Professional Documents
Culture Documents
Page 1 of 2
TECHNICAL INFORMATION Amps Ballasts Blocking Inductor Colour Rendering Colour Temperature BATTENS Batten Accessories Battens Bare Battens Diffused Battens Emergency BULKHEAD Bulkhead Wall lights Exit and Emergency Lamps DOWNLIGHTS Downlight 240v Low Voltage Downlights Low Voltage Waterproof FLOODLIGHTS Floodlights HIGHBAYS Industrial lighting OYSTERS Circular Fluorescent SHOPLIGHTERS Downlights Metal Halide Downlights PL Fluorescent SLIMLINE FLUORESCENT Display Lighting T-BARS Recessed Plaster Fittings T Bar Fittings WEATHERPROOF Weatherproof ALL PRODUCTS Current Dimming EMC Regulation
Lighting Calculations
How Many Fittings are Required for a Room The utilisation factor table and a few simple formulas allow us to calculate the number of fittings required for any room. Step 1: Understand the utilisation factor table that is available on most fittings. UTILISATION FACTOR TABLE (for 2x36 bare batten) LOR: 88.1% Reflectance SHR NOM 1.75: 1.0 Disregard SHR MAX.
Emergency Lighting Energy Efficiency Glare Control Glare Rating Systems HPF IP Ratings Lamps Lamp Efficiency Lead Lag Lighting Calculations Light Emmitting Diodes Lighting Measurements Low Temperature Operation Low Voltage Lighting
Ceiling 0.50
Wall 0.30
Floor 0.20
0.75 0.30
1.00 0.37
1.25 0.42
1.5 0.46
2.0 0.52
2.50 0.56
3.00 0.59
4.00 0.63
5.00 0.66
LPF Lumen Lumen Output of Lamps Lux Lux Levels Mounting Heights Mounting Terminology Power Power Factor
LOR
Light output ratio for this fitting. Not required in a simple calculation. Nominal Spacing to Height ratio. For a given mounting height we can see the nominal spacing between fittings. Eg. 1.75 to 1 means that for every 1 metre of mounting height (above work plane) we should have a maximum 1.75 metres between fittings. Used by lighting design software and not needed for manual calculations. Select a horizontal line for the reflectance values that best describe the room.
SHR NOM
0.7 0.5
0.5 0.3
0.2 0.2
Utilisation Factor (body of the table) This is a value between 0 and 1 that represents the percentage of total lamp lumens in the room that fall on the work plane. It takes into account the room reflectances, room shape, polar distribution and light output ratio of the fitting. Step 2: Calculate Room Index (K) Room Index: The room index is a number that describes the ratios of the rooms length, width and height. Formula: K=LxW Hm (L+W) Where: L = Room Length W = Room Width Hm = Mounting Height of Fitting (from working plane) Work Plane = Desk or Bench Height The result of this calculation will be a number usually between 0.75 and 5. Note: This formula for K is only valid when room length is less than 4 times the width or when the K value is greater than 0.75. Step 3: Using the room index and reflectance values in the utilisation factor table For the horizontal row select the reflectance that best describes the room.
http://www.ndlight.com.au/lighting_calculations.php
15-07-2011
Page 2 of 2
For the vertical column select the room index value K as calculated above. The utilisation factor for this fitting in this room is where the row and column intersect. Step 4: To calculate the number of fittings required use the following formula: Formula: N= ExA F x uF x LLF Where: N = Number of Fittings E = Lux Level Required on Working Plane A = Area of Room (L x W) F = Total Flux (Lumens) from all the Lamps in one Fitting UF = Utilisation Factor from the Table for the Fitting to be Used LLF = Light Loss Factor. This takes account of the depreciation over time of lamp output and dirt accumulation on the fitting and walls of the building. Typical LLF Values
Standard
Triphos
Step 5: Space the number of fittings uniformly around the room drawing and check the SHR nominal for the fitting has not been exceeded. If it has been exceeded re space the fittings to get back to SHR nom. Step 6: Work out the number of fittings required in each axis of the room:
HOME
ABOUT US
TECHNICAL
CONTACT US
HOSTING BY SPIT
http://www.ndlight.com.au/lighting_calculations.php
15-07-2011