Automatic Transfer Switch, 72x72 DIN Size

ATS-10
Automatic Transfer Switch 72 x 72 DIN Size

Description The ATS-10 provides the mains voltage monitoring and automatic transfer switching. In the event of a mains voltage failure, the remote start relay output is energized and the unit automatically transfers the load from the mains to the generator. Microprocessor technology allows exact measurement, set point adjustment and timing functions with the parameters to be simply programmed and displayed from the front panel. Operation The ATS-10 automatic transfer switch can detect failure of any phase of the mains supply. If at least one of the mains phase voltages goes outside set limits, the unit operates as follows: - The Mains Voltage Okay led turns from green to red. The mains contactor output is deenergized and the green Mains Contactor Closed led is extinguished. - The remote start output is energised after the Remote Start Delay parameter has expired. The generator start module receives this signal and initiates the engine start. - If the Unit Usage Type parameter (P00) is selected as 0 (Type-1); When the generator voltage is within set limits, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Engine Heating Period parameter is expired. After this time, the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter. If the Unit Usage Type parameter (P00) is selected as 1 (Type-2); When the Engine running signal is present, the yellow Generator Running led will illuminate. The unit will allow the generating set to run without load until the Load gen. signal is present. If this signal is present, the yellow Generator Contactor Closed led will start blinking and the unit wait for the Generator Contactor Delay parameter. - The generator contactor output will be energized and the yellow Generator Contactor Closed led will illuminate steadily when the Generator Contactor Delay parameter is expired. - If the mains voltage return to within limits, the Mains Voltage Okay led will turn to green and the unit waits for the Mains Return delay parameter for the mains voltage stabilization. - When the Mains Return Delay parameter is expired, the yellow Generator Contactor Closed led is extinguished and the generator contactor output is deenergized. Then the green Mains Contactor Closed led will start blinking and then the unit will wait for the Mains contactor Delay parameter. - When the Mains contactor Delay parameter is expired, the green Mains Contactor Closed led will illuminate steadily and the mains contactor output is energized. Then the remote start output is deenergized. - The unit is ready for a new mains failure. The ATS-10 has got a TEST mode feature. This mode allows the generating set to be tested without taking the load. This mode is also called Emergency backup mode which keeps the generating set running and makes a quick transfer if a mains failure occurs. In this mode, The remote start output will be energized but no load transfer will take place unless the occurrence of a mains failure. If a mains failure occurs, the load will be transferred to the generating set. If the mains voltage return to within limits and the Mains Return Delay parameter is expired, the load will be transferred to the mains, but the generating set will be kept running. The remote start output will only deenergized when the Test mode is cancelled.

Automatic Transfer Switch, 72x72 DIN Size


Specifications
Equipment Use Housing & Mounting Panel Cut-out Protection Weight Environmental Rating Operating / Storage Temperature Operating / Storage Humidity Installation Over Voltage Cat. Pollution Degree Mode of Operation EMC Electrical control equipment for generating sets 72mmx72mmx95mm (including connectors) DIN43700 plastic housing for panel mounting 69mmx69mm NEMA4X (IP65 at front panel, IP20 at rear side) Approximately 0.27 kg Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity -25C to +70C / -40C to +85C 90% max. (Non-condensing) II appliances, portable equipment II, Normal office or workplace, non-conductive pollution Continuous EN-61000-6-4, EMC generic emission standard for industrial equipment EN-61000-6-2, EMC generic immunity standard for industrial equipment Electrical Safety EN-61010-1, safety requirements for electrical equipment for measurement, control and laboratory use Battery Supply Voltage(Z) 8-32 VZ max. Operating current is 240 mA Generator Voltage Measurement 35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V Mains Voltage Measurement 35-300VL-NVRMS (@15.6-99.9 Hz). Accuracy: 1% FS. Resolution : 1V Cranking Dropouts Battery voltage can be 0VZ for max. 100msn during cranking (battery voltage should be at least nominal voltage before cranking) Contact Sensing Inputs Load Generator Signal (NO) Engine Running Signal (NO) Relay Outputs Remote Start Relay (1NO+1NC. 12A@32V Z) Mains Contactor Relay (1NC. 5A@250V V) Generator Contactor Relay (1NO. 5A@250V V) Display 4 Digits, 7 segments LED display showing : Mains Voltage (Phase-Phase and Phase-Neutral) Alternator Voltage. (If the Unit Usage Type parameter (P00) is selected as 0 (Type-1)) Program Parameters Status Indicators TEST Mode LED PROG Mode LED Mains Volgage Okay LED Generator Running LED Mains Contactor Closed LED Generator Contactor Closed LED

Automatic Transfer Switch, 72x72 DIN Size


Dimensions
Maximum 15mm / 0.590 inch
ATS-10

VL12

VL23

VL31

GEN V.

PROG
TEST

TEST

GEN-ATS

72mm

72mm

11.5mm / 0.452 inch

83.5 mm / 3.287 inch

Panel Cut-Out

69mm / 2.72 inch

69mm / 2.72 inch

Automatic Transfer Switch, 72x72 DIN Size


Front View Terminal Connections

ATS-10

VL12

VL23

VL31

GEN V.

MAINS N

GEN. L1

GEN. N

PROG
TEST

TEST
1
- BAT

12 A @220VV NO NC

P/N : ATS-10
ENGINE RUN. INPUT +

2
+ BAT

3
+ BAT OR - BAT

4
REMOTE START OUT

10

MAINS RELAY

12

13

14

15

16

17

18

19

C
11
LOAD GEN. INPUT +

ATS-10 Parameters List Type - 1 (P00 = 0): When Generator Voltage detected by ATS-10 Parameters List
No Definition of Parameter Min Max Default Unit

P00 Unit Usage Type P01 Mains Voltage Connection Level P02 Mains Voltage Disconnection Level P03 Mains Voltage Upper Limit P04 Mains Return Delay P05 Generator Contactor Delay P06 Mains Contactor Delay P07 Remote Start Delay P08 Engine Heating Period P09 Alternator Voltage Lower Limit P10 Alternator Voltage Upper Limit P11 Password

0 60 60 60 0 0.1 0.1 0 0 60 60 0

1 600 600 600 9999 25.0 25.0 9999 250 600 600 9999

0 320 300 440 30 1.0 1.0 0 10 320 440 0

VV VV VV sec sec sec sec sec VV VV

Type - 2 (P00 = 1): When Load Generator Logic Input detected by ATS-10 Parameters List
No Definition of Parameter Min Max Default Unit

P00 P01 P02 P03 P04 P05 P06 P07 P11

Unit Usage Type Mains Voltage Connection Level Mains Voltage Disconnection Level Mains Voltage Upper Limit Mains Return Delay Generator Contactor Delay Mains Contactor Delay Remote Start Delay Password

0 60 60 60 0 0.1 0.1 0 0

1 600 600 600 9999 25.0 25.0 9999 9999

1 320 300 440 30 1.0 1.0 0 0

VV VV VV sec sec sec sec

GEN. RELAY

2X5A @220VV

MAINS L1

MAINS L2

MAINS L3

Automatic Transfer Switch, 72x72 DIN Size


Three Phase Connection Schematic For Type - 1 (P00 = 0)
NOTE: If single phase sensing is required the single phase can be fed into all three phase inputs.
LOAD L3 L2 L1 N

MAINS CONTACTOR N L1 L2 L3 MAINS


12

GENERATOR CONTACTOR N L1 L2 L3 GENERATOR


16
MEASUREMENT CIRCUIT

FUSE-5

FUSE-4

FUSE-3

15

14

13

18

19

MEASUREMENT CIRCUIT

MAINS RELAY 5A@250VV

GEN. RELAY 5A@250VV

c
1

NO

12A@220VV NC

1
-BAT

2
+BAT

10
NOT CONNECTED

NOT CONNECTED

FUSE-1

+BAT OR -BAT

REMOTE START

c
1

BATTERY

BATTERY NEGATIVE MUST BE GROUNDED

Three Phase Connection Schematic For Type - 2 (P00 = 1)


NOTE: If single phase sensing is required the single phase can be fed into all three phase inputs.
MAINS CONTACTOR N L1 L2 L3 MAINS
12

LOAD L3 L2 L1 N

GENERATOR CONTACTOR N L1 L2 L3 GENERATOR


NOT CONNECTED

FUSE-5

FUSE-4

FUSE-3

15

14

13

18

19

FUSE-2

FUSE-2

17

11

17

16

MEASUREMENT CIRCUIT

MAINS RELAY 5A@250VV

GEN. RELAY 5A@250VV

c
1

NO

12A@220VV NC

1
-BAT

2
+BAT

5
ENGINE RUNNING INPUT OPTIONAL: USING FOR GEN. RUNNING LED

10

11
LOAD GENERATOR INPUT

FUSE-1

+BAT OR -BAT

REMOTE START

BATTERY

+BAT

c
1

BATTERY NEGATIVE MUST BE GROUNDED

The fuses should be as follows: 1A. T FUSE-1 FUSE-2, FUSE-3 1A. T FUSE-4, FUSE-5 1A. T 1- Connect the unit as shown in the appropriate diagram above. Be sure to connect the battery supply the right way round and battery negative should be grounded. The connectors can be unplugged from the rear of the unit to facilitate connection.

+BAT

Automatic Transfer Switch, 72x72 DIN Size


Easy Access Diagram to Programming Parameters

The Programming mode must be entered only while the mains voltage okay and the load supplied from mains. It is your responsibility if this equipment is used in a manner not specified in this instruction manual. Operation screen
F F F

PROG
TEST

PROG
TEST

PROG
TEST

When the button is pressed for 10 seconds, password is asked for accessing to the parameters.

Press button for accessing to the password entering screen Press the increment button. Operator password

Note: If Enter button is pressed and the password parameter is zero, pass screen is ignored and p 00 screen is shown.

PROG
TEST

PROG
TEST

PROG
TEST

Enter password with increment and decrement buttons.

Press the Enter button to confirm the password. If its correct, P00 is displayed. If the password is incorrect, the unit will drop out of program mode.

Press the increment button to access to the parameter value.

PROG
TEST

Press Enter button to confirm the changed value and access to the following parameter. On this way you can access to the all parameters.

Change the parameter value with increment and decrement buttons.

Note: If the PROG button is pressed or if no buttons are pressed for a period of 2 minutes, the unit will return to the normal operation screen.

Product Code
ATS-10 Automatic Transfer Switch, 72mmx72mmx95mm Size