MICRO CLEAN ZONES DATE : 4/6/2010

CLIENT : PELLETS PHARMA LIMITED

LOCATION : PASHMYLARAM, MEDAK

BASIS OF DESIGN FOR AIR CONDITIONED AREAS

REQUIRED ROOM CFM ASPER


FRESH AIR AS PER Ingress&

FRESH AIR QTY INCLUDING

DEHUMIFIED CFM FROM TR


FRESH QUANTITY AS PER
FRESH AIR AS PER AC/Hr

EXHAUST AIR QUANTITY


Exgress( pres balancing)

RESULTANT FRESH AIR

RELATIVE HUMIDITY
DEHUMIDIFIED CFM

AHU SELECTED CFM

FILTRATION LEVEL

STATIC PRESSURE
EQUIPMENT LOAD

CLASS@ REST
ROOM NAME

RESULTANT CFM

BLOWER MODEL
TEMPERATURE

COIL DETAILS
REMARKS
OCCUPANCY
OCCUPANCY

MOTOR KW
FINAL CFM
EXHAUST

AC LOAD
S.NO

VOLUME
LENGTH
AHU

HEIGHT

MCAPH
WIDTH

AC/Hr
AREA

m m m2 m m3 # KW cfm cfm cfm cfm cfm cfm T.R cfm cfm cfm cfm cfm cfm 0
C % µm BDB # mmWC

RM STORES 12.5 15.2 190.0 2.7 513.0 0 0 604.3 0 180 604 0 604 5 2000 1090 12 3626 3626 4230

A.C STORES 2.3 2.4 5.5 2.4 13.1 0 0 15.5 0 90 90 0 90 1 400 345 25 193 400 490

1 AHU-1 DISPENSING 2.3 1.6 3.6 2.4 8.6 3 2 10.2 60 90 90 0 90 0.75 300 122 25 127 300 390 6500 25±2 NA 20+10+5+3 NA 90 NFLP DX COIL

STAGING 2.3 2.1 4.8 2.4 11.6 0 0 13.7 0 90 90 0 90 0.75 300 133 25 171 300 390

ROOMS 2.3 8.1 18.6 2.4 44.7 0 0.0 52.7 90 90 0 0 90 2.25 900 456 25 658 900 990

7.5 6490
ISO
4 AHU-4 FBC 5.7 14.8 84.2 4.2 353.8 5 10 416.8 100 180 417 0 417 6 2400 3423 30 6252 6252 6669 7000 25±2 NA 20+10+5 150 NFLP DX COIL
CLASS 8

PREPARED BY ( MICRO CLEAN ZONES) CHECKED BY (MICRO CLEAN ZONES ) APPROVED BY (PELLETS PHARMA LTD)