55xx for Windows. Configuration for 5510 module.

Page 1 of 4
Configuration description
1 2 3 4 Filename - FROM MODULE Printed on 17/10/2012 03:25:25 p.m.

Module settings
Base module Module version Load control option fitted Multiset Communications (MSC) Link 5510 remote start module 8.04 Yes Extended functionality

Application settings
CANbus Enabled Gas engine enabled AC System Enable generator sequence alarm Phase sequence Generator VT(PT) Enabled Generator fitted Magnetic pickup fitted No No 3 phase, 3 wire Yes L1 L2 L3 No Yes Alternator poles 4 No

Miscellanous settings
Start button must be held down to crank Audible alarm prior to starting Number of start attempts Enable fast loading feature All warnings are latched Single list instrument display No No 3 Yes No No

Input settings
Low oil pressure input type High coolant temp input type Fuel level input type Digital Inputs 1 Generator closed auxiliary 2 Mains parallel mode 3 User configured Activation delay 4 Speed lower 5 Speed raise 6 User configured Activation delay 7 User configured Activation delay 8 User configured Activation delay 9 User configured Activation delay 0.0s 0.0s 0.0s 0.0s 0.0s Not used Not used Not used

Close to activate Close to activate Close to activate Active text : Close to activate Close to activate Close to activate Active text : Close to activate Active text : Close to activate Active text : Close to activate Active text : Shutdown Digital input 6 Electrical trip Digital input 7 Indication Digital input 8 Indication Digital input 9 Active from safety on Active from safety on Always active Never active Indication Digital input 3 Never active

Expansion input settings


P130 expansion enabled No

55xx for Windows. Configuration for 5510 module. Page 2 of 4


Configuration description
1 2 3 4 Filename - FROM MODULE Printed on 17/10/2012 03:25:25 p.m.

Output settings
Module relays 1 Energise 2 Energise 3 Energise 4 Energise 5 Energise Expansion Outputs A 1 Energise 2 Energise 3 Energise 4 Energise 5 Energise 6 Energise 7 Energise 8 Energise Expansion Outputs B 1 Energise 2 Energise 3 Energise 4 Energise 5 Energise 6 Energise 7 Energise 8 Energise Speed lower relay Speed raise relay Output not used Close generator Output not used Output Output Output Output Output Output Output Output Output Output Output Output Output Output Output Output not not not not not not not not not not not not not not not not used used used used used used used used used used used used used used used used

LED settings
1 2 3 4 Lit Lit Lit Lit Output Output Output Output not not not not used used used used

Timer settings
Starting timers Start delay Pre-heat Pre-heat bypass Sensor fail delay Cranking time Crank rest time Smoke limit Smoke limit off Safety on delay Overspeed overshoot Load timers Warming up time Breaker close pulse Breaker trip pulse 0s 0s 0m 2.0s 1m 6s 0s 0s 10s 0s 1s 5.0s 0.5s

Digital input 1 is assigned to generator auxiliary contact Gen fail to close 2.7s Gen fail to open 2.6s No digital input is assigned to mains auxiliary contact Return delay Cooling time ETS solenoid hold Fail to stop delay Other timers Batt low volts delay Batt high volts delay LCD auto scroll timer LCD page timer Reverse power alarm Generator transient delay Out of sync delay 30s 1m 0s 30s 1m 1m 2s 5m 2.0s 0.0s 0.2s

55xx for Windows. Configuration for 5510 module. Page 3 of 4


Configuration description
1 2 3 4 Filename - FROM MODULE Printed on 17/10/2012 03:25:25 p.m.

Mains decoupling
R.O.C.O.F. Vector shift Mains under voltage Mains over voltage Mains under frequency Mains over frequency Trip 0.20Hz/s 6.0 216V Ph-Ph 256V Ph-Ph 47.1 Hz 50.5 Hz Delay 0.7s 2.0s 0.1s 0.1s

Generator settings
Voltage and frequency settings Under volts trip Under volts pre-alarm Nominal generator voltage Over volts pre-alarm Over volts trip Under frequency trip Under frequency pre-alarm Nominal generator frequency Over frequency pre-alarm Over frequency trip Alternative voltage select Alternative frequency select Loading voltage Loading frequency Current settings CT primary CT secondary Generator full load rating Earth fault CT primary rating Delayed overcurrent Short circuit Earth fault Negative phase sequence Power settings Reverse power Synchronising ( auto sync ) settings Governor interface Action when on load AVR interface AVR output reversed Action when on load Enable ramping with P123 interface Synchronising ( check sync ) settings Enable synchronising Dead bus relay Check sync lower frequency Check sync upper frequency Check sync RMS voltage Check sync phase angle Fail to sync time Multi-set system settings MultiSet comms failure action Too few modules action Minimum modules on MultiSet comms link MultiSet comms alarms disabled action Starting options Balance engine hours Load level for less sets to run Load level for more sets to run Load control kW Load control mode Loss of excitation warning Loss of excitation trip Trip 9.5 kW Return Action Electrical trip Trip 139V Ph-Ph 192V Ph-Ph 240V Ph-Ph 285V Ph-Ph 309V Ph-Ph <Disabled> <Disabled> 60.0 Hz <Disabled> 66.9 Hz No No 212V Ph-Ph 45.0 Hz 400 A 5 A 298 A 600 A Trip 90% ( 268 A ) 150% ( 447 A ) 7% ( 31.3 A ) Curve/Multiplier 36 33 1000 Action Electrical trip Electrical trip Shutdown <Disabled> Return 212V Ph-Ph 271V Ph-Ph

230v norm / 115v alt 60Hz norm / 50Hz alt

Internal relays Adjust to nominal frequency Internal analogue No Adjust to nominal voltage No Yes 20V Ph-Ph -0.1 Hz 0.2 Hz 2.0V Ph-Ph 5 1m

Warning

Warning <Disabled> 1 <Disabled> Start sets as load requires <Disabled> 0% 100% None <Disabled> <Disabled>

55xx for Windows. Configuration for 5510 module. Page 4 of 4


Configuration description
1 2 3 4 Filename - FROM MODULE Printed on 17/10/2012 03:25:25 p.m.

Engine settings
Crank Crank Crank Crank disconnect disconnect on generator frequency disconnect on generator voltage disconnect on charge alternator Trip 10.9 Hz <Disabled> <Disabled> 0% Trip <Disabled> <Disabled> <Disabled> No Return

Speed settings Overspeed overshoot Plant battery settings Under volts warning Over volts warning Charge alternator warning Maintenance alarm settings Enable maintenance alarm

Exercise scheduler settings


Enable exercise scheduler No

Language settings
Default language User User User User defined defined defined defined language language language language 1 2 3 4 English (UK) Chinese (simplified) French (France) Spanish (International) Not used