Fitness for Service of Cracked Valve on High Pressure Steam Line Header
Sofyan PURBA
Inspection Section Technical Department
PT Badak NGL Bontang; East Kalimantan, Indonesia
Phone : +62-548-55388; Fax : +62-548-552234; e-mail : sofyan@badaklng.co.id

Abstract
Cracks were found on 24 valve at steam header line. This header connects high pressure steam header from
Module I to Module II, and the valve was installed in 1989. The cracks occurred at valve body and bonnet with
total of seven cracks were observed. Due to risk of valve failure; fitness for service needs to be conducted to
ensure valve service ability. Alternating current potential drop technique was used for measuring crack depth.
The crack dimensions and material properties are used as input for finite element analysis modelling. Fatigue
growth analysis and fracture mechanic analysis were conducted also to obtain of valve properties. The
assessment shows that the valve is still in safe region based on API 579 Level 3 assessment but need to monitor
the valve service temperature.
Keywords: valve, steam, crack, alternating current potential drop, finite element, fracture mechanic

1. Introduction
Badak LNG operates eight LNG Process Trains, Train A-H, to produce LNG with maximum
annual capacity of 22.5 MTPA. To support LNG production, a number of 11 water tube type
boilers are operated with steam production of 295 ton/hr/boiler at 62 kg/cm2.g and 450 0C in
Utilities-I, and 10 water tube type boilers with steam production of 379 ton/hr/boiler at 62
kg/cm2.g and 450 0C in Utilities-II. The steam from boiler is distributed thru the piping header
system to process area as driver for compressor or pump, power generation and heating
media.
On January 27, 2011 several cracks were detected on one block valve of the high pressure
steam header line, 31HS310-24-JF2H, as showed in figure 1. The steam line is an
interconnecting line between Utilities-I and Utilities-II. The crack found on the valve body
had a length of 170 mm. Six (6) crack indications were also found on the valve bonnet. These
had lengths ranging from 23 to 120 mm and were characterized as branched cracking. The
location of cracked valve is showed on the Figure 2 below.
Since the cracks exist, there is the risk that the valve may fail therefore detail assessment is
required to ensure the cracked valve fit for the service. To replace the cracked valve is not
easy task it is required well arrangement of Train E/F and Train C/D shutdown because the
valve located at superheated steam interconnecting line of Utilities-I and Utilities-II. Besides
that, the replacement valve is not available at that time so the replacement cannot be directly
conducted. By doing the assessment, it is expected that there is comprehensive analysis of the
valve condition and the remaining life prediction of the valve based on latest condition. For
this assessment, Level 3 Assessment As per API 579 [1] was performed. Level 1 and 2
assessments because of complicated geometry and/or loading conditions, expectation of crack
growth or has the potential to be active because of loading conditions, and high gradients in
stress on valve material.

Page 1 of 19

Figure 1. Crack observed on the valve

Figure 2. Location of cracked valve on Utilities area (Valve 6A)

2. Fitness for Service Approach


The valve assessment was divided in to several stages as described below. Before discussing
the assessment stage, the specification of the valve is described first.
2.1 Cracked Valve Specification
The 24cracked valve is gate type constructed using ANSI B16.34. This valve was installed in
1989 during construction of process train. Valve service is superheated steam with service
Page 2 of 19

pressure of 61- 62 kg/cm2 and service temperature of 450 oC (842 oF). To meet with high
temperature service, the valve material is made from 1 Cr- Mo material. Detail
specification of the valve can be seen on table 1.

Table 1. Technical specification of cracked valve


Design code
ANSI B 16.34
Size / ANSI Class
24 / 600
Valve type
Gate flexible wedge type disc
Year installed
1989
Material specification
ASTM A217 WC6
Service
High pressure superheated steam
Design pressure
75 kg/cm2 (1066 Psig)
Design temperature
450 o C (842 o F)
Operating pressure
61- 62 kg/cm2 (882 Psig)
Operating temperature
450 o C (842 o F)
Insulation
N/A
For future operation the surface temperature on the West and East side is 109
o
C and 77.9oC

2.2 Visual Inspection and Flaw Sizing


Visual inspection of the cracked valve and obtain information about the crack appearance,
location and orientation. To perform detailed flaw sizing using preferred method Alternating
Current Potential Drop (ACPD) [2]. For the ACPD flaw sizing on the block valve we are
therefore considering the thin skin-effect. For the flaw sizing the current is injected to the
component using two current injectors and the surface potential over the crack and reference
area is measured using a two point contacting probe. For flaw sizing accuracy determination it
is important to use a reference block with cracks of accurately know depths of the same
material as in the component where flaw sizing is to be performed. The basic principle for
thin skin flaw sizing is illustrated in Figure 3 below.

Figure 3. Basic principles of thin skin flaw sizing using the ACPD technique

Page 3 of 19

2.2 Valve Material Testing and Characterization


To obtain material tensile and fracture toughness at the operating temperature, it is not
possible to do the test on the cracked valve. As the solution, a series of tests on similar grade
material from a discarded valve originating from the same foundry as the assessed valve was
conducted. The material testing was to include hot tensile, fracture toughness/fracture
resistance and fatigue crack testing at the operating temperature of the cracked valve in view
of the temperature gradients measured on the valve surface. The testing programme was to be
designed to facilitate an accurate assessment of the remaining life of the valve based on
applicable procedures input data requirements of the applied FFS standard ASME/API 579
[1].
2.3 Finite Element Modelling
The assessment included detailed finite element analysis (FEA) of the valve using the Abaqus
software to develop a detailed finite element model of the block valve and the materials data
established from the testing. The analysis was to be performed based on information about
the operating pressure, temperature, surface temperature gradients, design stress/piping stress
analysis and historic records showing fluctuations over time associated with operation of the
steam system and the block valve, shut down history and changes to the operation of the valve
and steam line in question due to commissioning of new trains. Further, for the remaining life
prediction information about the future operation of the valve i.e. would it be kept open or
closed and how would the pressure and temperature be expected to vary based on the
operation of the steam turbines and the steam utility system is required.
2.4 Fitness for Service Assessment
The fitness-for-service and remaining life assessment methodology applied for the analysis of
the cracked block valve conforms to the API 579 procedures for crack assessment. As per
API 579 Section 9.2.2.2 A Level 3 Assessment should be performed due to the following
condition:
a. Advanced stress analysis techniques are required to define the state of stress at the
location of the flaw because of complicated geometry and/or loading conditions.
b. The flaw is determined or expected to be in an active subcritical growth phase or has
the potential to be active because of loading conditions (e.g. cyclic stresses) and/or
environmental conditions, and a remaining life assessment or on-stream monitoring of
the component is required.
c. High gradients in stress (either primary or secondary), material fracture toughness, or
material yield and/or tensile strength exist in the component at the location of the flaw
(e.g. mismatch between the weld and base metal).
For the block valve considered all above three conditions a), b) and c) apply therefore detailed
finite element modelling of the valve to determine the operating stress in the valve bonnet and
body at the crack locations, the flaws detected are expected to be in a sub-critical growth stage
and on-line monitoring has been performed, and is required for extension of the remaining
life. The block valve has been operating since 1989, and the maximum operating temperature
has not exceeded the design temperature of 450 oC i.e. the super critical steam temperature.
This implies that since the maximum valve body temperature is below of the steels melting
point i.e. Tm = 1530 oC, the block valve body and bonnet should not have been subject to
creep and creep fatigue. Further, the sub-critical crack growth to be considered for the
Page 4 of 19

remaining life assessment is crack growth associated with cyclic variations of the thermal and
pressure stress i.e. fatigue crack growth. The fatigue crack growth parameters of the ASTM
A217 WC6 grade cast steel were determined by testing at the anticipated future operating
temperature of the valve, as described in above.

3. Test Result
3.1 Flaw Sizing of Crack in the Valve Body and Bonnet
The results of 5 ACPD measurements performed at each location have been tabulated in Table 2
and Table 3 below. The measurement locations are seen marked using a blue paint marker on the
crack body in Figure 4 and 5. The deepest flaw was found to have a height of 31.8 mm at location
A4 of the body and 13.3 mm at location C6 of the bonnet. For assessing cracks in bonnet, the
network is idealized as a single planar predominant flaw in accordance of API 579. Based
maximum height of the branched network from the ACPD measurements, the idealized flaw
height determined as 1.2 x maximum crack height from measurement, i.e.: 16 mm and 130 mm
long.

3.2 Thickness Measurement


Thickness measurements at the areas adjacent to the valve body crack and bonnet cracks were
carried out at elevated temperature. The same reference block from the same manufacturer, same
year of manufacture and which had been cast from the same material ASTM A217 grade WC6 as
used for the crack height measurement trials was used as reference for the thickness
measurements. The thickness of the reference block was measured at room temperature and also
at elevated temperature 77.9C (temperature measured at the time the thickness of the valve body
was taken), and 63C (temperature measured at the time the thickness of the bonnet) was taken.
In Table 4 and 5 conservative estimates of the remaining ligament thickness are presented as the
difference between the minimum wall thickness recorded for each location, and the greatest crack
height recorded by ACPD. The numbering of the locations follows the same numbering
convention as used earlier for the crack height measurements.

Figure 4. Marking in the body

Figure 5. Marking in bonnet. Marking red location B, blue


location C, green location D and yellow location E

Page 5 of 19

Table 2. Crack height and length measurement result on the body


Location Height Maximum (mm)
A1
16.2
A2
23.6
A3
28.2
A4
31.8
A5
30.4
A6
22.2
A7
6.2
Crack length : 170 mm

Table 3. Crack height and length measurement result on the bonnet

Location
B1
B2
B3
B4

Height
Maximum
(mm)
2. 4
3.7
7.8
8.7

Height
Maximum
(mm)
C1
4.1
C2
6.7
C3
9.0
C4
7.2
C5
11.7
C6
13.3
C7
7.5
C8
4.1
Crack length : 120 mm

Location

Crack length : 33 mm

Location
D1
D2
D3
D4
D5

Height
Maximum
(mm)
6.2
11.7
6.9
5.2
5.3

Crack length : 70 mm

Location
E1
E2

Height
Maximum
(mm)
7.3
10.5

Crack length : 23 mm

Table 4. Thickness measurement result on the valve body


Location
A0
A1
A2
A3
A4
A5
A6
A7

Average wall
thickness (mm)
53
55
56
59
60
63
66
69

Max. Crack Height


(mm)
0
16.2
23.6
28.2
31.8
30.4
22.2
6.2

Thickness of remaining
ligament
53
38.8
32.4
30.8
28.2
32.6
43.8
62.8

3.3 Material Characterization Result


3.3.1 Chemical Analysis
Chemical analysis of the block valve material received for testing. The chemical analysis was
performed using the Optical Emission Spectrography (OES). The detailed results of the analysis
are tabulated in table 6. The cast valve body material is seen to meet the chemical requirements to
ASTM Grade apart from silicon, which exceeds the maximum of 0.60% weight.
3.3.2 Tensile Testing
Hot tensile testing of the block valve material was performed as per ASTM E21 2009 using a
Page 6 of 19

12.60 mm round bar test specimen with 50 mm gauge length. The test temperature was chosen as
130 oC, i.e.: approximately twice the temperature on the surface of the valve body and bonnet
measured as 77 oC and 65oC, respectively according to the latest measurements. This test
temperature conservatively, accounts for the temperature gradient in the valve material. For
reference and for comparison with the ASTM A 217 WC6 standard requirements, testing was also
performed at room temperature. It is seen from Table 7 that the cast valve meets the room
temperature yield and tensile strength requirements to ASTM A217 grade WC6.

Table 5. Thickness measurement result on the valve bonnet


Location
B1
B2
B3
B4
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
E1
E2

Average wall
thickness (mm)
53
52.5
52.6
52
35.75
NBW*
56
53
52.55
52
51
49.35
49.7
52
53
51.2
52.25
51.25
50.6

Max. Crack Height


(mm)
2.4
3.7
7.8
8.7
4.1
6.7
9
7.2
11.7
13.3
7.5
4.1
6.2
11.7
6.9
5.2
5.3
7.3
10.5

Thickness of remaining
ligament
50.6
48.3
44.7
43.3
31.6
47
45.8
40.8
38.7
43.5
45.1
43.2
40.3
45.1
45.2
46.7
43.2
39.9

* No back wall echo

Table 6. Chemical composition analysis result on valve body


Element
Carbon, C
Silicon, Si
Manganese, Mn
Phosphorous, P
Sulphur, S
Chromium, C
Molybdenum, Mo
Nickel, Ni
Iron, Fe
Others

Element
% weight
0.20
0.70
0.87
0.033
0.027
1.43
0.94
0.20
balance
0.37

ASTM A 217 - WC6


% weight
0.05 to 0.20
0.60 max
0.50 to 0.80
0.04 max
0.045 max
1.00 to 1.50
0.45 to 0.65
0.50 max*

*Allowed as a residual element

Page 7 of 19

Table 7. Tensile testing result


Room temp 23 oC
Elevated temp 130 oC
Room Temp Requirements to
ASTM A 217 Grade WC6

YS (MPa)
287
225
Minimum 275

TS (MPa)
587
487
485655

El (%)
14
16

RA (%)
13
23

3.3.3 Fracture Toughness (CTOD) Testing


Three crack tip opening displacement (CTOD) test specimens were extracted from the discarded
valve body of cast steel ASTM A 217 WC6. The specimens were machined to square section B x
B = 40 mm x 40 mm specimens as per BS 7448 Part 1 [4], and notched by mechanical notching
and pre-cracked by fatiguing in three point bending. The resulting total crack height to specimen
width was a/W = 0.33. Testing was performed at the test temperature of 130oC i.e. the same test
temperature as for the hot tensile test. The test results obtained have been summarized in Table 8.
It is seen that the three CTOD fracture toughness values are fairly similar, with a minimum value
of the three tests of 0.38 mm. Since two of the specimens i.e. Nos PS24#1 and PS24#3 exhibited
instability close to the maximum load plateau, the minimum critical value of 0.38 mm was applied
for the fracture assessment.
Table 8. CTOD test results obtained by testing
Test
specimen
No.
15600
PS 24 #1
15600
PS 24 #2
15600
PS 24 #3

Notch & precrack height,


Ao (mm)

Plastic component
of clip gauge opening,
Vp (mm)

Load
P (kN)

CTOD
(mm)

Comment

14.88

0.82

75.72

0.38

Critical event, c

15.02

0.96

72.11

0.43

Max. load
plateau, m

14.02

0.84

77.42

0.40

Critical event,

3.3.3 Fatigue Growth Testing

Fatigue crack growth testing was performed on a single edge notched tension specimen
(SENT) with B = 9.6 mm and W = 29.6 mm. The initial notch and fatigue pre-crack height
was a =5.4 mm. The testing was performed at the same temperature as the CTOD and hot
tensile testing i.e. at 130 oC. The fatigue crack growth testing was performed at 5 Hz varying
the stress range between 20 MPa, 40 MPa, 50 MPa, 75 MPa, 100 MPa and 150 MPa until the
crack exhibited stable propagation. The crack extension was monitored using ACPD and
visual measurement of the crack height on the side of the fatigue crack growth specimen. The
results of the fatigue crack growth testing of the block valve material in terms of crack height
versus number of stress cycles, are showed in Figure 6. Also showed in this figure are the
crack growth parameters A = 3.1E-17 and m = 4.4 at 130 oC obtained from the curve fitting.
The fatigue threshold was found from the tests to be approximately Ko = 184 Nmm-3/2.

Page 8 of 19

Figure 6. Results of fatigue crack growth testing of the 24 block valve material

3.4 Finite Element Modelling Result


The objective of the analysis was to study the stress distribution on the 24 block valve in the
closed condition, at the two crack locations (i.e. West Side valve body and bonnet crack) and
to provide the stress values as input data to the fitness-for-service and remaining life
estimation. The 3D finite element model of the block valve was developed based on the 2D
engineering design drawing for the valve and manufacturer specification brochure was also
reviewed for information purpose as well as thickness measurement. In the current model, the
dimensions of the bonnet cap have been assumed since the curvature is anticipated to affect
the stress distribution at the bonnet cap. The model is showed on the figure 7.
The material properties input for the finite element analysis was taken from the tensile test
results obtained from testing performed at high temperature (i.e. 130C). In order to input the
elastic-plastic material properties to Abaqus, it is important to generate best fit smooth
Ramberg-Osgood stress strain curve since stress strain data obtained from the testing will
normally have a number of irregularities which may not be acceptable for the FEA. The
engineering stress-strain curve generated does not give a true indication of the deformation
characteristics of a metal because it is based entirely on the original dimensions of the
specimen, and these dimensions change continuously during the test. Therefore the true
stress-strain curve should be adopted in the finite element analysis.
Fixed boundary condition (BC) is assigned to West Side of the block valve model while
simply supported boundary condition is assigned to the East Side. In simply supported BC,
the model is free to move axially. The BCs considered in the current analysis were based on
the piping isometric drawing as showed in Figure 8 and it is anticipated that the 24 block
valve is not rigidly fixed in all directions at both end of the pipe. To simulate the operating
condition of the 24 block valve in closed condition, internal pressure is applied to the West
Side (62.25 bar = 6.225 MPa), bonnet (61 bar = 6.1 MPa) and East Side (61 bar = 6.1 MPa) of
the 24 block valve model.
Page 9 of 19

Two (2) different operating temperature distributions were analysed, such as:
1. Low temperature case: measured at the block valve surface.
a. West Side: 114.4C
b. Bonnet: 73C
c. East Side: 70.6C
It is noted that there is no information available regarding the temperature distribution
inside the block valve. Hence, in the current analysis assumption has been made to increase
the temperature inside the block valve by 100C.
2. High temperature case: temperature distributions applied in at the outer surface of the
model were based on updated information / surface temperature measurement i.e. 415C
for the West side, 412C for the East side, 402C for the bonnet cap and 375C for the
valve body). For this case, the operating temperature inside the block valve is set to 440C
due to the flow of superheated steam inside the block valve.

Figure 7. Isometric view (left) and front view (right) of finite element model

Figure 8. Piping isometric drawing


Page 10 of 19

In Abaqus, to perform a thermal analysis an initial temperature condition needs to be defined.


In the current analysis, ambient temperature of 25C was assumed as the initial condition at
the outer and inner surface of the 24 block valve.
Based on the summary of 3D finite element results listed in Table 9, it can be seen that the
increase in temperature between the low and high temperature will further increase the stress
istributions at the valve body and the bonnet (i.e. ~72 MPa stress increase at valve body and
~74 MPa stress increase at the bonnet). For the low temperature case at the valve body crack
location it is seen that the stress does not decrease significantly if the temperature is reduced
by 10C (i.e. reduction of stress of 1 MPa). If the temperature is increased by 20C, then the
stress increases by 4.5 MPa. Hence, the stress range between low temperature -10C to low
temperature + 20C for the valve body is 4.5 MPa. Similarly we find that for the valve bonnet
the stress range between Low temperatures -10C to Low temperature + 20C is 9 MPa. The
cyclic stress and number of cycles assuming temperature fluctuation once a day are showed in
Table 10.
Table 9. Summary of FE results
Case
Low temperature
High temperature
Low temperature
minus 10C
Low temperature
plus 20C

Location
Valve body
Bonnet
Valve body
Bonnet
Valve body
Bonnet
Valve body
Bonnet

Von-Mises stress
(MPa)
78 to 129
57 to 122
157 to 194
132 to 195
77 to 128
54 to 116
84 to 130
61 to 127

Average (MPa)
103.5
89.5
175.5
163.5
102.5
85
107
94

Table 10. Cyclic stress and number of cycles assumed per year
Case
Low temperature
10oC + 20oC
Low temperature High temperature

Location
Valve body
Bonnet
Valve body
Bonnet

Stress range, (MPa)


4.5
9
72
74

Cycles per year


365
365
365
365

3.5 Fitness for Service Assessment Result


The failure criteria at Level 3B is determined as per API 579 [1], from the failure assessment
diagram (FAD). For the block valve assessment the Level 3B i.e. the material specific FAD is
established from the engineering stress-strain curve obtained from the hot tensile test. The
material fracture toughness is established by fracture mechanics testing of similar ASTM A
217 WC6 grade material from the discarded valve of same rating, same manufacturer and year
of manufacture, and which has been operating in the same service in the steam system. By
implementing procedure in API 579 [1], the failure assessment diagram (FAD) for 24 valve
is showed on the Figure 9.

Page 11 of 19

Figure 9. Material specific Failure Assessment Diagram for valve body/bonnet at 130 oC

For the valve body, the assessment was conducted using API 579 Section 9 [1] procedures at
Level 3B. It is seen from Figure 10 shows that the flaw is safe based on the maximum vonMises stress for the low temperature case +20 oC, derived from the finite element analysis.
Critical flaw sizes (heights versus lengths) were determined for cracks in the valve body
subjected to tensile stress due the temperature gradient in the valve assuming different wall
thicknesses reported in the vicinity of the valve body crack. The results presented in Figure 11
show that the 31.8 mm height and 170 mm long flaw is safe contained within the boundaries
of the FAD.

Figure 10. Location of failure assessment point for flaw in valve body

Page 12 of 19

Figure 11. Location of failure assessment point for flaw in valve body compared to the calculated
critical flaw heights versus flaw lengths

Figure 12. Valve body flaw profile and wall thickness profile established from similar valve cross
section and minimum wall thickness derived from UT and measurement

In Figure 12 the valve body flaw has been plotted against the minimum wall thickness
measured in the area around the flaw. The minimum wall thickness is estimated by UT
thickness measurements in taken in vicinity of the valve body crack, where back wall echo
could be detected. It is apparent that the thickness values derived by the UT measurements are
incorrect due to the problems of obtaining the back wall echo at the exact crack location. Is
believed that the minimum thickness measurement is taken at the location of the valve where
there is a recess for the valve seals. The t2 values showed in Figure 10.4 are based on the
updated information, which represents the wall thickness estimated by sectioning a similar
(same manufacturer and grade) discarded valve, at the same position where the valve body
crack was located and also by correlating this with the thickness derived from the
manufacturers drawing. The measurement have some inherent uncertainty, but are
considered far more reliable than the thicknesses derived from UT, which were associated
Page 13 of 19

with loss of back wall echo in the vicinity of the crack due to the thickness transition and
measurement at locations that are associated with thinner wall, presumably due to the
presence of the recess for the valve seals.
The valve is intended to operate the valve in the closed condition, under the defined low
temperature case, with minimal temperature excursions i.e. Low temperature -10oC and Low
temperature + 20oC. The remaining life of the valve can be estimated assuming the valve
remains in the closed position, and the operation of the steam system causes maximum
temperature swings between 10 oC below and 20 oC above the low temperature case, with a
frequency of once a day. Under these circumstances the remaining life can be estimated by
calculating the time for the flaw to propagate to become critical or grow through the wall
thickness, eventually causing a leak before break (rupture) at location A4. Calculations were
performed using the stress range 4.5 MPa, one cycle per day and using the crack growth
parameters showed in Table 9. The results of this analysis showed that under these conditions
no crack extension would be expected, as showed in Figure 13.

Figure 13. No crack growth is estimated for the valve body crack for thermal stress cycles

Similar analysis was run for illustration, assuming the temperature swings between the low
and high temperature case once a day. The analysis showed that if the valve experiences
temperature fluctuations between the low temperature case and the high temperature case
(inside 440 oC superheated steam) the body crack would grow as showed in Figure 14, and
the flaw would eventually become unsafe. The expected failure mode is leak before rupture.
For the crack in the bonnet, the same procedure is applied. It is seen from Figure 15 that the
16 mm height and 130 mm equivalent flaw is safe for the low temperature case i.e.: for a
membrane stress of 127 MPa as per the finite element analysis. The critical flaw size was
estimated for the low temperature case as showed in Figure 16.
Fatigue crack growth analysis was performed to check if the flaw in the bonnet would grow to
become critical. Based on the results of the finite element analysis it was found that the
primary membrane stress range associated with fluctuating temperature in the bonnet 10 oC
Page 14 of 19

below to 20 oC above the low temperature case was 9 MPa. It is seen from Figure 17 that the
flaw would not be expected to grow under these conditions, if the frequency of the cyclic
stress change associated with the temperature fluctuation is once a day.

Figure 14. Crack growth estimated for the valve body crack for thermal stress cycles associated
with temperature fluctuations between the low and high temperature once a day

Figure 15. Location of failure assessment point for flaw in valve bonnet

Page 15 of 19

Figure 16. Critical flaw sizes estimated for the valve bonnet for the low temperature operation case

Figure 17. Results of fatigue crack growth calculations for the re-categorized flaw for the low
temperature case

The fatigue calculation was also performed for illustration assuming a stress range of 74 MPa
associated with a swing between the low and high temperature case, once a day, as showed in
Figure 18. The analysis shows that if the valve experiences temperature fluctuations between
the low temperature case and the high temperature case (inside 440 oC superheated steam) the
branched bonnet cracks would grow and eventually become unsafe. The failure mode is
uncertain due to the nature of the branched cracking. Potentially this could cause fracture
before leak by interaction of the branched cracking.

Page 16 of 19

Figure 18. Results of fatigue crack growth calculations for the re-categorized flaw on the bonnet
for temperature fluctuations between the low and high temperature cases

4. Discussion
ACPD crack height measurements were performed of the 24 block valve. The results showed
that the 170 mm flaw located at the valve body on the West Side had a semi-elliptical shape
with a maximum height of 31.8 mm. ACPD measurements were also performed on the valve
bonnet and the greatest flaw height for the network of branched cracks was determined to
13.3 mm. Applying the API579 [1] procedure for re-categorisation of branched cracks the
characteristic idealized flaw or equivalent flaw size was determined to be 16 mm in height
and 130 mm long.
Based on hot tensile testing, crack tip opening displacement (CTOD) testing of a discarded
valve of the same material ASTM A217 grade WC6, and finite element modelling of the
valve in the closed position, the subsequent fracture mechanics analysis, showed that both the
body crack and the equivalent bonnet flaw was safe for the low temperature case considered.
Fatigue crack growth analysis showed that the flaw would not grow under the current low
temperature operating conditions, assuming temperature swings between 10 oC below the low
temperature and 20 oC above the low temperature case for the closed condition.
Crack growth analysis showed that sub-critical crack growth could take place and the flaws
could become unsafe depending on the operation of the steam system. If the valve experiences
significant temperature changes (between the low and high temperature case), once a day, a
leak (no rupture) could develop.
The valve is intended in the closed condition and under the defined low temperature case,
with minimal temperature excursions i.e. Low temperature -10 oC and Low temperature + 20
o
C. Under such strictly controlled conditions, the finite element analysis showed that the
valve body would experience a stress range of 4.5 MPa at the crack location. Fatigue crack
growth analysis was performed imposing a stress range of 4.5 MPa once a day. The results of
the analysis showed that under these conditions no crack extension would be expected.
Page 17 of 19

If the valve is continued operated under controlled conditions it is recommended that crack
monitoring of the body and bonnet flaws is performed to confirm that no crack extension is
taking place as the current fatigue crack growth analysis indicates. Since the analysis indicates
that the main growth occurs in the thickness direction hence, there may be difficult to detect
any crack growth on the valve surface. Therefore, the temperature monitoring shall be
conducted to avoid any high swing beyond lower temperature case.

5. Conclusion
Based on the above the results of the ACPD flaw height measurements, materials, CTOD,
fatigue crack growth and finite element modelling, Follows are the conclusion:
a. The results showed that the 170 mm long flaw located at the valve body on the West Side
had a semi-elliptical shape with a maximum height of 31.8 mm.
b. Failure assessment based on the minimum thickness and the stress derived from the finite
element analysis showed that the flaw is in the safe region of the Level 3B failure
assessment diagram.
c. Crack growth analysis showed that the crack in the valve body is not likely to grow if the
valve experiences limited temperature cycling (between 10 oC below to 20 oC above the
low temperature case) but sub-critical growth of the body crack will occur if the valve
experiences temperature cycling between the low and the high temperature case
(superheated steam at 440 oC inside), and the valve is likely to develop a leak before break
at the valve body crack location.
d. The largest flaw height associated with the network of branched cracks was 13.3 mm and
idealized or equivalent flaw size was determined to be 16 mm in height and 130 mm long.
e. The fracture mechanics analysis performed based on the API 579 Level 3B procedures
showed that for the current low temperature case, the crack is in the safe area of the failure
assessment diagram.
f. Fatigue crack growth analysis performed based on the stress range derived from the finite
element analysis assuming temperature fluctuation from 10 oC below to 20 oC above the
low temperature, showed that the equivalent crack in the bonnet would not grow. But, if
the temperature swings between the low temperature and the high temperature case (440
o
C superheated steam inside) the analysis showed that the equivalent bonnet flaw would
experience sub-critical crack extension.
g. Under the current low temperature case the valve can be operated safely, it is
recommended to perform crack monitoring to confirm that there is no crack extension
using ACPD. Close monitoring of temperature shall be conducted to prevent any
temperature swing beyond lower temperature case.

Acknowledgements
We express our gratitude to DNV Singapore for assistance in conducting this assessment.
Page 18 of 19

References
1.
2.
3.
4.

5.

American Petroleum Institute, Fitness for service, API 579-1/ASME FFS-1, JUNE 5,
2007.
Martin C Lugg, An Introduction to ACPD, TSC Technical Bulletin TSC/MCL/1146
Rev. 18, February 20, 2002.
British Standards Institution, Guide to methods for assessing the acceptability of flaws in
metallic structures, BS7910: 2005.
British Standards Institution, Fracture mechanic toughness test. Method for
determination of KIc, critical COD and critical J values of metallic material, BS7448
Part 1: 1991.
DNV, Fitness for service and remaining life assessment of block valve in high pressure
steam system PT Badak NGL Bontang , Technical Report no CTC_R_2011029, October
2011.

Page 19 of 19