
0-10
3- 0
1- 1
1- 6
2-11
2- 6
2- 2
2-11
3- 3
3- 8
4- 1
220.0
0-11
3- 3
1- 2
1- 8
3- 2
2- 9
2- 5
3- 2
3- 6
4- 0
4- 6
230.0
1- 0
3- 7
1- 3
1-10
3- 6
3- 0
2- 8
3- 5
3-10
4- 5
4-11
240.0
1- 1
3-11
1- 4
2- 0
3-10
3- 3
2-10
3- 9
4- 2
4- 9
5- 4
250.0
1- 2
4- 2
1- 6
2- 2
4- 2
3- 7
3- 1
4- 1
4- 6
5- 2
5-10
260.0
1- 3
4- 7
1- 7
2- 4
4- 6
3-10
3- 4
4- 5
4-11
5- 7
6- 3
270.0
1- 5
4-11
1- 9
2- 6
4-10
4- 2
3- 7
4- 9
5- 3
6- 1
6- 9
280.0
1- 6
5- 3
1-10
2- 8
5- 2
4- 5
3-11
5- 1
5- 8
6- 6
7- 3
FINAL SAG CHART
H Tens
1577. 1390. 1219. 1068.
938.
830.
741.
670.
612.
564.
538.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----180.0
0- 9
0-11
1- 0
1- 2
1- 4
1- 5
1- 8
1-10
2- 0
2- 2
2- 3
190.0
0-10
1- 0
1- 1
1- 3
1- 5
1- 7
1-10
2- 0
2- 2
2- 4
2- 6
200.0
1- 0
1- 1
1- 3
1- 5
1- 7
1- 9
2- 0
2- 2
2- 5
2- 7
2- 9
210.0
1- 1
1- 2
1- 4
1- 6
1- 9
2- 0
2- 2
2- 5
2- 8
2-11
3- 0
220.0
1- 2
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
2-11
3- 2
3- 4
230.0
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 8
2-11
3- 2
3- 5
3- 7
240.0
1- 4
1- 7
1- 9
2- 0
2- 3
2- 7
2-10
3- 2
3- 5
3- 9
3-11
250.0
1- 6
1- 8
1-11
2- 2
2- 5
2- 9
3- 1
3- 5
3- 9
4- 1
4- 3
260.0
1- 7
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
4- 1
4- 5
4- 7
270.0
1- 9
1-11
2- 3
2- 6
2-10
3- 3
3- 7
4- 0
4- 4
4- 9
4-11
280.0
1-10
2- 1
2- 4
2- 8
3- 1
3- 6
3-11
4- 3
4- 8
5- 1
5- 4

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 39 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN
Ruling Span: 250.0 Feet

INITIAL SAG CHART


H Tens
1913. 1768. 1624. 1483. 1346. 1217. 1098.
990.
896.
814.
744.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
0-11
0-11
1- 0
1- 1
1- 3
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
220.0
1- 0
1- 0
1- 1
1- 3
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
2- 5
230.0
1- 1
1- 2
1- 3
1- 4
1- 6
1- 7
1- 9
2- 0
2- 2
2- 5
2- 7
240.0
1- 2
1- 3
1- 4
1- 5
1- 7
1- 9
1-11
2- 2
2- 4
2- 7
2-10
250.0
1- 3
1- 4
1- 5
1- 7
1- 9
1-11
2- 1
2- 4
2- 7
2-10
3- 1
260.0
1- 4
1- 5
1- 7
1- 8
1-10
2- 1
2- 3
2- 6
2- 9
3- 1
3- 4
270.0
1- 5
1- 6
1- 8
1-10
2- 0
2- 3
2- 5
2- 9
3- 0
3- 3
3- 7
280.0
1- 6
1- 8
1-10
2- 0
2- 2
2- 5
2- 8
2-11
3- 3
3- 6
3-10
290.0
1- 8
1- 9
1-11
2- 1
2- 4
2- 7
2-10
3- 1
3- 5
3- 9
4- 2
300.0
1- 9
1-11
2- 1
2- 3
2- 6
2- 9
3- 0
3- 4
3- 8
4- 1
4- 5
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2864 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1970. 2862. 1577. 1092. 2049. 1027.
782.
607.
543.
478.
430.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
0-10
2-10
1- 1
1- 6
2- 9
2- 5
2- 1
2- 8
3- 0
3- 5
3- 9
220.0
0-11
3- 1
1- 2
1- 8
3- 1
2- 7
2- 3
2-11
3- 3
3- 9
4- 1
230.0
1- 0
3- 5
1- 3
1-10
3- 4
2-10
2- 6
3- 2
3- 7
4- 1
4- 6
240.0
1- 1
3- 8
1- 4
1-11
3- 7
3- 1
2- 9
3- 6
3-11
4- 5
4-11
250.0
1- 2
4- 0
1- 6
2- 1
3-11
3- 4
2-11
3- 9
4- 3
4- 9
5- 4
260.0
1- 3
4- 4
1- 7
2- 3
4- 3
3- 8
3- 2
4- 1
4- 7
5- 2
5- 9
270.0
1- 5
4- 8
1- 9
2- 6
4- 7
3-11
3- 5
4- 5
4-11
5- 7
6- 2
280.0
1- 6
5- 0
1-10
2- 8
4-11
4- 2
3- 8
4- 9
5- 3
6- 0
6- 8
290.0
1- 7
5- 5
2- 0
2-10
5- 3
4- 6
3-11
5- 1
5- 8
6- 5
7- 2
300.0
1- 8
5- 9
2- 1
3- 0
5- 7
4-10
4- 3
5- 5
6- 1
6-10
7- 8
FINAL SAG CHART
H Tens
1577. 1398. 1236. 1092.
970.
867.
782.
712.
655.
607.
577.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
1- 1
1- 2
1- 4
1- 6
1- 8
1-11
2- 1
2- 3
2- 6
2- 8
2-10
220.0
1- 2
1- 4
1- 6
1- 8
1-10
2- 1
2- 3
2- 6
2- 9
2-11
3- 1
230.0
1- 3
1- 5
1- 7
1-10
2- 0
2- 3
2- 6
2- 9
3- 0
3- 2
3- 4
240.0
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 9
3- 0
3- 3
3- 6
3- 8
250.0
1- 6
1- 8
1-11
2- 1
2- 5
2- 8
2-11
3- 3
3- 6
3- 9
4- 0
260.0
1- 7
1-10
2- 0
2- 3
2- 7
2-10
3- 2
3- 6
3- 9
4- 1
4- 3
270.0
1- 9
1-11
2- 2
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 7
280.0
1-10
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 0
290.0
2- 0
2- 3
2- 6
2-10
3- 2
3- 7
3-11
4- 4
4- 8
5- 1
5- 4
300.0
2- 1
2- 5
2- 8
3- 0
3- 5
3-10
4- 3
4- 7
5- 0
5- 5
5- 8

Section WSC02
Page 40 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN


Ruling Span: 275.0 Feet
INITIAL SAG CHART
H Tens
1946. 1803. 1662. 1524. 1391. 1266. 1149. 1044.
951.
869.
799.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 0
1- 1
1- 2
1- 4
1- 5
1- 7
1- 9
1-11
2- 1
2- 3
2- 5
240.0
1- 1
1- 2
1- 4
1- 5
1- 7
1- 8
1-10
2- 1
2- 3
2- 5
2- 8
250.0
1- 2
1- 4
1- 5
1- 6
1- 8
1-10
2- 0
2- 3
2- 5
2- 8
2-11
260.0
1- 4
1- 5
1- 6
1- 8
1-10
2- 0
2- 2
2- 5
2- 7
2-10
3- 1
270.0
1- 5
1- 6
1- 8
1- 9
1-11
2- 2
2- 4
2- 7
2-10
3- 1
3- 4
280.0
1- 6
1- 7
1- 9
1-11
2- 1
2- 3
2- 6
2- 9
3- 0
3- 4
3- 7
290.0
1- 7
1- 9
1-11
2- 1
2- 3
2- 5
2- 8
3- 0
3- 3
3- 7
3-10
300.0
1- 9
1-10
2- 0
2- 2
2- 5
2- 7
2-11
3- 2
3- 6
3-10
4- 1
310.0
1-10
2- 0
2- 2
2- 4
2- 7
2-10
3- 1
3- 5
3- 8
4- 1
4- 5
320.0
1-11
2- 1
2- 3
2- 6
2- 9
3- 0
3- 3
3- 7
3-11
4- 4
4- 8
330.0
2- 1
2- 3
2- 5
2- 8
2-11
3- 2
3- 6
3-10
4- 2
4- 7
5- 0
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2989 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1957. 2986. 1577. 1116. 2149. 1081.
820.
648.
581.
515.
465.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 0
3- 3
1- 3
1- 9
3- 2
2- 9
2- 5
3- 0
3- 4
3- 9
4- 2
240.0
1- 1
3- 7
1- 4
1-11
3- 5
2-11
2- 7
3- 3
3- 8
4- 1
4- 6
250.0
1- 2
3-10
1- 6
2- 1
3- 9
3- 2
2-10
3- 6
3-11
4- 5
4-11
260.0
1- 4
4- 2
1- 7
2- 3
4- 0
3- 5
3- 0
3-10
4- 3
4-10
5- 4
270.0
1- 5
4- 6
1- 9
2- 5
4- 4
3- 9
3- 3
4- 1
4- 7
5- 2
5- 9
280.0
1- 6
4-10
1-10
2- 7
4- 8
4- 0
3- 6
4- 5
4-11
5- 7
6- 2
290.0
1- 7
5- 2
2- 0
2- 9
5- 0
4- 3
3- 9
4- 9
5- 4
6- 0
6- 7
300.0
1- 9
5- 6
2- 1
3- 0
5- 4
4- 7
4- 0
5- 1
5- 8
6- 5
7- 1
310.0
1-10
5-11
2- 3
3- 2
5- 9
4-11
4- 3
5- 5
6- 1
6-10
7- 6
320.0
1-11
6- 3
2- 5
3- 4
6- 1
5- 2
4- 7
5- 9
6- 5
7- 3
8- 0
330.0
2- 1
6- 8
2- 7
3- 7
6- 6
5- 6
4-10
6- 2
6-10
7- 9
8- 6
FINAL SAG CHART
H Tens
1577. 1406. 1251. 1116. 1000.
902.
820.
752.
695.
648.
615.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 3
1- 5
1- 7
1- 9
2- 0
2- 2
2- 5
2- 7
2-10
3- 0
3- 2
240.0
1- 4
1- 6
1- 9
1-11
2- 2
2- 4
2- 7
2-10
3- 1
3- 3
3- 5
250.0
1- 6
1- 8
1-10
2- 1
2- 4
2- 7
2-10
3- 1
3- 4
3- 6
3- 9
260.0
1- 7
1- 9
2- 0
2- 3
2- 6
2- 9
3- 0
3- 4
3- 7
3-10
4- 0
270.0
1- 9
1-11
2- 2
2- 5
2- 8
3- 0
3- 3
3- 7
3-10
4- 1
4- 4
280.0
1-10
2- 1
2- 4
2- 7
2-11
3- 2
3- 6
3-10
4- 2
4- 5
4- 8
290.0
2- 0
2- 3
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
5- 0
300.0
2- 1
2- 4
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 1
5- 4
310.0
2- 3
2- 6
2-10
3- 2
3- 6
3-11
4- 3
4- 8
5- 1
5- 5
5- 9
320.0
2- 5
2- 8
3- 0
3- 4
3- 9
4- 2
4- 7
5- 0
5- 5
5- 9
6- 1
330.0
2- 7
2-10
3- 2
3- 7
4- 0
4- 5
4-10
5- 4
5- 9
6- 2
6- 6

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 41 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN
Ruling Span: 300.0 Feet

INITIAL SAG CHART


H Tens
1977. 1837. 1698. 1564. 1434. 1312. 1198. 1095. 1003.
922.
852.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
1- 3
1- 5
1- 6
1- 7
1- 9
1-11
2- 1
2- 3
2- 6
2- 8
2-11
270.0
1- 5
1- 6
1- 7
1- 9
1-11
2- 1
2- 3
2- 5
2- 8
2-11
3- 2
280.0
1- 6
1- 7
1- 9
1-10
2- 0
2- 3
2- 5
2- 8
2-11
3- 1
3- 5
290.0
1- 7
1- 8
1-10
2- 0
2- 2
2- 4
2- 7
2-10
3- 1
3- 4
3- 7
300.0
1- 8
1-10
2- 0
2- 2
2- 4
2- 6
2- 9
3- 0
3- 4
3- 7
3-10
310.0
1-10
1-11
2- 1
2- 3
2- 6
2- 8
2-11
3- 3
3- 6
3-10
4- 2
320.0
1-11
2- 1
2- 3
2- 5
2- 8
2-10
3- 2
3- 5
3- 9
4- 1
4- 5
330.0
2- 0
2- 2
2- 4
2- 7
2-10
3- 1
3- 4
3- 8
4- 0
4- 4
4- 8
340.0
2- 2
2- 4
2- 6
2- 9
3- 0
3- 3
3- 6
3-10
4- 3
4- 7
5- 0
350.0
2- 3
2- 6
2- 8
2-11
3- 2
3- 5
3- 9
4- 1
4- 6
4-10
5- 3
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3109 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1944. 3106. 1577. 1138. 2245. 1132.
856.
686.
617.
550.
499.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
1- 4
4- 0
1- 7
2- 2
3-10
3- 4
2-11
3- 7
4- 0
4- 6
4-11
270.0
1- 5
4- 4
1- 9
2- 4
4- 2
3- 7
3- 2
3-11
4- 4
4-10
5- 4
280.0
1- 6
4- 8
1-10
2- 6
4- 6
3-10
3- 4
4- 2
4- 8
5- 3
5- 9
290.0
1- 7
5- 0
2- 0
2- 9
4-10
4- 1
3- 7
4- 6
5- 0
5- 7
6- 2
300.0
1- 9
5- 4
2- 1
2-11
5- 2
4- 5
3-10
4-10
5- 4
6- 0
6- 7
310.0
1-10
5- 8
2- 3
3- 1
5- 6
4- 8
4- 1
5- 1
5- 8
6- 5
7- 0
320.0
1-11
6- 1
2- 5
3- 4
5-10
5- 0
4- 5
5- 5
6- 1
6-10
7- 6
330.0
2- 1
6- 5
2- 7
3- 6
6- 2
5- 3
4- 8
5-10
6- 5
7- 3
8- 0
340.0
2- 2
6-10
2- 8
3- 9
6- 7
5- 7
4-11
6- 2
6-10
7- 8
8- 5
350.0
2- 4
7- 3
2-10
3-11
7- 0
5-11
5- 3
6- 6
7- 3
8- 2
8-11
FINAL SAG CHART
H Tens
1577. 1413. 1267. 1138. 1028.
934.
856.
790.
734.
686.
651.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
1- 7
1- 9
2- 0
2- 2
2- 5
2- 8
2-11
3- 2
3- 5
3- 7
3-10
270.0
1- 9
1-11
2- 2
2- 4
2- 7
2-10
3- 2
3- 5
3- 8
3-11
4- 1
280.0
1-10
2- 1
2- 3
2- 6
2-10
3- 1
3- 4
3- 8
3-11
4- 2
4- 5
290.0
2- 0
2- 2
2- 5
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 6
4- 9
300.0
2- 1
2- 4
2- 7
2-11
3- 3
3- 6
3-10
4- 2
4- 6
4-10
5- 1
310.0
2- 3
2- 6
2-10
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
5- 1
5- 5
320.0
2- 5
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 1
5- 5
5- 9
330.0
2- 7
2-10
3- 2
3- 6
3-11
4- 3
4- 8
5- 1
5- 5
5-10
6- 1
340.0
2- 8
3- 0
3- 4
3- 9
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 6
350.0
2-10
3- 2
3- 7
3-11
4- 4
4-10
5- 3
5- 8
6- 1
6- 6
6-10

Section WSC02
Page 42 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#1/0 AWG 6/ 1 Stranding ACSR T-2 Conductor RAVEN


Ruling Span: 325.0 Feet
INITIAL SAG CHART
H Tens
2006. 1868. 1733. 1601. 1475. 1355. 1244. 1143. 1052.
972.
902.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
1- 7
1- 8
1-10
1-11
2- 1
2- 3
2- 6
2- 9
2-11
3- 2
3- 5
300.0
1- 8
1- 9
1-11
2- 1
2- 3
2- 5
2- 8
2-11
3- 2
3- 5
3- 8
310.0
1- 9
1-11
2- 1
2- 3
2- 5
2- 7
2-10
3- 1
3- 4
3- 8
3-11
320.0
1-11
2- 0
2- 2
2- 4
2- 7
2- 9
3- 0
3- 3
3- 7
3-10
4- 2
330.0
2- 0
2- 2
2- 4
2- 6
2- 9
2-11
3- 3
3- 6
3-10
4- 1
4- 5
340.0
2- 2
2- 3
2- 6
2- 8
2-11
3- 2
3- 5
3- 8
4- 0
4- 4
4- 8
350.0
2- 3
2- 5
2- 7
2-10
3- 1
3- 4
3- 7
3-11
4- 3
4- 7
5- 0
360.0
2- 5
2- 7
2- 9
3- 0
3- 3
3- 6
3-10
4- 2
4- 6
4-11
5- 3
370.0
2- 6
2- 8
2-11
3- 2
3- 5
3- 8
4- 0
4- 5
4- 9
5- 2
5- 7
380.0
2- 8
2-10
3- 1
3- 4
3- 7
3-11
4- 3
4- 7
5- 0
5- 5
5-10
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
3225 lb
-----------------------------------------------------------------------------------Design: 18.0 % Ult. @
0. Deg ,
.00 in Ice,
.00 psf Wind, Final
-----------------------------------------------------------------------------------H Tens
1930. 3222. 1577. 1160. 2337. 1181.
889.
723.
651.
584.
532.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .290 1.456
.290
.290 1.016
.436
.290
.290
.290
.290
.290
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
1- 7
4-10
2- 0
2- 8
4- 7
3-11
3- 6
4- 3
4- 9
5- 3
5- 9
300.0
1- 9
5- 2
2- 1
2-10
4-11
4- 2
3- 9
4- 7
5- 1
5- 8
6- 2
310.0
1-10
5- 6
2- 3
3- 1
5- 3
4- 6
4- 0
4-10
5- 5
6- 0
6- 7
320.0
2- 0
5-10
2- 5
3- 3
5- 7
4- 9
4- 3
5- 2
5- 9
6- 5
7- 0
330.0
2- 1
6- 2
2- 7
3- 5
6- 0
5- 1
4- 6
5- 6
6- 1
6-10
7- 6
340.0
2- 3
6- 7
2- 8
3- 8
6- 4
5- 5
4- 9
5-10
6- 6
7- 3
7-11
350.0
2- 4
7- 0
2-10
3-10
6- 8
5- 8
5- 0
6- 2
6-10
7- 8
8- 5
360.0
2- 6
7- 4
3- 0
4- 1
7- 1
6- 0
5- 4
6- 7
7- 3
8- 1
8-11
370.0
2- 7
7- 9
3- 2
4- 4
7- 6
6- 4
5- 7
6-11
7- 8
8- 7
9- 5
380.0
2- 9
8- 2
3- 4
4- 7
7-11
6- 9
5-11
7- 3
8- 1
9- 0
9-11
FINAL SAG CHART
H Tens
1576. 1421. 1282. 1160. 1055.
965.
889.
825.
770.
723.
685.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----290.0
2- 0
2- 2
2- 5
2- 8
2-11
3- 2
3- 6
3- 9
4- 0
4- 3
4- 6
300.0
2- 1
2- 4
2- 7
2-10
3- 2
3- 5
3- 9
4- 0
4- 3
4- 7
4-10
310.0
2- 3
2- 6
2- 9
3- 1
3- 4
3- 8
4- 0
4- 3
4- 7
4-10
5- 2
320.0
2- 5
2- 8
2-11
3- 3
3- 7
3-11
4- 3
4- 7
4-10
5- 2
5- 6
330.0
2- 7
2-10
3- 1
3- 5
3- 9
4- 2
4- 6
4-10
5- 2
5- 6
5-10
340.0
2- 8
3- 0
3- 4
3- 8
4- 0
4- 5
4- 9
5- 1
5- 6
5-10
6- 2
350.0
2-10
3- 2
3- 6
3-10
4- 3
4- 8
5- 0
5- 5
5-10
6- 2
6- 6
360.0
3- 0
3- 4
3- 8
4- 1
4- 6
4-11
5- 4
5- 9
6- 2
6- 7
6-11
370.0
3- 2
3- 6
3-11
4- 4
4- 9
5- 2
5- 7
6- 1
6- 6
6-11
7- 3
380.0
3- 4
3- 9
4- 2
4- 7
5- 0
5- 6
5-11
6- 5
6-10
7- 3
7- 8

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 43 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN
Ruling Span: 150.0 Feet

INITIAL SAG CHART


H Tens
1256. 1103.
981.
884.
807.
744.
692.
649.
612.
580.
553.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----110.0
0- 9
0-10
0-11
1- 0
1- 2
1- 3
1- 4
1- 5
1- 6
1- 7
1- 8
120.0
0-11
1- 0
1- 1
1- 3
1- 4
1- 5
1- 7
1- 8
1- 9
1-10
1-11
130.0
1- 0
1- 2
1- 4
1- 5
1- 7
1- 8
1-10
1-11
2- 1
2- 2
2- 3
140.0
1- 2
1- 4
1- 6
1- 8
1-10
2- 0
2- 1
2- 3
2- 4
2- 6
2- 7
150.0
1- 4
1- 6
1- 9
1-11
2- 1
2- 3
2- 5
2- 7
2- 9
2-10
3- 0
160.0
1- 6
1- 9
1-11
2- 2
2- 4
2- 7
2- 9
2-11
3- 1
3- 3
3- 5
170.0
1- 9
1-11
2- 2
2- 5
2- 8
2-10
3- 1
3- 3
3- 6
3- 8
3-10
180.0
1-11
2- 2
2- 5
2- 9
3- 0
3- 3
3- 5
3- 8
3-11
4- 1
4- 4
190.0
2- 2
2- 5
2- 9
3- 0
3- 4
3- 7
3-10
4- 1
4- 4
4- 7
4-10
200.0
2- 4
2- 8
3- 0
3- 4
3- 8
3-11
4- 3
4- 6
4-10
5- 1
5- 4
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2500 lb
-----------------------------------------------------------------------------------Design: 1250. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
1528. 2476. 1119.
799. 1693.
797.
640.
547.
509.
461.
425.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----110.0
0- 7
1- 3
0-10
1- 2
1- 4
1- 5
1- 5
1- 8
1- 9
1-11
2- 1
120.0
0- 9
1- 5
1- 0
1- 4
1- 7
1- 9
1- 8
1-11
2- 1
2- 4
2- 6
130.0
0-10
1- 8
1- 2
1- 7
1-11
2- 0
2- 0
2- 3
2- 6
2- 9
2-11
140.0
1- 0
1-11
1- 4
1-10
2- 2
2- 4
2- 3
2- 8
2-10
3- 2
3- 5
150.0
1- 1
2- 3
1- 6
2- 1
2- 6
2- 8
2- 7
3- 0
3- 3
3- 7
3-11
160.0
1- 3
2- 6
1- 8
2- 4
2-10
3- 0
2-11
3- 5
3- 8
4- 1
4- 5
170.0
1- 5
2-10
1-11
2- 8
3- 3
3- 5
3- 4
3-11
4- 2
4- 7
5- 0
180.0
1- 7
3- 2
2- 2
3- 0
3- 7
3-10
3- 9
4- 4
4- 8
5- 2
5- 7
190.0
1- 9
3- 6
2- 5
3- 4
4- 0
4- 3
4- 2
4-10
5- 3
5- 9
6- 3
200.0
1-11
3-11
2- 8
3- 8
4- 5
4- 8
4- 7
5- 4
5- 9
6- 4
6-11
FINAL SAG CHART
H Tens
1118.
983.
880.
799.
735.
683.
639.
603.
572.
547.
534.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
0- 8
0- 9
0-10
0-11
1- 0
1- 1
1- 2
1- 3
1- 4
1- 4
1- 5
110.0
0-10
0-11
1- 1
1- 2
1- 3
1- 4
1- 5
1- 6
1- 7
1- 8
1- 8
120.0
1- 0
1- 1
1- 3
1- 4
1- 6
1- 7
1- 8
1- 9
1-10
1-11
2- 0
130.0
1- 2
1- 4
1- 5
1- 7
1- 9
1-10
2- 0
2- 1
2- 2
2- 3
2- 4
140.0
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
2- 3
2- 5
2- 6
2- 8
2- 9
150.0
1- 6
1- 8
1-11
2- 1
2- 3
2- 5
2- 7
2- 9
2-11
3- 0
3- 1
160.0
1- 8
1-11
2- 2
2- 4
2- 7
2- 9
2-11
3- 2
3- 4
3- 5
3- 6
170.0
1-11
2- 2
2- 5
2- 8
2-11
3- 1
3- 4
3- 6
3- 9
3-11
4- 0
180.0
2- 2
2- 5
2- 9
3- 0
3- 3
3- 6
3- 9
3-11
4- 2
4- 4
4- 6
190.0
2- 5
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 5
4- 8
4-10
5- 0
200.0
2- 8
3- 0
3- 4
3- 8
4- 0
4- 4
4- 7
4-10
5- 2
5- 4
5- 6

Section WSC02
Page 44 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN


Ruling Span: 175.0 Feet
INITIAL SAG CHART
H Tens
1098.
999.
918.
851.
794.
747.
706.
671.
640.
613.
589.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
1- 2
1- 3
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
2- 0
2- 1
2- 2
140.0
1- 4
1- 6
1- 7
1- 9
1-10
1-11
2- 1
2- 2
2- 3
2- 4
2- 6
150.0
1- 6
1- 8
1-10
2- 0
2- 1
2- 3
2- 4
2- 6
2- 7
2- 9
2-10
160.0
1- 9
1-11
2- 1
2- 3
2- 5
2- 6
2- 8
2-10
2-11
3- 1
3- 2
170.0
1-11
2- 2
2- 4
2- 6
2- 8
2-10
3- 0
3- 2
3- 4
3- 6
3- 7
180.0
2- 2
2- 5
2- 7
2-10
3- 0
3- 2
3- 5
3- 7
3- 9
3-11
4- 1
190.0
2- 5
2- 8
2-11
3- 2
3- 4
3- 7
3- 9
3-11
4- 2
4- 4
4- 6
200.0
2- 8
2-11
3- 3
3- 6
3- 8
3-11
4- 2
4- 5
4- 7
4-10
5- 0
210.0
3- 0
3- 3
3- 6
3-10
4- 1
4- 4
4- 7
4-10
5- 1
5- 3
5- 6
220.0
3- 3
3- 7
3-11
4- 2
4- 6
4- 9
5- 0
5- 4
5- 7
5-10
6- 0
230.0
3- 7
3-11
4- 3
4- 7
4-11
5- 2
5- 6
5- 9
6- 1
6- 4
6- 7
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
2500 lb
-----------------------------------------------------------------------------------Design: 1250. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
1251. 2476. 1002.
787. 1736.
829.
663.
581.
546.
501.
466.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----130.0
1- 0
1- 8
1- 3
1- 7
1-10
1-11
1-11
2- 2
2- 4
2- 6
2- 8
140.0
1- 2
1-11
1- 6
1-10
2- 2
2- 3
2- 2
2- 6
2- 8
2-11
3- 1
150.0
1- 4
2- 3
1- 8
2- 1
2- 5
2- 7
2- 6
2-10
3- 1
3- 4
3- 7
160.0
1- 6
2- 6
1-11
2- 5
2- 9
2-11
2-10
3- 3
3- 5
3- 9
4- 0
170.0
1- 9
2-10
2- 2
2- 9
3- 2
3- 3
3- 3
3- 8
3-11
4- 3
4- 7
180.0
1-11
3- 2
2- 5
3- 0
3- 6
3- 8
3- 7
4- 1
4- 4
4- 9
5- 1
190.0
2- 2
3- 6
2- 8
3- 5
3-11
4- 1
4- 0
4- 7
4-10
5- 3
5- 8
200.0
2- 4
3-11
2-11
3- 9
4- 4
4- 6
4- 5
5- 1
5- 5
5-10
6- 3
210.0
2- 7
4- 4
3- 3
4- 1
4- 9
5- 0
4-11
5- 7
5-11
6- 5
6-11
220.0
2-10
4- 9
3- 7
4- 6
5- 3
5- 6
5- 4
6- 1
6- 6
7- 1
7- 7
230.0
3- 1
5- 2
3-11
4-11
5- 8
6- 0
5-10
6- 8
7- 1
7- 9
8- 4
FINAL SAG CHART
H Tens
1002.
915.
845.
787.
739.
698.
662.
632.
605.
581.
568.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----120.0
1- 1
1- 2
1- 3
1- 4
1- 6
1- 7
1- 7
1- 8
1- 9
1-10
1-11
130.0
1- 3
1- 5
1- 6
1- 7
1- 8
1-10
1-11
2- 0
2- 1
2- 2
2- 2
140.0
1- 6
1- 7
1- 9
1-10
2- 0
2- 1
2- 2
2- 4
2- 5
2- 6
2- 7
150.0
1- 8
1-10
2- 0
2- 1
2- 3
2- 5
2- 6
2- 8
2- 9
2-10
2-11
160.0
1-11
2- 1
2- 3
2- 5
2- 7
2- 9
2-10
3- 0
3- 1
3- 3
3- 4
170.0
2- 2
2- 4
2- 6
2- 9
2-11
3- 1
3- 3
3- 4
3- 6
3- 8
3- 9
180.0
2- 5
2- 7
2-10
3- 0
3- 3
3- 5
3- 7
3- 9
3-11
4- 1
4- 2
190.0
2- 8
2-11
3- 2
3- 5
3- 7
3-10
4- 0
4- 2
4- 5
4- 7
4- 8
200.0
2-11
3- 3
3- 6
3- 9
4- 0
4- 3
4- 5
4- 8
4-10
5- 1
5- 2
210.0
3- 3
3- 7
3-10
4- 1
4- 5
4- 8
4-11
5- 1
5- 4
5- 7
5- 8
220.0
3- 7
3-11
4- 3
4- 6
4-10
5- 1
5- 4
5- 7
5-10
6- 1
6- 3
230.0
3-11
4- 3
4- 7
4-11
5- 3
5- 7
5-10
6- 2
6- 5
6- 8
6-10

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 45 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN
Ruling Span: 200.0 Feet

INITIAL SAG CHART


H Tens
2947. 2656. 2377. 2114. 1875. 1664. 1484. 1333. 1208. 1105. 1020.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----160.0
0- 8
0- 9
0-10
0-11
1- 0
1- 2
1- 4
1- 5
1- 7
1- 9
1-10
170.0
0- 9
0-10
0-11
1- 0
1- 2
1- 4
1- 6
1- 7
1- 9
1-11
2- 1
180.0
0-10
0-11
1- 0
1- 2
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
2- 4
190.0
0-11
1- 0
1- 2
1- 3
1- 5
1- 7
1-10
2- 0
2- 3
2- 5
2- 7
200.0
1- 0
1- 2
1- 3
1- 5
1- 7
1- 9
2- 0
2- 3
2- 5
2- 8
2-11
210.0
1- 2
1- 3
1- 5
1- 7
1- 9
2- 0
2- 2
2- 5
2- 8
2-11
3- 2
220.0
1- 3
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
2-11
3- 3
3- 6
230.0
1- 4
1- 6
1- 8
1-10
2- 1
2- 4
2- 8
2-11
3- 3
3- 6
3-10
240.0
1- 6
1- 7
1-10
2- 0
2- 3
2- 7
2-10
3- 2
3- 6
3-10
4- 2
250.0
1- 7
1- 9
1-11
2- 2
2- 6
2- 9
3- 1
3- 5
3-10
4- 2
4- 6
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
3449. 3998. 2663. 1742. 2838. 1451. 1215.
942.
831.
732.
660.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----160.0
0- 7
1- 7
0- 9
1- 1
1- 9
1- 8
1- 7
2- 0
2- 3
2- 7
2-10
170.0
0- 8
1- 9
0-10
1- 3
1-11
1-11
1- 9
2- 3
2- 7
2-11
3- 3
180.0
0- 9
2- 0
0-11
1- 5
2- 2
2- 1
2- 0
2- 7
2-11
3- 3
3- 7
190.0
0-10
2- 2
1- 0
1- 7
2- 5
2- 4
2- 2
2-10
3- 2
3- 8
4- 0
200.0
0-11
2- 5
1- 2
1- 9
2- 8
2- 7
2- 5
3- 2
3- 7
4- 0
4- 5
210.0
1- 0
2- 8
1- 3
1-11
2-11
2-10
2- 8
3- 5
3-11
4- 5
4-11
220.0
1- 1
2-11
1- 4
2- 1
3- 3
3- 2
2-11
3- 9
4- 3
4-10
5- 5
230.0
1- 2
3- 3
1- 6
2- 3
3- 6
3- 5
3- 3
4- 2
4- 8
5- 4
5-11
240.0
1- 3
3- 6
1- 7
2- 5
3-10
3- 9
3- 6
4- 6
5- 1
5- 9
6- 5
250.0
1- 4
3- 9
1- 9
2- 8
4- 2
4- 0
3- 9
4-10
5- 6
6- 3
6-11
FINAL SAG CHART
H Tens
2663. 2313. 2004. 1741. 1526. 1353.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----160.0
0- 9
0-10
1- 0
1- 1
1- 3
1- 5
170.0
0-10
0-11
1- 1
1- 3
1- 5
1- 7
180.0
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
190.0
1- 0
1- 2
1- 4
1- 7
1- 9
2- 0
200.0
1- 2
1- 4
1- 6
1- 9
1-11
2- 2
210.0
1- 3
1- 5
1- 8
1-11
2- 2
2- 5
220.0
1- 4
1- 7
1-10
2- 1
2- 4
2- 8
230.0
1- 6
1- 8
2- 0
2- 3
2- 7
2-11
240.0
1- 7
1-10
2- 2
2- 5
2- 9
3- 2
250.0
1- 9
2- 0
2- 4
2- 8
3- 0
3- 5

1215. 1105. 1015.


942.
884.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----1- 7
1- 9
1-11
2- 0
2- 2
1- 9
1-11
2- 1
2- 3
2- 5
2- 0
2- 2
2- 4
2- 7
2- 9
2- 2
2- 5
2- 8
2-10
3- 0
2- 5
2- 8
2-11
3- 2
3- 4
2- 8
2-11
3- 2
3- 5
3- 8
2-11
3- 3
3- 6
3- 9
4- 0
3- 3
3- 6
3-10
4- 2
4- 5
3- 6
3-10
4- 2
4- 6
4- 9
3- 9
4- 2
4- 6
4-10
5- 2

Section WSC02
Page 46 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN


Ruling Span: 225.0 Feet
INITIAL SAG CHART
H Tens
2709. 2441. 2190. 1962. 1760. 1585. 1437. 1313. 1209. 1121. 1047.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----180.0
0-11
1- 0
1- 1
1- 3
1- 5
1- 6
1- 8
1-10
2- 0
2- 2
2- 4
190.0
1- 0
1- 1
1- 3
1- 5
1- 6
1- 8
1-10
2- 1
2- 3
2- 5
2- 7
200.0
1- 1
1- 3
1- 4
1- 6
1- 8
1-11
2- 1
2- 3
2- 5
2- 8
2-10
210.0
1- 3
1- 4
1- 6
1- 8
1-10
2- 1
2- 3
2- 6
2- 8
2-11
3- 1
220.0
1- 4
1- 6
1- 8
1-10
2- 1
2- 3
2- 6
2- 9
2-11
3- 2
3- 5
230.0
1- 6
1- 7
1-10
2- 0
2- 3
2- 6
2- 9
3- 0
3- 3
3- 6
3- 9
240.0
1- 7
1- 9
1-11
2- 2
2- 5
2- 8
2-11
3- 3
3- 6
3- 9
4- 1
250.0
1- 9
1-11
2- 1
2- 4
2- 8
2-11
3- 2
3- 6
3-10
4- 1
4- 5
260.0
1-10
2- 1
2- 3
2- 7
2-10
3- 2
3- 6
3- 9
4- 1
4- 5
4- 9
270.0
2- 0
2- 3
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
5- 1
280.0
2- 2
2- 5
2- 8
2-11
3- 3
3- 8
4- 0
4- 5
4- 9
5- 2
5- 6
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
3115. 3998. 2407. 1641. 2869. 1466. 1215.
979.
870.
777.
707.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----180.0
0-10
2- 0
1- 0
1- 6
2- 2
2- 1
2- 0
2- 5
2- 9
3- 1
35
190.0
0-11
2- 2
1- 2
1- 8
2- 5
2- 4
2- 2
2- 9
3- 1
3- 5
3- 9
200.0
1- 0
2- 5
1- 3
1-10
2- 8
2- 7
2- 5
3- 0
3- 5
3- 9
4- 2
210.0
1- 1
2- 8
1- 4
2- 0
2-11
2-10
2- 8
3- 4
3- 9
4- 2
4- 7
220.0
1- 2
2-11
1- 6
2- 2
3- 2
3- 1
2-11
3- 8
4- 1
4- 7
5- 0
230.0
1- 3
3- 3
1- 8
2- 5
3- 6
3- 5
3- 3
4- 0
4- 6
5- 0
5- 6
240.0
1- 5
3- 6
1- 9
2- 7
3- 9
3- 8
3- 6
4- 4
4-10
5- 5
6- 0
250.0
1- 6
3- 9
1-11
2-10
4- 1
4- 0
3- 9
4- 8
5- 3
5-11
6- 6
260.0
1- 7
4- 1
2- 1
3- 0
4- 5
4- 4
4- 1
5- 1
5- 8
6- 5
7- 0
270.0
1- 9
4- 5
2- 3
3- 3
4- 9
4- 8
4- 5
5- 6
6- 2
6-11
7- 7
280.0
1-10
4- 9
2- 5
3- 6
5- 1
5- 0
4- 9
5-10
6- 7
7- 5
8- 1
FINAL SAG CHART
H Tens
2406. 2108. 1853. 1641. 1468. 1328.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----180.0
1- 0
1- 2
1- 4
1- 6
1- 8
1-10
190.0
1- 2
1- 3
1- 6
1- 8
1-10
2- 0
200.0
1- 3
1- 5
1- 7
1-10
2- 0
2- 3
210.0
1- 5
1- 7
1- 9
2- 0
2- 3
2- 5
220.0
1- 6
1- 9
1-11
2- 2
2- 5
2- 8
230.0
1- 8
1-10
2- 1
2- 5
2- 8
2-11
240.0
1- 9
2- 0
2- 4
2- 7
2-11
3- 2
250.0
1-11
2- 2
2- 6
2-10
3- 2
3- 6
260.0
2- 1
2- 5
2- 8
3- 0
3- 5
3- 9
270.0
2- 3
2- 7
2-11
3- 3
3- 8
4- 0
280.0
2- 5
2- 9
3- 1
3- 6
3-11
4- 4

1215. 1121. 1044.


978.
923.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----2- 0
2- 2
2- 4
2- 5
2- 7
2- 2
2- 5
2- 7
2- 9
2-11
2- 5
2- 8
2-10
3- 0
3- 2
2- 8
2-11
3- 1
3- 4
3- 6
2-11
3- 2
3- 5
3- 8
3-10
3- 3
3- 6
3- 9
4- 0
4- 3
3- 6
3- 9
4- 1
4- 4
4- 7
3- 9
4- 1
4- 5
4- 8
5- 0
4- 1
4- 5
4- 9
5- 1
5- 4
4- 5
4- 9
5- 2
5- 6
5-10
4- 9
5- 2
5- 6
5-10
6- 3

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 47 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN
Ruling Span: 250.0 Feet

INITIAL SAG CHART


H Tens
2477. 2239. 2023. 1831. 1664. 1521. 1400. 1297. 1209. 1134. 1069.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
1- 4
1- 6
1- 8
1-10
2- 0
2- 2
2- 4
2- 6
2- 8
2-10
3- 1
220.0
1- 6
1- 7
1- 9
2- 0
2- 2
2- 4
2- 7
2- 9
2-11
3- 2
3- 4
230.0
1- 7
1- 9
1-11
2- 2
2- 4
2- 7
2- 9
3- 0
3- 3
3- 5
3- 8
240.0
1- 9
1-11
2- 1
2- 4
2- 7
2-10
3- 0
3- 3
3- 6
3- 9
4- 0
250.0
1-11
2- 1
2- 3
2- 6
2- 9
3- 0
3- 3
3- 7
3-10
4- 1
4- 4
260.0
2- 0
2- 3
2- 6
2- 9
3- 0
3- 3
3- 7
3-10
4- 1
4- 5
4- 8
270.0
2- 2
2- 5
2- 8
2-11
3- 3
3- 6
3-10
4- 2
4- 5
4- 9
5- 0
280.0
2- 4
2- 7
2-10
3- 2
3- 6
3- 9
4- 1
4- 5
4- 9
5- 1
5- 5
290.0
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
5- 1
5- 5
5- 9
300.0
2- 8
3- 0
3- 3
3- 7
4- 0
4- 4
4- 9
5- 1
5- 6
5-10
6- 2
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
2789. 3998. 2180. 1563. 2895. 1477. 1215. 1009.
904.
816.
750.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----210.0
1- 2
2- 8
1- 6
2- 1
2-10
2-10
2- 8
3- 3
3- 7
4- 0
4- 4
220.0
1- 4
2-11
1- 8
2- 4
3- 2
3- 1
2-11
3- 6
3-11
4- 4
4- 9
230.0
1- 5
3- 3
1-10
2- 6
3- 5
3- 4
3- 3
3-10
4- 4
4- 9
5- 2
240.0
1- 7
3- 6
2- 0
2- 9
3- 9
3- 8
3- 6
4- 2
4- 8
5- 2
5- 8
250.0
1- 8
3- 9
2- 2
2-11
4- 1
4- 0
3- 9
4- 7
5- 1
5- 7
6- 1
260.0
1-10
4- 1
2- 4
3- 2
4- 5
4- 3
4- 1
4-11
5- 6
6- 1
6- 7
270.0
1-11
4- 5
2- 6
3- 5
4- 9
4- 7
4- 5
5- 4
5-11
6- 7
7- 1
280.0
2- 1
4- 9
2- 8
3- 8
5- 1
5- 0
4- 9
5- 8
6- 4
7- 0
7- 8
290.0
2- 3
5- 1
2-10
3-11
5- 5
5- 4
5- 1
6- 1
6-10
7- 7
8- 3
300.0
2- 5
5- 5
3- 1
4- 3
5-10
5- 8
5- 5
6- 6
7- 3
8- 1
8- 9
FINAL SAG CHART
H Tens
2179. 1935. 1730. 1562. 1423. 1309.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----210.0
1- 6
1- 8
1-11
2- 1
2- 4
2- 6
220.0
1- 8
1-10
2- 1
2- 4
2- 6
2- 9
230.0
1-10
2- 0
2- 3
2- 6
2- 9
3- 0
240.0
2- 0
2- 2
2- 6
2- 9
3- 0
3- 3
250.0
2- 2
2- 5
2- 8
2-11
3- 3
3- 6
260.0
2- 4
2- 7
2-11
3- 2
3- 6
3-10
270.0
2- 6
2- 9
3- 1
3- 5
3- 9
4- 1
280.0
2- 8
3- 0
3- 4
3- 8
4- 1
4- 5
290.0
2-10
3- 2
3- 7
4- 0
4- 4
4- 9
300.0
3- 1
3- 5
3-10
4- 3
4- 8
5- 1

1214. 1134. 1067. 1008.


958.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----2- 8
2-10
3- 1
3- 3
3- 5
2-11
3- 2
3- 4
3- 6
3- 9
3- 3
3- 5
3- 8
3-10
4- 1
3- 6
3- 9
4- 0
4- 2
4- 5
3- 9
4- 1
4- 4
4- 7
4- 9
4- 1
4- 5
4- 8
4-11
5- 2
4- 5
4- 9
5- 0
5- 4
5- 7
4- 9
5- 1
5- 5
5- 8
6- 0
5- 1
5- 5
5- 9
6- 1
6- 5
5- 5
5-10
6- 2
6- 6
6-11

Section WSC02
Page 48 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN


Ruling Span: 275.0 Feet
INITIAL SAG CHART
H Tens
2263. 2060. 1880. 1723. 1587. 1471. 1370. 1284. 1210. 1145. 1088.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 9
1-11
2- 1
2- 3
2- 6
2- 8
2-10
3- 0
3- 3
3- 5
3- 7
240.0
1-11
2- 1
2- 3
2- 6
2- 8
2-11
3- 1
3- 4
3- 6
3- 8
3-11
250.0
2- 1
2- 3
2- 6
2- 8
2-11
3- 2
3- 4
3- 7
3-10
4- 0
4- 3
260.0
2- 3
2- 5
2- 8
2-11
3- 2
3- 5
3- 8
3-10
4- 1
4- 4
4- 7
270.0
2- 5
2- 7
2-10
3- 1
3- 5
3- 8
3-11
4- 2
4- 5
4- 8
4-11
280.0
2- 7
2-10
3- 1
3- 4
3- 8
3-11
4- 2
4- 6
4- 9
5- 0
5- 3
290.0
2- 9
3- 0
3- 4
3- 7
3-11
4- 2
4- 6
4-10
5- 1
5- 5
5- 8
300.0
2-11
3- 3
3- 6
3-10
4- 2
4- 6
4-10
5- 2
5- 5
5- 9
6- 1
310.0
3- 2
3- 5
3- 9
4- 1
4- 5
4-10
5- 2
5- 6
5-10
6- 2
6- 6
320.0
3- 4
3- 8
4- 0
4- 4
4- 9
5- 1
5- 6
5-10
6- 2
6- 7
6-11
330.0
3- 7
3-11
4- 3
4- 8
5- 0
5- 5
5-10
6- 3
6- 7
7- 0
7- 4
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
2491. 3997. 1992. 1501. 2917. 1486. 1214. 1034.
934.
851.
788.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----230.0
1- 7
3- 3
2- 0
2- 7
3- 5
3- 4
3- 3
3- 9
4- 2
4- 7
4-11
240.0
1- 9
3- 6
2- 2
2-10
3- 8
3- 8
3- 6
4- 1
4- 6
5- 0
5- 4
250.0
1-10
3- 9
2- 4
3- 1
4- 0
3-11
3- 9
4- 5
4-11
5- 5
5-10
260.0
2- 0
4- 1
2- 6
3- 4
4- 4
4- 3
4- 1
4-10
5- 4
5-10
6- 3
270.0
2- 2
4- 5
2- 8
3- 7
4- 8
4- 7
4- 5
5- 2
5- 9
6- 3
6- 9
280.0
2- 4
4- 9
2-11
3-10
5- 0
4-11
4- 9
5- 7
6- 2
6- 9
7- 3
290.0
2- 6
5- 1
3- 1
4- 1
5- 5
5- 4
5- 1
6- 0
6- 7
7- 3
7-10
300.0
2- 8
5- 5
3- 4
4- 5
5- 9
5- 8
5- 5
6- 5
7- 1
7- 9
8- 4
310.0
2-10
5-10
3- 7
4- 8
6- 2
6- 1
5-10
6-10
7- 6
8- 3
8-11
320.0
3- 0
6- 2
3- 9
5- 0
6- 7
6- 5
6- 2
7- 3
8- 0
8-10
9- 6
330.0
3- 3
6- 7
4- 0
5- 4
7- 0
6-10
6- 7
7- 9
8- 6
9- 4 10- 1
FINAL SAG CHART
H Tens
1991. 1797. 1635. 1501. 1388. 1294.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----230.0
2- 0
2- 2
2- 5
2- 7
2-10
3- 0
240.0
2- 2
2- 4
2- 7
2-10
3- 1
3- 3
250.0
2- 4
2- 7
2-10
3- 1
3- 4
3- 7
260.0
2- 6
2- 9
3- 1
3- 4
3- 7
3-10
270.0
2- 8
3- 0
3- 3
3- 7
3-10
4- 2
280.0
2-11
3- 3
3- 6
3-10
4- 2
4- 5
290.0
3- 1
3- 5
3- 9
4- 1
4- 5
4- 9
300.0
3- 4
3- 8
4- 1
4- 5
4- 9
5- 1
310.0
3- 7
3-11
4- 4
4- 8
5- 1
5- 5
320.0
3- 9
4- 2
4- 7
5- 0
5- 5
5-10
330.0
4- 0
4- 5
4-11
5- 4
5- 9
6- 2

1214. 1145. 1085. 1034.


988.
----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----3- 3
3- 5
3- 7
3- 9
3-11
3- 6
3- 8
3-11
4- 1
4- 3
3- 9
4- 0
4- 3
4- 5
4- 8
4- 1
4- 4
4- 7
4-10
5- 0
4- 5
4- 8
4-11
5- 2
5- 5
4- 9
5- 0
5- 4
5- 7
5-10
5- 1
5- 5
5- 8
6- 0
6- 3
5- 5
5- 9
6- 1
6- 5
6- 8
5-10
6- 2
6- 6
6-10
7- 1
6- 2
6- 7
6-11
7- 3
7- 7
6- 7
7- 0
7- 4
7- 9
8- 1

Issued 11-01-14

SAG AND TENSION

E.C.S.
INFORMATION SECTION

Section WSC02
Page 49 of 50

DISTRIBUTION CHARTS STANDARD CONDUCTOR


2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN
Ruling Span: 300.0 Feet

INITIAL SAG CHART


H Tens
2078. 1911. 1765. 1637. 1526. 1430. 1347. 1274. 1210. 1153. 1103.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
2- 5
2- 7
2-10
3- 1
3- 3
3- 6
3- 8
3-11
4- 1
4- 4
4- 6
270.0
2- 7
2-10
3- 1
3- 3
3- 6
3- 9
4- 0
4- 2
4- 5
4- 8
4-10
280.0
2- 9
3- 0
3- 3
3- 6
3- 9
4- 0
4- 3
4- 6
4- 9
5- 0
5- 3
290.0
3- 0
3- 3
3- 6
3- 9
4- 1
4- 4
4- 7
4-10
5- 1
5- 4
5- 7
300.0
3- 2
3- 6
3- 9
4- 1
4- 4
4- 7
4-11
5- 2
5- 5
5- 9
6- 0
310.0
3- 5
3- 8
4- 0
4- 4
4- 7
4-11
5- 3
5- 6
5-10
6- 1
6- 5
320.0
3- 8
3-11
4- 3
4- 7
4-11
5- 3
5- 7
5-11
6- 2
6- 6
6-10
330.0
3-10
4- 2
4- 6
4-11
5- 3
5- 7
5-11
6- 3
6- 7
6-11
7- 3
340.0
4- 1
4- 5
4-10
5- 2
5- 7
5-11
6- 3
6- 8
7- 0
7- 4
7- 8
350.0
4- 4
4- 8
5- 1
5- 6
5-11
6- 3
6- 8
7- 0
7- 5
7- 9
8- 2
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
2240. 3997. 1844. 1454. 2937. 1494. 1214. 1055.
960.
883.
822.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----260.0
2- 3
4- 1
2- 9
3- 5
4- 4
4- 3
4- 1
4- 8
5- 2
5- 7
6- 0
270.0
2- 5
4- 5
2-11
3- 8
4- 8
4- 7
4- 5
5- 1
5- 7
6- 1
6- 6
280.0
2- 7
4- 9
3- 2
4- 0
5- 0
4-11
4- 9
5- 5
6- 0
6- 6
7- 0
290.0
2- 9
5- 1
3- 4
4- 3
5- 4
5- 3
5- 1
5-10
6- 5
7- 0
7- 6
300.0
3- 0
5- 5
3- 7
4- 7
5- 9
5- 8
5- 5
6- 3
6-10
7- 6
8- 0
310.0
3- 2
5-10
3-10
4-10
6- 1
6- 0
5-10
6- 8
7- 4
8- 0
8- 7
320.0
3- 4
6- 2
4- 1
5- 2
6- 6
6- 5
6- 2
7- 1
7-10
8- 6
9- 1
330.0
3- 7
6- 7
4- 4
5- 6
6-11
6-10
6- 7
7- 7
8- 4
9- 0
9- 8
340.0
3-10
7- 0
4- 7
5-10
7- 4
7- 3
7- 0
8- 0
8-10
9- 7 10- 3
350.0
4- 0
7- 5
4-11
6- 2
7- 9
7- 8
7- 5
8- 6
9- 4 10- 2 10-11
FINAL SAG CHART
H Tens
1843. 1690. 1562. 1453. 1361. 1282.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----260.0
2- 9
2-11
3- 2
3- 5
3- 8
3-11
270.0
2-11
3- 2
3- 5
3- 8
3-11
4- 2
280.0
3- 2
3- 5
3- 8
4- 0
4- 3
4- 6
290.0
3- 4
3- 8
4- 0
4- 3
4- 6
4-10
300.0
3- 7
3-11
4- 3
4- 7
4-10
5- 2
310.0
3-10
4- 2
4- 6
4-10
5- 2
5- 6
320.0
4- 1
4- 5
4-10
5- 2
5- 6
5-10
330.0
4- 4
4- 9
5- 1
5- 6
5-10
6- 3
340.0
4- 7
5- 0
5- 5
5-10
6- 3
6- 7
350.0
4-11
5- 4
5- 9
6- 2
6- 7
7- 0

1213. 1154. 1101. 1054. 1013.


----- ----- ----- ----- ----60.
70.
80.
90.
100.
Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----4- 1
4- 4
4- 6
4- 8
4-11
4- 5
4- 8
4-10
5- 1
5- 3
4- 9
5- 0
5- 3
5- 5
5- 8
5- 1
5- 4
5- 7
5-10
6- 1
5- 5
5- 9
6- 0
6- 3
6- 6
5-10
6- 1
6- 5
6- 8
6-11
6- 2
6- 6
6-10
7- 1
7- 5
6- 7
6-11
7- 3
7- 7
7-10
7- 0
7- 4
7- 8
8- 0
8- 4
7- 5
7- 9
8- 2
8- 6
8-10

Section WSC02
Page 50 of 50

E.C.S.
INFORMATION SECTION

DISTRIBUTION CHARTS STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

2 -#4/0 AWG 6/ 1 Stranding ACSR T-2 Conductor PENGUIN


Ruling Span: 325.0 Feet
INITIAL SAG CHART
H Tens
1926. 1791. 1673. 1569. 1478. 1398. 1328. 1265. 1210. 1160. 1115.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
100.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----280.0
3- 0
3- 3
3- 5
3- 8
3-11
4- 1
4- 4
4- 7
4- 9
5- 0
5- 2
290.0
3- 3
3- 5
3- 8
3-11
4- 2
4- 5
4- 8
4-11
5- 1
5- 4
5- 6
300.0
3- 5
3- 8
3-11
4- 3
4- 6
4- 9
5- 0
5- 3
5- 5
5- 8
5-11
310.0
3- 8
3-11
4- 3
4- 6
4- 9
5- 1
5- 4
5- 7
5-10
6- 1
6- 4
320.0
3-11
4- 2
4- 6
4-10
5- 1
5- 4
5- 8
5-11
6- 2
6- 6
6- 9
330.0
4- 2
4- 6
4- 9
5- 1
5- 5
5- 9
6- 0
6- 4
6- 7
6-10
7- 2
340.0
4- 5
4- 9
5- 1
5- 5
5- 9
6- 1
6- 5
6- 8
7- 0
7- 4
7- 7
350.0
4- 8
5- 0
5- 4
5- 9
6- 1
6- 5
6- 9
7- 1
7- 5
7- 9
8- 0
360.0
4-11
5- 4
5- 8
6- 1
6- 5
6- 9
7- 2
7- 6
7-10
8- 2
8- 6
370.0
5- 3
5- 7
6- 0
6- 5
6- 9
7- 2
7- 7
7-11
8- 3
8- 8
9- 0
380.0
5- 6
5-11
6- 4
6- 9
7- 2
7- 7
7-11
8- 4
8- 9
9- 1
9- 6
DESIGN SAG CHART
NESC Heavy Load Zone
Max Tension =
4000 lb
-----------------------------------------------------------------------------------Design: 2000. lb @
0. Deg ,
.50 in Ice,
4.00 psf Wind, Initial
-----------------------------------------------------------------------------------H Tens
2041. 3996. 1730. 1417. 2953. 1500. 1214. 1073.
983.
910.
853.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
-20.
0.
0.
30.
32.
60.
60.
90.
120.
167.
212.
Wt lb/f> .582 1.917
.582
.582 1.485
.742
.582
.582
.582
.582
.582
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----- ----280.0
2-10
4- 9
3- 4
4- 1
5- 0
4-11
4- 9
5- 4
5-10
6- 4
6- 9
290.0
3- 0
5- 1
3- 7
4- 4
5- 4
5- 3
5- 1
5- 9
6- 3
6- 9
7- 3
300.0
3- 3
5- 5
3-10
4- 8
5- 8
5- 7
5- 5
6- 2
6- 9
7- 3
7- 9
310.0
3- 6
5-10
4- 1
5- 0
6- 1
6- 0
5-10
6- 7
7- 2
7- 9
8- 3
320.0
3- 8
6- 2
4- 4
5- 4
6- 6
6- 5
6- 2
7- 0
7- 8
8- 3
8- 9
330.0
3-11
6- 7
4- 7
5- 8
6-11
6- 9
6- 7
7- 5
8- 1
8- 9
9- 4
340.0
4- 2
7- 0
4-11
6- 0
7- 4
7- 2
7- 0
7-11
8- 7
9- 3
9-11
350.0
4- 5
7- 5
5- 2
6- 4
7- 9
7- 7
7- 5
8- 4
9- 1
9-10 10- 6
360.0
4- 8
7-10
5- 6
6- 8
8- 2
8- 1
7-10
8-10
9- 8 10- 5 11- 1
370.0
4-11
8- 3
5-10
7- 1
8- 8
8- 6
8- 3
9- 4 10- 2 11- 0 11- 9
380.0
5- 2
8- 8
6- 1
7- 6
9- 2
9- 0
8- 8
9-10 10- 9 11- 7 12- 5
FINAL SAG CHART
H Tens
1729. 1608. 1505. 1416. 1339. 1272.
(LBS)
----- ----- ----- ----- ----- ----Temp F>
0.
10.
20.
30.
40.
50.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----280.0
3- 4
3- 7
3-10
4- 1
4- 4
4- 6
290.0
3- 7
3-10
4- 1
4- 4
4- 7
4-10
300.0
3-10
4- 1
4- 5
4- 8
4-11
5- 2
310.0
4- 1
4- 5
4- 8
5- 0
5- 3
5- 6
320.0
4- 4
4- 8
5- 0
5- 4
5- 7
5-11
330.0
4- 8
5- 0
5- 4
5- 8
6- 0
6- 3
340.0
4-11
5- 3
5- 8
6- 0
6- 4
6- 8
350.0
5- 2
5- 7
6- 0
6- 4
6- 8
7- 1
360.0
5- 6
5-11
6- 4
6- 8
7- 1
7- 5
370.0
5-10
6- 3
6- 8
7- 1
7- 6
7-11
380.0
6- 1
6- 7
7- 0
7- 6
7-11
8- 4

1213. 1161. 1114. 1072.


----- ----- ----- ----60.
70.
80.
90.
Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----4- 9
4-11
5- 2
5- 4
5- 1
5- 4
5- 6
5- 9
5- 5
5- 8
5-11
6- 2
5-10
6- 1
6- 4
6- 7
6- 2
6- 6
6- 9
7- 0
6- 7
6-10
7- 2
7- 5
7- 0
7- 3
7- 7
7-11
7- 5
7- 9
8- 1
8- 4
7-10
8- 2
8- 6
8-10
8- 3
8- 8
9- 0
9- 4
8- 8
9- 1
9- 6
9-10

1034.
----100.
Ft-In
----5- 7
6- 0
6- 5
6-10
7- 3
7- 8
8- 2
8- 8
9- 2
9- 8
10- 2

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 1 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

#2 7/1 ACSR
Sparate
Ruling Span = 150.0 Feet
Maximum Design Tension 33.5% of Ultimate 1221# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# - Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In Wt.
= .107 Lb./F RTS
= 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1221
819
367
153
108

100

110

120

130

1-02
1-00
0-08
0-11
1-03

1-04
1-02
0-10
1-01
1-07

1-07
1-05
1-00
1-03
1-10

1-11
1-08
1-02
1-06
2-02

140
150
160
Sag in Feet and Inches
2-02
2-06
2-10
1-11
2-02
2-06
1-04
1-06
1-09
1-09
2-00
2-03
2-06
2-10
3-03

170

180

190

200

3-02
2-09
1-11
2-07
3-08

3-07
3-01
2-02
2-10
4-01

4-00
3-06
2-05
3-02
4-06

4-05
3-10
2-08
3-06
5-00

"

Note: indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
580
507
438
374
317
270
232
202
180
170

100

110

120

130

0-03
0-03
0-04
0-04
0-05
0-06
0-06
0-07
0-08
0-09
0-10

0-03
0-04
0-04
0-05
0-06
0-07
0-08
0-09
0-10
0-11
1-00

0-04
0-04
0-05
0-06
0-07
0-08
0-09
0-10
1-00
1-01
1-02

0-05
0-05
0-06
0-07
0-08
0-09
0-10
1-00
1-02
1-03
1-04

140
150
160
Sag in Feet and Inches
0-05
0-06
0-07
0-06
0-07
0-08
0-07
0-08
0-09
0-08
0-09
0-10
0-09
0-10
0-11
0-10
1-00
1-01
1-00
1-02
1-04
1-02
1-04
1-06
1-04
1-06
1-09
1-06
1-09
1-11
1-07
1-10
2-01

170

180

190

200

0-08
0-09
0-10
0-11
1-01
1-03
1-06
1-08
1-11
2-02
2-04

0-08
0-09
0-11
1-00
1-02
1-05
1-08
1-11
2-02
2-05
2-07

0-09
0-10
1-00
1-02
1-04
1-07
1-10
2-01
2-05
2-09
2-11

0-10
1-00
1-01
1-03
1-06
1-09
2-00
2-04
2-08
3-00
3-02

E.C.S.
INFORMATION SECTION

Section WSC03
Page 2 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

#2 7/1 ACSR
Sparate
Ruling Span = 175.0 Feet
Maximum Design Tension 36.1% of Ultimate 1315# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# - Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In Wt.
= .107 Lb./F RTS
= 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs..
4
0
6
0
0

Ten.
Lbs.
1315
886
396
174
124

120

130

140

150

1-06
1-04
0-11
1-02
1-07

1-09
1-06
1-01
1-04
1-10

2-00
1-09
1-03
1-06
2-02

2-04
2-00
1-05
1-09
2-06

160
170
180
Sag in Feet and Inches
2-07
3-00
3-04
2-03
2-07
2-11
1-07
1-10
2-00
2-00
2-03
2-06
2-09
3-02
3-06

190

200

210

220

230

3-08
3-02
2-03
2-10
3-11

4-01
3-06
2-06
3-01
4-04

4-06
3-11
2-09
3-05
4-09

4-11
4-03
3-00
3-09
5-03

5-05
4-08
3-03
4-01
5-09

190

200

210

220

230

0-09
0-10
1-00
1-01
1-03
1-06
1-09
2-00
2-03
2-05
2-07

0-10
0-11
1-01
1-03
1-05
1-08
1-11
2-02
2-05
2-08
2-10

0-11
1-01
1-02
1-04
1-07
1-10
2-01
2-05
2-08
3-00
3-01

1-00
1-02
1-04
1-06
1-09
2-00
2-03
2-07
2-11
3-03
3-05

1-01
1-03
1-05
1-08
1-10
2-02
2-06
2-10
3-03
3-07
3-09

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs..
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
582
511
445
384
332
287
251
222
201
191

120

130

140

150

0-04
0-04
0-05
0-06
0-06
0-07
0-09
0-10
0-11
1-00
1-01

0-05
0-05
0-06
0-07
0-07
0-09
0-10
0-11
1-01
1-02
1-03

0-05
0-06
0-07
0-08
0-09
0-10
0-11
1-01
1-03
1-04
1-05

0-06
0-07
0-08
0-09
0-10
0-11
1-01
1-03
1-05
1-06
1-07

160
170
180
Sag in Feet and Inches
0-07
0-08
0-08
0-08
0-08
0-09
0-09
0-09
0-11
0-10
0-11
1-00
0-11
1-00
1-02
1-01
1-02
1-04
1-03
1-05
1-06
1-05
1-07
1-09
1-07
1-09
2-00
1-09
2-00
2-02
1-10
2-01
2-04

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 3 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

#2 7/1 ACSR
Sparate
Ruling Span = 200.0 Feet
Maximum Design Tension 38.6% of Ultimate 1406# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# - Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In Wt.
= .107 Lb./F RTS
= 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1406
949
423
194
141

150

160

170

180

2-02
1-11
1-04
1-07
2-02

2-06
2-02
1-06
1-10
2-06

2-09
2-05
1-08
2-00
2-09

3-01
2-08
1-11
2-03
3-01

190
200
210
Sag in Feet and Inches
3-05
3-10
4-03
3-00
3-04
3-08
2-01
2-04
2-07
2-06
2-10
3-01
3-06
3-10
4-03

220

230

240

250

4-07
4-00
2-10
3-05
4-08

5-00
4-04
3-01
3-08
5-01

5-06
4-09
3-04
4-00
5-06

5-11
5-02
3-08
4-04
6-00

220

230

240

250

1-00
1-02
1-03
1-06
1-08
1-11
2-02
2-05
2-09
3-00
3-01

1-01
1-03
1-05
1-07
1-10
2-01
2-04
2-08
3-00
3-03
3-05

1-03
1-04
1-06
1-09
2-00
2-03
2-07
2-11
3-03
3-06
3-08

1-04
1-06
1-08
1-11
2-02
2-06
2-09
3-02
3-06
3-10
4-00

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
584
516
452
395
345
303
269
241
222
211

150

160

170

180

0-06
0-07
0-07
0-08
0-10
0-11
1-00
1-02
1-03
1-05
1-06

0-07
0-07
0-08
0-10
0-11
1-00
1-02
1-04
1-06
1-07
1-08

0-08
0-08
0-09
0-11
1-00
1-02
1-04
1-06
1-08
1-09
1-10

0-08
0-09
0-10
1-00
1-02
1-04
1-06
1-08
1-10
2-00
2-01

190
200
210
Sag in Feet and Inches
0-09
0-10
0-11
0-10
0-11
1-00
1-00
1-01
1-02
1-01
1-03
1-04
1-03
1-05
1-06
1-05
1-07
1-09
1-08
1-10
2-00
1-10
2-00
2-03
2-00
2-03
2-06
2-03
2-05
2-08
2-04
2-07
2-10

E.C.S.
INFORMATION SECTION

Section WSC03
Page 4 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

#2 7/1 ACSR
Sparate
Ruling Span = 225.0 Feet
Maximum Design Tension 41.0% of Ultimate 1493# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# - Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In
Wt. = .107 Lb./F
RTS = 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1493
1009
449
213
157

170

180

190

200

2-07
2-03
1-07
1-10
2-06

2-11
2-06
1-09
2-01
2-09

3-03
2-10
2-00
2-04
3-01

3-07
3-01
2-02
2-06
3-05

210
220
230
Sag in Feet and Inches
4-00
4-04
4-09
3-05
3-09
4-01
2-05
2-08
2-11
2-10
3-01
3-04
3-09
4-02
4-06

240

250

260

270

280

5-02
4-06
3-02
3-08
4-11

5-07
4-10
3-05
3-11
5-04

6-01
5-03
3-08
4-03
5-09

6-06
5-08
4-00
4-07
6-03

7-00
6-01
4-03
4-11
6-08

240

250

260

270

280

1-03
1-04
1-06
1-09
1-11
2-02
2-05
2-09
3-00
3-03
3-04

1-04
1-06
1-08
1-10
2-01
2-04
2-08
3-00
3-03
3-06
3-08

1-05
1-07
1-09
2-00
2-03
2-07
2-10
3-02
3-06
3-09
3-11

1-06
1-08
1-11
2-02
2-05
2-09
3-01
3-05
3-10
4-01
4-03

1-08
1-10
2-01
2-04
2-08
2-11
3-04
3-09
4-01
4-05
4-07

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
586
520
460
406
358
319
286
258
242
231

170

180

190

200

0-08
0-08
0-09
0-11
1-00
1-01
1-03
1-05
1-06
1-08
1-09

0-08
0-09
0-10
1-00
1-01
1-03
1-05
1-07
1-09
1-10
1-11

0-09
0-10
1-00
1-01
1-03
1-05
1-07
1-09
1-11
2-00
2-01

0-10
0-11
1-01
1-02
1-04
1-06
1-09
1-11
2-01
2-03
2-04

210
220
230
Sag in Feet and Inches
0-11
1-00
1-01
1-00
1-02
1-03
1-02
1-03
1-05
1-04
1-05
1-07
1-06
1-08
1-09
1-08
1-10
2-00
1-11
2-01
2-03
2-01
2-04
2-06
2-04
2-06
2-09
2-06
2-09
3-00
2-07
2-10
3-01

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 5 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

#2 7/1 ACSR
Sparate
Ruling Span = 250.0 Feet
Maximum Design Tension 43.3% of Ultimate 1576# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In Wt.
= .107 Lb./F RTS
= 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Ice
In.
0.5
0.5
0
0
0

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1576
1067
474
232
173

200

210

220

230

3-05
2-11
2-01
2-04
3-01

3-09
3-03
2-04
2-07
3-05

4-01
3-07
2-06
2-10
3-09

4-06
3-11
2-09
3-01
4-01

240
250
260
Sag in Feet and Inches
4-11
5-04
5-09
4-03
4-07
5-00
3-00
3-03
3-06
3-04
3-08
3-11
4-06
4-10
5-03

270

280

290 300

6-02
5-04
3-09
4-03
5-08

6-08
5-09
4-01
4-07
6-01

7-02
6-02
4-04
4-11
6-06

270

280

290 300

1-06
1-08
1-11
2-01
2-05
2-08
3-00
3-03
3-07
3-09
3-11

1-08
1-10
2-00
2-03
2-07
2-10
3-02
3-06
3-10
4-00
4-03

1-09
1-11
2-02
2-05
2-09
3-01
3-05
3-09
4-02
4-04
4-06

7-08
6-07
4-08
5-03
7-00

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Ice
In.
0
0
0
0
0
0
0
0
0
0
0

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
588
525
467
416
371
333
301
275
261
251

200

210

220

230

0-10
0-11
1-01
1-02
1-04
1-06
1-08
1-10
2-00
2-01
2-02

0-11
1-00
1-02
1-04
1-06
1-08
1-10
2-00
2-02
2-03
2-05

1-00
1-02
1-03
1-05
1-07
1-09
2-00
2-02
2-05
2-06
2-07

1-01
1-03
1-05
1-07
1-09
1-11
2-02
2-05
2-07
2-09
2-10

240
250
260
Sag in Feet and Inches
1-03
1-04
1-05
1-04
1-06
1-07
1-06
1-08
1-09
1-08
1-10
2-00
1-11
2-01
2-03
2-01
2-03
2-06
2-04
2-06
2-09
2-07
2-10
3-00
2-10
3-01
3-04
3-00
3-03
3-06
3-01
3-04
3-08

1-10
2-01
2-04
2-07
2-11
3-03
3-08
4-00
4-05
4-08
4-10

E.C.S.
INFORMATION SECTION

Section WSC03
Page 6 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

#2 7/1 ACSR
Sparate
Ruling Span = 275.0 Feet
Maximum Design Tension 45.5% of Ultimate 1657# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 655# Limiting Condition
Area = .0654 Sq. In.
Dia = .325 In Wt.
= .107 Lb./F RTS
= 3640 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 56.6
Data from Chart No. 1-670
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind.
Lbs.
4
0
6
0
0

Ten.
Lbs.
1657
1123
498
251
189

220

230

240

250

3-11
3-05
2-05
2-07
3-05

4-03
3-08
2-08
2-10
3-09

4-08
4-00
2-10
3-01
4-01

5-01
4-04
3-01
3-04
4-05

260
270
280
Sag in Feet and Inches
5-06
5-11
6-04
4-09
5-01
5-06
3-04
3-07
3-11
3-08
3-11
4-03
4-10
5-02
5-07

290

300

310

320

330

6-09
5-10
4-02
4-06
6-00

7-03
6-03
4-05
4-10
6-05

7-09
6-08
4-09
5-02
6-10

8-03
7-01
5-01
5-06
7-03

8-09
7-07
5-04
5-10
7-09

290

300

310

320

330

1-09
1-11
2-02
2-05
2-08
3-00
3-03
3-07
3-11
4-00
4-02

1-10
2-01
2-04
2-07
2-10
3-02
3-06
3-10
4-02
4-04
4-06

2-00
2-03
2-05
2-09
3-01
3-05
3-09
4-01
4-05
4-07
4-09

2-02
2-04
2-07
2-11
3-03
3-07
4-00
4-04
4-09
4-11
5-01

2-03
2-06
2-09
3-01
3-05
3-10
4-03
4-08
5-00
5-03
5-05

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind.
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
655
590
530
475
426
383
347
316
292
280
270

220

230

240

250

1-00
1-02
1-03
1-05
1-07
1-09
1-11
2-01
2-03
2-04
2-05

1-01
1-03
1-04
1-06
1-08
1-11
2-01
2-03
2-06
2-07
2-08

1-03
1-04
1-06
1-08
1-10
2-00
2-03
2-06
2-08
2-09
2-11

1-04
1-05
1-07
1-10
2-00
2-03
2-05
2-08
2-11
3-00
3-02

260
270
280
Sag in Feet and Inches
1-05
1-06
1-08
1-07
1-08
1-10
1-09
1-10
2-00
1-11
2-01
2-03
2-02
2-04
2-06
2-05
2-07
2-09
2-08
2-10
3-01
2-11
3-01
3-04
3-02
3-05
3-08
3-03
3-06
3-09
3-05
3-08
3-11

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 7 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR


4/0 6/1 ACSR,
Penguin
Ruling Span = 150.0 Feet

Maximum Design Tension 26.7% of Ultimate 2226# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 1503# Limiting Condition
Area = .1939 Sq. In.
Dia = .563 In Wt.
= .291 Lb./F RTS
= 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.0
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2226
1508
709
365
273

100

110

120

130

0-10
0-10
0-09
1-00
1-04

1-00
1-00
0-11
1-03
1-08

1-02
1-02
1-01
1-06
2-00

1-04
1-05
1-03
1-09
2-03

140
150
160
Sag in Feet and Inches
1-07
1-09
2-00
1-07
1-10
2-01
1-05
1-08
1-10
2-00
2-03
2-07
2-08
3-00
3-05

170

180

190

200

2-03
2-04
2-01
2-11
3-11

2-07
2-07
2-04
3-03
4-04

2-10
2-11
2-07
3-08
4-10

3-02
3-02
2-11
4-00
5-04

170

180

190

200

0-09
0-10
1-00
1-02
1-05
1-07
1-11
2-02
2-05
2-07
2-08

0-10
0-11
1-01
1-04
1-07
1-10
2-01
2-05
2-08
2-11
3-00

0-11
1-01
1-03
1-05
1-09
2-00
2-04
2-08
3-00
3-03
3-04

1-00
1-02
1-04
1-07
1-11
2-03
2-07
3-00
3-03
3-07
3-09

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1298
1105
932
784
664
571
501
447
413
395

100

110

120

130

0-03
0-04
0-04
0-05
0-06
0-07
0-08
0-09
0-10
0-11
1-00

0-04
0-05
0-05
0-06
0-07
0-08
0-10
0-11
1-00
1-01
1-02

0-05
0-05
0-06
0-07
0-09
0-10
1-00
1-01
1-03
1-04
1-04

0-05
0-06
0-07
0-08
0-10
1-00
1-01
1-03
1-05
1-06
1-07

140
150
160
Sag in Feet and Inches
0-06
0-07
0-08
0-07
0-08
0-09
0-08
0-09
0-11
0-10
0-11
1-00
0-11
1-01
1-03
1-01
1-03
1-05
1-03
1-06
1-08
1-06
1-08
1-11
1-08
1-10
2-01
1-09
2-00
2-04
1-10
2-01
2-05

E.C.S.
INFORMATION SECTION

Section WSC03
Page 8 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

4/0 6/1 ACSR


Penguin
Ruling Span = 175.0 Feet
Maximum Design Tension 28.3% of Ultimate 2364# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 1503# Limiting Condition
Area = .1939 Sq. In.
Dia = .563 In Wt.
= .291 Lb./F RTS
= 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.0
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2364
1624
775
409
312

120

130

140

150

1-01
1-01
1-00
1-04
1-09

1-03
1-03
1-02
1-07
2-00

1-06
1-06
1-04
1-09
2-04

1-08
1-08
1-06
2-01
2-08

160
170
180
Sag in Feet and Inches
1-11
2-02
2-05
1-11
2-02
2-05
1-09
1-11
2-02
2-04
2-07
2-11
3-00
3-05
3-10

190

200

210

220

230

2-08
2-08
2-05
3-03
4-03

3-00
3-00
2-08
3-07
4-08

3-03
3-03
2-11
4-00
5-02

3-07
3-07
3-02
4-04
5-08

3-11
3-11
3-06
4-09
6-03

190

200

210

220

230

0-11
1-00
1-03
1-05
1-08
1-11
2-02
2-05
2-08
2-11
3-00

1-00
1-02
1-04
1-07
1-10
2-01
2-05
2-08
2-11
3-03
3-04

1-01
1-03
1-06
1-09
2-00
2-04
2-07
2-11
3-03
3-07
3-08

1-03
1-05
1-07
1-10
2-02
2-06
2-10
3-03
3-07
3-11
4-00

1-04
1-06
1-09
2-00
2-04
2-09
3-02
3-06
3-11
4-03
4-05

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1306
1123
961
823
711
622
553
499
458
440

120

130

140

150

0-05
0-05
0-06
0-07
0-08
0-09
0-11
1-00
1-01
1-02
1-03

0-05
0-06
0-07
0-08
0-09
0-11
1-00
1-02
1-03
1-05
1-05

0-06
0-07
0-08
0-09
0-11
1-00
1-02
1-04
1-06
1-07
1-08

0-07
0-08
0-09
0-11
1-00
1-02
1-04
1-06
1-08
1-10
1-11

160
170
180
Sag in Feet and Inches
0-08
0-09
0-10
0-09
0-10
0-11
0-10
1-00
1-01
1-00
1-02
1-03
1-02
1-04
1-06
1-04
1-06
1-08
1-06
1-09
1-11
1-09
1-11
2-02
1-11
2-02
2-05
2-01
2-04
2-07
2-02
2-05
2-09

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 9 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

4/0 6/1 ACSR


Penguin
Ruling Span = 200.0 Feet
Maximum Design Tension 29.9% of Ultimate 2497# at 0F with ice & 4# wind Final
Tension at 0F = 18% of Ultimate 1503# Limiting Condition
Area = .1939 Sq. In.
Dia = .563 In Wt.
= .291 Lb./F RTS
= 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.0
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2497
1733
836
451
351

150

160

170

180

1-07
1-07
1-05
1-10
2-05

1-10
1-10
1-07
2-01
2-08

2-01
2-00
1-09
2-04
3-01

2-03
2-03
2-00
2-08
3-05

190
200
210
Sag in Feet and Inches
2-07
2-10
3-01
2-06
2-09
3-01
2-03
2-06
2-09
3-00
3-03
3-07
3-09
4-02
4-08

220

230

240

250

3-05
3-04
3-00
3-11
5-01

3-09
3-08
3-03
4-04
5-06

4-00
4-00
3-06
4-08
6-00

4-05
4-04
3-10
5-01
6-06

220

230

240

250

1-03
1-05
1-07
1-10
2-01
2-05
2-08
3-00
3-03
3-06
3-08

1-04
1-06
1-09
2-00
2-03
2-07
2-11
3-03
3-07
3-10
4-00

1-05
1-08
1-11
2-02
2-06
2-10
3-02
3-06
3-10
4-02
4-05

1-07
1-09
2-00
2-04
2-08
3-01
3-05
3-10
4-02
4-07
4-09

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1314
1141
989
860
754
669
602
548
504
483

150

160

170

180

0-07
0-08
0-09
0-10
1-00
1-02
1-03
1-05
1-06
1-08
1-09

0-08
0-09
0-10
1-00
1-01
1-03
1-05
1-07
1-09
1-11
2-00

0-09
0-10
1-00
1-01
1-03
1-05
1-07
1-09
2-00
2-02
2-03

0-10
0-11
1-01
1-03
1-05
1-07
1-10
2-00
2-02
2-05
2-06

190
200
210
Sag in Feet and Inches
0-11
1-00
1-01
1-00
1-02
1-03
1-02
1-04
1-05
1-04
1-06
1-08
1-07
1-09
1-11
1-09
2-00
2-02
2-00
2-03
2-05
2-03
2-06
2-09
2-05
2-08
3-00
2-08
2-11
3-03
2-09
3-01
3-04

E.C.S.
INFORMATION SECTION

Section WSC03
Page 10 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

4/0 6/1 ACSR


Penguin
Ruling Span = 225.0 Feet
Maximum Design Tension 31.4% of Ultimate - 2625# at 0F with 1/2" ice
& 4# wind Final Tension at 0F = 18% of Ultimate - 1503# - Limiting
Condition
Area = .1939 Sq. In
Dia = .563 In
Wt. = .291 Lb./F
RTS = 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is
44.0 Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2625
1837
894
492
387

170

180

190

200

1-11
1-11
1-08
2-02
2-09

2-02
2-02
1-11
2-05
3-01

2-05
2-05
2-01
2-09
3-05

2-08
2-08
2-04
3-00
3-10

210
220
230
Sag in Feet and Inches
2-11
3-03
3-06
2-11
3-02
3-06
2-06
2-09
3-00
3-04
3-08
4-00
4-02
4-07
5-00

240

250

260

270 280

3-10
3-09
3-04
4-04
5-06

4-02
4-01
3-07
4-08
5-11

4-06
4-05
3-10
5-01
6-05

4-10
4-09
4-02
5-05
6-11

5-03
5-01
4-06
5-10
7-05

240

250

260

270

280

1-05
1-07
1-10
2-01
2-05
2-08
3-00
3-03
3-07
3-10
4-00

1-07
1-09
2-00
2-03
2-07
2-11
3-03
3-07
3-11
4-02
4-05

1-08
1-11
2-02
2-06
2-09
3-02
3-06
3-10
4-02
4-06
4-09

1-10
2-00
2-04
2-08
3-00
3-05
3-09
4-02
4-06
4-11
5-01

1-11
2-02
2-06
2-10
3-03
3-08
4-00
4-05
4-10
5-03
5-06

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1322
1159
1015
894
794
713
647
594
549
523

170

180

190

200

0-09
0-10
0-11
1-01
1-03
1-04
1-06
1-08
1-10
2-00
2-01

0-10
0-11
1-01
1-02
1-04
1-06
1-08
1-10
2-00
2-02
2-03

0-11
1-00
1-02
1-04
1-06
1-08
1-11
2-01
2-03
2-05
2-07

1-00
1-02
1-04
1-06
1-08
1-10
2-01
2-03
2-06
2-08
2-10

210
220
230
Sag in Feet and Inches
1-01
1-03
1-04
1-03
1-04
1-06
1-05
1-07
1-08
1-07
1-09
1-11
1-10
2-00
2-02
2-01
2-03
2-06
2-03
2-06
2-09
2-06
2-09
3-00
2-09
3-00
3-03
3-00
3-03
3-07
3-01
3-05
3-09

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 11 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

4/0 6/1 ACSR


Penguin
Ruling Span = 250.0 Feet
Maximum Design Tension 32.9% of Ultimate - 2748# at 0F with 1/2" ice & 4# wind Final Tension
at 0F = 18% of Ultimate - 1503# - Limiting Condition
Area = .1939 Sq. In
Dia = .563 In
Wt. = .291 Lb./F
RTS = 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.0
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2748
1936
947
530
423

200

210

220

230

2-07
2-06
2-02
2-09
3-06

2-10
2-09
2-05
3-01
3-10

3-01
3-00
2-08
3-04
4-03

3-04
3-04
2-10
3-08
4-07

240
250
260
Sag in Feet and Inches
3-08
4-00
4-04
3-07
3-11
4-02
3-01
3-05
3-08
4-00
4-04
4-08
5-00
5-05
5-10

270

280

290

300

4-08
4-06
3-11
5-01
6-04

5-00
4-10
4-03
5-05
6-10

5-04
5-03
4-06
5-10
7-03

5-09
5-07
4-10
6-03
7-10

270

280

290

300

1-10
2-00
2-03
2-07
2-11
3-03
3-07
3-11
4-03
4-06
4-09

1-11
2-02
2-06
2-09
3-01
3-06
3-10
4-02
4-06
4-10
5-01

2-01
2-04
2-08
3-00
3-04
3-09
4-01
4-06
4-10
5-03
5-06

2-03
2-06
2-10
3-02
3-07
4-00
4-05
4-09
5-02
5-07
5-10

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1331
1176
1041
927
832
754
689
636
592
562

200

210

220

230

1-00
1-02
1-03
1-05
1-07
1-09
2-00
2-02
2-04
2-06
2-08

1-01
1-03
1-05
1-07
1-09
2-00
2-02
2-04
2-07
2-09
2-11

1-03
1-04
1-06
1-09
1-11
2-02
2-05
2-07
2-10
3-00
3-02

1-04
1-06
1-08
1-11
2-01
2-04
2-07
2-10
3-01
3-04
3-06

240
250
260
Sag in Feet and Inches
1-05
1-07
1-08
1-07
1-09
1-11
1-10
2-00
2-02
2-01
2-03
2-05
2-04
2-06
2-08
2-07
2-09
3-00
2-10
3-01
3-04
3-01
3-04
3-07
3-04
3-07
3-11
3-07
3-11
4-02
3-09
4-01
4-05

E.C.S.
INFORMATION SECTION

Section WSC03
Page 12 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

4/0 6/1 ACSR


Penguin
Ruling Span = 275.0 Feet
Maximum Design Tension 34.3% of Ultimate - 2867# at 0F with 1/2" ice & 4# wind Final Tension
at 0F = 18% of Ultimate - 1503# - Limiting Condition
Area = .1939 Sq. In
Dia = .563 In
Wt. = .291 Lb./F
RTS = 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.0
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2867
2030
997
566
457

220

230

240

250

3-00
2-11
2-06
3-02
3-11

3-03
3-02
2-09
3-05
4-03

3-06
3-05
3-00
3-09
4-08

3-10
3-09
3-03
4-01
5-00

260
270
280
Sag in Feet and Inches
4-02
4-05
4-09
4-00
4-04
4-08
3-06
3-09
4-00
4-05
4-09
5-01
5-05
5-10
6-04

290

300

310

320

330

5-02
5-00
4-04
5-06
6-09

5-06
5-04
4-07
5-10
7-03

5-10
5-08
4-11
6-03
7-09

6-03
6-01
5-03
6-08
8-03

6-08
6-05
5-07
7-01
8-09

290

300

310

320 330

2-01
2-04
2-07
2-11
3-03
3-07
3-11
4-03
4-07
4-11
5-02

2-03
2-06
2-09
3-01
3-06
3-10
4-02
4-06
4-11
5-03
5-06

2-04
2-08
3-00
3-04
3-08
4-01
4-06
4-10
5-03
5-07
5-11

2-06
2-10
3-02
3-06
3-11
4-04
4-09
5-02
5-07
5-11
6-03

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1503
1339
1193
1066
958
867
792
729
676
632
598

220

230

240

250

1-03
1-04
1-06
1-08
1-11
2-01
2-03
2-06
2-08
2-10
3-00

1-04
1-06
1-08
1-10
2-01
2-03
2-06
2-08
2-11
3-01
3-03

1-05
1-07
1-10
2-00
2-03
2-06
2-08
2-11
3-02
3-04
3-07

1-07
1-09
1-11
2-02
2-05
2-08
2-11
3-02
3-05
3-08
3-10

260
270
280
Sag in Feet and Inches
1-08
1-10
1-11
1-11
2-00
2-02
2-01
2-03
2-05
2-04
2-06
2-09
2-07
2-10
3-00
2-11
3-01
3-04
3-02
3-05
3-08
3-05
3-08
4-00
3-08
4-00
4-03
3-11
4-03
4-07
4-02
4-06
4-10

2-08
3-00
3-04
3-09
4-02
4-07
5-01
5-06
5-11
6-04
6-08

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 13 of 18

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR


556.5 Kcmil 18/1 ACSR
Osprey
Ruling Span = 150.0 Feet

Maximum Design Tension 18.2% of Ultimate - 2500# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 2500# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 36
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP

WIND

TEN.

LBS.

LBS

100

110

120

130

140

150

160

170

180

190

200

Sag in Feet and Inches

0*

2407

1-00

1-03

1-05

1-08

2-00

2-03

2-07

2-11

3-03

3-07

4-00

32*

1603

1-02

1-05

1-08

2-00

2-03

2-07

3-00

3-04

3-09

4-02

4-07

60

752

1-03

1-07

1-10

2-02

2-06

2-10

3-03

3-08

4-01

4-06

5-00

120

467

1-08

2-00

2-05

2-09

3-03

3-08

4-02

4-09

5-04

5-11

6-06

212

400

1-11

2-04

2-09

3-03

3-09

4-04

4-11

5-06

6-02

6-10

7-07

170

180

190

200

210

220

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

120

130

140

150

160

LBS.

LBS

20

849

0-11

1-01

1-04

1-06

Sag in Feet and Inches


1-09

2-00

2-04

2-07

2-11

3-03

3-07

30

771

1-00

1-03

1-05

1-08

2-00

2-03

2-07

2-11

3-03

3-07

4-00

40

710

1-01

1-04

1-07

1-10

2-02

2-05

2-09

3-01

3-06

3-11

4-04

50

660

1-02

1-05

1-08

2-00

2-03

2-07

3-00

3-04

3-09

4-02

4-08

60

618

1-03

1-06

1-10

2-01

2-05

2-09

3-02

3-07

4-00

4-05

4-11

70

583

1-04

1-07

1-11

2-03

2-07

3-00

3-04

3-09

4-03

4-09

5-03

80

554

1-05

1-08

2-00

2-04

2-09

3-01

3-06

4-00

4-06

5-00

5-06

90

528

1-06

1-09

2-01

2-06

2-10

3-03

3-09

4-02

4-08

5-03

5-09

100

505

1-06

1-10

2-02

2-07

3-00

3-05

3-10

4-04

4-11

5-05

6-00

E.C.S.
INFORMATION SECTION

Section WSC03
Page 14 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

556.5 Kcmil 18/1 ACSR


Osprey
Ruling Span = 175.0 Feet
Maximum Design Tension 18.2% of Ultimate - 2500# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 2500# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 36
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP

WIND

TEN.

LBS.

LBS

120

130

140

150

160

170

180

190

200

210

220

230

Sag in Feet and Inches

0*

2417

1-05

1-08

2-00

2-03

2-07

2-10

3-03

3-07

4-00

4-04 4-09 5-03

32*

1658

1-08

1-11

2-02

2-06

2-10

3-03

3-07

4-00

4-05

4-11 5-05 5-11

60

793

1-09

2-00

2-04

2-08

3-01

3-06

3-10

4-04

4-09

5-03 5-09 6-03

120

512

2-02

2-06

2-11

3-04

3-10

4-04

4-10

5-05

6-00

6-07 7-02 7-10

212

442

2-06

2-11

3-05

3-11

4-05

5-00

5-07

6-03

6-11

7-07 8-04 9-02

180

190

200

210

2-09

3-01

3-05 3-09 4-01

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

LBS.

LBS

995

120

130

140

150

1-02

1-04

1-06

1-09

160

170

220

230

Sag in Feet and Inches


2-00

2-03

2-06

10

905

1-03

1-05

1-08

1-11

2-02

2-06

2-09

3-01

3-05

3-09 4-01 4-06

20

833

1-04

1-07

1-10

2-01

2-04

2-08

3-00

3-04

3-08

4-00 4-05 4-10

30

775

1-05

1-08

1-11

2-03

2-06

2-10

3-02

3-07

3-11

4-04 4-09 5-02

40

726

1-06

1-10

2-01

2-05

2-09

3-01

3-05

3-10

4-03

4-08 5-01 5-07

50

685

1-08

1-11

2-02

2-06

2-10

3-03

3-07

4-00

4-05

4-11 5-05 5-11

60

650

1-09

2-00

2-04

2-08

3-00

3-05

3-10

4-03

4-08

5-02 5-08 6-03

70

620

1-10

2-01

2-05

2-09

3-02

3-07

4-00

4-05

4-11

5-05 5-11 6-06

80

593

1-11

2-02

2-06

2-11

3-04

3-09

4-02

4-08

5-02

5-08 6-03 6-09

90

569

1-11

2-03

2-08

3-00

3-05

3-11

4-04

4-10

5-04

5-11 6-06 7-01

100

548

2-00

2-04

2-09

3-02

3-07

4-00

4-06

5-00

5-07

6-02 6-09 7-04

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 15 of 18

DISTRIBUTION CHARTS NON-STANDARD CONDUCTOR


556.5 Kcmil 18/1 ACSR
Osprey
Ruling Span = 200.0 Feet

Maximum Design Tension 29.2% of Ultimate - 4000# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 4000# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 36
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP

WIND

TEN.

LBS.

LBS

150

160

170

180

190

200

210

220

230

240

250

Sag in Feet and Inches

0*

3819

1-05

1-08

1-10

2-01

2-03

2-06

2-09

3-00

3-04 3-07

3-11

32*

2611

1-07

1-10

2-01

2-04

2-07

2-10

3-02

3-05

3-09 4-01

4-05

60

1285

1-08

1-11

2-02

2-05

2-08

2-11

3-03

3-07

3-11 4-03

4-07

120

728

2-05

2-08

3-01

3-05

3-09

4-02

4-08

5-01

5-06 6-00

6-06

212

575

3-00

3-05

3-10

4-04

4-10

5-04

5-10

6-05

7-00 7-08

8-03

200

210

220

230

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

LBS.

LBS

150

160

170

180

190

240

250

Sag in Feet and Inches

2424

0-09

0-10

0-11

1-01

1-02

1-03

1-05

1-07

1-08 1-10 2-00

10

2064

0-10

1-00

1-01

1-03

1-04

1-06

1-08

1-10

2-00 2-02 2-04

20

1764

1-00

1-02

1-03

1-05

1-07

1-09

1-11

2-01

2-04 2-06 2-09

30

1525

1-02

1-04

1-06

1-08

1-10

2-00

2-03

2-05

2-08 2-11 3-02

40

1339

1-04

1-06

1-08

1-10

2-01

2-04

2-06

2-09

3-00 3-03 3-07

50

1195

1-06

1-08

1-10

2-01

2-04

2-07

2-10

3-01

3-05 3-08 4-00

60

1082

1-07

1-10

2-01

2-04

2-07

2-10

3-01

3-05

3-09 4-01 4-05

70

992

1-09

2-00

2-03

2-06

2-09

3-01

3-05

3-09

4-01 4-05 4-10

80

919

1-11

2-02

2-05

2-08

3-00

3-04

3-08

4-00

4-05 4-09 5-02

90

859

2-00

2-03

2-07

2-11

3-03

3-07

3-11

4-04

4-08 5-01 5-06

100

808

2-02

2-05

2-09

3-01

3-05

3-09

4-02

4-07

5-00 5-05 5-11

E.C.S.
INFORMATION SECTION

Section WSC03
Page 16 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

556.5 Kcmil 18/1 ACSR


Osprey
Ruling Span = 225.0 Feet
Maximum Design Tension 29.2% of Ultimate - 4000# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 4000# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 36
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP WIND
F

TEN.

LBS.

170

180

190

200

210

LBS

220

230

240

250

260

270

280

Sag in Feet and Inches

0*

3828

1-10

2-00

2-03

2-06

2-09

3-00

3-04

3-07

3-11

4-03

4-07 4-11

32*

2660

2-00

2-03

2-06

2-09

3-01

3-04

3-08

4-00

4-04

4-08

5-01 5-05

60

1320

2-01

2-04

2-07

2-11

3-02

3-06

3-09

4-01

4-06

4-10

5-03 5-07

120

780

2-10

3-02

3-06

3-11

4-04

4-09

5-02

5-08

6-01

6-07

7-01 7-08

212

620

3-07

4-00

4-05

4-11

5-05

6-00

6-06

7-01

7-08

8-04

8-11 9-08

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

LBS.

LBS

2201

170

180

190

200

1-00

1-02

1-03

1-05

210

220

230

240

250

260

270

280

2-00

2-02

2-04 2-07 2-09

Sag in Feet and Inches


1-07

1-08

1-10

10

1904

1-02

1-04

1-06

1-08

1-09

2-00

2-02

2-04

2-06

2-09 2-11 3-02

20

1664

1-04

1-06

1-08

1-10

2-00

2-03

2-05

2-08

2-11

3-01 3-04 3-07

30

1473

1-06

1-08

1-11

2-01

2-04

2-06

2-09

3-00

3-03

3-06 3-09 4-01

40

1323

1-08

1-11

2-01

2-04

2-07

2-10

3-01

3-04

3-07

3-11 4-02 4-06

50

1203

1-10

2-01

2-04

2-07

2-10

3-01

3-04

3-08

4-00

4-03 4-07 5-00

60

1107

2-00

2-03

2-06

2-09

3-01

3-04

3-08

4-00

4-04

4-08 5-00 5-05

70

1027

2-02

2-05

2-08

3-00

3-03

3-07

3-11

4-03

4-08

5-00 5-05 5-10

80

961

2-04

2-07

2-11

3-02

3-06

3-10

4-02

4-07

4-11

5-04 5-09 6-02

90

906

2-05

2-09

3-01

3-05

3-09

4-01

4-06

4-10

5-03

5-08 6-02 6-07

100

858

2-07

2-11

3-03

3-07

3-11

4-04

4-08

5-01

5-07

6-00 6-06 6-11

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC03
Page 17 of 18

DISTRIBUTION CHARTS NON-STANDARD CONDUCTOR


556.5 Kcmil 18/1 ACSR
Osprey
Ruling Span = 250.0 Feet

Maximum Design Tension 29.2% of Ultimate - 4000# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 4000# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 36
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP

WIND

TEN.

LBS.

LBS

200

210

220

230

240

250

260

270

280

290

300

Sag in Feet and Inches

0*

3838

2-06

2-09

3-00

3-04

3-07

3-11

4-02

4-06

4-10 5-03 5-07

32*

2703

2-09

3-00

3-04

3-07

3-11

4-03

4-07

5-00

5-04 5-09 6-02

60

1351

2-10

3-01

3-05

3-08

4-00

4-04

4-09

5-01

5-06 5-10 6-03

120

827

3-08

4-01

4-06

4-11

5-04

5-09

6-03

6-09

7-03 7-09 8-03

212

662

4-07

5-01

5-07

6-01

6-08

7-02

7-09

8-05

9-00 9-08 10-04

250

260

270

280

2-09

3-00 3-02 3-05

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

LBS.

LBS

200

210

2016

1-06

1-08

220

230

240

290

300

Sag in Feet and Inches


1-10

2-00

2-02

2-05

2-07

10

1779

1-09

1-11

2-01

2-03

2-06

2-08

2-11

3-02

3-04 3-07 3-10

20

1588

1-11

2-02

2-04

2-07

2-09

3-00

3-03

3-06

3-09 4-00 4-04

30

1435

2-02

2-04

2-07

2-10

3-01

3-04

3-07

3-11

4-02 4-06 4-09

40

1312

2-04

2-07

2-10

3-01

3-04

3-08

3-11

4-03

4-07 4-11 5-03

50

1211

2-06

2-09

3-01

3-04

3-08

3-11

4-03

4-07

4-11 5-03 5-08

60

1127

2-09

3-00

3-03

3-07

3-11

4-03

4-07

4-11

5-04 5-08 6-01

70

1057

2-11

3-02

3-06

3-10

4-02

4-06

4-10

5-03

5-08 6-01 6-06

80

997

3-01

3-05

3-09

4-01

4-05

4-09

5-02

5-07

6-00 6-05 6-10

90

946

3-03

3-07

3-11

4-03

4-08

5-00

5-05

5-10

6-04 6-09 7-03

100

901

3-05

3-09

4-01

4-06

4-11

5-03

5-09

6-02

6-08 7-01 7-07

E.C.S.
INFORMATION SECTION

Section WSC03
Page 18 of 18

Issued 11-01-14

DISTRIBUTION CHARTS - NON-STANDARD CONDUCTOR

SAG AND TENSION

556.5 Kcmil 18/1 ACSR


Osprey
Ruling Span = 275.0 Feet
Maximum Design Tension 29.2% of Ultimate - 4000# at 0F with 1/2 " ice & 4#
wind Final Tension at 0F with 1/2 " ice & 4# wind - 4000# - Limiting Condition
Area = .4612 Sq. In
Dia = .879 In
Wt. = .604 Lb./F
RTS = 13700 Lb.
Blowout Angle for 6# Wind is 36
NESC Heavy Load Zone
Data from Chart No. 1-844
Creep IS a Factor
Design Sag Chart
TEMP

WIND

TEN.

LBS.

LBS

220

230

240

250

260

270

280

290

300

310

320

330

Sag in Feet and Inches

0*

3849

3-00

3-03

3-07

3-11

4-02

4-06

4-10

5-03 5-07 5-11

6-04

6-09

32*

2742

3-03

3-07

3-11

4-03

4-07

4-11

5-03

5-08 6-01 6-06

6-11

7-04

60

1376

3-04

3-08

3-11

4-03

4-08

5-00

5-04

5-09 6-02 6-07

7-00

7-05

120

869

4-03

4-08

5-01

5-06

5-11

6-05

6-10

7-04 7-11 8-05

9-00

9-06

212

700

5-03

5-09

6-03

6-10

7-04

7-11

8-06

9-02 9-10 10-06 11-02 11-10

"

Note: indicates 1/2 ice load

Final Sag Chart


TEMP

WIND

TEN.

LBS.

LBS

220

230

240

250

260

270

280

290

300

310

320

330

Sag in Feet and Inches

1871

2-00

2-02

2-04

2-07

2-09

3-00

3-02

3-05

3-08 3-11 4-02 4-05

10

1684

2-03

2-05

2-07

2-10

3-01

3-04

3-07

3-10

4-01 4-04 4-08 4-11

20

1531

2-05

2-08

2-11

3-01

3-04

3-08

3-11

4-02

4-06 4-09 5-01 5-05

30

1407

2-08

2-11

3-02

3-05

3-08

3-11

4-03

4-07

4-10 5-02 5-06 5-11

40

1304

2-10

3-01

3-05

3-08

4-00

4-03

4-07

4-11

5-03 5-07 6-00 6-04

50

1217

3-01

3-04

3-07

3-11

4-03

4-07

4-11

5-03

5-08 6-00 6-05 6-10

60

1145

3-03

3-06

3-10

4-02

4-06

4-10

5-03

5-07

6-00 6-05 6-10 7-03

70

1082

3-05

3-09

4-01

4-05

4-09

5-02

5-06

5-11

6-04 6-09 7-02 7-08

80

1028

3-07

3-11

4-03

4-08

5-00

5-05

5-10

6-03

6-08 7-01 7-07 8-01

90

981

3-09

4-02

4-06

4-10

5-03

5-08

6-01

6-06

7-00 7-06 7-11 8-05

100

939

3-11

4-04

4-08

5-01

5-06

5-11

6-04

6-10

7-04 7-09 8-04 8-10

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC05
Page 1 of 5

SECONDARY CHARTS - INITIAL SAG

#4 with #4 ACSR Neutral


Terrier, Duplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

464

433

402

372

341

311

283

257

233

211

192

10

20

30

70

80

90

100

0- 2
0- 3
0- 4
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
0-11
1- 1
1- 2
1- 4

0- 2
0- 3
0- 4
0- 5
0- 5
0- 6
0- 7
0- 8
0-10
0-11
1- 0
1- 2
1- 3
1- 5

0- 3
0- 3
0- 4
0- 5
0- 6
0- 7
0- 8
0- 9
0-10
1- 0
1- 1
1- 3
1- 4
1- 6

0- 3
0- 4
0- 4
0- 5
0- 6
0- 7
0- 8
0-10
0-11
1- 1
1- 2
1- 4
1- 6
1- 7

40
50
60
Sag in Feet and Inches
0- 3
0- 3
0- 4
0- 4
0- 4
0- 4
0- 5
0- 5
0- 6
0- 6
0- 6
0- 7
0- 7
0- 7
0- 8
0- 8
0- 9
0- 9
0- 9
0-10
0-11
0-11
1- 0
1- 1
1- 0
1- 1
1- 2
1- 2
1- 3
1- 4
1- 3
1- 5
1- 6
1- 5
1- 7
1- 9
1- 7
1- 9
1-11
1- 9
1-11
2- 1

0- 4
0- 5
0- 6
0- 7
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 1
2- 4

0- 4
0- 5
0- 7
0- 8
0-10
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 4
2- 7

0- 5
0- 6
0- 7
0- 9
0-11
1- 0
1- 3
1- 5
1- 7
1-10
2- 1
2- 3
2- 7
2-10

0- 5
0- 6
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 3
2- 6
2- 9
3- 1

#2 with #4 ACSR Neutral


Cockle, Triplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

352

333

315

298

283

269

257

245

235

225

216

10

20

30

70

80

90

100

0- 5
0- 7
0- 9
0-10
1- 1
1- 3
1- 5
1- 8
1-11
2- 2
2- 5
2- 9
3- 0
3- 4

0- 6
0- 7
0- 9
0-11
1- 1
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-11
3- 2
3- 7

0- 6
0- 8
0- 9
1- 0
1- 2
1- 4
1- 7
1-10
2- 1
2- 5
2- 9
3- 0
3- 5
3- 9

0- 6
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
1-11
2- 3
2- 6
2-10
3- 2
3- 7
3-11

40
50
60
Sag in Feet and Inches
0- 7
0- 7
0- 7
0- 8
0- 9
0- 9
0-10
0-11
1- 0
1- 1
1- 1
1- 2
1- 3
1- 4
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
2- 0
2- 1
2- 2
2- 3
2- 4
2- 6
2- 7
2- 8
2-10
2-11
3- 0
3- 2
3- 4
3- 4
3- 7
3- 9
3- 9
3-11
4- 2
4- 2
4- 4
4- 7

0- 7
0-10
1- 0
1- 3
1- 6
1- 9
2- 1
2- 4
2- 9
3- 1
3- 6
3-11
4- 4
4-10

0- 8
0-10
1- 1
1- 3
1- 7
1-10
2- 2
2- 6
2-10
3- 3
3- 8
4- 1
4- 6
5- 0

0- 8
0-10
1- 1
1- 4
1- 7
1-11
2- 3
2- 7
2-11
3- 4
3- 9
4- 3
4- 9
5- 3

0- 8
0-11
1- 2
1- 5
1- 8
2- 0
2- 4
2- 8
3- 1
3- 6
3-11
4- 5
4-11
5- 5

E.C.S.
INFORMATION SECTION

Section WSC05
Page 2 of 5

Issued 11-01-14

SECONDARY CHARTS INITIAL SAG

SAG AND TENSION

1/0 with #2 ACSR Neutral


Janthina, Triplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

748

709

671

635

600

567

536

507

480

456

433

10

20

30

70

80

90

100

0- 4
0- 5
0- 7
0- 8
0-10
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 4
2- 7

0- 4
0- 6
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 8

0- 5
0- 6
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-10

0- 5
0- 6
0- 8
0- 9
0-11
1- 1
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 9
3- 0

40
50
60
Sag in Feet and Inches
0- 5
0- 5
0- 6
0- 7
0- 7
0- 7
0- 8
0- 9
0- 9
0-10
0-10
0-11
1- 0
1- 1
1- 1
1- 2
1- 3
1- 4
1- 4
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
1-11
2- 0
2- 1
2- 2
2- 3
2- 4
2- 5
2- 7
2- 7
2- 9
2-11
2-10
3- 0
3- 3
3- 2
3- 4
3- 7

0- 6
0- 8
0-10
1- 0
1- 2
1- 5
1- 7
1-10
2- 2
2- 5
2- 9
3- 1
3- 5
3- 9

0- 6
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
2- 0
2- 3
2- 7
2-10
3- 3
3- 7
3-11

0- 7
0- 8
0-11
1- 1
1- 3
1- 6
1- 9
2- 1
2- 4
2- 8
3- 0
3- 5
3- 9
4- 2

0- 7
0- 9
0-11
1- 2
1- 4
1- 7
1-10
2- 2
2- 6
2-10
3- 2
3- 7
4- 0
4- 5

1/0 with 1/0 ACSR Neutral


Neritina, Triplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

1099

1035

973

912

853

798

746

697

653

612

576

10

20

30

70

80

90

100

0- 3
0- 4
0- 5
0- 6
0- 8
0- 9
0-10
1- 0
1- 2
1- 4
1- 5
1- 8
1-10
2- 0

0- 4
0- 4
0- 6
0- 7
0- 8
0- 9
0-11
1- 1
1- 3
1- 4
1- 7
1- 9
1-11
2- 1

0- 4
0- 5
0- 6
0- 7
0- 9
0-10
1- 0
1- 1
1- 3
1- 5
1- 8
1-10
2- 0
2- 3

0- 4
0- 5
0- 6
0- 8
0- 9
0-11
1- 0
1- 2
1- 4
1- 7
1- 9
1-11
2- 2
2- 5

40
50
60
Sag in Feet and Inches
0- 4
0- 4
0- 5
0- 5
0- 6
0- 6
0- 7
0- 7
0- 8
0- 8
0- 9
0- 9
0-10
0-10
0-11
0-11
1- 0
1- 1
1- 1
1- 2
1- 3
1- 3
1- 4
1- 5
1- 6
1- 7
1- 8
1- 8
1- 9
1-11
1-10
2- 0
2- 2
2- 1
2- 3
2- 5
2- 4
2- 6
2- 8
2- 7
2- 9
2-11

0- 5
0- 6
0- 8
0-10
1- 0
1- 2
1- 4
1- 7
1- 9
2- 0
2- 3
2- 6
2-10
3- 2

0- 5
0- 7
0- 9
0-10
1- 0
1- 3
1- 5
1- 8
1-11
2- 2
2- 5
2- 9
3- 0
3- 4

0- 6
0- 7
0- 9
0-11
1- 1
1- 4
1- 6
1- 9
2- 0
2- 3
2- 7
2-11
3- 3
3- 7

0- 6
0- 8
0-10
1- 0
1- 2
1- 5
1- 7
1-10
2- 2
2- 5
2- 9
3- 1
3- 5
3- 9

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC05
Page 3 of 5

SECONDARY CHARTS - INITIAL SAG

4/0 with 2/0 ACSR Neutral


Cerapus, Triplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

1260

1193

1129

1069

10

20

30

0- 5
0- 6
0- 7
0- 9
0-11
1- 0
1- 3
1- 5
1- 7
1-10
2- 1
2- 3
2- 7
2-10

0- 5
0- 6
0- 8
0- 9
0-11
1- 1
1- 3
1- 6
1- 8
1-11
2- 2
2- 5
2- 8
3- 0

0- 5
0- 6
0- 8
0-10
1- 0
1- 2
1- 4
1- 7
1- 9
2- 0
2- 3
2- 7
2-10
3- 2

0- 5
0- 7
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
1-11
2- 2
2- 5
2- 8
3- 0
3- 4

1012

959

910

865

823

785

750

40
50
60
Sag in Feet and Inches
0- 6
0- 6
0- 6
0- 7
0- 7
0- 8
0- 9
0- 9
0-10
0-11
0-11
1- 0
1- 1
1- 2
1- 2
1- 3
1- 4
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
1-11
2- 0
2- 1
2- 2
2- 3
2- 4
2- 6
2- 6
2- 8
2-10
2-10
3- 0
3- 2
3- 2
3- 4
3- 6
3- 6
3- 8
3-11

70

80

90

100

0- 6
0- 8
0-10
1- 1
1- 3
1- 6
1- 9
2- 0
2- 4
2- 8
3- 0
3- 4
3- 8
4- 1

0- 7
0- 9
0-11
1- 1
1- 4
1- 7
1-10
2- 1
2- 5
2- 9
3- 1
3- 6
3-11
4- 3

0- 7
0- 9
0-11
1- 2
1- 5
1- 8
1-11
2- 3
2- 7
2-11
3- 3
3- 8
4- 1
4- 6

0- 7
0- 9
1- 0
1- 2
1- 5
1- 9
2- 0
2- 4
2- 8
3- 0
3- 5
3-10
4- 3
4- 8

1175

1102

1036

978

70

80

90

100

0- 6
0- 7
0- 9
0-11
1- 1
1- 3
1- 6
1- 9
2- 0
2- 3
2- 6
2-10
3- 2
3- 6

0- 6
0- 8
0- 9
0-11
1- 2
1- 4
1- 7
1-10
2- 1
2- 5
2- 8
3- 0
3- 4
3- 8

0- 6
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
1-11
2- 3
2- 6
2-10
3- 2
3- 7
3-11

0- 7
0- 8
0-11
1- 1
1- 3
1- 6
1- 9
2- 1
2- 4
2- 8
3- 0
3- 5
3- 9
4- 2

4/0 with 4/0 ACSR Neutral


Zuzara, Triplex
Ruling Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

1904

1781

1662

1550

10

20

30

0- 4
0- 5
0- 6
0- 7
0- 8
0-10
0-11
1- 1
1- 3
1- 5
1- 7
1- 9
1-11
2- 2

0- 4
0- 5
0- 6
0- 7
0- 9
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-10
2- 1
2- 4

0- 4
0- 5
0- 6
0- 8
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1-10
2- 0
2- 3
2- 6

0- 4
0- 5
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 8

1444

1346

1257

40
50
60
Sag in Feet and Inches
0- 5
0- 5
0- 5
0- 6
0- 6
0- 7
0- 7
0- 8
0- 8
0- 9
0- 9
0-10
0-11
0-11
1- 0
1- 1
1- 1
1- 2
1- 3
1- 4
1- 5
1- 5
1- 6
1- 7
1- 7
1- 9
1-10
1-10
1-11
2- 1
2- 1
2- 2
2- 4
2- 4
2- 6
2- 8
2- 7
2- 9
2-11
2-10
3- 0
3- 3

E.C.S.
INFORMATION SECTION

Section WSC05
Page 4 of 5

Issued 11-01-14

SECONDARY CHARTS INITIAL SAG

SAG AND TENSION

1/0 with 1/0 ACSR


Neutral
Standardbred
Quadruplex Ruling
Span - 150 Feet
Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

1074

1019

966

916

867

822

780

740

704

671

640

10

20

30

70

80

90

100

0- 4
0- 6
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 6
1- 9
2- 0
2- 2
2- 5
2- 8

0- 5
0- 6
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 7
1-10
2- 1
2- 4
2- 7
2-10

0- 5
0- 6
0- 8
0- 9
0-11
1- 1
1- 4
1- 6
1- 8
1-11
2- 2
2- 5
2- 9
3- 0

0- 5
0- 6
0- 8
0-10
1- 0
1- 2
1- 4
1- 7
1-10
2- 0
2- 4
2- 7
2-10
3- 2

40
50
60
Sag in Feet and Inches
0- 5
0- 6
0- 6
0- 7
0- 7
0- 8
0- 9
0- 9
0- 9
0-10
0-11
1- 0
1- 0
1- 1
1- 2
1- 3
1- 4
1- 4
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
1-11
2- 0
2- 1
2- 2
2- 3
2- 5
2- 5
2- 7
2- 8
2- 9
2-10
3- 0
3- 0
3- 2
3- 4
3- 4
3- 6
3- 9

0- 6
0- 8
0-10
1- 0
1- 3
1- 5
1- 8
1-11
2- 3
2- 6
2-10
3- 2
3- 6
3-11

0- 6
0- 8
0-10
1- 1
1- 3
1- 6
1- 9
2- 0
2- 4
2- 8
3- 0
3- 4
3- 9
4- 1

0- 7
0- 9
0-11
1- 1
1- 4
1- 7
1-10
2- 2
2- 5
2- 9
3- 1
3- 6
3-11
4- 4

0- 7
0- 9
0-11
1- 2
1- 5
1- 8
1-11
2- 3
2- 7
2-11
3- 3
3- 8
4- 1
4- 6

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC05
Page 5 of 5

SECONDARY CHARTS - INITIAL SAG


4/0 with 4/0 ACSR
Neutral Appaloosa
Quadruplex Ruling
Span - 150 Feet

Hz. Tens.
(LBS)
Temp F>
Span
70
80
90
100
110
120
130
140
150
160
170
180
190
200

1887

1783

1685

1592

10

20

30

0- 5
0- 6
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 8
1-10
2- 1
2- 4
2- 7
2-10

0- 5
0- 6
0- 8
0- 9
0-11
1- 1
1- 4
1- 6
1- 9
1-11
2- 2
2- 5
2- 9
3- 0

0- 5
0- 7
0- 8
0-10
1- 0
1- 2
1- 4
1- 7
1-10
2- 1
2- 4
2- 7
2-11
3- 2

0- 5
0- 7
0- 9
0-11
1- 1
1- 3
1- 5
1- 8
1-11
2- 2
2- 5
2- 9
3- 1
3- 5

1506

1426

1352

40
50
60
Sag in Feet and Inches
0- 6
0- 6
0- 6
0- 7
0- 8
0- 8
0- 9
0-10
0-10
0-11
1- 0
1- 0
1- 1
1- 2
1- 3
1- 4
1- 5
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
2- 0
2- 0
2- 2
2- 3
2- 4
2- 5
2- 7
2- 7
2- 9
2-11
2-11
3- 1
3- 3
3- 3
3- 5
3- 7
3- 7
3- 9
4- 0

1285

1223

1167

1115

70

80

90

100

0- 7
0- 8
0-11
1- 1
1- 4
1- 6
1- 9
2- 1
2- 4
2- 8
3- 0
3- 5
3- 9
4- 2

0- 7
0- 9
0-11
1- 2
1- 4
1- 7
1-11
2- 2
2- 6
2-10
3- 2
3- 7
4- 0
4- 5

0- 7
0- 9
1- 0
1- 2
1- 5
1- 8
2- 0
2- 3
2- 7
3- 0
3- 4
3- 9
4- 2
4- 7

0- 8
0-10
1- 0
1- 3
1- 6
1- 9
2- 1
2- 5
2- 9
3- 1
3- 6
3-11
4- 4
4-10

477MCM with 477MCM ACSR Neutral


Quadruplex
Ruling Span - 150 Feet
Refer to WSC06 Page 9 for Initial, Design and Final Sag Charts

(END)

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC06
Page 1 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG


Sag and Tension Design Conditions
Creep is NOT a factor
* limiting condition @ 0 deg F, 1/2" ice, 4lb wind

Conductor

Blowout
Angle 6 lb.
wind

Ruling
Span

degrees
477 QUAD

27.3

Maximum Design Tension @ 0 deg F,


1/2" ice, 4 lb. wind
% of Ultimate Strength

150

35.2%

Pounds
4155

Limiting Condition @ 0 deg F


No Ice, No Wind, Final
% of Ultimate Strength
20%

Pounds
2360

E.C.S.
INFORMATION SECTION

Section WSC06
Page 2 of 10

Issued 11-01-14

SECONDARY CHARTS DESIGN AND FINAL SAG

SAG AND TENSION

#4 Duplex Secondary
Terrier
Conductor: #4
Neutral #4 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 50% of Ultimate - 930 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F with 1/2" ice & 4 # wind - 930 # - Limiting Condition
Area = .0382 Sq. In.
Dia = .565
In Wt. = .117
Lb./F
RTS = 1860 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 67.5
Data from Chart No. 1-1023
Creep is NOT a Factor
Design Sag Chart
Temp
F
0
32
60
120
212

Ice
In.
0.5
0.5
0
0
0

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
930
647
312
131
105

100

110

120

1-09
1-07
1-03
1-02
1-05

2-01
1-10
1-06
1-05
1-09

2-05
2-03
1-10
1-08
2-01

130
140
150
Sag in Feet and Inches
2-10
3-04
3-10
2-07
3-00
3-05
2-01
2-05
2-10
1-11
2-03
2-07
2-05
2-09
3-02

160

170

180

190 200

4-04
3-11
3-02
2-11
3-07

4-10
4-05
3-07
3-03
4-01

5-05
4-11
4-00
3-08
4-07

6-01
5-06
4-06
4-01
5-01

140
150
160
Sag in Feet and Inches
1-01
1-03
1-05
1-03
1-05
1-07
1-04
1-07
1-09
1-06
1-09
1-11
1-08
1-10
2-01
1-09
2-00
2-04
1-11
2-02
2-05
1-11
2-03
2-06
2-00
2-03
2-07
2-01
2-04
2-08
2-01
2-05
2-09

170

180

190 200

1-07
1-09
2-00
2-02
2-05
2-07
2-09
2-10
2-11
3-00
3-01

1-10
2-00
2-03
2-05
2-08
2-11
3-01
3-02
3-03
3-05
3-06

2-00
2-03
2-06
2-09
3-00
3-03
3-05
3-06
3-08
3-09
3-10

6-09
6-01
4-11
4-06
5-08

"

Note: indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Ice
In.
0
0
0
0
0
0
0
0
0
0
0

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
269
242
218
197
180
166
156
151
147
142
138

100

110

120

130

0-07
0-08
0-09
0-09
0-10
0-11
1-00
1-00
1-00
1-01
1-01

0-08
0-09
0-10
0-11
1-00
1-01
1-02
1-03
1-03
1-03
1-04

0-10
0-11
1-00
1-01
1-03
1-04
1-05
1-05
1-06
1-06
1-07

1-00
1-01
1-02
1-03
1-05
1-06
1-07
1-08
1-09
1-09
1-10

2-03
2-06
2-09
3-00
3-03
3-07
3-09
3-11
4-00
4-02
4-03

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC06
Page 3 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG


#2 Triplex Secondary Cockle
Conductor: #2
Neutral: #4 ACSR
Ruling Span = 150.0 Feet

Maximum Design Tension 50% of Ultimate - 930 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F with 1/2" ice & 4 # wind - 930 # - Limiting Condition
Area = .0382 Sq. In
Dia = .750 In
Wt. = .233 Lb./F
RTS = 1860 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 58.1
Data from Chart No. 1-1023
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
930
676
335
173
154

100

110

120

130

2-00
1-11
1-08
1-09
1-11

2-05
2-04
2-00
2-01
2-04

2-11
2-09
2-05
2-06
2-09

3-05
3-03
2-10
2-11
3-03

140
150
160
Sag in Feet and Inches
3-11
4-06
5-01
3-09
4-03
4-10
3-03
3-09
4-03
3-04
3-10
4-04
3-09
4-04
4-11

170

180

190

200

5-09
5-06
4-10
4-11
5-06

6-06
6-01
5-05
5-06
6-02

7-02
6-10
6-00
6-02
6-11

8-00
7-06
6-08
6-10
7-08

170

180

190

200

3-05
3-07
3-09
3-11
4-00
4-02
4-04
4-06
4-08
4-08
4-09

3-10
4-00
4-02
4-04
4-06
4-08
4-10
5-00
5-02
5-03
5-04

4-03
4-05
4-08
4-10
5-00
5-03
5-05
5-07
5-09
5-10
6-00

4-08
4-11
5-02
5-04
5-07
5-09
6-00
6-02
6-05
6-06
6-07

"

Note: indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
00

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
250
239
229
220
211
203
196
190
184
181
178

100

110

120

130

1-02
1-03
1-04
1-04
1-05
1-06
1-06
1-07
1-08
1-08
1-08

1-05
1-06
1-07
1-08
1-09
1-09
1-10
1-11
2-00
2-00
2-00

1-09
1-10
1-11
1-11
2-00
2-01
2-02
2-03
2-04
2-04
2-05

2-00
2-01
2-02
2-03
2-05
2-06
2-07
2-08
2-09
2-09
2-10

140
150
160
Sag in Feet and Inches
2-04
2-08
3-00
2-05
2-09
3-02
2-06
2-11
3-04
2-08
3-00
3-05
2-09
3-02
3-07
2-10
3-03
3-09
2-11
3-05
3-10
3-01
3-06
4-00
3-02
3-07
4-01
3-02
3-08
4-02
3-03
3-09
4-03

E.C.S.
INFORMATION SECTION

Section WSC06
Page 4 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

Issued 11-01-14

SAG AND TENSION

1/0 Triplex Secondary


Janthina
Conductor: 1/0
Neutral: # 2 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 47.7% of Ultimate - 1360 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F = 20% of Ultimate - 570 # - Limiting Condition
Area = .0608 Sq. In
Dia = .950 In
Wt. = .376 Lb./F
RTS = 2850 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 51.6
Data from Chart No. 1-1023
Creep is NOT a Factor
Design Sag Chart
Temp
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1360
1042
574
318
275

100

110

120

130

1-08
1-07
1-04
1-06
1-09

2-00
1-11
1-08
1-10
2-01

2-04
2-03
1-11
2-02
2-06

2-09
2-08
2-03
2-06
2-11

140
150
160
Sag in Feet and Inches
3-02
3-08
4-02
3-01
3-06
4-00
2-08
3-00
3-05
2-11
3-04
3-10
3-05
3-11
4-05

170

180

190

200

4-08
4-06
3-10
4-04
5-00

5-03
5-00
4-04
4-10
5-07

5-10
5-07
4-10
5-05
6-03

6-05
6-02
5-04
6-00
6-11

170

180

190

200

2-05
2-07
2-09
2-11
3-01
3-03
3-05
3-07
3-09
3-10
4-00

2-09
2-11
3-01
3-03
3-05
3-07
3-10
4-00
4-02
4-04
4-06

3-00
3-03
3-05
3-07
3-10
4-00
4-03
4-05
4-08
4-10
5-00

3-04
3-07
3-09
4-00
4-03
4-05
4-08
4-11
5-01
5-04
5-07

"

Note: * indicates 1/2 ice load

Final Sag Chart


Temp
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
570
535
503
475
449
426
406
387
371
356
342

100

110

120

130

0-10
0-11
1-00
1-00
1-01
1-02
1-02
1-03
1-04
1-04
1-05

1-00
1-01
1-02
1-03
1-04
1-04
1-05
1-06
1-07
1-08
1-09

1-03
1-04
1-05
1-06
1-07
1-08
1-09
1-09
1-10
1-11
2-00

1-05
1-06
1-07
1-09
1-10
1-11
2-00
2-01
2-02
2-03
2-04

140
150
160
Sag in Feet and Inches
1-08
1-11
2-02
1-09
2-00
2-03
1-10
2-02
2-05
2-00
2-03
2-07
2-01
2-05
2-09
2-02
2-06
2-10
2-04
2-08
3-00
2-05
2-09
3-02
2-06
2-11
3-03
2-08
3-00
3-05
2-09
3-02
3-07

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC06
Page 5 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

1/0 Triplex Secondary


Neritina
Conductor: 1/0
Neutral: 1/0 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 39.7% of Ultimate - 1739 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F = 20% of Ultimate - 876 # - Limiting Condition
Area = .0968 Sq. In
Dia = .980 In
Wt. = .430 Lb./F
RTS = 4380 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 48.7
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
1739
1327
738
410
346

100

110

120

130

1-04
1-04
1-02
1-04
1-07

1-07
1-07
1-05
1-08
1-11

1-11
1-11
1-08
1-11
2-03

2-03
2-02
1-11
2-03
2-08

140
150
160
Sag in Feet and Inches
2-07
3-00
3-04
2-06
2-11
3-04
2-03
2-06
2-10
2-07
3-00
3-05
3-01
3-07
4-00

170

180

190

200

3-09
3-09
3-03
3-10
4-07

4-03
4-02
3-08
4-03
5-01

4-09
4-08
4-00
4-09
5-08

5-03
5-02
4-06
5-03
6-03

170

180

190

200

1-10
2-00
2-02
2-04
2-06
2-08
2-10
3-00
3-02
3-05
3-07

2-00
2-02
2-05
2-07
2-09
3-00
3-02
3-05
3-07
3-09
4-00

2-03
2-05
2-08
2-10
3-01
3-04
3-06
3-09
4-00
4-03
4-05

2-06
2-09
2-11
3-02
3-05
3-08
3-11
4-02
4-05
4-08
4-11

"

Note: indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
876
806
742
686
636
593
554
521
492
466
443

100

110

120

130

0-08
0-09
0-09
0-10
0-11
0-11
1-00
1-01
1-02
1-02
1-03

0-09
0-10
0-11
1-00
1-01
1-02
1-03
1-03
1-04
1-05
1-06

0-11
1-00
1-01
1-02
1-03
1-04
1-05
1-06
1-07
1-08
1-09

1-01
1-02
1-03
1-04
1-06
1-07
1-08
1-09
1-11
2-00
2-01

140
150
160
Sag in Feet and Inches
1-03
1-05
1-07
1-04
1-06
1-09
1-06
1-08
1-11
1-07
1-10
2-00
1-08
1-11
2-02
1-10
2-01
2-04
1-11
2-03
2-06
2-01
2-04
2-08
2-02
2-06
2-10
2-04
2-08
3-00
2-05
2-09
3-02

E.C.S.
INFORMATION SECTION

Section WSC06
Page 6 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

Issued 11-01-14

SAG AND TENSION

4/0 Triplex Secondary


Zuzara
Conductor: 4/0
Neutral: 4/0 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 32.9% of Ultimate - 2748 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F = 20% of Ultimate - 1670 # - Limiting Condition
Area = .1939 Sq. In
Dia = 1.320 In
Wt. = .806 Lb./F
RTS = 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 39.3
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
Wind
Ten.
100
F
Lbs..
Lbs.
0*
4
2748
1-02
32*
0
2142
1-02
60
6
1245
1-01
120
0
757
1-04
212
0
629
1-08
Note: * indicates 1/2" ice load

110

120

130

1-04
1-05
1-04
1-08
2-00

1-07
1-08
1-07
2-00
2-04

1-11
2-00
1-10
2-03
2-09

140
150
160
Sag in Feet and Inches
2-02
2-06
2-10
2-03
2-07
2-11
2-01
2-05
2-09
2-08
3-00
3-05
3-02
3-08
4-02

170

180

190

200

3-02
3-04
3-01
3-11
4-08

3-07
3-09
3-05
4-04
5-03

4-00
4-02
3-10
4-10
5-10

4-05
4-07
4-03
5-04
6-06

170

180

190

200

1-09
1-11
2-01
2-03
2-06
2-08
2-10
3-00
3-03
3-05
3-07

2-00
2-02
2-04
2-07
2-09
3-00
3-02
3-05
3-07
3-09
4-00

2-03
2-05
2-07
2-10
3-01
3-04
3-06
3-09
4-00
4-03
4-05

2-06
2-08
2-11
3-02
3-05
3-08
3-11
4-02
4-05
4-08
4-11

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1670
1530
1405
1295
1198
1113
1040
976
921
872
829

100

110

120

130

0-08
0-08
0-09
0-10
0-11
0-11
1-00
1-01
1-02
1-02
1-03

0-09
0-10
0-11
1-00
1-01
1-02
1-03
1-03
1-04
1-05
1-06

0-11
1-00
1-01
1-02
1-03
1-04
1-05
1-06
1-07
1-08
1-09

1-01
1-02
1-03
1-04
1-06
1-07
1-08
1-09
1-11
2-00
2-01

140
150
160
Sag in Feet and Inches
1-03
1-05
1-07
1-04
1-06
1-09
1-05
1-08
1-10
1-07
1-09
2-00
1-08
1-11
2-02
1-10
2-01
2-04
1-11
2-03
2-06
2-01
2-04
2-08
2-02
2-06
2-10
2-04
2-08
3-00
2-05
2-09
3-02

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC06
Page 7 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

4/0 Triplex Secondary


Cerapus
Conductor: 4/0
Neutral: 2/0 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 32.9% of Ultimate - 2054 # at 0F with 1/2" ice 4 # wind
Final Tension at 0F = 20% of Ultimate - 1062 # - Limiting Condition
Area = 0.1221 Sq. In.
Dia = 1.260 In.
Wt. = 0.699 lbs/FT
RTS = 5310
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 41.3
Data from Chart No. 1-939
Creep is NOT a Factor

Design Sag Chart

Temp

Wind

Tens

100

110

120

130

140

Lbs.

Lbs.

0*

2052

1- 5

1- 8

2- 0

2- 4

2- 9

32*

1621

1- 5

1- 9

2- 0

2- 5

60

936

1- 4

1- 7

1-10

120

587

1- 6

1-10

212
0
499
1-10
Note: * indicates 1/2" ice load

2- 2

150

160

170

180

190

200

3- 1

3- 7

4- 0

4- 6

5- 0

5- 6

2- 9

3- 2

3- 7

4- 0

4- 6

5- 0

5- 7

2- 2

2- 6

2-10

3- 3

3- 8

4- 1

4- 7

5- 1

2- 2

2- 7

3- 0

3- 5

3-10

4- 4

4-10

5- 5

6- 0

2- 7

3- 0

3- 6

4- 0

4- 6

5- 1

5- 9

6- 5

7- 1

Sag in Feet and Inches

Final Sag Chart


Temp.

Wind

Tens.

100

110

120

130

Lbs.

Lbs.

1062

0-10

1- 0

1- 3

1- 5

10

994

0-11

1- 1

1- 4

20

934

1- 0

1- 2

30

880

1- 0

40

832

50

60

140

150

160

170

180

190

200

1- 8

1-11

2- 2

2- 5

2- 9

3- 0

3- 4

1- 6

1- 9

2- 0

2- 4

2- 7

2-11

3- 3

3- 7

1- 5

1- 7

1-11

2- 2

2- 5

2- 9

3- 1

3- 5

3- 9

1- 3

1- 6

1- 9

2- 0

2- 3

2- 7

2-11

3- 3

3- 8

4- 0

1- 1

1- 4

1- 7

1-10

2- 1

2- 5

2- 9

3- 1

3- 5

3-10

4- 3

789

1- 2

1- 5

1- 8

1-11

2- 3

2- 6

2-11

3- 3

3- 8

4- 1

4- 6

750

1- 2

1- 5

1- 9

2- 0

2- 4

2- 8

3- 0

3- 5

3-10

4- 3

4- 8

70

716

1- 3

1- 6

1-10

2- 1

2- 5

2- 9

3- 2

3- 7

4- 0

4- 5

4-11

80

685

1- 4

1- 7

1-11

2- 2

2- 7

2-11

3- 4

3- 9

4- 2

4- 8

5- 2

90

657

1- 4

1- 8

1-11

2- 3

2- 8

3- 0

3- 5

3-11

4- 4

4-10

5- 4

100

631

1- 5

1- 9

2- 0

2- 5

2- 9

3- 2

3- 7

4- 1

4- 6

5- 0

5- 7

Sag in Feet and Inches

E.C.S.
INFORMATION SECTION

Section WSC06
Page 8 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

Issued 11-01-14

SAG AND TENSION

1/0 Quadruplex Secondary


Standardbred
Conductor: 1/0
Neutral: 1/0 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 40.6% of Ultimate - 1777 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F = 20% of Ultimate - 876 # - Limiting Condition
Area = .0968 Sq. In
Dia = 1.110 In
Wt. = .572 Lb./F
RTS = 4380 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 44.1
Data from Chart No. 1-938
Creep is NOT a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs..
4
0
6
0
0

Ten.
Lbs.
1777
1390
791
485
415

100

110

120

130

1-06
1-06
1-04
1-06
1-09

1-09
1-09
1-07
1-10
2-02

2-01
2-01
1-10
2-02
2-06

2-05
2-05
2-02
2-06
3-00

140
150
160
Sag in Feet and Inches
2-10
3-03
3-08
2-10
3-03
3-08
2-06
2-11
3-03
2-11
3-04
3-10
3-05
3-11
4-06

170

180

190

200

4-02
4-02
3-08
4-04
5-00

4-08
4-08
4-02
4-10
5-08

5-02
5-02
4-07
5-04
6-03

5-09
5-09
5-01
5-11
7-00

170

180

190

200

2-05
2-07
2-09
2-11
3-01
3-03
3-05
3-06
3-08
3-10
4-00

2-08
2-10
3-01
3-03
3-05
3-07
3-09
4-00
4-02
4-04
4-06

3-00
3-02
3-05
3-07
3-09
4-00
4-03
4-05
4-07
4-10
5-00

3-04
3-06
3-09
4-00
4-02
4-05
4-08
4-11
5-01
5-04
5-06

"

Note: *indicates 1/2 ice load

Final Sag Chart


Temp.
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs..
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
876
821
772
727
688
652
620
592
566
543
522

100

110

120

130

0-10
0-11
1-00
1-00
1-01
1-02
1-02
1-03
1-04
1-04
1-05

1-00
1-01
1-02
1-03
1-04
1-04
1-05
1-06
1-07
1-08
1-08

1-03
1-03
1-05
1-05
1-06
1-07
1-08
1-09
1-10
1-11
2-00

1-05
1-06
1-07
1-08
1-10
1-11
2-00
2-01
2-02
2-03
2-04

140
150
160
Sag in Feet and Inches
1-08
1-11
2-02
1-09
2-00
2-03
1-10
2-02
2-05
2-00
2-03
2-07
2-01
2-05
2-08
2-02
2-06
2-10
2-04
2-08
3-00
2-05
2-09
3-02
2-06
2-11
3-03
2-08
3-00
3-05
2-09
3-02
3-07

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC06
Page 9 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

4/0 Quadruplex Secondary


Appaloosa
Conductor: 4/0
Neutral 4/0 ACSR
Ruling Span = 150.0 Feet
Maximum Design Tension 33.7% of Ultimate - 2817 # at 0F with 1/2" ice & 4 # wind
Final Tension at 0F = 20% of Ultimate - 1670 # - Limiting Condition
Area = .1939 Sq. In
Dia = 1.490 In
Wt. = 1.063 Lb./F
RTS = 8350 Lb.
NESC Heavy Load Zone
Blowout Angle for 6# Wind is 35.0
Data from Chart No. 1-938
Creep IS a Factor
Design Sag Chart
Temp.
F
0*
32*
60
120
212

Wind
Lbs.
4
0
6
0
0

Ten.
Lbs.
2810
2252
1352
906
754

100

110

120

130

1-03
1-04
1-03
1-06
1-10

1-06
1-07
1-06
1-10
2-02

1-10
1-11
1-09
2-02
2-07

2-01
2-02
2-01
2-06
3-00

140
150
160
Sag in Feet and Inches
2-05
2-09
3-02
2-07
2-11
3-04
2-05
2-09
3-01
2-11
3-04
3-10
3-06
4-00
4-07

170

180

190

200

3-07
3-09
3-06
4-03
5-02

4-00
4-02
3-11
4-10
5-09

4-05
4-08
4-05
5-04
6-05

4-11
5-02
4-10
5-11
7-01

170

180

190

200

2-04
2-06
2-08
2-10
3-00
3-02
3-04
3-06
3-08
3-10
4-00

2-07
2-10
3-00
3-02
3-04
3-07
3-09
3-11
4-01
4-03
4-06

2-11
3-01
3-04
3-06
3-09
3-11
4-02
4-04
4-07
4-09
5-00

3-03
3-05
3-08
3-11
4-02
4-05
4-07
4-10
5-01
5-03
5-06

Note: *indicates 1/2" ice load

Final Sag Chart


Temp
F
0
10
20
30
40
50
60
70
80
90
100

Wind
Lbs.
0
0
0
0
0
0
0
0
0
0
0

Ten.
Lbs.
1670
1560
1462
1374
1296
1227
1165
1110
1060
1016
975

100

110

120

130

0-10
0-11
0-11
1-00
1-01
1-01
1-02
1-03
1-04
1-04
1-05

1-00
1-01
1-02
1-03
1-03
1-04
1-05
1-06
1-07
1-08
1-08

1-02
1-03
1-04
1-05
1-06
1-07
1-08
1-09
1-10
1-11
2-00

1-05
1-06
1-07
1-08
1-09
1-10
2-00
2-01
2-02
2-03
2-04

140
150
160
Sag in Feet and Inches
1-07
1-10
2-01
1-09
2-00
2-03
1-10
2-01
2-04
1-11
2-03
2-06
2-01
2-04
2-08
2-02
2-06
2-10
2-03
2-07
3-00
2-05
2-09
3-01
2-06
2-10
3-03
2-07
3-00
3-05
2-09
3-01
3-06

E.C.S.
INFORMATION SECTION

Section WSC06
Page 10 of 10

SECONDARY CHARTS DESIGN AND FINAL SAG

H Tens
2815. 2660.
(LBS)
----- ----Temp >
0.
10.
Sag
Ft-In Ft-In
Span
----- ----100.0
1- 0
1- 1
110.0
1- 3
1- 3
120.0
1- 5
1- 6
130.0
1- 8
1- 9
140.0
1-11
2- 1
150.0
2- 3
2- 4
160.0
2- 6
2- 8
170.0
2-10
3- 0
180.0
3- 2
3- 4
190.0
3- 6
3- 9
200.0
3-11
4- 2

Issued 11-01-14

SAG AND TENSION

477 Quadruplex with 477 Neutral


RULING SPAN 150 FT
INITIAL STRINGING CHART DATA:
2519. 2390. 2273. 2168. 2072. 1986. 1907. 1835.
----- ----- ----- ----- ----- ----- ----- ----20.
30.
40.
50.
60.
70.
80.
90.
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
----- ----- ----- ----- ----- ----- ----- ----1- 1
1- 2
1- 3
1- 4
1- 4
1- 5
1- 6
1- 6
1- 4
1- 5
1- 6
1- 7
1- 8
1- 8
1- 9
1-10
1- 7
1- 8
1- 9
1-10
1-11
2- 0
2- 1
2- 2
1-10
2- 0
2- 1
2- 2
2- 3
2- 4
2- 5
2- 7
2- 2
2- 3
2- 5
2- 6
2- 7
2- 9
2-10
2-11
2- 6
2- 7
2- 9
2-10
3- 0
3- 2
3- 3
3- 5
2-10
2-11
3- 1
3- 3
3- 5
3- 7
3- 8
3-10
3- 2
3- 4
3- 6
3- 8
3-10
4- 0
4- 2
4- 4
3- 7
3- 9
3-11
4- 1
4- 4
4- 6
4- 8
4-10
3-11
4- 2
4- 4
4- 7
4- 9
5- 0
5- 2
5- 5
4- 4
4- 7
4-10
5- 1
5- 4
5- 6
5- 9
6- 0

DESIGN CHART DATA:


H Tens
2645. 3860. 3191. 1993.
(LBS)
----- ----- ----- ----Temp >
-20.
0.
32.
60.
Wind lbs
0
4
0
6
Wt. lb./f> 2.176 4.334 3.886 2.450
Sag
Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----100.0
1- 1
1- 5
1- 7
1- 7
110.0
1- 3
1- 9
1-11
1-11
120.0
1- 6
2- 1
2- 3
2- 3
130.0
1- 9
2- 5
2- 7
2- 8
140.0
2- 1
2-10
3- 0
3- 1
150.0
2- 4
3- 2
3- 6
3- 6
160.0
2- 8
3- 8
3-11
4- 0
170.0
3- 0
4- 1
4- 5
4- 6
180.0
3- 5
4- 7
5- 0
5- 0
190.0
3- 9
5- 1
5- 7
5- 7
200.0
4- 2
5- 8
6- 2
6- 2

1491.
----120.
0
2.176
Ft-In
----1-10
2- 3
2- 8
3- 2
3- 7
4- 2
4- 9
5- 4
6- 0
6- 8
7- 4

1770.
----100.
Ft-In
----1- 7
1-11
2- 3
2- 8
3- 1
3- 6
4- 0
4- 6
5- 0
5- 7
6- 2

1213.
----212.
0
2.176
Ft-In
----2- 3
2- 9
3- 3
3-10
4- 5
5- 1
5- 9
6- 6
7- 4
8- 2
9- 0

FINAL STRINGING CHART:


H Tens
2358. 2238. 2131. 2036. 1950. 1872. 1802. 1738. 1680. 1627.
(LBS)
----- ----- ----- ----- ----- ----- ----- ----- ----- ----Temp >
0.
10.
20.
30.
40.
50.
60.
70.
80.
90.
Sag
Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In Ft-In
Span
----- ----- ----- ----- ----- ----- ----- ----- ----- ----100.0
1- 2
1- 3
1- 4
1- 5
1- 5
1- 6
1- 7
1- 7
1- 8
1- 9
110.0
1- 5
1- 6
1- 7
1- 8
1- 9
1-10
1-10
1-11
2- 0
2- 1
120.0
1- 8
1-10
1-11
2- 0
2- 1
2- 2
2- 3
2- 4
2- 4
2- 5
130.0
2- 0
2- 1
2- 2
2- 4
2- 5
2- 6
2- 7
2- 8
2- 9
2-10
140.0
2- 4
2- 5
2- 7
2- 8
2- 9
2-11
3- 0
3- 1
3- 3
3- 4
150.0
2- 8
2- 9
2-11
3- 1
3- 2
3- 4
3- 5
3- 7
3- 8
3-10
160.0
3- 0
3- 2
3- 4
3- 6
3- 7
3- 9
3-11
4- 1
4- 2
4- 4
170.0
3- 5
3- 7
3- 9
3-11
4- 1
4- 3
4- 5
4- 7
4- 9
4-11
180.0
3- 9
4- 0
4- 2
4- 4
4- 7
4- 9
4-11
5- 1
5- 4
5- 6
190.0
4- 2
4- 5
4- 8
4-10
5- 1
5- 3
5- 6
5- 8
5-11
6- 1
200.0
4- 8
4-11
5- 2
5- 5
5- 8
5-10
6- 1
6- 4
6- 6
6- 9

1578.
----100.
Ft-In
----1- 9
2- 2
2- 6
2-11
3- 5
3-11
4- 6
5- 0
5- 8
6- 3
6-11

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC07
Page 1 of 8

SERVICE CHARTS - STANDARD CONDUCTOR


Service Drop Sag Calculations

Figure 07-1 can be used to determine the location of maximum sag (D) and the minimum
ground clearance (attachment height minus Sb).
Refer to the service charts on the following pages to obtain the final sag(s).

Figure 07-1
Application where "h" is less than 4X sag.
Sb = S(1-h/4S) 2
D = L/2(1-h/4S)
Sb = Sag below lower Support
S = Final Sag
h = The difference in attachment heights in ft. (Pole & Building)
D = The distance from the lower support point to the point of maximum sag below the
lower support in ft. L = The span length in ft.

Section WSC07
Page 2 of 8

E.C.S.
INFORMATION SECTION

SERVICE CHARTS - STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

#2 TRIPLEX - COCKLE
INITIAL SAG

Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
125.0
125.0
125.0

T e m p F
Sag
Tension
500
279
140
739
500
279
750
500
900
750
500

0.
Ft-In
----0- 4
1- 6
3- 4
0- 5
1- 5
3- 7
1- 0
3- 1
1- 1
2- 3
5- 3

30.
Ft-In
----0- 6
1- 7
3- 5
0- 6
1- 8
3- 8
1- 3
3- 3
1- 3
2- 7
5- 5

60.
Ft-In
----0- 8
1- 8
3- 5
0- 7
1-10
3- 9
1- 6
3- 5
1- 7
2-10
5- 7

90.
Ft-In
----0-10
1- 9
3- 6
0- 9
2- 0
3-10
1- 9
3- 8
1- 10
3- 2
5- 9

32.
4
0.5
Ft-In
----0-11
1- 9
3- 5
1- 4
2- 1
3-10
2- 5
5- 8
3- 0
5-10
5- 9

60.
194.
6
0
0
0
Ft-In Ft-In
----- ----0-11
1- 3
1- 9
2- 0
3- 5
3- 7
1- 1
1- 6
2- 0
2- 5
3-10
4- 1
2- 1
2- 7
5- 7
6- 1
2- 7
3- 0
5- 9
6- 4
5- 9
6- 2

30.
Ft-In
----0- 7
1- 7
3- 4
0- 8
1- 9
3- 8
1- 7
5- 3
1-10
3- 0
5- 6

60.
90.
F t - I n Ft-In
----- ----0-10
0-11
1- 9
1-10
3- 5
3- 5
0-10
1- 1
1-11
2- 1
3- 9
3-10
1-10
2- 1
5- 7
5-10
2- 2
2- 6
3- 3
3- 6
5- 8
5-10

DESIGN SAG
Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
125.0
125.0
125.0

Temp F
Wind lbs.
Ice in.
Sag
Tension
500*
279
140
740
500*
279
750
500*
900
750
500*

0.
4
0.5
Ft-In
----1-0
1-8
3-5
1-5
2-1
3-9
2-6
5-7
3-3
5-10
5-10

FINAL SAG

Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
125.0
125.0
125.0

T e m p F
Sag
Tension
500
279
140
739
500
279
750
500
900
750
500

0.
Ft-In
----0-5
1-6
3-4
0-6
1-7
3-7
1-3
5-0
1-6
2-8
5-4

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC07
Page 3 of 8

SERVICE CHARTS - STANDARD CONDUCTOR


1/0 TRIPLEX - JANTHINA
INITIAL SAG

Span

50.0
50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
125.0
125.0
125.0
125.0

30.
Temp F
0.
Sag
Ft-In Ft-In
Tension ----------- ----846
0- 3 0- 3
500
0-10 1- 0
285
1-10 1-11
142
3-11 3-11
855
0- 8 0-10
500
2- 2 2- 4
285
4- 3 4- 4
500
4- 2 4- 3
428
4-11 5- 1
997
2- 1 2- 5
855
3- 1 3- 4
712
4- 2 4- 5
500
6- 7 6- 9

60.
Ft-In
----0- 5
1- 2
2- 0
4- 0
1- 1
2- 6
4- 5
4- 5
5- 2
2- 9
3- 7
4- 7
6- 11

90.
Ft-In
----0- 7
1- 3
2- 1
4- 0
1- 4
2- 8
4- 6
4- 7
5- 3
3- 0
3-10
4-10
7- 1

60.
6
0
Ft-In
----0- 7
1- 2
2- 0
4- 0
1- 4
2- 7
4- 5
2- 6
4- 6
5- 3
3- 3
3-11
7- 0

194.
0
0
Ft-In
----1- 0
1- 6
2- 3
4- 1
1-11
2-11
4- 8
3- 0
4-10
5- 7
3-11
4- 6
7- 5

DESIGN SAG

Span

50.0
50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0
125.0
125.0
125.0

32.
Temp F
0.
Wind lbs.
4
4
Ice in.
0.5
0.5
Sag
Ft-In Ft-In
Tension -------------846
0- 8
0- 8
500*
1- 2
1- 2
285
1-11
2- 0
142
3-11
3-11
855
1- 6
1- 6
500*
2- 6
2- 7
285
4- 4
4- 5
855
2- 7
2- 7
500*
4- 5
4- 6
428
5- 2
5- 2
997
3- 5
3- 5
855
4- 0
4- 0
500*
6-11
7- 0
FINAL SAG

Span
50.0
50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0
125.0
125.0
125.0

Temp F
Sag
Tension
846
500
285
142
855
500
285
855
500
428
997
855
500

0.
Ft-In
----0- 3
0-11
1-10
3-11
0- 9
2- 3
4- 3
1-10
4- 2
4-11
2- 5
3- 3
6- 8

30.
Ft-In
----0- 4
1- 0
1-11
3-11
1- 0
2- 5
4- 4
2- 1
4- 4
5- 1
2- 9
3- 7
6-10

60.
90.
Ft-In Ft-In
----- ----0- 6
0- 8
1- 2
1- 3
2- 0
2- 1
4- 0
4- 0
1- 3
1- 5
2- 6
2- 8
4- 5
4- 8
2- 4
2- 7
4- 5
4- 7
5- 2
5- 4
3- 1
3- 4
4- 0 --6-11
7- 1

*Note: The permitted load on a 2-inch mast with a 2 ft. high service attachment is 500 lbs.

Section WSC07
Page 4 of 8

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SERVICE CHARTS - STANDARD CONDUCTOR

SAG AND TENSION

4/0 TRIPLEX ZUZURA


INITIAL SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

30.
Temp F
0.
Ft-In
Sag
Ft-In
----T e n s i o n ---------500
1- 5
1-7
251
3- 0
3-1
1002
1- 6
1-8
500
3- 4
3-5
1503
1- 6
1-9
1002
2- 9
3-0
751
3-10
4-0
500
6- 0
6-1

60.
90.
Ft-In Ft-In
----- ----1- 8
3- 2
1-10
3- 6
2- 1
3- 2
4- 2
6- 2

13232346-

9
2
0
8
4
4
4
3

DESIGN SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

T e m p F
0.
32.
Wind lbs. 4
4
Ice in.
0.5
0.5
Sag
Ft-In
Ft-In
T e n s i o n ---------- - - - - 500*
1-7
1- 8
251
3-1
3- 1
1002
1-9
1-10
500*
3-5
3- 6
1503
2-0
2- 2
1002
3-1
3- 2
752
4-1
4- 2
500*
6-1
6- 2

60.
194.
6
0
0
0
Ft-In Ft-In
----- ----1- 8
1-11
3- 2
3- 3
1-11
2- 5
3- 7
3-10
2- 3
2-11
3- 3
3- 9
4- 3
4- 8
6- 3
6- 6

FINAL SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

T e m p F
Sag
Tension
500
251
1002
500
1503
1002
752
500

0.
Ft-In
----1- 6
3- 1
1- 7
3- 4
1- 8
2-10
3-11
6- 0

30.
Ft-In
----1- 7
3- 1
1- 9
3- 6
1-11
3- 1
4- 1
6- 2

60.
90.
F t - I n Ft-In
----- ----1- 8
3- 2
1-11
3- 7
2- 2
3- 3
4- 3
6- 3

13232346-

9
2
1
8
5
5
4
4

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC07
Page 5 of 8

SERVICE CHARTS - STANDARD CONDUCTOR


4/0 TRIPLEX CERAPUS
INITIAL SAG

Span

50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0
100.0

Span

50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0
100.0

T e m p F
Sag
Tension
500
159
956
637
500
956
796
637
500

90
0
30
60
Ft-In Ft-In Ft-In Ft-In
------ ------ ------ -----1-8
1-4
1-5
1-7
4-8
4-7
4-7
4-8
1-11
1-4
1-6
1-9
2-9
2-4
2-6
2-7
3-5
3-1
3-3
3-4
3-2
2-7
2-10
3-0
3
-10
3-4
3-6
3-8
4
-8
4-4
4-5
4-7
5
11
5-7
5-9
5-10

DESIGN SAG
194
T e m p F
0
32
60
0
Wind lbs.
4
4
6
0
Ice in.
0.5
0.5
0
Sag
Ft-In
Ft-In Ft-In Ft-In
Tension
------- ------ ------ -----1-10
500
1-6
1-7
1-7
4-9
159
4-7
4-8
4-8
2-4
956
1-8
1-10
1-10
3-0
637
2-7
2-8
2-8
3-8
500
3-3
3-4
3-4
3-8
956
3-0
3-1
3-2
4-2
796
3-7
3-8
3-9
5-0
637
4-6
4-7
4-8
6-2
500
5-9
5-10
5-11

Note:
The design temperature of 194 deg. F. is 90 deg. C. which is the
temperature limit for XLPE insulation

Span

50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0
100.0

FINAL SAG
90
T e m p F
0
30
60
Sag
Ft-In Ft-In Ft-In Ft-In
Tension
------ ------ ------ -----1-8
500
1-4
1-6
1-7
4-8
159
4-7
4-8
4-8
2-0
956
1-5
1-7
1-10
2-10
637
2-5
2-7
2-8
3-5
500
3-2
3-3
3-4
3-3
956
2-8
2-11
3-1
3
-10
796
3-5
3-7
3-9
4
-9
637
4-4
4-6
4-8
6
-0
500
5-8
5-9
5-10

Section WSC07
Page 6 of 8

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SERVICE CHARTS - STANDARD CONDUCTOR

SAG AND TENSION

1/0 QUADRUPLEX-COSTENA
INITIAL SAG

Span
50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

Temp F
Sag
Tension
500
250
1000
500
1498
1000
750
500

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

0.
Ft-In
----1- 2
2- 7
0-11
2- 9
0- 9
1-11
3- 1
5- 0

DESIGN SAG

30.
Ft-In
----1- 3
2- 7
1- 1
2-10
0-11
2- 2
3- 3
5- 1

32.
4
0.5
Ft-In
-----

Temp F
0.
Wind lbs.
4
Ice in.
0.5
Sag
Ft-In
Tension ---------500
1- 4
1250
2- 7
21000
1- 5
1500
2-11
31498
1- 9
11000
2- 7
2750
3- 5
3500
5- 2
5-

5
8
6
0
9
8
6
3

60.
Ft-In
----1- 5
2- 8
1- 4
3- 0
1- 1
2- 5
3- 5
5- 3

90.
Ft-In
----1- 6
2- 9
1- 6
3- 1
1- 4
2- 8
3- 7
5- 4

60.
194.
6
0
0
0
Ft-In Ft-In
----- -----

12131235-

5
8
6
0
7
7
6
3

1- 8
2-10
2- 0
3- 4
2- 3
3- 2
4- 0
5- 7

FINAL SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0
100.0

Temp F
Sag
Tension
500
250
1000
500
1498
1000
750
500

0.
30.
Ft-In
Ft-In
--------------1- 2
1- 4
2- 7
2- 7
1- 0
1- 3
2- 9
2-11
0-10
1- 1
2- 1
2- 4
3- 2
3- 4
5- 0
5- 2

60.
90.
Ft-In Ft-In
----- ----1- 5
1- 6
2- 8
2- 9
1- 5
1- 8
3- 0
3- 1
1- 5
1- 8
2- 6
2- 9
3- 6
3- 8
5- 3
5- 4

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC07
Page 7 of 8

SERVICE CHARTS - STANDARD CONDUCTOR


4/ 0 QU AD R U P L E X AP P AL OO S A
INITIAL SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0

30.
Temp F
0.
Sag
Ft-In Ft-In
Tension ---------- ----501
1- 8 1-10
250
3- 6 3- 7
1002
1- 9 1-11
501
3-10 4- 0
1503
1-11 2- 2
1002
3- 4 3- 6
752
4- 6 4- 8

60.
Ft-In
----1-11
3- 7
2- 1
4- 1
2- 5
3- 8
4-10

90.
Ft-In
----1-11
3- 8
2- 3
4- 2
2- 7
3- 9
4-11

60.
6
0
Ft-In
----1-11
3- 8
2- 2
4- 1
2- 7
3- 9
4-10

194.
0
0
Ft-In
----2- 1
3- 9
2- 7
4- 4
3- 2
4- 2
5- 2

60.
Ft-In
----1-11
3- 8
2- 2
4- 1
2- 6
3- 8
4-10

90.
Ft-In
----2- 0
3- 8
2- 4
4- 2
2- 9
3-10
5- 0

DESIGN SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0

32.
Temp F
0.
Wind lbs.
4
4
Ice in.
0.5
0.5
Sag
Ft-In
Ft-In
Tension --------- ----501
1- 9
1-10
250
3- 7
3- 7
1002
2- 0
2- 2
501
3-11
4- 0
1503
2- 4
2- 6
1002
3- 6
3- 8
752
4- 8
4- 9
FINAL SAG

Span

50.0
50.0
75.0
75.0
100.0
100.0
100.0

Temp F
Sag
Tension
501
250
1002
501
1503
1002
752

0.
Ft-In
----1- 9
3- 6
1-10
3-11
2- 0
3- 4
4- 7

30.
Ft-In
----1-10
3- 7
2- 0
4- 0
2- 3
3- 6
4- 9

Section WSC07
Page 8 of 8

E.C.S.
INFORMATION SECTION

SERVICE CHARTS - STANDARD CONDUCTOR

Issued 11-01-14

SAG AND TENSION

477 Q U A D R U P L E X NO TRADE NAME


INITIAL SAG

Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0

30.
Temp F
0.
Sag
Ft-In Ft-In
Tension --------- ----750
1-10 1-11
500
2- 9 2-10
250
5- 9 5- 9
1501
2- 0 2- 2
1001
3- 1 3- 2
750
4- 1 4- 3
3002
1- 4 1- 7
2001
2- 7 2-10
1501
3- 2 3- 5

60.
Ft-In
----2- 0
2-11
5-10
2- 4
3- 4
4- 4
1-11
3- 0
3- 7

90.
Ft-In
----2- 1
2-11
5-10
2- 6
3- 5
4- 5
2- 2
3- 3
3- 9

DESIGN SAG

Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0

32.
Temp F
0.
Wind lbs.
4
4
Ice in.
0.5
0.5
Sag
Ft-In
Ft-In
Tension --------- ----750
2- 0
1-10
500
2-10
2- 9
250
5- 9
5- 9
1500
2- 3
2- 2
1001
33
3- 2
750
43
4- 2
3002
2- 1
1-10
2001
2-10
2- 7
1501
3- 7
3- 4

60.
194.
6
0
0
0
Ft-In Ft-In
----- ----2- 0 2- 3
2-11 3- 1
5-10 5-11
2- 5 2-11
3- 4 3- 9
4- 4 4- 7
2- 2 3- 2
2-11 3- 9
3- 8 4- 5

FINAL SAG

Span

50.0
50.0
50.0
75.0
75.0
75.0
100.0
100.0
100.0

Temp F
Sag
Tension
750
500
250
1501
1001
750
3000
2000
1500

0.
Ft-In
----1-10
2- 9
5- 9
2- 1
3- 1
4- 2
1- 8
2- 8
3- 8

(END)

30.
Ft-In
----1-11
2-10
5- 9
2- 3
3- 3
4- 3
2- 0
2-11
3-10

60.
Ft-In
----2- 0
2-11
5-10
2- 5
3- 4
4- 4
2- 3
3- 2
4- 0

90.
Ft-In
----2- 1
2-11
5-10
2- 6
3- 5
4- 5
2- 6
3- 4
4- 2

Issued 11-01-14

E.C.S.
INFORMATION SECTION

SAG AND TENSION

Section WSC08
Page 1 of 1
SAG TEMPLATES

1. SAG CRITERIA
Sag Templates have been developed to evaluate the following conditions:
a. Uplift
b. Maximum Sag for Neutral Clearance to ground.
c. Maximum Sag for Phase Clearance to ground.
Uplift will be determined using -20 F Final Sag.
Neutral and Phase Ground Clearance Requirements outlined in NESC 232 A. are the greater of:
1) 120 F no wind displacement or
2) Maximum conductor temperature the line is designed to operate at (if > 120 F) or
3) 32 F, no wind displacement, radial ice for heavy loading district.
Neutral Sag will be the greater of final sag at 120 F or 32 F, ice, no wind.
Phase Sag will be the greater of final sag at 212 F or 32 F, ice, no wind.
2. RULING SPAN INCREMENTS
a. Urban Ruling Spans at 100, 125, 150 and 175 FT.
b. Rural Ruling Spans are 200, 225, 250, 275, 300, 325 and 350 FT (when provided).
3. SAG TEMPLATE SCALE
The Standards Advisory Team selected the following scale for Alliant Energy templates.
Horizontal: 1 inch = 200 FT.
Vertical: 1 inch = 20 FT.
This scale permits templates to be developed on a standard 8-1/2 x 11 Mylar.
4. CLEARANCE REFERENCE CURVE
Clearance reference marks have been proposed to assist clearance relative to ground. Clearances
vary by State. Hence, several reference points are given.
5. MARGIN OF ERROR FOR DETERMINING CLEARANCE
The Standards Advisory Team selected a 3.0 FT. margin of error to account for variations in terrain,
pole setting depth, framing, etc. This margin of error is incorporated in the Department of
Transportation (DOT) ground clearance reference provided on the charts.
6. AVAILABLE SAG CHARTS
Sag Charts are available for 1/0, 266 18/1, T2-1/0, T2-4/0 and 477 ACSR.

E.C.S.
INFORMATION SECTION

Issued 11-01-14

SAG AND TENSION

Section WSC09
Page 1 of 1
SAGGING REPORT

1. PROJECT SAG DATA RECORDING WORKSHEET

FIELD SAGGING REPORT


WR Number:

Date:

Title:
Conductor size & Type:

Phase:

Neutral:
Phasing: ABC or ______

Line section
Point#
1-30

Point# Length
5

Field Engineer / Company

800

Ruling
Temp
span
802

50

Date
28-Feb

Time or Tension (circle one)


CA - South &
BNorth
NWest
Middle
&
Neutral
East
3.2
3.2
3.2
3.2

Line Foreman / Company

ALWAYS USE 3RD WAVE


SAG TO BE CHECKED IN TWO LOCATIONS AND IN A LEVEL SPAN WHOSE LENGTH IS