DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION

ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FD-FA
1. Colocar dimensiones de la viga continua
30.0 cm
3 3/4 ''
80.0 cm

As Positivo
2 1/2"

5.04 cm

Verificar As min y As max

Para evitar el pandeo del estribo


8.40 cm

40.0 cm
As Negativo
9 1/2 ''

11.04 cm

Cumple con As min y As max

190.0 cm
11.04 cm

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO
REFUERZO NEGATIVO
f`c =
210.00
Kg/cm2
f`c =
210.00
fy =
4200.00
Kg/cm2
fy =
4200.00
b=
190.00 cm
b=
30.00 cm
h=
120.00 cm
h=
120.00 cm
barra =
1/2 ''
barra =
1/2 ''
estribo =
3/8 ''
estribo =
3/8 ''
recub. =
recub. =
2.50 cm
7.50 cm
d=
d=
115.91 cm
110.91 cm
M=
22.03 Tn-m
M=
44.48 Tn-m
0.624 cm
8.659 cm
a=
a=
5.04 cm
11.04 cm
As =
As =
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO
As Positivo
8.40 cm
3/4 ''
barra =
2.850 cm
As =
Tomamos
3 3/4 ''

Kg/cm2
Kg/cm2

ACERO NEGATIVO
As Negativo
11.04 cm
1/2 ''
barra =
1.267 cm
As =
Tomamos
9 1/2 ''

ACERO MINIMO:
min =
0.0024
As min = 8.40 cm
3/4 ''
barra =
As = 2.850 cm
Tomamos
3 3/4 ''
ACERO MAXIMO
max =
0.0163
56.57 cm
As max =
3/4 ''
barra =
As = 2.850 cm
Tomamos
20 3/4 ''

0.43

ACERO TRANSVERSAL
adm Suelo =
diseo =
Tomando B =
Mom. Neg =

15.000 Tn/m
22.500 Tn/m
1.00 m
7.20 Tn-m

3/8 ''

@ 0.27

30.0 cm
80.0 cm

1/2 '' @ 0.2


80.0 cm

40.0 cm
190.0 cm

Vu =
Wu =
recub. =
barra =
estribo =
b=
d=

25.000 Tn
1.49 Tn/m
7.50 cm

22.50 Tn/m
VERIFICACION POR CORTANTE
A cara de columna
.Vc =

REFUERZO NEGATIVO
f`c =
210.00
fy =
4200.00
b = 100.00 cm
h=
40.00 cm
barra =
1/2 ''
estribo =
3/8 ''
recub. =
7.50 cm
d=
30.91 cm
M = 7.20 Tn-m
1.486 cm
a=
6.31 cm
As =
1/2 ''
barra =
As = 1.267 cm
@=
20.00

38.344 Tn

>

Vud =
24.541 Tn

Kg/cm2
Kg/cm2

Ok

1/2 ''
3/8 ''
190.00 cm
30.91 cm
DISEO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO


Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d =
2.218 m
estribo =
3/8 ''
La separacion de los estribos debe ser:
S d/4 =
S = 27.00 cm
27.73 cm
S
30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

3/8 ''

@ 0.27

La separacion de los estribos debe ser:


S=

55.00 cm

3/8 ''

@ 0.55

DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION


ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE F10-F6
1. Colocar dimensiones de la viga continua
30.0 cm
4 3/4 ''
80.0 cm

As Positivo
2 1/2"

9.20 cm

Cumple con As min y As max

Para evitar el pandeo del estribo


9.20 cm

40.0 cm
As Negativo
8 5/8 ''

14.93 cm

Cumple con As min y As max

180.0 cm
14.93 cm

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO
REFUERZO NEGATIVO
f`c =
210.00
Kg/cm2
f`c =
210.00
fy =
4200.00
Kg/cm2
fy =
4200.00
b=
180.00 cm
b=
30.00 cm
h=
120.00 cm
h=
120.00 cm
barra =
1/2 ''
barra =
1/2 ''
estribo =
3/8 ''
estribo =
3/8 ''
recub. =
recub. =
2.50 cm
7.50 cm
d=
d=
115.91 cm
110.91 cm
M=
40.08 Tn-m
M=
59.29 Tn-m
1.202 cm
11.710 cm
a=
a=
9.20 cm
14.93 cm
As =
As =
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO
As Positivo
9.20 cm
3/4 ''
barra =
2.850 cm
As =
Tomamos
4 3/4 ''

Kg/cm2
Kg/cm2

ACERO NEGATIVO
As Negativo
14.93 cm
5/8 ''
barra =
1.979 cm
As =
Tomamos
8 5/8 ''

ACERO MINIMO:
min =
0.0024
As min = 8.40 cm
3/4 ''
barra =
As = 2.850 cm
Tomamos
3 3/4 ''
ACERO MAXIMO
max =
0.0163
56.57 cm
As max =
3/4 ''
barra =
As = 2.850 cm
Tomamos
20 3/4 ''

0.43

ACERO TRANSVERSAL
adm Suelo =
diseo =
Tomando B =
Mom. Neg =

15.000 Tn/m
22.500 Tn/m
1.00 m
6.33 Tn-m

3/8 ''

@ 0.27

30.0 cm
80.0 cm

1/2 '' @ 0.225


75.0 cm

40.0 cm
180.0 cm

Vu =
Wu =
recub. =
barra =
estribo =
b=
d=

25.000 Tn
1.49 Tn/m
7.50 cm

22.50 Tn/m
VERIFICACION POR CORTANTE
A cara de columna
.Vc =

REFUERZO NEGATIVO
f`c =
210.00
fy =
4200.00
b = 100.00 cm
h=
40.00 cm
barra =
1/2 ''
estribo =
3/8 ''
recub. =
7.50 cm
d=
30.91 cm
M = 6.33 Tn-m
1.302 cm
a=
5.53 cm
As =
1/2 ''
barra =
As = 1.267 cm
@=
22.50

36.325 Tn

>

Vud =
24.541 Tn

Kg/cm2
Kg/cm2

Ok

1/2 ''
3/8 ''
180.00 cm
30.91 cm
DISEO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO


Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d =
2.218 m
estribo =
3/8 ''
La separacion de los estribos debe ser:
S d/4 =
S = 27.00 cm
27.73 cm
S
30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

3/8 ''

@ 0.27

La separacion de los estribos debe ser:


S=

55.00 cm

3/8 ''

@ 0.55

DISEO DEL REFUERZO PARA VIGAS CONTINUAS DE CIMENTACION - CONECTADAS


ACERO LONGITUDINAL
VIGAS CONTINUAS DE CIMENTACION EJE FB-FC
1. Colocar dimensiones de la viga continua
30.0 cm
3 3/4 ''
80.0 cm

As Positivo
2 1/2"

5.01 cm

Verificar As min y As max

Para evitar el pandeo del estribo


8.40 cm

40.0 cm
As Negativo
10 1/2 ''

11.52 cm

Cumple con As min y As max

180.0 cm
11.52 cm

2. Colocar Diametro de Barra Longitudinal asumida, Estribo y Momento.


REFUERZO POSITIVO
REFUERZO NEGATIVO
f`c =
210.00
Kg/cm2
f`c =
210.00
fy =
4200.00
Kg/cm2
fy =
4200.00
b=
180.00 cm
b=
30.00 cm
h=
120.00 cm
h=
120.00 cm
barra =
1/2 ''
barra =
1/2 ''
estribo =
3/8 ''
estribo =
3/8 ''
recub. =
recub. =
2.50 cm
7.50 cm
d=
d=
115.91 cm
110.91 cm
M=
21.90 Tn-m
M=
46.33 Tn-m
0.655 cm
9.035 cm
a=
a=
5.01 cm
11.52 cm
As =
As =
3. Aceros Negativos y Positivos Finales
ACERO POSITIVO
As Positivo
8.40 cm
3/4 ''
barra =
2.850 cm
As =
Tomamos
3 3/4 ''

Kg/cm2
Kg/cm2

ACERO NEGATIVO
As Negativo
11.52 cm
1/2 ''
barra =
1.267 cm
As =
Tomamos
10 1/2 ''

ACERO MINIMO:
min =
0.0024
As min = 8.40 cm
3/4 ''
barra =
As = 2.850 cm
Tomamos
3 3/4 ''
ACERO MAXIMO
max =
0.0163
56.57 cm
As max =
3/4 ''
barra =
As = 2.850 cm
Tomamos
20 3/4 ''

0.43

ACERO TRANSVERSAL
adm Suelo =
diseo =
Tomando B =
Mom. Neg =

15.000 Tn/m
22.500 Tn/m
1.00 m
6.33 Tn-m

3/8 ''

@ 0.27

30.0 cm
80.0 cm

1/2 '' @ 0.225


75.0 cm

40.0 cm
180.0 cm

Vu =
Wu =
recub. =
barra =
estribo =
b=
d=

25.000 Tn
1.49 Tn/m
7.50 cm

22.50 Tn/m
VERIFICACION POR CORTANTE
A cara de columna
.Vc =

REFUERZO NEGATIVO
f`c =
210.00
fy =
4200.00
b = 100.00 cm
h=
40.00 cm
barra =
1/2 ''
estribo =
3/8 ''
recub. =
7.50 cm
d=
30.91 cm
M = 6.33 Tn-m
1.302 cm
a=
5.53 cm
As =
1/2 ''
barra =
As = 1.267 cm
@=
22.50

36.325 Tn

>

Vud =
24.541 Tn

Kg/cm2
Kg/cm2

Ok

1/2 ''
3/8 ''
180.00 cm
30.91 cm
DISEO DE REFUERZO TRANSVERSAL

REFUERZO DENTRO DE LA ZONA DE CONFINAMIENTO


Se colocar refuerzo Transversal por confinamiento a una distancia "2d" medida desde la cara del apoyo.
2d =
2.218 m
estribo =
3/8 ''
La separacion de los estribos debe ser:
S d/4 =
S = 27.00 cm
27.73 cm
S
30.00 cm
REFUERZO FUERA DE LA ZONA DE CONFINAMIENTO

3/8 ''

@ 0.27

La separacion de los estribos debe ser:


S=

55.00 cm

3/8 ''

@ 0.55