You are on page 1of 54

Technical Specification

Datasheet
SCADAPack Smart RTU
Compact, versatile controller for telemetry and remote SCADA solutions

01

SCADAPack
Smart RTUs that combine the monitoring and
communications capabilities of remote terminal units
(RTU) with the processing and data-logging power of
programmable logic controllers (PLC), providing superior
functionality wherever remote processes require
automatic supervision and autonomous control.
SCADAPack Smart RTUs are the foundation for a range of
solutions offering specific software and configuration
tools to enhance performance in oil and gas and water/
wastewater applications.

02

Selection Guide

SCADAPack 100, 300, 32



Modbus core database, DNP3 level 2 layer, optional DF1 support


Programming and configuration: TelePACE Studio, IEC61131-3, C/C++

314

330

334

350

357

32P

32 P4

32 P4A

32 P4B

100

8: 0-20mA,
4-20mA
0-5V
0-10V

n/a

8: 0-20mA,
4-20mA
0-5V
0-10V

5: 0-10V,
0-20mA
1: 0-32.7VDC

5: 0-10V,
0-20mA
1: 0-32.7VDC
8: 0-20mA,
4-20mA
0-10V
0-5V

n/a

8: 0-20/
4-20mA
or 0-5/1-5V

8: 0-20mA/
0-10V
1: 0-32.768V

8: 0-20/
4-20mA
0-5/0-10V

3: 0-20/
4-20mA
0-5/1-5 VDC
1: 0-32.7
VDC

2 or 4:
0-20mA
4-20mA
Optional

n/a

Analog Inputs
On-board1

Analog Outputs
On-board1

2: 0-20mA
4-20mA
Optional

n/a

2: 0-20mA
4-20mA
Optional

2: 0-20mA
4-20mA
Optional

n/a

16: 12/24V
48V
115/125V
240V

n/a

16: 12/24V
48V
115/125V
240V

8: Dry
contact,
Shared with
output points.

8: Dry
contact,
shared with
output points
32: (12/24V,
48V,
115/125V,
240V)

3: 24VAC/
30VDC,
shared with
Counter
inputs
1: 30V
interrupt

3: 24VAC/
30VDC,
shared with
Counter
inputs
1: 30V
interrupt
16:
12-24/120/
220V-VAC

3: 24VAC/
30VDC,
shared with
Counter
inputs
1: 30V
interrupt
32: dry
contact
Shared with
outputs

3: 24VAC/
30VDC
Shared with
Counter
inputs,
1: 30V
interrupt input
32: 12/24V,
48V,
115/125V,
240V

6: selectable
as input or
output

n/a

10: dry
contact
or solid-state

8: open drain,
Shared with
input points.

8: open drain,
Shared with
input points.
16: dry
contact

1: Controller
Status Output

1: Controller
Status Output
12: Dry
contact

1: Controller
Status Output
32: dry
contact
Shared with
inputs

1: Controller
Status Output
16: Dry
contact

6: selectable
as input or
output

Digital Inputs
On-board1

Digital Outputs
On-board1

10: dry
contact or
10:
solid-state

Frequency Inputs
On-board1

1: 0-10Hz or 0-5kHz (dry contact)

3: 0-5 kHz shared with digital inputs, 1: 0-500Hz, interrupt input

1: 0-6 kHz
turbine
or dry contact

2: 0-10kHz (turbine or dry contact)

n/a

General
Turbine
Inputs
Serial Ports

2: RS232/
RS485

USB Ports

1: Peripheral

1: Host, 1: Peripheral

n/a

1, 10/100BaseT

Ethernet
Ports
EFM Flow
Runs
Programming
Software
Modbus
DNP3

2: RS232/RS485
1: RS232

1: RS485, 1: RS232/RS485,
1: RS232

2: RS232
1: RS232/
RS485

2: RS232
1: RS232/
RS485

1: RS232
1: RS232/
RS485

n/a

1: 10BaseT

n/a

10

TP Studio, IEC61131-3, C++


Master and Slave: Modbus RTU, Modbus ASCII, Modbus/TCP, Modbus UDP
Level 2 Slave

Number of on-board I/O may be further expanded for any SCADAPack using Expansion I/O Modules.
Refer to individual product data sheets for detailed specifications.
1

3: RS232, 1: RS232/RS485

TP Studio,
IEC61131, C

03

Contents

SCADAPack Smart RTU

I/O Expansion Modules*

SCADAPack 314

Analog Input Modules

Specifications .............................................................................................. 4
Model Code ................................................................................................ 5

SCADAPack 330 | 334


Specifications 330 ....................................................................................... 6
Specifications 334 ....................................................................................... 7
Model Code ................................................................................................ 8

5502 - Differential analog input module .....................................................


5504 - Thermocouple input module ..........................................................
5505 - RTD input module ..........................................................................
5506 - Analog input module ......................................................................

Analog Output Modules


5302 - Analog output module .................................................................... 24
5304 - Analog output module .................................................................... 25

SCADAPack 350 | 357

Digital Input Modules

Specifications 350 ..................................................................................... 10


Specifications 357 ..................................................................................... 11
Model Code .............................................................................................. 12

SCADAPack 32



Specifications P4A ....................................................................................


Specifications P4 .......................................................................................
Specifications P4B ....................................................................................
Model Code ..............................................................................................

14
15
16
17

SCADAPack 100
Specifications ............................................................................................ 18
Model Code .............................................................................................. 19

20
21
22
23

5403 - High level digital input module ........................................................


5404 - High level digital input module ........................................................
5405 - Digital input module .......................................................................
5410 - High speed counter/accumulator ...................................................
5414 - Compact digital input module ........................................................

26
27
28
29
30

Digital I/O Modules


5401 - Configurable digital I/O module ...................................................... 31
5402 - Configurable digital input or output module .................................... 32

Digital Output Modules







5406A - Dry contact relay out module ....................................................... 33


5407 - Dry contact relay out module ......................................................... 34
5408 - Triac digital output module .............................................................. 35
5409 - FET digital output module .............................................................. 36
5411 - Digital output module ..................................................................... 37
5415 - Compact relay digital output module .............................................. 38

Combination I/O Modules


5606 - Analog/digital I/O module ............................................................... 39
5607 - Analog/digital I/O module ............................................................... 40

I/O Simulator Modules


5421 - Toggle switch digital input module .................................................. 41
5521 - Potentiometer input module ........................................................... 42

UPS Power Supply


5103 - Uninterruptible Power Supply ......................................................... 43

Non-Programmable Controller Modules


5201 - RS-485 communication controller .................................................. 44
5202 - RS-232 communication controller .................................................. 45

Communication Modules
Modems, Interface Modules & Gateways






5901 - Dial-up modem .............................................................................. 46


5902 - Bell 202 radio or leased line modem .............................................. 47
5904 - HART interface module ................................................................... 48
5908 - Wireless data transceiver ............................................................... 49.
5908-WO2 - Wireless data transceiver ...................................................... 50.
5910 - Ethernet switch .............................................................................. 51
5915 - SDI-12 interface module ................................................................ 52

* IO Expansion Module Compatibility Notes:


The SCADAPack 100 does not support IO Expansion modules.

04

Product Data Sheet SCADAPack 314


Specifications

P314: 5212 controller board and integrated 56O7 I/O board


Controller
Processors

CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer


Microcontroller co-processor, 20 MHz clock

Memory

16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

Non-Volatile RAM

CMOS SRAM with lithium battery retains contents for 2 years with no power

Datalog Capacity

465k words

I/O
Analog Inputs

8 software configurable: 0-20/4-20mA / 0-5/0-10V (15-bit)


3 internal: measure incoming power supply voltage for solar applications, battery voltage, and controller temperature

Analog Outputs

Standard: None
2 with optional 5305 on 5607 I/O board: 0-20/4-20mA (12-bit)

Digital I/O

16 digital inputs: 12/24V, 48V, 115/125V, 240V


10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),
DC solid state rating: 3A, 60 VDC

Counter Inputs

1 dry contact: 0-10Hz or 0-5kHz


2 turbine or dry contact: 0-10kHz

Communications
Serial Ports COM1, COM2

RS-232 port, 8-pin modular RJ45 jack, full or half-duplex, or


RS-485 port, 2-wire, half-duplex

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

USB Peripheral Port

USB 2.0 compliant B-type receptacle

Wireless1

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

5, 6, and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts

Dimensions

5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant, zinc-plated steel with black enamel paint

Environment

5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)

Power
5212 Controller Board

 1 - 30VDC, 30mW at 12V during sleep mode.


1
500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, and USB disabled
300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, USB disabled
Add 190mW when enabling the USB port
Add 30 to 90mW when enabling the LEDs
8.5W at 24V maximum, 5V supply fully-loaded

5607 I/O Module

11 - 30VDC, 10.3mA plus analog outputs


235mA (max.) at 5V required from 5212 controller board

Warranty

3 years on parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the
requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations

Hazardous Locations
Europe

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

Hazardous Locations

IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2). Does not include Wireless versions.

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

05

Product Data Sheet SCADAPack 314


Model Code

TBUP314-1A20-AB00 represents a sample code for a SCADAPack 314, 5607 I/O board and Modbus protocol emulation

Model
TBUP314

Code
1

Code
A

Select: Controller
SCADAPack 314 , 32 Bit controller, 8 Analog Inputs, 16 Digital Inputs, 10 Digital Outputs, 3 Accumulators

Future Option
None

Select: Gas Flow Run-Time Option


None
Flow Computer Runs

2 Run Gas Flow

4 Run Gas Flow

2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

Code
2

Code
0
1

Code
A

Select: Protocol Option


Modbus and DNP 3.0 (Level 2) protocol emulation

Select: Programming Environment


Telepace Ladder Logic and C Language firmware loaded - IEC enabled (programming tools sold separately)
IEC 61131-3 and C Language firmware loaded - Telepace enabled (programming tools sold separately)

Select: Analog Inputs


8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

Code

Select: Digital Inputs/Outputs

16 DI (12/24V) and 10 dry contact relays

16 DI (120V) and 10 dry contact relays

16 DI (12/24V) and 10 DC solid-state relays, ATEX and IECEx certification

Code

16 DI (120V) and 10 solid state relays

Select: Analog Outputs

None

2 channel analog output option, 0 - 20mA

Code
0

Select: Integrated Communication Interfaces


None
FreeWave & MDS Radios (requires one RS232 port)

900Mhz FreeWave Spread Spectrum Radio

900MHz MDS Spread Spectrum Radio


Trio Radios - 900MHz (requires one RS232 port)

900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)


Trio Radios - 2.4GHz (requires one RS232 port)

2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

06

Product Data Sheet SCADAPack 330


Specifications

P330: 5210 controller board only


Controller
Processors

CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer


Microcontroller co-processor, 20 MHz clock

Memory

16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

Non-Volatile RAM

CMOS SRAM with lithium battery retains contents for 2 years with no power

Datalog Capacity

465k words

I/O
Counter Inputs

1, 0-10Hz or 0-5kHz (dry contact)


2, 0-10kHz (turbine or dry contact)

Communications
Serial Ports COM1, COM2

RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or


RS-485 port, 2-wire, half duplex

Serial Port COM3

RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

Ethernet Port

RJ45, 10/100BaseT

Ethernet Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Network Protocols

IP, ARP, TCP, TFTP, UDP and ICMP

USB Host Port

USB 2.0 compliant A-type receptacle, provides up to 100mA at 5V

USB Peripheral Port

USB 2.0 compliant B-type receptacle

Wireless1

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

6-pole removable terminal block, 12 to 22AWG, 15A contacts

Dimensions

5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

Packaging

Corrosion resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)

Power Input

Warranty

3 years on parts and labor

11 - 30VDC, 15mW at 12V during Sleep


500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled
300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled
Add 800mW when enabling LAN
Add 190mW when enabling USB
Add 25 to 100mW when enabling the LEDs
8.5W at 24V maximum, 5V supply fully loaded

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the
requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.
UL Std. No. 1604 - Hazardous (Classified) Locations.

Hazardous Locations - Europe

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

Hazardous Locations

IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

07

Product Data Sheet SCADAPack 334


Specifications

P334: 5210 controller board and integrated 5607 I/O board


Controller
Processors

CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer


Microcontroller co-processor, 20 MHz clock

Memory

16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

Non-Volalite RAM

CMOS SRAM with lithium battery retains contents for 2 years with no power

Datalog Capacity

465k words

I/O
Analog Inputs

8, 0-20/4-20mA / 0-5/0-10V (15-bit) software configurable

Analog Outputs

Standard: None
2, 0-20/4-20mA (12-bit) with optional 5305 on 5607 I/O board

Digital I/O

16, 12/24V, 48V, 115/125V, 240V digital inputs


10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),
DC solid state rating: 3A, 60 VDC

Counter Inputs

1, 0-10Hz or 0-5kHz (dry contact); 2, 0-10kHz (turbine or dry contact)

Communications
Serial Ports COM1, COM2

RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or


RS-485 port, 2-wire, half duplex

Serial Port COM3

RS-232 port, 8-pin modular RJ45 jack, full or half duplex with RTS/CTS control and operator interface power control

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

Ethernet Port

RJ45, 10/100BaseT

Ethernet Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Network Protocols

IP, ARP, TCP, TFTP, UDP and ICMP

USB Host Port

USB 2.0 compliant A-type receptacle, provides up to 100mA at 5V

USB Peripheral Port

USB 2.0 compliant B-type receptacle

Wireless

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts

Dimensions

5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)

Power
5210 Controller Board

11 - 30VDC, 15mW at 12 V during Sleep


500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, LAN and USB disabled
300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, LAN and USB disabled
Add 800mW when enabling LAN
Add 190mW when enabling USB
Add 25 to 100mW when enabling the LEDs
8.5W at 24V maximum, 5V supply fully loaded

5607 I/O Module

11 - 30VDC, 10.3mA plus analog outputs


325mA (max.) at 5V required from 5210 controller board

Warranty

3 years on parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.
UL Std. No. 1604 - Hazardous (Classified) Locations.

Hazardous Locations - Europe

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

Hazardous Locations

IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

08

Product Data Sheet SCADAPack 330 | 334


Model Code

TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation

Model

Select: Controller

TBUP330

SCADAPack 330, 32 Bit controller, 3 Accumulators

TBUP334

SCADAPack 334, with Model 5607 I/O board, comes with above I/O plus 8 Analog I/P, 16 Digital I/P and 10 Digital O/P

Code
1

Code
A

Future Option
None

Select: Gas Flow Run-Time Option


None
Flow Computer Runs

2 Run Gas Flow

4 Run Gas Flow

2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

Code
2

Code

Select: Protocol Option


Modbus and DNP 3.0 (Level 2) protocol emulation

Select: Programming Environment

Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)

IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)

Code
A

Code

Select: Analog Inputs


P330: None P334: 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

Select: Digital Inputs/Outputs

P330 - None

P334 - 16 DI (12/24V) and 10 dry contact relays

P334 - 16 DI (120V) and 10 dry conta ct relays

P334 - 16 DI (12/24V) and 10 DC solid state relays, ATEX and IECEx certification

Code

P334 - 16 DI (120V) and 10 solid state relays

Select: Analog Outputs

None

P334 only - 2 channel analog output option, 0 - 20mA

Model codes continue on next page

09

Product Data Sheet SCADAPack 330 | 334


Model Code

TBUP334-1A20-AB00 represents a sample code for a SCADAPack334, 5607 I/O board and Modbus protocol emulation

Code
0

Select: Integrated Communication Interfaces


None
FreeWave & MDS Radios (requires one RS232 port)

900Mhz FreeWave Spread Spectrum Radio

900MHz MDS Spread Spectrum Radio


Trio Radios - 900MHz (requires one RS232 port)

900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)


Trio Radios - 2.4GHz (requires one RS232 port)

2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

10

Product Data Sheet SCADAPack 350


Specifications

P350: 5209 controller board only


Controller
Processors

CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer


Two Microcontroller co-processors, 20 MHz clock

Memory

16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

Non-Volatile RAM

CMOS SRAM with lithium battery retains contents for 2 years with no power

Datalog Capacity

465k words

I/O
Analog Inputs

5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)


1, 0-32.7VDC (15-bit)

Analog Outputs

Standard: None
2, 0-20/4-20mA (12-bit) with optional 5305

Digital I/O

8, user selectable as dry contact inputs or open drain outputs

Counter Inputs

1, 0-10Hz (dry contact)


2, 0-10kHz (turbine or dry contact)

Communications
Serial Port COM1

RS-485 port, 2-pole removable terminal block, 2-wire, half duplex

Serial Port COM2

RS-232 port, 8-pin modular RJ45 jack, full or half duplex, or


RS-485 port, 2-wire, half duplex

Serial Port COM3

RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

Ethernet Port

RJ45, 10/100BaseT

Ethernet Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Network Protocols

IP, ARP, TCP, TFTP, UDP and ICMP

USB Host Port

USB 2.0 compliant A-type receptacle, provides up to 100mA at 5V

USB Peripheral Port

USB 2.0 compliant B-type receptacle

Wireless

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

6 and 12- pole removable terminal blocks, 12 to 22AWG, 15A contacts

Dimensions

8.40 inch (213mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

Packaging

Corrosion resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)

Power Input

Voltage Converter

12VDC to 24VDC

Warranty

3 years on parts and labor

11 - 30VDC, 12mW at 12V during Sleep


510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled.
320mW at 12V during reduced power mode operation. 12MHz., LEDs off, no expansion, LAN and USB disabled
1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled
Add 25 to 100mW when enabling the LED
12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certified
to the requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.
UL Std. No. 1604 - Hazardous (Classified) Locations.

Hazardous Locations - Europe

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

Hazardous Locations

IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

11

Product Data Sheet SCADAPack 357


Specifications

P357: 52O9 controller board and integrated 56O6 I/O board


Controller
Processors

CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer


Microcontroller co-processor, 20 MHz clock

Memory

16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM

Non-Volatile RAM

CMOS SRAM with lithium battery retains contents for 2 years with no power

Datalog Capacity

465k words

I/O
Analog Inputs

5, user selectable 0-10V (15-bit) or 0-20mA plus overrange (14-bit)


1, 0-32.7VDC (15-bit) ; 8, 0-20/4-20mA / 0-5/0-10V (15-bit) software configurable

Analog Outputs

Standard: None
2, 0-20/4-20mA (12-bit) with optional 5305 on 5209 controller board
2, 0-20/4-20mA (12-bit) with optional 5305 on 5606 I/O board

Digital I/O

8, user selectable as dry contact inputs or open drain outputs


32, 12/24V, 48V, 115/125V, 240V digital inputs; 16, relay outputs - dry contact or DC solid state

Counter Inputs

1, 0-10Hz (dry contact); 2, 0-10kHz (turbine or dry contact)

Communications
Serial Port COM1

RS-485 port, 2-pole removable terminal block, 2-wire, half duplex

Serial Port COM2

RS-232 port, 8-pin modular RJ45 jack, full or half duplex RS-232, or
RS-485 port, 2-wire, half duplex

Serial Port COM3

RS-232 port, 8-pin modular RJ45 jack, half duplex with RTS/CTS control and operator interface power control

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

Ethernet Port

RJ45, 10/100BaseT

Ethernet Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Network Protocols

IP, ARP, TCP, TFTP, UDP and ICMP

USB Host Port

USB 2.0 compliant A-type receptacle, provides up to 100mA at 5V

USB Peripheral Port

USB 2.0 compliant B-type receptacle

Wireless1

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

5, 6, 9, 10 and 12-pole removable terminal blocks, 12 to 22AWG, 15A contacts

Dimensions

8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant zinc-plated steel with black enamel paint

Environment
Power

5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)

5209 Controller Board

5606 I/O Module

600mA (max.) at 5V required from 5209 controller board


11 - 30VDC, 12mA plus analog outputs

Voltage Converter

12VDC to 24VDC

Warranty

3 years on parts and labor

11 - 30VDC, 12mW at 12V during Sleep


510mW at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN and USB disabled
320mW at 12V during normal operation. 12MHz., LEDs off, no expansion, LAN and USB disabled
1.2W at 12V during normal operation. 32MHz., LEDs off, no expansion, LAN enabled and USB disabled
Add 25 to 100mW when enabling the LEDs
12W at 24V maximum. 5V supply fully loaded and Vloop on and boosted, fully loaded

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4, UL listed and CSA certified
to the requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.
UL Std. No. 1604 - Hazardous (Classified) Locations.

Hazardous Locations - Europe

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.

Hazardous Locations

IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless version

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

12

Product Data Sheet SCADAPack 350 | 357


Model Code

TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation

Model

Select: Controller

TBUP350

SCADAPack 350 , 32 Bit controller, 5 Analog Inputs, 8 configurable Digital I/O, 3 Accumulators

TBUP357

SCADAPack 357, with Model 5606 I/O board, comes with above I/O plus 8 Analog I/P, 32 Digital I/P and 16 Digital O/P

Code
1

Code
A

Future Option
None

Select: Gas Flow Run-Time Option


None
Flow Computer Runs

2 Run Gas Flow

4 Run Gas Flow

2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)

Code
2

Code

Select: Protocol Option


Modbus and DNP 3.0 (Level 2) protocol emulation

Select: Programming Environment

Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)

IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)

Code
A

Code

Select: Analog Inputs


P350: 5 selectable as 0-10V or 0-20mA inputs. P357: adds another 8 selectable as 0-20, 4-20mA, 0-5V or 0-10V

Select: Digital Inputs/Outputs

P350 - 8 configurable Digital I/O, individually selectable as DI (Dry Contact) or DO (Open Drain)

P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Dry Contact Relay Outputs on 5606 I/O board

P357 - Includes P350 I/O plus 32 DI (120V) and 16 Dry Contact Relay Outputs on 5606 I/O board

P357 - Includes P350 I/O plus 32 DI (12/24V) and 16 Solid State Relay Outputs on 5606 I/O board, ATEX and IECEx certification

P357 - Includes P350 I/O plus 32 DI (120V) and 16 Solid State Relay Outputs on 5606 I/O board

Code

Select: Analog Outputs

None

P350 or P357 - 2 channel analog output option, 0 - 20mA (P357 - 2 channel A/O option on the 5606)

P357 only - 4 channel analog output option, 0 - 20mA (consists of the 2 channel A/O option board on both modules)

Model codes continue on next page

13

Product Data Sheet SCADAPack 350 | 357


Model Code

TBUP357-1A20-AB00 represents a sample code for a SCADAPack 357, 5606 I/O board and Modbus protocol emulation

Code
0

Select: Integrated Communication Interfaces


None
FreeWave & MDS Radios (requires one RS232 port)

900Mhz FreeWave Spread Spectrum Radio

900MHz MDS Spread Spectrum Radio


Trio Radios - 900MHz (requires one RS232 port)

900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)

900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)

900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)


Trio Radios - 2.4GHz (requires one RS232 port)

2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

14

Product Data Sheet SCADAPack 32


Specifications

P4A, integrated 56O4 I/O board


Controller
Processor

Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

Memory

8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

Non Volatile RAM

CMOS RAM with lithium battery retains contents for 2 years with no power

I/O
Analog Inputs

8, user selectable 0 - 10V (15 bit) or 0 - 20mA (14 bit)


1, 0 - 32.678V (10 bit)

Analog Outputs

2 with optional 5305 analog output module, output range 0-20mA

Digital Inputs

4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation

Digital Outputs

1, 30V / 60mA (used as status output)

Digital I/O (5604 I/O board)

32 configurable as input or output (1 Amp DC max output / dry contact input)

Communications
Serial Port COM1

Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

Serial Ports COM2, COM4

RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control
Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

Serial Port COM3

Located on 5604 I/O module. Same specifications as COM2 and COM4

Baud Rates
COM1, COM2, COM4

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

Baud Rate COM3

1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

Ethernet Port

RJ45, 10BaseT

Network Protocols

IP: ARP, TCP, TFTP, UDP, ICMP

Ethernet Port Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Wireless1

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

Dimensions

8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C (40F) to 70C (158F)

Power Input

11 - 30 VDC, 4.3W typical (10.8W full I/O capacity in use )

Warranty

3 years on parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the
requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations

Safety

CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,
Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

15

Product Data Sheet SCADAPack 32


Specifications

P4, integrated 56O1A I/O board


Controller
Processor

Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

Memory

8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

Non Volatile RAM

CMOS RAM with lithium battery retains contents for 2 years with no power

I/O
Analog Inputs

8, user selectable 0 - 5V (15 bit) or 0 - 20mA (14 bit)

Analog Outputs

2 with optional 5303 analog output module, output range 0-20mA

Digital Inputs

4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation


16 on 5601A I/O module - 6.5mA typical at 24V and 3.5mA typical at 115V

Digital Outputs

1 on controller board , 30V, 60mA (used as status output)


12 on 5601A I/O module - Sealed mechanical relay:
0.4A at 125 Vrms, 2A at 30V resistive loads
1.0A at 30V, 0.2A at 125Vrms inductive load with pf=0.4, L/R=7ms
250Vrms, 220V maximum operating voltage

Communications
Serial Port COM1

Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

Serial Ports COM2, COM4

RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control. Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

Serial Port COM3

Located on 5601A I/O module. Same specifications as COM2 and COM4

Baud Rates
COM1, COM2, COM4

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

Baud Rate COM3

1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

Ethernet Port

10BaseT, RJ45

Network Protocols

IP:ARP, TCP, TFTP, UDP, ICMP

Ethernet Port Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Wireless

Spread spectrum radio at 900MHz2 and 2.4 GHz2

General
I/O Terminations

6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

Dimensions

8.40 inch (213mm) wide, 6.13 inch (155mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C (40F) to 70C (158F)

Power Input:

11 - 30 VDC, 3.5W typical all relays off, 6.5W typical all relays on

Warranty

3 years on parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the
requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations

Safety

CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,
Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

16

Product Data Sheet SCADAPack 32


Specifications

P4B, integrated 56O6 I/O board


Controller
Processor

Hitachi SH-3 32-bit CMOS microcontroller, 120MHz clock, integrated watchdog timer

Memory

8 Mb SDRAM, 4 Mb FLASH, 1 Mb CMOS RAM

Non Volatile RAM

CMOS RAM with lithium battery retains contents for 2 years with no power

I/O
Analog Inputs

8, single-ended, software selectable 0-5V / 0-10 V or 0-20mA / 4-20mA (15 bit resolution)

Analog Outputs

2 with optional 5305 analog output module, output range 0-20mA

Digital Inputs

4 on controller board - 3 Digital Input/Counter, 1 Interrupt with optical isolation,


32 on 5606 I/O module:
0.67 mA typical at 24V on the 12/24V range
0.37 mA typical at 48V on the 48V range
0.35 mA typical at 120V on the 115/125V range
0.35 mA typical at 240V on the 240V range

Digital Outputs

1 on controller board, 30V, 60mA (used as status output)


16 relay outputs on 5606 I/O module - dry contact or DC solid state:
Dry contact rating: 3A, 30VDC or 240VAC (Resistive)
DC solid state rating: 3A, 60 VDC

Communications
Serial Port COM1

Configurable RS-232 or RS-485, 2 wire half duplex or 4 wire full/half duplex

Serial Ports COM2, COM4

RS-232, DTE, 8 pin modular jack, full or half duplex with RTS/CTS control
Implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

Baud Rates
COM1, COM2, COM4

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1, PPP

Ethernet Port

RJ45, 10BaseT

Network Protocols

IP: ARP, TCP, TFTP, UDP, ICMP

Ethernet Port Protocols

Modbus TCP, Modbus RTU in UDP, Modbus ASCII in UDP, DNP in TCP, DNP in UDP

Wireless

Spread spectrum radio at 900MHz2 and 2.4 GHz2

General
I/O Terminations

5, 6, 8, 9 and 10 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

Dimensions

8.40 inch (213mm) wide, 6.48 inch (164mm) high, 2.80 inch (72mm) deep

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C (40F) to 70C (158F)

Power Input:

11 - 30 VDC, 4.3W typical (10.8W full I/O capacity in use )

Warranty

3 years on parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4
UL Listed and CSA certified to the following standards:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations

Hazardous Locations
Europe

Model 5606 SSR, 24DI version only ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)
Does not include Wireless versions.

Hazardous Locations

Model 5606 SSR version only IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2) Does not include Wireless versions.

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

17

Product Data Sheet SCADAPack 32


Model Code

TBUP4-102-02-0-0 represents a sample code for a P4 with DNP, 0-5V inputs, 12-24V outputs

Model

Select: Controller

TBUP4

SCADAPack 32, 32 Bit controller with Integrated Ethernet Port

Code

Select: Lower I/O Module


5601A lower I/O module, includes 16 Digital Inputs, 12 Digital Outputs and 8 Analog Inputs (see options below)

5604 lower I/O module, includes 32 configurable Digital I/O and 8 selectable Analog Inputs (0-10v or 0-20mA)

5606 lower I/O module, includes 32 D/I, 16 Dry Contact D/O and 8 software configurable A/I

5606-A lower I/O module, includes 32 D/I, 16 Solid State Relay D/O and 8 software configurable A/I

No lower I/O module (provides controller module only)

Code
1

Select: Communications Serial Ports


TBUP4/P4A/P4N: 3 RS232, 1 RS232/485, 1 Ethernet TBUP4B/P4C: 2 RS232, 1 RS232/485, 1 Ethernet
Integrated FreeWave & MDS Radios (requires one RS232 port)

900Mhz FreeWave Spread Spectrum Radio Consult CMI for availability in your market area

900MHz MDS Spread Spectrum Radio

Consult CMI for availability in your market area

Trio Radios - 900MHz (requires one RS232 port)


B

900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)

900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)

900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)


Trio Radios - 2.4GHz (requires one RS232 port)

2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

Code
0

2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

Select: Gas Flow Run-time Option


None
Flow Computer Runs

2 Run Gas Flow

4 Run Gas Flow

10 Run Gas Flow


Flow Computer Runs - Gas Transmission Version (Requires Realflo 6.72+)

2 Run Gas Flow

4 Run Gas Flow

Code
2
5

Code

Select: Protocol Option/Programming Environment


Modbus and DNP 3.0 (Level 2) protocol with Telepace Ladder Logic and C Language firmware loaded - IEC enabled
Modbus and DNP 3.0 (Level 2) protocol with IEC 61131-3 and C Language firmware loaded - Telepace enabled

Select: Analog Inputs

01

0-20mA, single ended (On TBUP4 & TBUP4A, Default on TBUP4B which is software configurable to 0-5v or 0-10v)

02

0-5 volt, single ended (TBUP4 Only)

03

0-10 volt, single ended (TBUP4A Only)

Code

Select: Digital Inputs/Outputs

24 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: SS Relay D/O TBUP4A: Config I/O TBUP4N: No I/O

120 volt D/I TBUP4 & TBUP4B: Dry Contact D/O TBUP4C: Solid State Relay D/O (Not for TBUP4A or TBUP4N)

Code

Select: Analog Outputs

None (required for TBUP4N)

2 channel Analog Output option, 0-20 mA

18

Product Data Sheet SCADAPack 100


Specifications

SCADAPack 100
Controller
Processors

16-bit CMOS micro-controller, 14.74MHz clock, integrated watchdog timer


micro-controller co-processor: 14.74MHz clock

Memory

256KBytes CMOS RAM (controller ID number A182921 or less)


1024KBytes CMOS RAM (controller ID number A182922 or greater)
512kBytes flash ROM, 1kBytes EEPROM

Non-volatile RAM

CMOS RAM with lithium battery retains contents for 2 years with no power

I/O
Analog Inputs

3 at 5V/20mA: 250W resistance user configurable with jumper link


1 at 32.768V

Resolution

12 bits over the 5V and 32.768V measurement range

Digital I/O

6 points, each point is an input and an output, dry contact input, 1.0A max output rating

Counter Inputs

1, maximum frequency 5kHz, dry contact input, wetting current typically 5mA with 24V input power

Communications
Communication Port COM1

RS-485 serial port, 2 pole removable terminal block, 2 wire half duplex, bias resistors installed

Communication Port COM1

RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex,
implemented Td, Rd, +5V

Communication Port COM2

RS-232 compatible serial port (CMOS), Data Terminal Equipment (DTE), 8 pin modular jack, full or half duplex with RTS/CTS
control, implemented Td, Rd, CTS, RTS, DCD, DTR, +5V

Baud Rates COM1 & COM2

300, 600, 1200, 2400, 4800, 9600, 19200, 38400

Serial Protocols

Modbus RTU, Modbus ASCII, DNP3, DF1

Serial Protocol Modes

Slave, Master, Master/Slave, Store and Forward

Wireless1

Spread spectrum radio at 900MHz2 and 2.4GHz2

General
I/O Terminations

5 and 12 pole, removable terminal blocks. 12 to 22 AWG 15A contacts Screw termination 6 lb.-in. (0.68 Nm) torque

Dimensions

5.65 inch (144mm) wide, 5.00 inch (127mm) high, 1.80 inch (45mm) deep

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C (40F) to 70C (158F)

DC Power Input:

30V maximum, 10.0 to 11.5V turn on, 9.5V typical turn off, UL508 rated 13.75-28Vdc. Class 2, less than 500mW (at 12V) LEDs off,
2.9W maximum

Output Capacity

5V at 0.425A capacity, 5V at 0.060A required by 5208 controller, 5V at 0.365A available on COM1 and COM2

Warranty

3 years parts and labor

Certifications
Hazardous Locations
North America

Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations.


Temperature Code T4 per CSA Std C22.2 No. 213-M1987 / UL1604 UL listed and CSA certified to the following standards:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations

Hazardous Locations

ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) Does not include Wireless versions

Safety

CSA (cCSAus) certified to the requirements of: CSA C22.2 No. 142-M1987 and UL508. (Process Control Equipment,
Industrial Control Equipment) UL (cULus) listed: UL508 (Industrial Control Equipment)

1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

19

Product Data Sheet SCADAPack 100


Model Code

TBUP100-1A20-AA00 represents a sample code for a TBUP100 with DNP, 0-5V inputs

Model

Select: Controller

TBUP100

SCADAPack 100, comes with 3 Analog Inputs, 6 configurable Digital I/O, 1 Accumulator

TBUP110

SCADAPack 100, Gas Flow Controller with 1 Gas Flow Run (I/O as above)

Code
1

Code
A

Code
2

Code

Select: Communication Serial Ports


2 Communication Ports (RJ45 Type) : 1 RS-232 and 1 RS232/485

Select: Memory Configuration


1 MB CMOS RAM (512K OS, 512K APP), 512K FLASH ROM

Select: Protocol Option


Modbus and DNP 3.0 (Level 2) protocol emulation

Select: Programming Environment

Telepace Ladder Logic and C Language firmware loaded - IEC enabled (Programming Tools sold separately)

IEC 61131-3 and C Language firmware loaded - Telepace enabled (Programming Tools sold separately)

Code
A

Code
A

Code
0

Code
0

Select: Analog Inputs


3 Analog Inputs, individually selectable as 0-20mA or 0-5 volts

Select: Digital Inputs/Outputs


6 configurable Digital I/O, individually selectable as Digital Input (Dry Contact) or Digital Output (Open Drain)

Select: Analog Outputs


None

Select: Integrated Communication Interfaces


None
FreeWave & MDS Radios (requires one RS232 port)

900Mhz FreeWave Spread Spectrum Radio consult CMI for availability in your market area

900Mhz MDS Spread Spectrum Radio consult CMI for availability in your market area
Trio Radios - 900MHz (requires one RS232 port)

900MHz SCADAWave Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)

900MHz SCADAWave Spread Spectrum Radio with encryption, 915-928MHz (AUS)

900MHz SCADAWave Spread Spectrum Radio, 915-928MHz (BRAZIL)

900MHz SCADAWave Spread Spectrum Radio, 921-928MHz (NZ)


Trio Radios - 2.4GHz (requires one RS232 port)

2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)

2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)

2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)

20

Product Data Sheet 5502 Differential analog input module


Specifications

5502 Differential analog input module


General
Input Points

8: voltage or current inputs, each input is switch selectable as voltage or current

Ranges

Voltage -10V to +10V, Current -20mA to +20mA

Resolution

Voltage 1.22mV, Current 4.88A

Input Resistance

Voltage > 10M, Current 250

Converter Type

13-bit plus sign successive approximation

Accuracy

+/- 0.1% of full scale at 25C (77F)


+/- 0.2% of full scale over temperature range

Isolation

550VAC from any input to the chassis or the system power supplies.
140VAC/200VDC between inputs

Common Mode Rejection

>96dB at 50/60Hz, >50dB at 10KHz. with 1K imbalance


>50dB at 1KHz. with 10K imbalance

Normal Mode Rejection

>45dB at 50/60Hz

Transient Protection

Transient suppressors and fuses on each input


2.5kV surge withstand capability as per ANSI/IEEE, C37.90.1-1989

Over-Scale Input Capacity

12VDC maximum. Exceeding 12V will cause the fuse to blow.

Input Fuses

1/8 Amp.

Reading Update Time

170ms with 60Hz. rejection selected. 185mS with 50Hz rejection selected.

Power Requirements

5V @ 100mA

Terminations

2: 8 pole, removable terminal blocks, 12 - 22 AWG, 15A contacts

Dimensions

144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

Class 1, Division 2 for use in hazardous locations

Part Number

TBUX297211

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

21

Product Data Sheet 5504 Thermocouple input module


Specifications

5504 Thermocouple input module


General
Input Points

8 thermocouples or millivolt signals

Thermocouple Types
and Ranges

J:
K:
E:
T:
mV

Resolution

0.004mV, approximately 0.10C (0.18F)

Input Resistance

1M

Accuracy Over -40C to 60C


Operating Temperature Range

J:
K:
E:
T:
mV

Cold Junction Compensation

0.5C (0.9F) maximum error from 0C to 60C (32F to 140F)


1C (1.8F) maximum error from -40C to 0C (-40F to 32F)

Converter Type

20000 count, integrating

Common Mode Voltage Range

10V can be applied to the inputs, relative to the -24V power supply input

Isolation

500VAC from the logic power

Transient Protection

MOVs on each input

Response Time

0.5 seconds

Power Requirements

> 5V @40mA
> 20 to 28V @ 45mA

Terminations

10 pole and 8 pole, two fixed terminal blocks, 12 - 22 AWG, 15 amp contacts

Dimensions

144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

Class 1, Division 2 for use in hazardous locations

Part Number

TBUX297166

-200C to 760C (-328F to 1400F)


-270C to 1370C (-454F to 2498F)
-270C to 1000C (-454F to 1832F)
-270C to 400C (-454F to 752F)
80mV

0.20% of full scale


0.20% of full scale
0.15% of full scale
0.50% of full scale
0.15% of full scale

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

22

Product Data Sheet 5505 RTD input module


Specifications

5505 RTD input module


General
Input Points

4, RTD

RTD Type

100-ohm platinum, 3 and 4-wire, auto-detection and compensation

Calibration

0.00385/ /C standard based on ASTM E 1137/E 1137M-04, ITS-90

Ranges

5505: Can be configured to return data in ohms, C, F or K


-200C to 800C (-328F to 1472F)
0 to 500
5503 Emulation: Dipswitch selectable
0C to 200C (32F to 392F)
-100C to 100C (-148F to 212F)
-200C to 0C (-328F to 32F)
0C to 800C (32F to 1472F)
0C to 400C (32F to 752F)
0 to 400

Data Format

5505: 32-bit floating point and 12 status bits


5503 Emulation: 16-bit signed integer

Resolution

5505: > 17-bit effective


5505 Emulation: 15-bit

RTD Status

Accuracy on RTD Ranges

Percent of full scale over operational temperature range including linearization errors: +0.10%/-0.05%

Accuracy on 0 to 500ohms

Percent of full scale over operational temperature range: 0.03%

Excitation Current

4mA, 7.2% duty cycle in 4-wire mode, 14.4% in 3-wire mode, 250ms scan interval

Line Resistance

100 max., in each line

Converter Type

24-bit delta-sigma

Response Time

380ms typical for 10% to 90% signal change at minimum filter setting

Transient Protection

2.5kV surge-withstand capability as per ANSI/IEEE C37.90.1-1989

Isolation

Isolation from logic supply and chassis, voltage 500Vrms

5V Power Requirements

6mA

11 - 30VDC
Power Requirements

12V operation: 4mA


plus 0.6mA per 4-wire RTD
plus 1.2mA per 3-wire RTD
24V operation: 2.2mA
plus 0.3mA per 4-wire RTD
plus 0.6mA per 3-wire RTD

11-30VDC - Connector

Removable. Shared with RTD inputs 0-1

11-30VDC - Isolation

Isolation from logic supply and chassis

Terminations

8 and 10 pole, removable terminal block,12 to 22 AWG, 15A contacts

Dimensions

74mm wide x 124mm high x 45mm deep (2.9in. x 4.9in. x 1.8in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 70C (-40F to 158F) operation, -40C to 85C (-40F to 185F) storage

Safety

Non-Incendive Electrical Equipment for Use in Class I, Division2


Groups A, B C and D Hazardous Locations
ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)

Part Number

TBUX297318

RTD is good (not open)


RTD in range
RTD 3 or 4-wire
RTD status not available in 5503 Emulation

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

23

Product Data Sheet 5506 Analog input module


Specifications

5506 Analog input module


General
Input Points

Ranges

LED Indicators

8 red LEDs, indicating current input, voltage input and under or over-range signal applied

Input Configuration

Individual inputs configurable with 4mA/1V (20%) offset and for voltage/current operation when configured as a 5506. All inputs
dipswitch-selectable with 4mA/1V (20%) offset and for voltage/current operation when configured to emulate a 5501 module.

Input Resistance

250 ohms - Current configuration ; 66k ohms - Voltage configuration

Resolution

15-bits over the 0-5V and 0-20mA measurement range

Type

Single-ended

Accuracy

0.1% of full scale at 25C (77F) ; 0.2% over temperature range

Transient Protection

2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

Normal Mode Rejection


At 60 Hz with 60Hz Scanning

53dB with 3Hz filter


50dB with 6Hz filter
49dB with 11Hz filter
45dB with 30Hz filter

Normal Mode Rejection


At 50 Hz with 50Hz Scanning

73dB with 3Hz filter


56dB with 6Hz filter
52dB with 11Hz filter
49dB with 30Hz filter

Response Time for 10% to


90% Signal Change
(60Hz Scanning)

250ms with 3Hz filter


130ms with 6Hz filter
60ms with 11Hz filter
30ms with 30Hz filter

Response Time for 10% to


90% Signal Change
(50Hz Scanning)

300ms with 3Hz filter


140ms with 6Hz filter
80ms with 11Hz filter
40ms with 30Hz filter

Over-Scale Input Capacity


(without damage)

Continuous: 0.10A/14V on the 20mA inputs ; 0.05A/14V on the 5V inputs

Isolation

500Vac isolation from logic supply and chassis

5V Power Requirements

22mA, LEDs off


45mA, LEDs on

11-30VDC Power Requirements

11mA

11-30VDC - Connector

Removable, 4 positions

11-30VDC - Isolation

Isolation from logic supply and chassis

Terminations

10 pole, removable terminal block,12 to 22 AWG, 15A contacts

Dimensions

2.9 inch (74 mm) wide, 4.9 inch (124 mm) high, 1.8 inch (45 mm) deep

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 70C (-40F to 158F) operation, -40C to 85C (-40F to 185F) storage

Safety

Non-Incendive Electrical Equipment for Use in Class I, Division2


Groups A, B C and D Hazardous Locations
ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2)

Part Number

TBUX297319

0-20mA
4-20mA
0-5V
1-5V

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

24

Product Data Sheet 5302 Analog output module


Specifications

5302 Analog output module


General
Output points

4 ( 2 when used with 5201 and 5201 controllers)

Output signal ranges

0-20mA or 4-20mA, switch configurable

Output Type

Single ended regulation on positive side with common negative return

Maximum Load Resistance

1000W with 24VDC loop power, 400W with 12VDC loop power , 250Wwith 9VDC loop power

Isolation

1500VAC field to logic

D/A Resolution

12-bit over the 0-20mA ranges

Absolute Accuracy

+/- 0.05% of full scale at 25C (77F), +/- 0.2% of full scale over temperature range

Noise and Ripple

0.04% maximum

Transient Protection

2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

Response Time

250ms typical for 10% to 90% signal change

Addressing

DIP switch configurable

Power Requirements

5V @ 45mA, 9 - 30V @ 15mA quiescent plus 80mA max.

Terminations

10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 70C (-40F to 158F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297176

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

25

Product Data Sheet 5304 Analog output module


Specifications

5304 Analog output module


General
Output points

Output Modes

Current mode, jumper link selectable


Voltage mode, 5V full scale, jumper link selectable,
Voltage mode, 10V full scale, jumper link selectable

Output signal ranges

0-20mA or 4-20mA, switch configurable


0-5V or 1-5V, switch configurable, 0-10V or 2-10V, switch configurable

Output Type

Single ended regulation on positive side with common negative return

Maximum Load Resistance

1000 with 24VDC loop power, 400 with 12VDC loop power, 250 with 9VDC loop power

Minimum Load Resistance


in Voltage Mode

2k for 10V full scale, with min 20VDC power applied


1k for 5V full scale, with min 15VDC power applied

Isolation

500VAC field to logic

D/A Resolution

12-bit over the 0-20mA / 0-5V/ 0-10V ranges

Absolute Accuracy

+/- 0.05% of full scale at 25C (77F), +/- 0.2% of full scale over temperature range

Noise and Ripple

0.04% maximum

Transient Protection

2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989


Inductive load protection diodes included

Response Time

2ms typical to 90% signal change

Addressing

DIP switch configurable

12-24V Operating
Voltage Limits

9V or (20mA x load resistance) +4V (whichever is greater) in current mode


(1.5 x Range / load resistance) + Range + 2.5V in voltage mode, 30V maximum

Power Requirements

6mA min., 25mA maximum


15mA quiescent plus 80mA max. in current mode
15mA quiescent plus 20mA max. in voltage mode

Terminations

10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 70C (-40F to 158F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

Description

5304-20

TBUX297248

4 channel isolated analog output module, 0-20mA

5304-10

TBUX297252

4 channel isolated analog output module, 0-10 volts

5304-5

TBUX297253

4 channel isolated analog output module, 0-5 volts

5304-C

TBUX297254

4 channel isolated analog output module, Custom (specify range of each input)

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

26

Product Data Sheet 5403 High level digital input module


Specifications

5403 High level digital input module


General
Number of Digital Inputs

Input Logic-HI Level

OFF to ON transition threshold is typically 50% of full scale signal range

Over-Voltage Tolerance

150% sustained over-voltage without damage

Input Current

5mA typical

Response Time

OFF to ON: 7ms typical


ON to OFF: 24ms typical

Isolation

1500VAC in groups of 4 inputs

Addressing

DIP switch configurable

Power Requirements

5V @ 45mA all LEDs ON, 5V @ 25mA with LEDs disabled

Visual Indicators

16: red LEDs controlled for power reduction

Field Terminations

1: 10 pole, removable terminal block


12 to 22 AWG
15A contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

Signal range

5403-12

TBUX297110

12 volts AC/DC

5403-24

TBUX297109

24 volts AC/DC

5403-48

TBUX297108

48 volts AC/DC

5403-120

TBUX297107

120 volts AC/DC

5403-240

TBUX297106

240 volts AC/DC

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

27

Product Data Sheet 5404 High level digital input module


Specifications

5404 High level digital input module


General
Number of Digital Inputs

16

Input Logic-HI Level

OFF to ON transition threshold is typically 50% of full scale signal range

Over-Voltage Tolerance

150% sustained over-voltage without damage

Input Current

5mA typical

Response Time

OFF to ON: 7ms typical


ON to OFF: 24ms typical

Isolation

1500VAC in groups of 4 inputs

Addressing

DIP switch configurable

Power Requirements

5V @ 80mA all LEDs ON, 5V @ 25mA with LEDs disabled

Visual Indicators

16: red LEDs controlled for power reduction

Field Terminations

2: 10 pole, removable terminal block


12 to 22 AWG
15A contacts

Dimensions

144mm wide x 118mm high x 44mm deep (5.65in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

Signal range

5404-12

TBUX297158

12 volts AC/DC

5404-24

TBUX297157

24 volts AC/DC

5404-48

TBUX297156

48 volts AC/DC

5404-120

TBUX297155

120 volts AC/DC

5404-240

TBUX297154

240 volts AC/DC

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

28

Product Data Sheet 5405 Digital input module


Specifications

5405 Digital input module


General
Input Points

32

Ranges

12-24VDC, 16-24VAC, 120VAC/DC

Over-Voltage Tolerance

150% sustained over-voltage without damage

Input Current

DC Input Logic Levels

OFF to ON transition threshold is typically 7.5VDC on the 24VDC range


OFF to ON transition threshold is typically 55VDC on the 120VDC range

AC Input Levels

OFF to ON transition threshold is typically 6VAC on the 24VAC range


OFF to ON transition threshold is typically 45VAC on the 120VAC range

Transient Protection

2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989

Isolation

Isolated in 4 groups of 8. Inputs 0-15 are on the bottom edge.


Inputs 16-31 are on the top edge. Isolation 500VAC/DC from chassis and logic ground

Power Requirements

5V @ 10mA with all inputs ON

Terminations

4: 9 pole, removable terminal blocks, 12 to 22 AWG, 15A contacts

Dimensions

144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.88in.)

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Addressing

Configurable with 4 DIP switches

AC/DC Operation

2: DIP switches determine AC/DC and 50/60Hz operation

Visual Indicators

32: Red LEDs, field powered. Cannot be disabled to conserve power

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

Description

5405-120

TBUX297249

32 point, 120V discrete input module

5405-24

TBUX297247

32 point, 12-24V discrete input module

6.0mA typical @ 24VDC on the 24V range


3.5mA typical @ 24VAC on the 24V range
2.5mA typical @ 120VDC on the 120V range
1.5mA typical @ 120VAC on the 120V range

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

29

Product Data Sheet 5410 High speed counter/accumulator


Specifications

5410 High speed counter/accumulator


General
Counter Input Points

Count Length

32-bit, range is 0 to 4,294,967,295

Over-Voltage Protection

Transient suppressor on each input

Input Voltage Range

Typical operating inputs 5 to 24V, 3V minimum, 28V maximum

Input Current

8mA typical, 13mA maximum

Input Logic Level

OFF to ON threshold is typically 2V

Maximum Input Frequency

10kHz with filters off, 5kHz with quadrature counters, 60Hz with de-bounce filters on

Maximum Pulse High Width

50 microseconds (s), 100s with quadrature counters


8.3 milliseconds with de-bounce filters

Minimum Pulse Low Width

50 microseconds (s), 100s with quadrature counters


8.3 milliseconds with de-bounce filters

Isolation

500VAC input to input, 500VAC input to logic circuit

Addressing

DIP switch configurable

Terminations

8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Visual Indicators

4: red LEDs
LED on time stretched for easy viewing controlled for power reduction

Power Requirements

5V @ 35mA with all LEDs on, 5V @ 15mA with LEDs disabled

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

Class 1, Division 2 for use in hazardous locations

Part Number

TBUX297149

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

30

Product Data Sheet 5414 Compact digital input module


Specifications

5414 Compact digital input module


General
Number of Digital Inputs

16

Ranges

Factory configurable as:


12/24V
48V
115/125V
240V

Input Current

Over-voltage Tolerance

150% sustained over-voltage without damage

Power Requirements

5V@6mA with LEDs off


5V@40mA with LEDs on

Visual Indicators

Logic powered LEDs. Can be disabled to conserve power

Field Terminations

12 to 22 AWG, 15A contacts

Dimensions

74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing


40C to 70C (40F to 158F) operation
40C to 85C (40F to 185F) storage

Safety

Model

Part Number

Signal Range

5414-24

TBUX297378

12/24V AC/DC, ATEX and IECEx

5414-48

TBUX297379

48V AC/DC (Not available outside of North America)

5414-120

TBUX297380

115/125V AC/DC (Not available outside of North America)

5414-240

TBUX297381

240V AC/DC (Not available outside of North America)

0.6 0.9mA at 24V on the 12/24V range


0.3 0.4mA at 48V on the 48V range
0.3 0.4mA at 120V on the 115/125V range
0.3 0.4mA at 240V on the 240V range

Class I, Division 2, Groups A, B, C and D and CSA certified to UL508 standards


ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5414-24 only)
Maximum permitted voltage in Canada or North America is 240VAC
Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC

Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP)
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

31

Product Data Sheet 5401 Configurable digital I/O module


Specifications

5401 Configurable digital I/O module


General
Number of Inputs or Outputs

Voltage Range

See relay specifications below

Load Current

See relay specifications below

Surge Current

See relay specifications below

Off-State Leakage

See relay specifications below

Transient Protection

Integral to the solid-state relay

Response Time

See relay specifications below

Isolation

1500VAC

Addressing

DIP switch configurable

Input/Output Assignment

DIP switch selection for each I/O point

Power Requirements

5V @ 90mA

Visual Indicators

8: red LEDs, permanently enabled

Field Terminations

2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

TBUX297121

8-point input or output module (requires solid-state relays)

Model

Part Number

Solid-State Relays for use with Model 5401

IACM-5

TBUX297122

90-140 VAC/VDC input relay

IACM-5A

TBUX297132

180-280 VAC/VDC input relay

IACM-5E

TBUX297133

10-32VDC, 15-32VAC, no polarity

IDCM-5

TBUX297124

3-32VDC input relay

OACM-5

TBUX297123

24-140VAC output relay, 3A

OACM-5H

TBUX297134

24-280VAC output relay, 5A

ODCM-5

TBUX297125

3-60VDC output relay, 3A

ODCM-5A

TBUX297135

10-200VDC, 1A

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

32

Product Data Sheet 5402 Configurable digital input or output module


Specifications

5402 Configurable digital input or output module


General
Number of Inputs or Outputs

16

Voltage Range

See relay specifications below

Load Current

See relay specifications below

Surge Current

See relay specifications below

Off-State Leakage

See relay specifications below

Transient Protection

Integral to the solid-state relay

Response Time

See relay specifications below

Isolation

1500VAC

Addressing

DIP switch configurable

Input/Output Assignment

DIP switch selectable as all inputs or outputs

Power Requirements

5V @ 150mA

Visual Indicators

16: red LEDs, permanently enabled

Field Terminations

4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

Class 1, Division 2 for use in hazardous locations

Part Number

TBUX297153 - 16-point input or output module (requires solid-state relays)

Model

Part Number

Solid-State Relays for use with Model 5402

IACM-5

TBUX297122

90-140 VAC/VDC input relay

IACM-5A

TBUX297132

180-280 VAC/VDC input relay

IACM-5E

TBUX297133

10-32VDC, 15-32VAC, no polarity

IDCM-5

TBUX297124

3-32VDC input relay

OACM-5

TBUX297123

24-140VAC output relay, 3A

OACM-5H

TBUX297134

24-280VAC output relay, 5A

ODCM-5

TBUX297125

3-60VDC output relay, 3A

ODCM-5A

TBUX297135

10 - 200VDC output relay, 1A

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

33

Product Data Sheet 5406A Dry contact relay out module


Specifications

5406A Dry contact relay out module


General
Number of Relay Outputs

16

Type

Sealed mechanical relay, Form A (normally open) contacts

Contact Ratings

6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads


3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC
3A maximum in Class 1, Division 2 hazardous locations

Operating Frequency

18,000 operations/hour mechanically, 1,800 electrically at rated load

Service Life

1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load


100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4)
100,000 operations at 3.5A inductive loads (pf=0.4)

Operate Time

10mS maximum, 5mS typical

Release Time

10mS maximum, 2mS typical

Bounce Time

3mS typical

Contact Isolation

1000VAC

Logic Isolation

1500VAC

Addressing

DIP switch configurable

Power Requirements

5V Bus Power - 5V @ 600mA with all LEDs and all relays energized
External Power - 5V @ 65mA with all LEDs and all relays energized

Visual Indicators

16: red LEDs, controlled for power reduction

Field Terminations

4: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts


Additional three pins on connector P3 to support external power

Dimensions

215mm wide x 118mm high x 44mm deep (8.37in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297284

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

34

Product Data Sheet 5407 Dry contact relay out module


Specifications

5407 Dry contact relay out module


General
Number of Relay Outputs

Type

Sealed mechanical relay, Form A (normally open) contacts.


Can be modified for Form B contacts.

Contact Ratings

6A @ 250VAC resistive loads, 6A @ 30VDC resistive loads


3.5A at 30VDC/250VAC inductive load (pf=0.4. L/R=7 ms), 1/4 HP 125VAC
3A maximum in Class 1, Division 2 hazardous locations

Operating Frequency

18,000 operations/hour mechanically, 1,800 electrically at rated load

Service Life

1,500,000 operations at 0-250mA loads, 600,000 operations at 1A resistive load


100,000 operations at 6A resistive load, 300,000 operations at 1A inductive loads (pf=0.4)
100,000 operations at 3.5A inductive loads (pf=0.4)

Operate Time

10mS maximum, 5mS typical

Release Time

10mS maximum, 2mS typical

Bounce Time

3mS typical

Contact Isolation

1000VAC

Logic Isolation

1500VAC

Addressing

DIP switch configurable

Power Requirements

5V @ 300mA all LEDs and all relays energized

Visual Indicators

8: red LEDs, controlled for power reduction

Field Terminations

2: 8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297126

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

35

Product Data Sheet 5408 Triac digital output module


Specifications

5408 Triac digital ouput module


General
Number of Triac Outputs

Output Voltage Range

24 to 240VAC, 47 to 63Hz

Load Current

0.75A at 60C (140F), 1.0A at 25C (77F)

Surge Current

55A for 1 cycle @ 60Hz

Triac Rating

600VAC @ 8.0A

Gate Control

Zero crossing turn ON/turn OFF

OFF-State Leakage

0.5mA typical, 0.75mA maximum at 115VAC


1.0mA typical, 1.5mA maximum at 240VAC

Transient Protection

Integral 275V MOV on each output

Snubber

RC snubber on each output allows inductive loads

Response Time

1/2 AC cycle maximum, 8.3 ms @ 60Hz

Isolation

1500VAC

Addressing

DIP switch configurable

Power Requirements

5V @ 120mA with all LEDs and outputs turned on


5V @ 80mA with LEDs disabled and all outputs turned on

Visual Indicators

8: red LEDs controlled for power reduction


1: green field power LED

Field Terminations

10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297103

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

36

Product Data Sheet 5409 FET digital output module


Specifications

5409 FET digital ouput module


General
Output Points

Output Voltage Range

12-24VDC

Load Current

2A continuous per output, 10A total

Surge Current

8A for 2ms

MOSFET Rating

50V, 12A

ON-State Voltage Drop

0.5V maximum at 2A

OFF-State Leakage

<1uA at 24V, 25C

Transient Protection

Inductive load protection diodes included

Isolation

1500VAC

Addressing

DIP switch configurable

Power Requirements

5V @ 70mA with all LEDs and outputs turned on


5V @ 40mA with LEDs disabled and all outputs turned on
24V @ 30mA typical, 10V min., 32V max

Terminations

10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Visual Indicators

8: red LEDs, controllable by CPU for power reduction


1: green field power LED

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

Class 1, Division 2 for use in hazardous locations

Part Number

TBUX297117

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

37

Product Data Sheet 5411 Digital output module


Specifications

5411 Digital output module


General
Output Points

32

Output Rating

1.0A maximum
0.35V maximum drop at 1.0A
0.05V maximum drop at 0.1A

Transient Protection

2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989


Inductive load protection diodes included

Isolation

Isolated in 2 groups of 16
Isolation 500VAC/DC from chassis and logic ground

Terminations

2: 9 and two 10 pole, removable terminal blocks


12 to 22 AWG, 15A contacts

Power Requirements

Visual Indicators

32: Red LEDs, can be disabled to conserve power

Dimensions

144mm wide x 127mm high x 45mm deep (5.65in. x 5.00in. x 1.80in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 70C (-40F to 158F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297246

5V @ 150mA with all LEDs and outputs turned on


5V @ 40mA with all LEDs disabled and all outputs turned on
24V @ 5mA with all outputs ON
8V min. , 30V max

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

38

Product Data Sheet 5415 Compact relay digital output module


Specifications

5415 Compact relay digital output module


General
Number of Digital Outputs

12

Type

Form A Contacts (Normally open), Dry Contact or Solid State Relay variants
4 contacts per common

Contact Rating

12A maximum per common


Dry Contact Version: 3A, 30VDC or 250VAC (Resistive)
Solid State Relay Version: 60VDC max., 3A max. at 50C (122F), 2A max. at 70C (158F)

Switching Capacity
(Dry Contact Version)

5A, 30VDC (150W Resistive)


5A X 250VAC (1250VA Resistive)

5V Power Requirements

5mA Quiescent
Dry Contact version:
150mA relays on, LEDs on

130mA relays on, LEDs off

Peak current during off-to-on transition of any, or all relays
280mA total for 15ms duration
Solid State Relay version: Relays on, LEDs on - 144mA

Relays on, LEDs off - 120mA

10-30VDC
Power Requirements

Dry Contact version:


1.0W maximum with 1.65W peak for 15ms durations
Solid State Relay version: 1.0W maximum

Visual Indicators

Logic powered LEDs. Can be disabled to conserve power

Field Terminations

12 to 22 AWG, 15A contacts

Dimensions

74mm wide x 124mm high x 45mm deep (2.90in. x 4.90in. x 1.80in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing


40C to 70C (40F to 158F) operation
40C to 85C (40F to 185F) storage

Safety

Model

Part Number

Signal Range

5415

TBUX297382

12 Point Compact Mechanical Relay Output Module

5415-A

TBUX297384

12 Point Compact Solid-State Relay Output Module, ATEX and IECEx

Class I, Division 2, Groups A, B, C and D and CSA certified to UL508 standards


ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2) (5415-A only)
Maximum permitted voltage in Canada or North America is 240VAC
Maximum permitted voltage outside of Canada or North America is 30VAC/42.4PK/60VDC

Note: Module not supported on 16-bit SCADAPack platform (SCADAPack, SCADAPack Light, SCADAPack Plus, SCADAPack 100 and SCADAPack LP)
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

39

Product Data Sheet 5606 Analog/digital I/O module


Specifications

5606 Analog/digital I/O module


General
Digital Input Points

32
Factory configurable: 12/24V, 48V, 115/125V, 240V
150% sustained over-voltage without damage

Digital Output Points

16
Form A (Normally open) relay contacts
Rating: 3A, 30Vdc or 240Vac (Resistive)
4 contacts per common

Analog Input Points

8
Single-ended
Software configurable, 0-20mA, 4-20mA, 0-10V, 0-5V
Resolution: 15-bit over the 0-10V and 0-20mA measurement range
Accuracy: 0.1% of full scale at 25C (77F), 0.2% over temperature range

Analog Outputs

2 (with optional 5305 module)


0-20mA sourcing
Resolution: 12-bit
Accuracy: (specified from 0.5-20mA.), 0.15% of full scale at 25C (77F)
0.25% of full scale over temperature range

5V Power Requirements

Digital Output Relays Continuous - 190mA, Digital Output Relays Peak - 375mA
LEDs - 195mA, Quiescent - 30mA
Total - 415 to 600mA

11-30VDC Power Requirements

12mA plus analog outputs


9-30Vdc operation possible when optional 5305 analog outputs not installed

Addressing

8 modules, DIP switch-selectable

Dimensions

213mm wide x 155mm high x 72mm deep (8.40in. x 6.13in. x 1.80in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C to 70C (40F to 158F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed
ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)

Part Number

TBUX297328
TBUX297329
TBUX297330
TBUX297331
TBUX297334
TBUX297335
TBUX297336
TBUX297337
TBUX297498
TBUX297499
TBUX297500
TBUX297501
TBUX297502
TBUX297503
TBUX297504
TBUX297505

(5606-24)
(5606-48)
(5606-120)
(5606-240)
(5606-24-AO)
(5606-48-AO)
(5606-120-AO)
(5606-240-AO)
(5606-24-A)
(5606-48-A)
(5606-120-A)
(5606-240-A)
(5606-24-AO-A)
(5606-48-AO-A)
(5606-120-AO-A)
(5606-240-AO-A)

Note: 5606 module is not supported by the Non-Programmable Controller Modules (Model 5201 & 5202)
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

40

Product Data Sheet 5607 Analog/digital I/O module


Specifications

5607 Analog/digital I/O module


General
Digital Input Points

16
Factory configurable: 12/24V, 48V, 115/125V, 240V
150% sustained over-voltage without damage

Digital Output Points

10
Form A Contacts (Normally open)
Dry Contact Relay or DC Solid State Relay
5 contacts per common
Dry Contact Relay Version:
3A, 30Vdc or 250Vac (Resistive)
DC Solid State Relay Version:
3A continuous maximum at 50C (122F) ambient TBC
2A continuous maximum at 70C (158F) ambient TBC
9A peak, 100ms

Contact Rataing

Analog Input Points

8
Single-ended
Software configurable, 0-20mA, 4-20mA, 0-10V, 0-5V
Resolution: 15 bits over the 0-10V measurement range, 14 bits over the 0-5V and 0-20mA measurement range
Accuracy: 0.1% of full scale at 25C (77F), 0.2% over temperature range

Analog Outputs

2 (with optional 5305 module)


0-20mA sourcing
Resolution: 12-bit
Accuracy: (specified from 0.5-20mA.), 0.15% of full scale at 25C (77F)
0.25% of full scale over temperature range

5V Power Requirements

Dry Contact Relay version:


Digital Output Relays Continuous - 105mA plus 90mA transients (15ms) when relays switch on.
LEDs - 107mA
Quiescent - 23mA
Total - up to 235mA
Solid State Relay version:
Digital Output Relays Continuous - 100mA
LEDs - 110mA
Quiescent - 23mA
Total - up to 233mA

11-30VDC Power Requirements

10.3mA plus analog outputs


9-30Vdc operation possible when optional 5305 analog outputs not installed

Addressing

8 modules, DIP switch-selectable

Dimensions

144mm wide x 165mm high x 72mm deep (5.65in. x 6.50in. x 1.80in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, 40C to 70C (40F to 158F)

Safety

Class I, Division 2 Groups A, B, C and D Hazardous Locations and CSA certified to UL508 standards
ATEX II 3G and IECEx: Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2), (24VDI/Solid State Relay type only)

Part Number

TBUX297478
TBUX297479
TBUX297480
TBUX297481
TBUX297482
TBUX297483
TBUX297484
TBUX297485
TBUX297490
TBUX297491
TBUX297492
TBUX297493
TBUX297494
TBUX297495
TBUX297496
TBUX297497

(5607-24)
(5607-48)
(5607-120)
(5607-240)
(5607-24-AO)
(5607-48-AO)
(5607-120-AO)
(5607-240-AO)
(5607-24-A)
(5607-48-A)
(5607-120-A)
(5607-240-A)
(5607-24-AO-A)
(5607-48-AO-A)
(5607-120-AO-A)
(5607-240-AO-A)

Note: 5607 module is not supported by the Non-Programmable Controller Modules (Model 5201 & 5202), SCADAPack LP, SCADAPack 100 and SCADAPack ER.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

41

Product Data Sheet 5421 Toggle switch digital input module


Specifications

5421 Toggle switch digital input module


General
Input Points

Signal Range

N/A (toggle switch)

Addressing

DIP switch configurable

Power Requirements

5V @ 45mA with all LEDs on


5V @ 5mA with LEDs disabled

Visual Indicators

8: red LEDs, controlled for power reduction

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297104

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

42

Product Data Sheet 5521 Potentiometer input module


Specifications

5521 Potentiometer input module


General
Input Points

Resolution

12 bits

Repeatability

0.1% over temperature range

Converter Type

Successive approximation

Signal Range

N/A (multi-turn potentiometer)

Power Requirements

5V @ 20mA

Dimensions

4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C/F to 60C /140F

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297119

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

43

Product Data Sheet 5103 Uninterruptible power supply


Specifications

5103 Uninterruptible power supply


General
AC/DC Input

16 to 24VAC for 5/24V outputs operational, 24VAC required for battery charging
14.5+/-0.5V for 5/24V outputs operational, 20VDC required for battery charging

DC/Battery Input

Turn on at 11.5V 0.3VDC, Turn off at 10.5V 0.5VDC, Maximum input is 36VDC

Input Power

35VA maximum at 24VAC, 1.9A at 13.5VDC

Outputs

5VDC at 2.0 ampere, 24VDC at 0.5 ampere, 17W total available from the two outputs
11 to 14VDC battery charger at 200mA (factory adjusted to 13.5V for gelled electrolyte lead/acid battery)

Mode

Isolated switch-mode, 30KHz switch frequency

Line Regulation

< 1% over operating range

Load Regulation

5V output: 5.15V 1% over operating range


24V output: 17%

Output Ripple

o
o
5V output: < 10mV at 20 C (68 F)
o
o
24V output: < 50mV at 20 C (68 F)

Visual Indicators

5V and 24V green LEDs show power status

Power Requirements

35VA maximum @ 24VAC, 1.9A @ 13.5VDC

Terminations

10 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing


-40C to 60C (-40F to 140F)

Safety

Non-Incendive Electrical Equipment for Use in Class I, Division 2 Groups A, B, C and D Hazardous Locations.
Temperature Code T4 at 60C ambient. UL Listed to the following standards:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations.
CSA Std. C22.2 No. 142-M1987 - Process Control Equipment.
UL Std. No. 1604 - Hazardous (Classified) Locations.
UL Std. No. 508 - Industrial Control Equipment.

Part Number

TBUX297102

Accessories
Model

Part Number

Description

1206

TBUX294034

12V 6 AH gelled electrolyte battery

ACX-24

TBUX294000

120/24VAC, 40VA transformer

ACX-24E

TBUX294167

220/24VAC, 40VA transformer

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

44

Product Data Sheet 5201 RS-485 communication controller


Specifications

5201 RS-485 communication controller


General
Processor

M37702 16-bit CMOS microcontroller, 14.754 MHz, clock integrated watchdog timer

Memory

64kBytes total, 32kBytes CMOS RAM, 64kBytes EPROM

Communication Port

RS-485, 2-wire half duplex, 4-wire full/half duplex, optional termination resistors

Baud Rates

9600, 19200, 38400, 115200

Parity

None

Word Length & Stop Bits

8 bits, 1 stop bit

Cable Length

Maximum 1200m (4000ft)

Protocol

TeleBUS (compatible with Modbus RTU and Modbus ASCII)

Protocol Modes

Slave or master

Slave Addresses

Switch configurable from 1 to 255

Physical I/O Capacity

64 digital I/O, 64 analog inputs, 32 analog outputs, maximum 40 I/O modules

Visual Indicators

RS-485 received data LED , RS-485 transmitted data LED


I/O module LED power status LED, Status LED (shows functional status)

Push-button

I/O Module LED Power toggle

Status Output

Opto coupler open collector transistor, 30VDC, 60mA, opens on fault

Power Requirements

5V @ 130mA

Terminations

8 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing; -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297101

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

45

Product Data Sheet 5202 RS-232 communication controller


Specifications

5202 RS-232 communication controller


General
Processor

M37702 16-bit CMOS microcontroller, 14.7546 MHz clock, integrated watchdog timer

Memory

64kBytes total, 32kBytes CMOS RAM, 64kBytes EPROM

Communication Port

RS-232, Data Terminal Equipment (DTE), DE-9P male connector

Baud Rates

300, 600, 1200, 2400, 4800, 9600, 19200, 38400

Parity

None

Word Length & Stop Bits

8 bits, 1 stop bit

Duplex

Full or half with RTS/CTS control

Cable Length

Maximum 15.2m (50ft)

Protocol

TeleBUS (compatible with Modbus RTU and Modbus ASCII)

Protocol Modes

Slave or master

Slave Addresses

Switch configurable from 1 to 255

Physical I/O Capacity

64 digital inputs, 64 digital outputs, 64 analog inputs, 32 analog outputs, maximum 40 I/O modules

Visual Indicators

Push-button

I/O Module LED Power toggle

Status Output

Opto coupler open collector transistor, 30VDC, 60mA, opens on fault

Power Requirements

5V @ 60mA

Terminations

2 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

108mm wide x 118mm high x 44mm deep (4.25in. x 4.625in. x 1.75in.)

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing; -40C to 60C (-40F to 140F)

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297111

RS-232 received data (RxD) LED, RS-232 transmitted data (TxD) LED
RS-232 clear to send (CTS) LED, RS-232 request to send (RTS) LED
RS-232 data carrier detect (DCD) LED, I/O module LED power status LED
Status LED (shows functional status)

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

46

Product Data Sheet 5901 High speed modem


Specifications

5901 High speed modem


General
Telco Data Rate

300 to 56k bps

Data Compression
and Error Correction

MNP 2-4, MNP 5, V42 bis, MNP 10

DTE Data Rate

Auto detect DTE speeds of 300, 600, 1200, 2400, 4800, 7200, 9600, 12000, 14400, 19200, 38400, and 57600 bps

Features

Compatible with all ITU-T standard modems from 14,400 to 300 bps
Permanently stores modem settings in memory (NVRAM)
Supports the industry-standard AT command set

Ringer Equivalency Number

0.8B

Visual Indicators

TD:
RD:
DTR:
OH:

Power Requirements

5901 - 5V @ 200mA
5901SA - 115 VAC at 10 VA for the 9VDC, 500mA, 2.1mm, center pin positive AC adapter

Terminations

2 pole, removable terminal block, 12 - 22 AWG, 15 amp contacts, RJ11C modular jack

Dimensions

4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep

Mounting

5901 - 7.5 x 35 DIN rail


5901SA - desktop, rubber feet

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C/F to 70C /158F

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

5901

TBUX297198

5901SA

TBUX297199

Transmitted data LED


Received data LED
Data Transmitter Ready LED
Off Hook LED

Note: Serial communication cable sold separately


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

47

Product Data Sheet 5902 Bell 202 modem


Specifications

5902 Bell 202 modem


General
Data Rate

1200 baud

Transmit Carrier

Switched or constant

Duplex

Full or half. Half duplex requires DTE to implement hardware RTS/CTS handshake

Wires

Two or four

Transmit Level

-35dBm to 0dBm into 600, potentiometer adjustable

Receive Sensitivity

-30dBm to +3dBm, potentiometer adjustable to -40dBm

Output and Input Impedance

600 balanced, transformer isolated

Anti-Streaming

None, 10Sec, 30Sec, 60Sec

RTS/CTS Delay

Wire: 25ms, 50ms, 125ms, 250ms


Radio: 67ms, 133ms, 266ms, 1000ms

CTS Hold Time

1ms, 8ms

Carrier Detect Delay

Wire: 19ms, 30ms, 51ms, 92ms


Radio: 33ms, 67ms, 133ms, 265ms

Carrier Loss Delay

6ms, 10ms, 23ms, 39ms, constant carrier reception half duplex

Carrier Detect Level

-30dBm, adjustable from -20dBm to -40dBm

Radio Transmit Key Output

Optical coupler open collector transistor, 5 to 15VDC, 25mA

Visual Indicators

Transmitted Data LED, Received Data LED, Clear to Send LED, Request to Send LED, Carrier Detect LED, Radio Key Output LED

Power Requirements

5902 - 5V @ 60mA
5902SA - 115VAC at 10VA

Terminations

8 pole, removable terminal block, RJ45

Dimensions

4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95 % RH, non-condensing, -40C/F to 60C/140F

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Model

Part Number

Description

5902

TBUX297120

Bell 202 modem module, 1200 baud, FSK, 2/4 wire, with radio PTT key control & RF carrier detect

5902SA

TBUX297194

Same as 5902 but with a 115VAC AD adapter for connection to other PCs or RS-232 devices

5902SAF

TBUX297195

Same as 5902SA but with a full duplex to half duplex converter - for devices without RTS/CTS support

Note: Serial communication cable sold separately


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

48

Product Data Sheet 5904 Hart interface module


Specifications

5904 HART interface module


General
Modulation

Bell 202 Frequency Shift Key (FSK)


Mark = 1200 Hz
Space = 2200 Hz

Data Rate

1200 baud

Transmit Level

500mVp-p into 250

Receive Sensitivity

120mVp-p guaranteed on
80mVp-p guaranteed off

Output Impedance

300
Transformer isolated

Input Impedance

4000
Transformer isolated

Load Resistor

250, 1 Watt maximum

Visual Indicators

TX: Transmitted data LED


RX: Received data LED

Power Requirements

5V @ 20mA

Terminations

4 pole, removable terminal block, 12 to 22 AWG, 15 amp contacts

Dimensions

4.25 inch (108 mm) wide, 4.625 inch (118 mm) high, 1.75 inch (44 mm) deep

Mounting

7.5 x 35 DIN rail

Packaging

Corrosion-resistant zinc-plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing, -40C/F to 70C /158F

Safety

cCSAus and cULus Class I, Division 2 Hazardous Area Rating, UL508 listed

Part Number

TBUX297205

This IO Expansion module is not supported by the SCADAPack E RTU.


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

49

Product Data Sheet 5908 Wireless data transceiver


Specifications

5908 Wireless data transceiver


General
Frequency

902 to 928 MHz, 230 kHz bandwidth

Transmitter
Output Power

1 mW to 1 W (+30dBm)

Range

60 miles (Line of sight with unity gain antenna)

Modulation

Spread Spectrum GFSK, 120 kBs - 170 kBs

Spreading Method

Frequency hopping

Receiver
Sensitivity

-108dBm for 10-6 BER standard speed, -111dBm for 10-6 BER low speed
-110dBm for 10-4 BER standard speed, -113dBm for 10-4 BER low speed

Selectivity

20dB at fc 115 kHz , 60dB at fc 145 kHz

System Gain

140dB

Data Transmission
Error Detection

32 Bit CRC, resend on error

Forward Error Correction


(low speed)

(24,12) Golay, retransmit on uncorrectable error

Data Encryption

Substitution, dynamic key

Max Link Throughput

115 Kbaud standard speed, 38.4 Kbaud low speed

Data Interface

RS-232/RS-485 1200 baud to 230.4 Kbaud, asynch, full duplex, RJ45 connector

Power Requirements
Supply Voltage

7 to 30 VDC (900 MHz model) 10 to 30 UDC (2.46 GHz model)


5908

5908-2.4G
mA@12VDC
mA@30VDC
mA@12VDC
mA@30VDC

Transmit

500

200

325

150

Receive

86

43

115

60

Idle

21

12

30

13

Sleep

Operating Modes

Point-to-Point , Point-to-Multipoint, Peer-to-Peer, Store and Forward Repeater

Operating Environment

-40C/F to 75C/167F, 0 to 95% humidity non-condensing

Model

Part Number

Description

5908

TBUX297270

Radio Transceiver, FreeWave 900MHz Spread Spectrum, powered by 6-30 Volts DC

5908-2.4G*

TBUX297283

Radio Transceiver, FreeWave 2.4GHz Spread Spectrum, powered by 6-30 Volts DC

Note: Serial communication cable sold separately


* Not available in all areas Consult Schneider Electric for availability in your area
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

50

Product Data Sheet 5908-WO2 Wireless data transceiver


Specifications

5908-WO2 Wireless data transceiver


General
Frequency

Up to 128 frequencies within 902 - 928 MHz., configurable in 3.2 MHz zones

Transmitter
Output Power

1.0 W (+30dBm) maximum (at antenna connector)

Modulation

CPFSK

Spreading Method

Frequency hopping based on network address

Receiver
Type

Double conversion super heterodyne

Sensitivity

-108dBm @ 1 X 10-6 BER

Network Addresses

65,000

Data Transmission
Error Detection

CRC16; Resend on error

Data Interface

RS-232/RS-485 (user selectable)

Max Link Throughput

Continuous up to 115.2 kbps

Baud Rates

1.2 to 115.2 kbps

Power Requirements
Power

7.5W max

Supply Voltage

9 to 30VDC

Transmit Current

510mA @ 13.8VDC

Receive Current

115mA @ 13.8VDC

Sleep Mode Current

8mA @ 13.8VDC

Operating Modes

Point-to-Point, Point-to-Multipoint, Store-and-Forward Repeater

Operating Environment

-40C/F to 70C/158F, 5%RH to 95%RH, non-condensing

Model

Part Number

Description

5908-WO2

TBUX297310

Radio Transceiver, MDS 900MHz Spread Spectrum, powered by 9-30 Volts CD

Note: Serial communication cable sold separately


Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

51

Product Data Sheet 5910 Ethernet switch


Specifications

5910 Ethernet switch


General
Ethernet Switch Type

5 ports, unmanaged, store & forward, 10/100BaseT

Ethernet Terminations

RJ45 ports (shielded)

Protocols

IEEE 802.3, IEEE 802.3u (TBC), IEEE802.3x

Speed and Connection

Auto-detecting 10/100 Mbps operation,


Auto MDI/MDI-X operation (no need for cross-wired cables)

Memory Bandwidth

1.4 Gbps

Duplex Operation

Full duplex IEEE802.3x and half duplex back pressure flow control

MAC Addressing

Dedicated lookup engine with 1K MAC addresses. Learning, aging and migration

Ethernet Isolation

1500 Vrms

Visual Indicators

Each port has - ACT/LINK and 10/100 (Speed) indicators

Input Power

Input Power Terminations

4 pole terminal strip and removable terminal block.


12 to 22 AWG

Dimensions

.25 inch (144 mm) wide, 4.625 inch (118 mm) high, 2.00 inch (51 mm) deep

Mounting

Desktop, rubber feet or 7.5 x 35 DIN rail

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing


40oC to 70oC
40oF to 158oF

Model

Part Number

Description

5910

TBUX297288

Ethernet Switch, 5 port, 10/100Mb autodetect, 12-24 Vdc power

5910SA

TBUX297289

Same as 5910, with the addition of a 115 Vac adapter

External Power: 11-30Vdc


1.8W at 12Vdc
2.2W at 30Vdc
Bus Power: 5V at 375mA

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

52

Product Data Sheet 5915 SDI-12 interface module


Specifications

5915 SDI-12 interface module


General
SDI-12 bus Terminations

12 to 22 AWG
15A contacts

Dimensions

2.90 inch (74mm) wide, 4.90 inch (124mm) high, 1.80 inch (45mm) deep

Packaging

Corrosion resistant zinc plated steel with black enamel paint

Environment

5% RH to 95% RH, non-condensing


40oC to 70oC (40oF to 158oF) operation
40oC to 85oC (40oF to 185oF) storage

Addressing

None required

Power Requirements
12V

6mA Idle
6.5mA active, with LEDs disabled
24mA active, continuous transmit, both LEDs on

Communications Port P1
Port Type

RS-232 compatible serial port

Connector

8 pin modular jack (RJ45)

Pins Used

Transmit, Receive and Ground

Connection

DTE

Protocol

SDI-12 only

Baud

1200bps (as per SDI-12 protocol)

Bits

7 (as per SDI-12 protocol)

Parity

Even (as per SDI-12 protocol)

Hardware Handshaking

None

Protection

15kV ESD protected

Communications Port P2
Port Type

SDI-12 port

Connector

4-way removable terminal block

Pins Used

12V, Ground, SDI-12 data

Protocol

SDI-12 only

Protection

MOV and current-limit

Indicators
Tx

Illuminates when transmitting data from Master Controller to a slave device on the bus

Rx

Illuminates when receiving data from a slave device AND when ever the Master Controller transmits.

Model

Part Number

Description

5915

TBUX297475

SDI-12 Module, serial to SDI-12 converter for SCADAPack 32 and SCADAPack 3xx-Series
controllers, c/w config. CD

Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.

SCADAPack

2012 Schneider Electric. All rights reserved.

Make the most of your energy

Schneider Electric
Telemetry & Remote SCADA Solutions
48 Steacie Drive
Kanata, ON, K2K 2A9, Canada
Phone: +1 (613) 591-1943
Fax: +1 (613) 591-1022
www.schneider-electric.com
Document Number TBUL00001-13

January 2012

You might also like