COMMISSIONING RECORD

Site Details:- Met Police Cannon Row (TPHQ) Date:- 14.10.2008

AHU Reference:- Briefing Room Supply AHU 4 Fan 1

INVERTER DETAILS

Drive Type:- ACH550-01-08A8-4 Serial Number:- 4080101422

MOTOR DATA

Manufacturer:- ABB Frame Size:- M3AA112M

Motor FLC (A):- 9.0 Amps Motor RPM:- 1455 rpm

Motor Power (kW):- 4.0 kW Motor Voltage:- 400Vac

Motor Connection (Star/Delta):- Delta

ENGINEER

Name:- Phil Underwood

Signature:-______________________________________________________________
ACH550 Parameter Settings List
Parameter Para HVAC Settings Parameter Para
Name Number Default Value Name Number
Group 99 Language 9901 ENGLISH English Group 14 Relay Output 1 1401
START-UP Applic Macro 9902 HVAC Default PID RELAY Relay Output 2 1402
DATA Mot Ctrl Mode 9904 Scalar:Freq Scalar OUTPUTS Relay Output 3 1403
Mot Nom Volts 9905 230/400/460 400 v All other parameters in this group do not need to be set unless
Mot Nom Curr 9906 1.0 * IN 9.0 A are required.
Mot Nom Freq 9907 50/60 HZ 50 Hz Group 15 AO1 Content Sel 1501
Mot Nom Speed 9908 1440/1750 RPM 1455 rpm ANALOGUE AO! Content Min 1502
Mot Nom Power 9909 1.0 * PN 4.0 kW OUTPUTS AO1 Content Max 1503
ID Run 9910 OFF/IDMAGN Off Minimum AO1 1504
Group 1 Output Freq 0103 Maximun AO1 1505
OPERATE Current 0104 3 Line of Characters as Reqd. Filter AO1 1506
DATA Power 0106 AO2 Content Sel 1507
Group 3 AO" Content Min 1508
FB ACTUAL Not Required Unless Sending Signals Via Modbus Ect AO2 Content Max 1509
SIGNALS Minimum AO2 1510
Group 4 Maximum AO2 1511
FAULT Indication Only No Settings Filter AO2 1512
HISTORY Group 16 Run Enable 1601
Group 10 Ext 1 Commands 1001 DI1 DI1 SYSTEM Parameter Lock 1602
START/ Ext 2 Commands 1002 DI1 DI1 CONTOLS Pass Code 1603
STOP/DIR Direction 1003 Forward Forward Fault Reset Sel 1604
Group 11 Keypad Ref Sel 1101 Ref 1 (Hz/rpm) Ref 1 Hz User Par Set Chg 1605
REF Ext 1/Ext2 Sel 1102 EXT 1 PID Local Lock 1606
SELECT Ref 1 Select 1103 AI1 AI1 Param Save 1607
Ref 1 Min 1104 0.0 Hz/0 rpm 35 Hz Start Enable 1 1608
Ref 1 Max 1105 50 Hz/1500 rpm 50 Hz Start Enable 2 1609
Ref 2 Select 1106 PID1 Out PID Out Display Alarms 1610
Ref 2 Min 1107 0.0% 0.0% Paramerter View 1611
Ref 2 Max 1108 100.0% 100.0% Goup 17
Group 12 Const Speed Sel 1201 DI3 - Overrides This Group is not required for normal set up
CONSTANT Cnst Speed 1 1202 5/6 Hz -
SPEEDS Const Speed 2 1203 10/12 Hz - Group 20 Minimum Speed 2001
Const Speed 3 1204 15/18 Hz - LIMITS Maximum Speed 2002
Const Speed 4 1205 20/24 Hz - Max Current 2003
Const Speed 5 1206 25/30 Hz - Undervoltage Ctrl 2006
Const Speed 6 1207 40/48 Hz - Minimum Freq 2007
Const Speed 7 1208 50/60 Hz - Maximum Freq 2008
Timed Mode Sel 1209 CS1/2/3/4 - Min Torque Sel 2013
Group 13 Minimum AI1 1301 20.0% 20.0% Max Torque Sel 2014
ANALOGUE Maximum AI1 1302 100.0% 100.0% Min Torque 1 2015
INPUTS Filter AI1 1303 0.1 s 0.1 s Min Torque 2 2016
Minimum AI2 1304 20.0% 20.0% Max Torque 1 2017
Maximum AI2 1305 100.0% 100.0% Max Torque 2 2018
Filter AI2 1306 0.1 s 0.1 s

Sheet 1
ACH550 Parameter Settings List
HVAC Settings
Default Value
Ready Ready
Run Run
Fault (-1) Fault
d to be set unless delays

Output Freq Output Freq


0.0 Hz 0.0 Hz
50.0/60.0 Hz 50.0 Hz
4.0 mA 4.0 mA
20.0 mA 20.0 mA
0.1 s 0.1 s
Current Current
0.0 A 0.0 A
Defined by 0104 -
4.0 mA 4.0 mA
20.0 mA 20.0 mA
0.1 s 0.1 s
Not Sel Not sel
Open Open
0 0
Keypad Keypad
Not Sel Not sel
Not Sel Not sel
Done Done
DI4 Not sel
Not Sel Not sel
No No
Default Default

r normal set up

0 rpm 0 rpm
1500/1800 rpm 1500 rpm
1.1 * IN 9.9 A
Enable (Time) -
0.0 Hz 35 Hz
50.0/60.0 Hz 50 Hz
Min Torque 1 -
Max Torque 1 -
-300.0% -
-300.0% -
300.0% -
300.0% -

Sheet 1
ACH550 Parameter Settings List
Parameter Para HVAC Settings Parameter Para
Name Number Default Value Name Number
Group 21 Start Function 2101 Ramp - Group 31 Number Of Trails 3101
START/ Stop Function 2102 Coast - Automatic Trial Time 3102
STOP DC MAGN Time 2103 0.30 s - Reset Delay Time 3103
DC Hold Ctl 2104 Not Sel - AR Over Current 3104
DC Current Ref 2106 30% - AR Over Voltage 3105
DC Brake Time 2107 0.0 s - AR Under Voltage 3106
Start Inhibit 2108 Off - AR AI<Min 3107
Emerg Stop Sel 2109 Not Sel - AR External Fault 3108
Torq Boost Curr 2110 100% - Group 32
Start Delay 2113 0.00 s - Super- These setting are not required unless supervisin
Group 22 Acc/Dec 1/2 Sel 2201 Not Sel - vision various parameter via the output relays.
ACCEL/ Acceler Time 1 2202 30.0 s 5.0 s Group 33 Firmware 3301
DECEL Deceler Time 1 2203 30.0 s 5.0 s Infromation Loading Package 3302
Ramp Shape 1 2204 0.0 s - Test Date 3303
Acceler Time 2 2205 60.0 s - Drive Rating 3304
Deceler Time 2 2206 60.0 s - Parameter Table 3305
Ramp Shape 2 2207 0.0 s - Group 34 Signal 1 Param 3401
Emerg Dec Time 2208 1.0 s - Panel Signal 1 Min 3402
Ramp Input 0 2209 Not Sel - Display Signal 1 Max 3403
Group 23 Prop Gain 2301 10 - Output 1 DSP Form 3404
SPEED Integration Time 2302 2.50 s - Outpu 1 Unit 3405
CONTROL Derivation Time 2303 0 ms - Output 1 Min 3406
Acc Compensation 2304 0.00 s - Output 1 Max 3407
Autotune Run 2305 Off - Signal 2 Param 3408
Group 25 Signal 2 Min 3409
CRITICAL Settings not required unless resonance problems occur Signal 2 Max 3410
SPEEDS Output 2 DSP Form 3411
Group 26 Output 2 Unit 3412
MOTOR Setting in this group are not required Output 2 Min 3413
CONTOLS Output 2 Max 3414
Group 29 Signal 3 Param 3415
Maint- Settings in this group are not required Signal 3 Min 3416
Trigger Signal 3 Max 3417
Group 30 AI <Min Function 3001 Not Sel Fault Output 3 DSP Form 3418
Fault Panel comm Error 3002 Fault Fault Output 3 Unit 3419
Functions Mot Therm Prot 3005 Fault Fault Output 3 Min 3420
Stall Function 3010 Not Sel Fault Output 3 Max 3421
Stall Frequency 3011 20.0 Hz 20.0 Hz
Stall Time 3012 20 s 20 s
Earth Fault 3017 Enable Enable
AI1 Fault Limit 3021 0.0% 40.0%
AI2 Fault Limit 3022 0.0% 40.0%
Wiring Fault 3023 Enable Enable
CB Temp Fault 3024 1 Enable

Sheet 2
ACH550 Parameter Settings List
HVAC Settings
Default Value
5 3
30.0 s 30.0 s
6.0 s 6.0 s
Disable Disable
Enable Disable
Enable Enable
Enable Enable
Enable Enable

less supervising
relays.
Version 312B HEX
Version 1003 HEX
yy.ww 07.32
XXXY 8A84 HEX
Version 312 B HEX
Output Freq Output 1 Freq
0.0 Hz 0.0 Hz
500.0 Hz 500.0 Hz
Direct Direct
% %
0.0% 0.00%
1000.0% 1000.00%
Current PID 1 Setpoint
0.0 A 0 ppm
- 2000 ppm
Direct Direct
A ppm
0.0 A 0 ppm
- 2000 ppm
AI1 PID Feedback
0.0% 0 ppm
100.0% 2000 ppm
Direct Direct
V/mA ppm
0.0 v / 0.0 mA 0 ppm
10.0 v / 20.0 mA 2000 ppm

Sheet 2
Group 40 and 81 Settings
Parameter Para HVAC Settings Parameter Para
Name Number Default Value Name Number
Group 40 Gain 4001 2.5 1 Group 81 Reference Step 1 8103
Process Intergration Time 4002 3.0 s 5.0 s PFA Reference Step 2 8104
PID Set 1 Derivation Time 4003 0.0 s 0.0 s Control Reference Step 3 8105
PID Deriv Filter 4004 1.0 s 1.0 s Start Freq 1 8109
Error Value Invert 4005 No Yes Start Freq 2 8110
Units 4006 % ppm Start Freq 3 8111
Unit Scale 4007 1 0 Low Freq 1 8112
0% Value 4008 0.0% 0 ppm Low Freq 2 8113
100% Value 4009 100.0% 2000 ppm Low Freq3 8114
Set Point Select 4010 Kepad Internal Aux Mot Start D 8115
Internal Set Point 4011 40.0% 585 ppm Aux Mot Stop D 8116
Set Point Min 4012 0.0% 0.0% NR of Aux Mot 8117
Set Point Max 4013 100.0% 100.0% Auto Change Inter 8118
FBK Sel 4014 Act 1 Act1 Auto Change Lev 8119
FBK Multiplier 4015 Not Sel Not Sel Interlocks 8120
Act 1 Input 4016 AI2 AI2 Reg Bypass Ctrl 8121
Act 2 Input 4017 AI2 AI2 PFA Start Delay 8122
Act 1 Minimum 4018 0% 0% PFA Enable 8123
Act 1 Maximum 4019 100% 100% ACC In Aux Stop 8124
Act 2 Minimum 4020 0% 0% Dec In Aux Start 8125
Act 2 Maximum 4021 100% 100% Timed Auto Chng 8126
Sleep Selection 4022 Not Sel Not Sel Motors 8127
PID Sleep Level 4023 0.0 Hz 0.0 Hz Aux Start Order 8128
PID Sleep Delay 4024 60.0 s 60.0 s
Wake-Up Dev 4025 0.0% 0 ppm
Wake- Up Delay 4026 0.50 s 0.5 s
PID Param Set 4027 Set 1 Set 1
Group 40 and 81 Settings
HVAC Settings
Default Value
0.0%
0.0%
0.0%
50 Hz
50 Hz
50 Hz
25 Hz
25 Hz
25 Hz
5.0 s
3.0 s
1
Not Sel
50.0%
DI4
No
0.50 s
Active
Not Sel
Not Sel
Not Sel
2
Even Runtime