You are on page 1of 6

Type HORM 4

Pilot Wire Protection Relay


Type HORM 4
Pilot Wire Protection Relay

HORM 4 relay
withdrawn from case

Features Relay description tap of the summation CT secondary


winding. The relay can operate
l High speed operation. The three line currents are therefore, only if the potential of
l Equipped with supervision and summated by a summation points a/b or c/d is positive with
injection facilities. transformer with a centre tap to respect to winding mid-points O’ &
l Pilot circuits upto 1000 ohms and provide a single phase current for O” respectively.
1 microfarad. comparison over a pilot circuit.
A padding resistor is provided to Figure 2(a) shows the voltage
l Upto four output contacts distribution around the pilots during
adjust the pilot loop resistance to a
available. the positive half-cycle. It also shows
constant value of 1000 ohms, thus
ensuring that the settings remain the components around the pilot
Application loop circuit which are active during
close to the design value for all pilot
This is a well established type of this half-cycle of current flow. It is
circuits. The padding resistance is
protection for feeders. It is based on obvious from the voltage diagram
set to 0.5 (1000-Rp) on each relay,
the Merz-Price circulating current that the potential of points a/b and
where Rp is the pilot loop resistance
system and suitable for operation c/d can either be zero or negative,
in ohms. but never positive. The same
over privately owned two core pilots
The operation of HORM4 relay can situation results during negative
with a relatively high core resistance
be understood by referring to half-cycle also (see Figure 2(b)).
(upto 1000 ohms. loop) and low
Figure 2 which shows the basic Stability is thus achieved during
intercore insulation level.
circuit 2(c) and voltage distribution through faults and load.
The majority of plain feeders can be around the pilots during one full During internal faults, say, with
protected with this form of cycle of the current wave [2(a) and infeeds from both ends, diodes D4
protection, which features a unit 2(b)] during a through-fault/load. and D5 will allow the current from
protection scheme with no time or From Figure 2(c) it will be seen that each half of the summation
current grading problems even on the relay operating coil is basically transformer secondary to flow
ring circuits. connected between the midpoint of through the relay during alternate
the diodes D4/D5 and the centre- half cycles thereby causing fast relay
operation.
Pilot supervision For N = 3 CT requirements
Neutral connection in CT secondary Minimum knee point voltage of line
Reliability of the pilot wire protection
should be made to terminal 9. CTs
depends greatly on the integrity of
pilots. It is therefore necessary to A–B 125
50 + 1f (RCT + 2RL) volts
monitor the healthiness of the B–C 125 VK =
In
interconnecting pilots continuously C–A 62
and sound an alarm in case the A–B–C 72 where
pilots are found faulty. Pilot wire For N = 5 In = Rated current of relay (A)
supervision is usually carried out by Neutral connection should be made If = Max through-fault current
injecting a small dc current into the to terminal 10. under steady state
pilot circuit and monitoring its
l Sending end: conditions referred to the
continuity of flow.
upto 2 x receiving end. CT secy. circuit (A).
The pilot supervision circuits are
Drop-off/pick-up value of relay RCT = Resistance of line CT secy.
shown in Figure1 itself. Capacitors
winding (ohms)
C1 are provided to block the dc 25% of setting
supervision current from flowing RL = Resistance of a single lead
through the relay. A rectified ac Aux. voltage relay & from the line CTs to the
current of about 4.8 mA is injected supervision relay (ohms).
into the pilots at one end through (a) 220, 110, 50/48, 30V dc
The knee point voltage of a current
the injection transformer IT, rectifier (b) Injection: 240V ac 50 Hz.
transformer is expressed as the
Rt resistor r1 and choke L. At the
Operating time voltage, applied to the secy. winding
other end, a sensitive attracted
with the primary on open circuit,
armature unit RL1 is connected 60 m.secs. at 3 x Is.
which when increased by 10%
across the pilots throgh resistor r1
causes the magnetising current to
and diode d1 and choke L. Relay RL1 Throughfault stability
increase by 50%.
normally remains picked-up under 50 times relay rating
pilot healthy conditions. It drops-off It is not recommended that any
only when: Accuracy other burdens should be connected
±10% of setting in the same current transformer
i) pilots are opened
circuit but where this is unavoidable
ii) pilots are shorted
Thermal rating the additional burdens should be
iii) pilots are cross-connected.
added into the above expression for
20 x rated current for 3 secs.
When RL1 drops off an alarm is knee point voltage. In addition to
given by the N/C contact of a the above, the secondary
Pilot
follower relay RL2. RL2 is slugged on magnetising current of the current
drop off to allow for momentary Any type of pilot having an transformers at opposite ends of the
resetting of RL1 during heavy insulation grade which can feeder should not differ by more
through fault conditions which can withstand 500V between cores may than 0.05 In at
reduce or neutralise the dc be used. The pilots should have a
supervision currents cyclically and loop resistance excluding the relay 50 volts.
cause RL1 to drop off intermittently. of 1000 ohms. and a total intercore In
capacitance of less than 1.0
microfarad. The pilot circuit should Contacts
Technical data
be capable of standing a pressure Four make contacts are provided on
Current rating test of 5 KV rms between the two HORM 4. One normally closed
1A/5A cores connected together and earth. contact on supervision for pilot
alarm.
Rated frequency
Contact rating
50 Hz
Make and carry Make and carry
Current setting Current continuously for 1 second Break

l Receiving end: AC 1250VA with 7500VA with 1250VA with


Summation ratio 1/1/N maxima of 5A maxima of 30A maxima of
and 660V and 660V 5A and 660V
Type of fault Fault settings [%In]
N=3 N=5 DC 1250W with 7500W with 100W (resistive)
maxima of 5A maxima of 30A 50W (inductive)
A-N 25 18 and 660V and 660V L/R = 0.04 second
B-N 32 21 with maxima of 5A & 660V
C-N 42 25
alarm

Figure 1:
Typical schematic diagram of relay type HORM 4
with pilot supervision

’ D1

Figure 2:
Behaviour of HORM 4 during external fault
Insulation Environmental withstand Case size
The relay will withstand 5 kV for The relay meets the requirements 1-1/2, D.E. – HORM 4
1 second between the pilot and of BS 2011 to clause 20/40/4 ID, S.E. - injection and
case circuit and all other and is satisfactory for normal supervision
independent circuits. 2 kV rms for use.
1 minute between all other case
terminals connected together and
Information required
Mechanical durability with order
the case.
The relay will perform a
2 kV rms for 1 minute between minimum of 10,000 operations. Current rating 1A or 5A
all other independent circuits of
the relay including contact
circuits.
1 kV rms for 1 minute across the
contacts of the normally open
outgoing contact pairs.
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
© 1998 ALSTOM Limited

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice

PR:032:0799:A Printed in India.

You might also like