Altistart 22 soft start - soft stop units


Three-phase power supply voltage 230440 V

Connection to the motors power supply in line

1
M

Connection to the motors power supply in line

Motor power given in kW in accordance with standard IEC/EN 60947-4-2. 220 V control power supply on CL1, CL2 Motor Soft start - soft stop unit, 230440 V - 50/60 Hz Power indicated Factory Nominal Dissipated Dimensions Reference Weight on rating plate setting for current power at (W x D x H) current (IcL) nominal (In) (2) current (1) 230 V 400 V 440 V kg kW kW kW A A W mm
4 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 7.5 15 22 30 37 45 55 75 90 110 132 160 220 250 315 7.5 15 22 30 37 45 55 75 90 110 132 160 220 250 355 14.8 28.5 42 57 69 81 100 131 162 195 233 285 388 437 560 17 32 47 62 75 88 110 140 170 210 250 320 410 480 590 39 44 48 59 63 66 73 82 91 117 129 150 177 218 251 130 x 169 x 265 130 x 169 x 265 130 x 169 x 265 145 x 207 x 295 145 x 207 x 295 145 x 207 x 295 150 x 229 x 356 150 x 229 x 356 150 x 229 x 356 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 304 x 340 x 455 304 x 340 x 455 ATS 22D17Q ATS 22D32Q ATS 22D47Q ATS 22D62Q ATS 22D75Q ATS 22D88Q ATS 22C11Q ATS 22C14Q ATS 22C17Q ATS 22C21Q ATS 22C25Q ATS 22C32Q ATS 22C41Q ATS 22C48Q ATS 22C59Q 7.000 7.000 7.000 12.000 12.000 12.000 18.000 18.000 18.000 33.000 33.000 33.000 33.000 50.000 50.000

ATS 22D17ppp ATS 22D32ppp ATS 22D47ppp

Connection to the motors inside delta connection


Motor power given in kW in accordance with the standard IEC/EN 60947-4-2. 220 V control power supply Motor Soft start - soft stop unit, 230440 V - 50/60 Hz Power indicated Factory Nominal Dissipated Dimensions Reference Weight on rating plate setting for current power at (W x D x H) (4) current (IcL) nominal (In) (2) current (1) (3) 230 V 400 V 440 V kg kW kW kW A A W mm
5.5 11 18.5 22 30 37 45 55 75 90 110 132 160 220 250 11 22 45 55 55 75 90 110 132 160 220 250 315 355 400 15 22 45 55 75 75 90 110 132 160 220 250 355 400 500 14.8 28.5 42 57 69 81 100 131 162 195 233 285 388 437 560 17 32 47 62 75 88 110 140 170 210 250 320 410 480 590 39 44 48 59 63 66 73 82 91 117 129 150 177 218 251 130 x 169 x 265 130 x 169 x 265 130 x 169 x 265 145 x 207 x 295 145 x 207 x 295 145 x 207 x 295 150 x 229 x 356 150 x 229 x 356 150 x 229 x 356 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 304 x 340 x 455 304 x 340 x 455 ATS 22D17Q ATS 22D32Q ATS 22D47Q ATS 22D62Q ATS 22D75Q ATS 22D88Q ATS 22C11Q ATS 22C14Q ATS 22C17Q ATS 22C21Q ATS 22C25Q ATS 22C32Q ATS 22C41Q ATS 22C48Q ATS 22C59Q 7.000 7.000 7.000 12.000 12.000 12.000 18.000 18.000 18.000 33.000 33.000 33.000 33.000 50.000 50.000

M
Connection to the motors inside delta connection

ATS 22D62ppp ATS 22D75ppp ATS 22D88ppp

10
Presentation: page 60461/2

(1) In refers to the maximum continuous current for class 10. It equates to the nominal current of a standard 4-pole, 400 V, class 10 motor (standard application). (2) IcL refers to the starter rating. (3) In = motor current / 3. (4) Soft starters, when connected in an inside delta conguration, allow the use of motors of a larger size relative to the soft starters. In this conguration, the motors nominal current can be up to 1.5 IcL.

Combinations: page 60463/2 60462-EN.indd version: 3.0

References (continued)

Altistart 22 soft start - soft stop units


Three-phase power supply voltage 208600 V

Connection to the motor's power supply in line


Motor power given in kW in accordance with standard IEC/EN 60947-4-2. 220 V control power supply Motor Soft start - soft stop unit, 230600 V - 50/60 Hz Power indicated Factory Nominal Dissipated Dimensions Reference Weight on rating plate setting for current power at (W x D x H) current (IcL) nominal (In) (2) current (1) 230 V 400 V 440 V 500 V kW
4 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160

M
Connection to the motors power supply in line

kW
7.5 15 22 30 37 45 55 75 90 110 132 160 220 250 315

kW
7.5 15 22 30 37 45 55 75 90 110 132 160 220 250 355

kW
9 18.5 30 37 45 55 75 90 110 132 160 220 250 315 400

A
14 27 40 52 65 77 96 124 156 180 240 302 361 414 477

A
17 32 47 62 75 88 110 140 170 210 250 320 410 480 590

W
39 44 48 59 63 66 73 82 91 117 129 150 177 218 251

mm
130 x 169 x 265 130 x 169 x 265 130 x 169 x 265 145 x 207 x 295 145 x 207 x 295 145 x 207 x 295 150 x 229 x 356 150 x 229 x 356 150 x 229 x 356 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 304 x 340 x 455 304 x 340 x 455 ATS 22D17S6 ATS 22D32S6 ATS 22D47S6 ATS 22D62S6 ATS 22D75S6 ATS 22D88S6 ATS 22C11S6 ATS 22C14S6 ATS 22C17S6 ATS 22C21S6 ATS 22C25S6 ATS 22C32S6 ATS 22C41S6 ATS 22C48S6 ATS 22C59S6

kg
7.000 7.000 7.000 12.000 12.000 12.000 18.000 18.000 18.000 33.000 33.000 33.000 33.000 50.000 50.000

ATS 22C1pppp

Motor power given in HP. 110 V control power supply Motor Soft start - soft stop unit, 208600 V - 50/60 Hz Factory Nominal Dissipated Dimensions Power indicated on rating plate setting for current power at (W x D x H) current (IcL) nominal (In) (2) current (1) 208 V 230 V 460 V 575 V HP
3 7.5 15 20 25 30 40 50 60 75 100 125 150

5
Reference Weight

6
kg
ATS 22D17S6U ATS 22D32S6U ATS 22D47S6U ATS 22D62S6U ATS 22D75S6U ATS 22D88S6U ATS 22C11S6U ATS 22C14S6U ATS 22C17S6U ATS 22C21S6U ATS 22C25S6U ATS 22C32S6U ATS 22C41S6U ATS 22C48S6U ATS 22C59S6U 7.000 7.000 7.000 12.000 12.000 12.000 18.000 18.000 18.000 33.000 33.000 33.000 33.000 50.000 50.000

HP
5 10 15 20 25 30 40 50 60 75 100 125 150 200

HP
10 20 30 40 50 60 75 100 125 150 200 250 300 350 400

HP
15 25 40 50 60 75 100 125 150 200 250 300 350 400 500

A
14 27 40 52 65 77 96 124 156 180 240 302 361 414 477

A
17 32 47 62 75 88 110 140 170 210 250 320 410 480 590

W
39 44 48 59 63 66 73 82 91 117 129 150 177 218 251

mm
130 x 169 x 265 130 x 169 x 265 130 x 169 x 265 145 x 207 x 295 145 x 207 x 295 145 x 207 x 295 150 x 229 x 356 150 x 229 x 356 150 x 229 x 356 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 206 x 299 x 425 304 x 340 x 455 304 x 340 x 455

ATS 22C2pppp ATS 22C32ppp ATS 22C41ppp

9
ATS 22C48ppp ATS 22C59ppp (1) In refers to the maximum continuous current for class 10. It equates to the nominal current of a standard 4-pole, 400 V, class 10 motor (standard application). (2) IcL refers to the starter rating.

10
Presentation: page 60461/2 60462-EN.indd version: 3.0 Combinations: page 60463/2

References (continued)

Altistart 22 soft start - soft stop units


Options: Dialogue and conguration tools

SoMove setup software

1
SoMove setup software

Presentation This software enables the user to congure, set, debug and organize maintenance tasks for the Altistart 22 soft start - soft stop unit. It can also be used to customize the integrated display terminal menus. It can be downloaded from our website, www.schneider-electric.com. Reference
Description SoMove setup software USB/RJ45 cordset equipped with a USB connector and an RJ45 connector. For connecting a PC to the Altistart 22 soft start - soft stop unit. Length: 2.5 m For soft start soft stop units ATS 22 ATS 22 Reference TCSM CNAM 3M002P Weight kg 0.115

Remote display terminal


Presentation This terminal enables the human machine interface of the Altistart 22 soft start - soft stop unit to be positioned remotely on the door of a oor-standing enclosure. It has IP 54/NEMA 12 or IP 65 degree of protection depending on the model. It is used to: b Set and congure the soft start - soft stop unit remotely b Display the status and faults of the soft start - soft stop unit remotely Its maximum operating temperature is 50C. Please refer to our website at "www.schneider-electric.com" if the temperature exceeds this. Description 1 4-digit display 2 Selection/validation key ENT: opens a menu or validates the value chosen 3 Navigation keys , 4 Selection key ESC: used to exit a menu References
Description Degree of protection IP 54/NEMA 12 IP 65 Length m 1 3 Dimensions WxDxH mm 50 x 15 x 70 66 x 19 x 106 Reference Weight kg 0.250 0.275 0.050 0.150

5
4

1 2 3

VW3 G22 101

Remote display terminals A remote-mounting cordset is also required VW3 A1 104 Rpp Remote-mounting cordsets equipped with 2 RJ45 connectors

VW3 G22 101 VW3 G22 102 VW3 A1 104 R10 VW3 A1 104 R30

7
Modbus serial link (1) Programmable controller

Modbus serial link


Connection via splitter box and RJ45 connectors
Description Number 1 2 Length m 0.3 1 3 Modbus T-junction boxes (with integrated cable) 3 R = 120 C = 1 nf R = 120 (1) Cable depends on the type of controller or PLC (2) Sold in lots of 2 (3) Depends on the bus architecture 4 4 0.3 1 Unit reference LU9 GC3 VW3 A8 306 R03 VW3 A8 306 R10 VW3 A8 306 R30 VW3 A8 306 TF03 VW3 A8 306 TF10 VW3 A8 306 RC VW3 A8 306 R Weight kg 0.500 0.025 0.060 0.130 0.190 0.210 0.010 0.010

3 4 Modbus splitter box


with 10 RJ45 connectors Cordsets for Modbus serial link with 2 RJ45 connectors

4 2

ATS 22

Example of a connection using a Modbus serial link via a splitter box with RJ45 connectors

Line terminators (2) (3)

10
Presentation: page 60461/2 Combinations: page 60462/2 60462-EN.indd version: 3.0

References (continued)

Altistart 22 soft start - soft stop units


Options: Modbus serial link, fans, accessories and documentation

Fans
The ATS 22C21QC59Q, ATS 22C21S6C59S6 and ATS 22C21S6UC59S6U soft start - soft stop units come with an integrated fan. The ATS 22D17QC17Q, ATS 22D17S6C17QS6 and ATS 22D17S6UC17S6U soft start - soft stop units are ventilated by means of natural convection. For more demanding applications, such as those with a greater number of starts, the Altistart 22 range offers fans as an option. These are driven by the soft start - soft stop unit and attached to the back of the device. The fan's noise level is less than 60 dBA. References
Description VW3 G22 40p Fans Power supply voltage for control V 220 For soft start soft stop units Dimensions WxDxH mm ATS 22D17QD47Q, ATS 22D17S6D47S6 ATS 22D62QD88Q, ATS 22D62S6D88S6 ATS 22C11QC17Q, ATS 22C11S6C17S6 110 ATS 22D17S6UD47S6U ATS 22D62S6UD88S6U ATS 22C11S6UC17S6U 130 x 40 x 265 145 x 40 x 295 150 x 40 x 350 130 x 40 x 265 145 x 40 x 295 150 x 40 x 350 VW3 G22 400 VW3 G22 401 VW3 G22 402 VW3 G22 U400 VW3 G22 U401 VW3 G22 U402 Reference Weight

kg 1.200 1.400 1.600 1.200 1.400 1.600

Protection shrouds for power terminals (to be used with eyelet connections) The ATS 22C11QC59Q, ATS 22C11S6C59S6 and ATS 22C11S6UC59S6U soft start - soft stop units have 6 unprotected power terminals. These terminals can be tted with protection shrouds.
Description Set of 6 power terminal protection shrouds For soft start soft stop units ATS 22C11QC17Q, ATS 22C11S6C17S6, ATS 22C11S6UC17S6U ATS 22C21QC59Q, ATS 22C21S6C59S6, ATS 22C21S6UC59S6U Reference LA9 F702 Weight kg 0.250

LA9 F70p

LA9 F703 (1)

0.250

Documentation
Description Description of the Motion & Drives Offer DVD ROM It consists of: b Technical documentation (programming manuals, installation manuals, quick reference guides) b SoMove setup software b Brochures, catalogues. The documentation relating to the ATS 22 offer is also available on our website, www.schneider-electric.com. (1) To be used with M10 x 35 mm screws, not supplied. Reference VW3 A8 200 Weight kg 0.100

10
Presentation: page 60461/2 60462-EN.indd version: 3.0 Combinations: page 60463/2