ARABIA ELECTRIC LTD.

Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

1. General Information about the Relay:


Panel No. 7SA522 SIEMENS CT Ratio
Secondary Rated Current ( In )

1200 / 1 A 1 A 110 / 0.1 KV 100 V


Not Connected 110- 125 DCV

Relay Type Manufacturer SERIAL NO MLFB - No. Software Version Test Equipment

PT Ratio
Secondary Rated Voltage ( Un ) ( PH PH )

7SA522-4DB00-4QN4 4.61 OMICRON CMC 156

U4

Voltage Transformer is

DC. Auxiliary . Voltage

Frequency

Fn

60 Hz

2 . Mechanical Check and Visual Inspection


Item 1 2 3 Description Check the name plate data according to the drawings and specifications Check for transportation damage and correct positioning Verify tightness of all connections Remarks

3. Electrical Checks
Item 1 2 3 4 5 6 7 Description All connections checked according to the wiring diagram Auxiliary power supply checked for rating and polarity CT shorting checked Indications checked Casing earthing checked Contact earthing checked Contact resistance of tripping and alarm checked Remarks

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 1 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

4. General Functions in the Relay : Function


Phase Distance Protection Earth Distance Protection Power Swing Detection Teleprotection For Distance Protection DTT Direct Transfer Trip Instantaneous High Speed SOTF Over Current Week Infeed ( Trip & / Or Echo ) Back Up Over Current Protection Earth Fault Over Current Protection Teleprotection For Earth Fault Over Current Auto Reclose Function Synchronism & Voltage Check Fault Locator

Selected
Quadrilateral Quadrilateral Enabled PUTT ( Z1B acceleration )/ POTT / BLOCKING / Un BLOCKING Disabled Enabled Enabled Time Over Current Curve IEC Time Over Current Curve IEC Disabled Not Applicable in this type Not Applicable in this type Enabled

5. Power System Data :


OHL / UG Cable CT Star Point System Star point Line Length Line Angle
X = Line Reactance( / Km ) Zero Sequence Compensation Factors Under Ground Cable Line Towards Line

Solid Earthed Km 85

RE / RL XE / XL

Z1 = Z2----- Z5 = Z1 = Z2----- Z5 =

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 2 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

6. Secondary Injection Measurements :


Setting: * 1201=Distance * Protection = OFF.

We should insure that:


1 CT. & VT. Ratios are as setting in Power System Data 1 , Address ( 0203 ---0206 ) 2 From Setting Group A : Power System Data 2 , insure the value of % in : Address (1103 ) Measurement : Full Scale Voltage ( 100 % ) (1104 ) Measurement : Full Scale Current ( 100 % ) 3 The Direction of the Earthing is as per approved Drawings & as setting in Power System Data 1

( i ) If the direction of the Earthing is Towards the line ( Cable ): The Current is Lagging the Voltage by 45 ( As shown below )

V1 I1

= 57.73 V 0 = 1A - 45

V2 I2

= 57.73 V -120 = 1A -165

V3 I3

= 57.73 V +120 = 1A +75

( ii ) If the direction of the Earthing is Towards the Bus Bar: The Current is Leading the Voltage by 135 ( As shown below )

V1 = 57.73 V 0 I 1 = 1 A +135
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

V2 I2

= 57.73 V -120 = 1A

+15

V3 I3

= 57.73 V +120 = 1A

-105

Client: SEC - CSD Name: Signature: Date:


Page 3 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

90 135 I

0 180

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 4 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

-45 270

Injected quantities: * Inject 3 Phases Currents & Voltages.

( i ) The angle between I & V is ( 0 )


Phase - L1 57.73 V 0 1 A 0 Phase -L2 57.73 V -120 1A -120 Phase -L3 57.73 V +120 1A +120

( ii ) The angle between I & V is (- 45 )


L1 57.73 V 0 1 A -45 L2 57.73 V -120 1A -165 L3 57.73 V +120 1A +75

( iii ) The angle between I & V is ( +135 )


L1 57.73 V 0 1 A +135 siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

L2 57.73 V -120 1 A +15 Client: SEC - CSD Name: Signature: Date:


Page 5 of 55

L3 57.73 V +120 1A -105 Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Note : Print out from the Relay is Attached ( Primary & Secondary & % values )

Measured Values In The Relay

Parameters
Current Current Current

At angle 00
primary
secondary

At angle - 45o
primary
secondary

At angle + 135
primary
secondary

% values

% values

% values

IL1 IL2 IL3


3I0

I1 - positive Sequence
I2 - Negative Sequence Voltage UL1E Voltage UL2E Voltage UL3E Voltage UL12 Voltage UL21 Voltage UL31 3U0 U1 - positive Sequence U2 - Negative Sequence Apparent power(S) Active power(P) siemens Reactive power(Q) Frequency Name: Power Factor
Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 6 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Signature:

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

7. Impedance Secondary Measurements :

Note : Before starting this test , for easy calculation & to get correct readings In the relay configuration , Setting Group A , power system data 2
Address (1116-1119) : setting for Zero Sequence Compensation Factors
RE / RL =0 & XE / XL = 0 ,

Also Zero Sequence Compensation Factors in the Tester setting should be Zero

( I ) Inject the impedance ( Z ) = 6 Calculate :


R= Z x COS

with angle = 60 o ( in Forward Side )


, X= Z x SIN
( Primary & Secondary )

Then measure the impedance ( Z )

( II ) Inject the impedance ( Z ) = 6 with angle = 240 o ( in Reverse Side ) Calculate :


R= Z x COS ( Z ) , X= Z x SIN

Then measure the impedance Note :


[

( Primary & Secondary )

C.T ratio = 1200 / 1

&

V.T ratio = 110 / 0.1 K.V

= 1200

= 1100

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 7 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

110 / 13.8 K.V S/S The Primary measured values = Secondary measured values X [ V.T ratio /

AL- BAWADI

C.T ratio ]
= 0.92

Phase L1 - N L2 - N L3 - N L1 L2 L2 L3 L3 L1

Impedance RL1 XL1 RL2 XL2 RL3 XL3 RL12 XL12 RL23 XL23 RL31 XL31

Calculated

= 60o Measured Z
Primary Secondary

Calculated

= 240o Measured Z
Primary Secondary

Z 3 5.196 3 5.196 3 5.196 3 5.196 3 5.196 3 5.196

Z -3 -5.196 -3 -5.196 -3 -5.196 -3 -5.196 -3 -5.196 -3 -5.196

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 8 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

8- Distance protection pick up threshold ( Fault Detection Test ):


8.1- Phase Fault Current Threshold Detection ( I ph >

) Test

Address : ( 1202 )

*1201 : Distance Protection is = ON *1202 : Phase Current Threshold ( I ph > ) for Distance Measurement= 0.2A *1203 : 3Io Threshold for Neutral Current PickUp = 0.1A Note:* 3Io Earth Fault setting should be < I ph Phase Fault setting.
*You must inject voltage more than the setting voltage at Address ( 2913A ) : Maximum Voltage Threshold U < ( 3 Phase ) = 5V

Or ( 2915 )
& & ( 2910 ) ( 2901 )

: Voltage Failure supervision : Fuse Failure Monitoring : Measurement Supervision

= OFF = OFF = OFF

Then
*Inject Phase - Phase Current more than the setting at Address ( 1202 ) & Zero Voltage.
0 180

Also Note

:- Address No. ( 1209 ) : Criterion of Earth Fault Recognition


Not important if it is (3I0 OR 3U0) / (3I0 AND 3U0)

Phase

Phase Fault I ph > Setting (Address:1202) 0.2 A

Measurement (A) Pick Up (A) Drop Off (A)

L10 L2 180 L20 L3 180 L30 L1 180


inject voltage =0 )

>

the setting voltage at Address ( 2913A ) Or Fuse Failure=Off ( The Volt

&

I ph > Trip

Inject Phase - Phase Current more than the setting at Address ( 1202 )

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 9 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

8.2-Earth fault detection Test: 8.2.1- Earth Fault Current Threshold *1201 *1202 *1203 *1209 *1204 Note:-

( 3Io ) Detection

Address : ( 1202 )

: Distance Protection is = ON : Phase Current Threshold ( I ph > ) for Distance Measurement= 0.1A : 3Io Threshold for Neutral Current ( Earth Fault ) PickUp = 0.4A
: Criterion of Earth Fault Recognition should be selected as = ( 3I0 OR 3U0 )

: ( 3 VO )Threshold Zero Sequence Voltage pick up

=5V

1 - ( 3Io ) Threshold for Neutral Current ( earth fault ) PickUp setting ( Address:1203A ) should be above the phase fault setting (Address: 1202) 2 You must inject voltage more than the setting voltage at Address ( 2913A ): Maximum Voltage Threshold U < ( 3 Phase ) = 5V Or ( 2915 ) : Voltage Failure supervision = OFF & ( 2910 ) : Fuse Failure Monitoring = OFF & ( 2901 ) : Measurement Supervision = OFF
Then , Inject Phase Earth Fault Current (single phase current ) more than the setting at Address ( 1202 ) & more than the setting at Address ( 1203 ) & Zero Voltage.

Phase L1 - N L2 - N L3 - N
Note :

Earth Fault 3Io > (Neutral Current ) Setting (Address:1203) 0.4A

Measurement (A) Pick up (A) Drop off (A)

I ph > will operate ( Pick Up ) first, because the setting is less , but the Trip will be with 3Io value.

inject voltage

>

the setting voltage at Address ( 2913A ) Or Fuse Failure=Off ( The Volt =0 )

3Io & Trip

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 10 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Inject Phase - Earth Current more than the setting at Address ( 1203 )

8.1.2- Zero Sequence Voltage Threshold Check { 3 VO Detection }(Address 1204 ) * 1204 *1209A *1202 *1203 : (3 VO )Threshold Zero Sequence Voltage pick up

=5V

: Criterion of Earth Fault Recognition should be selected as = ( 3I0 AND 3U0 )

: Phase Current Threshold ( I ph > ) for Distance Measurement = 0.1A


= 0.4A = OFF = OFF = OFF ) Setting
)

: 3Io Threshold for Neutral Current ( Earth Fault ) PickUp Note : ( 2915 ) : Voltage Failure supervision & ( 2910 ) : Fuse Failure Monitoring & ( 2901 ) : Measurement Supervision Then 1 - Inject Phase Earth Fault Current (Single Phase Current ) more than ( 3I0
(Address 1203 ) and also more than Phase Current

( I ph > ) Setting (Address 1202


}

Inject 3-Phase Current = Rated Current = 1 A

2 - Inject 3 VO Zero Sequence Voltage V L1N = 6v, V L2N =10V, V L3 N =10V, Reduce slowly V L1N voltage till relay E/F element operates, then: take the pick up value of the relay by switching On & Off of fault & check the pick up value of distance relay.

Setting value of 3Vo (V)


5

Measured Pick Up value (V)

make Unbalance in 3

VO , Reduce slowly V L1N &

3 VO

Inject 3-Phase Current = Rated Current = 1 A

Trip

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 11 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

9- Zones reach & Time Testing (

Manual Check )

To test the ZONE Reach & Time , we adjust the ZONES from the relay Settings as following: Settings Device configuration : 0112 Phase Distance Quadrilateral 0113 Earth Distance Quadrilateral From Setting Group A : 0013 Distance zones (Quadrilateral ) Zone-Z1 1301 1302 1303 1304 1305 1306 1351 1352 1353 1354 1355 1356 1311 1312 1313 1314 1315 1316 Operating Mode Zone-1 R ( Z1 ) , Resistance for Ph- Ph Faults X ( Z1 ) , Reactance RE( Z1 ) , Resistance for Ph- E Faults T1-1 Phase , delay for single phase faults T1-multi Ph , delay for single phase faults Operating Mode Z1B( OverReach Zone ) R (Z1B ) , Resistance for Ph- Ph Faults X (Z1B) , Reactance RE(Z1B) , Resistance for Ph- E Faults T1B-1 Phase , delay for single phase faults T1B-multi Ph , delay for single phase faults Operating Mode Zone-2 R ( Z2 ) , Resistance for Ph- Ph Faults X ( Z2 ) , Reactance RE( Z2 ) , Resistance for Ph- E Faults T2-1 Phase , delay for single phase faults T2-multi Ph , delay for single phase faults Client: SEC - CSD Name: Signature: Date:
Page 12 of 55

Forward 1.0 2.5 1.0 0.0 Sec. 0.0 Sec. Forward 1.3 3.5 1.3 0.3 Sec. 0.3 Sec. Forward 2.0 5.0 2.0 0.5 Sec. 0.5 Sec. Consultant: Saudconsult Name:

Zone-Z1B

Zone-Z2

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation Zone-Z3 : SEC WRB : : 1321 1322 1323 1324 1325 1331 1332 1333 1334 1335 1341 1342 1343 1344 1345 1346 Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Operating Mode Zone-3 R ( Z3 ) , Resistance for Ph- Ph Faults X ( Z3 ) , Reactance RE( Z3 ) , Resistance for Ph- E Faults T3 delay Operating Mode Zone-4 R ( Z4 ) , Resistance for Ph- Ph Faults X ( Z4 ) , Reactance RE( Z4 ) , Resistance for Ph- E Faults T4 delay

Reverse
3.0 6.0 3.0 1.0 Sec.

Zone-Z4

Forward 5.0 10.0 5.0 1.5 Sec.

Zone-Z5

Operating Mode Zone-5 Non-Directional R ( Z5 ) , Resistance for Ph- Ph Faults 7.0 X ( Z5 ) +, Reactance for Forward direction 12.0 RE( Z5 ), Resistance for Ph- E Faults 7.0 T5 delay 2.5 Sec. X ( Z5 ) -, Reactance for Reverse direction 12.0

Note : In Reverse Zone , we can inject by the same angle of Forward , but
Inverse the Earthing in the Relay Or Inverse the direction of injection.

Test Procedure with OMCRON :


1- Distance Advanced Distance 2- Choose Shot Test . 3- Put the Points 4- Choose Add To 5 Choose ALL , Then OK.

We should insure from the Parameter


siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

that the Earthing is as the actual.


Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Client: SEC - CSD Name: Signature: Date:


Page 13 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S Fault Types

Settings
Impedance

Zones Z1

Time

Axis

Time
L1 - N L1 - N L1 - N L1 L2 L1 L2 L1 L2 L1 L2 L3
(m Sec. )

1 0 2.5 1.3 0.3 3.5 2 0.5 5 3 1 6 5 1.5 10 7 12 -7 -12

R0 X90

Z5 Forward Z4 Reverse Z3 Forward Z2 Forward Z1B Forward

R0 X90

R0 X90 R180 X270 R0 X90 R0 X90 R180 X270

Non Directional

2.5

Note : Zones reach & Time Testing (


siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Auto Check )
Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Client: SEC - CSD Name: Signature: Date:


Page 14 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : Contract No.:

AL- BAWADI 110 / 13.8 K.V See the Attached Print out from the Relay
:

S/S

10- Distance directionality check :


Note :1- If any Zone is adjusted to be Non-Directional , you must reverse it ( or adjusted it to be Inactive ) to be able to determine the Undefined Areas. 2 - You must Configure LEDs for Distance Pick Up Forward and Distance Pick Up Reverse.
Settings Device configuration : 0112 Phase Distance 0113 Earth Distance Quadrilateral Quadrilateral

From Setting Group A : 0013 Distance zones (Quadrilateral ) Zone-Z5 1341 Operating Mode Zone-5 Inactive From Masking I / O ( Configuration Matrix ) : LED13 = 3719 = Distance FORWARD LED14 = 3720 = Distance REVERSE

3 - The 3-Phase Fault Injection , 1- Phase Fault Injection & Ph-Ph Fault Injection Must Be same For All Types Of Faults.

Test Procedure with OMCRON :


Apply a constant value of the Impedance Z , and change the angle, Select the zone operating time as sufficiently long ( e.g. 22 Sec. ) so that the relay should not trip while rotating / changing the angle. 1- Distance Advanced Distance 2- Choose Check Test .
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 15 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S 3- Apply a constant value of the Impedance Z 4- Choose Sequence 5 Determine the Range you want to test & Determine the increment in the Angle.

Angels

Direction
Forward Un-defined Reverse Un-defined

Expected Angels From To 338 ( - 22 ) 120 150 300( - 60 ) 120 150 300 ( - 60 ) 338

Measured Angels From To

158

120
Undefiened

150

FORWARD

REVERSE
Undefiened

338

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 16 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S 300

11- Distance Teleprotection Schemes :


11.1. Permissive Under Reach ( Send Logics ( CS ) Z1 Fault

PUTT ) (Z1B Acceleration)

Instantaneous Trip with Z1 Time + CS

Trip Logic

Z1B Fault + CR Z1B Fault w/ o CR

Instantaneous Trip with Z1B Time w/ o CS Trip with Z2 Time w/ o CS


( Remote ) S / S Location of Fault

( Local ) S / S Location of Fault

Relay action
Inst. Trip with Z1 Time + CS Inst. Trip with Z1B Time Inst. Trip with Z1 Time + CS Trip with Z2 Time +No CS

Relay action
Inst. Trip with Z1 Time + CS Inst. Trip with Z1 Time + CS

Z1 Z1B Z1 Z1B W/O CR Z2 , Z3, Z4, Z5 + CR

Z1 Z1 Z1B

+ CR

Inst. Trip with Z1B Time

Trip with each Zone Time +No CS

CR Trip with Z3(reverse) Time Z3(reverse) W/O CR Trip with each Zone Time
Z3(reverse) W/O

Address No: 3850 BO for Distance Trip Z1B With Teleprotection Scheme 4006 BI for Distance Teleprotection Carrier reception channel 1 ( Carrier Receive ) LED 13 = Distance Teleprotection Carrier reception Signal
Client: SEC - CSD Name: Signature: Date:
Page 17 of 55

Settings: Specify the followings

4054
siemens Name: Signature: Date:

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

CSD DAR ENGINEERING AL FANAR

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

4056

( Carrier Receive ) LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send )

1 - From DIGSI Program : Settings Device Configuration , Choose the Scheme PUTT . Address No: 0121 : Teleprotection for Distance protection PUTT (Z1B Acceleration) 2 - Setting Group A : Address No: 0021 : Teleprotection for Distance protection 3 Choose Export , then OK 4 Save the File by any Name ( Rio File )

Test Procedure with OMCRON :


1- Distance Advanced Distance 2- Open Setting , then Choose Extended Zones Active to show ( Active ) Z1B. 3- Open the Saved File : From ( Parameters : Choose Test Object , then Inport )

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 18 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.2

Permissive Over Reach ( POTT )


Z1 Fault Z1B Fault + CR Z1B Fault w/ o CR Instantaneous Trip with Z1 Time + CS Instantaneous Trip with Z1B Time + CS Trip with Z2 Time Instantaneous Trip with Z1B Time + CS + CS

Send Logics ( CS )

Trip Logic

Z1B Fault + CR

( Local ) S / S Location of Fault

Relay action
Inst. Trip with Z1 Time + CS + CS Inst. Trip with Z1B Time + CS Inst. Trip with Z1 Time

( Remote ) S / S Location of Fault

Relay action
Inst. Trip with Z1 Time + CS Inst. Trip with Z1 Time + CS

Z1 Z1B Z1
Z1B W/O CR Z3(reverse) + CR Z2 , Z3, Z4, Z5

+ CR

Z1 Z1 Z1B
Z1B W/O

+ CR
CR

Inst. Trip with Z1B Time + CS Trip with Z3(reverse) Time

Trip with Z2 Time


Trip with Z3(reverse) Time

+ CS

Z3(reverse) + CR Z3(reverse) W/O

Trip with Z2 Time CR

+ CS

Trip with each Zone Time +No CS

Trip with each Zone Time

Note: If the Fault is in Z3 ( Reverse Zone ):


1- Z3 Fault ( Reverse ) + CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.,

The Trip will be Instantaneous . With Z1B Time

2- Z3 Fault ( Reverse ) W/O CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.,

The Trip will be with Z3( Reverse) Time.


3- Z3 Fault ( Reverse ) + CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.,
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 19 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

The Trip will be with the Time at Address : 2110A : Transient Block: Block
Transient after external fault = 500 m Sec.

Settings Address No: 3850 BO for Distance Trip Z1B With Tele Protection Scheme 4006 4054 BI for Distance Teleprotection Carrier reception channel 1 ( Carrier Received ) LED 13 = Distance Teleprotection Carrier Signal Received ( Carrier Received ) { LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send ) { LED 14 = ECHO Send Signal

4056 4246

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 20 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.2.1.

Weak Infeed Function ( with POTT Scheme ) Echo only

( ECHO only / ECHO And Trip ) Address No: 2501


11. 2.1.1.

Settings : Configure Address No: 00379 CB Auxiliary Contact 3 Pole Closed [CB. Close ] ( Binary Input ) 00380 CB Auxiliary Contact 3 Pole Open [CB. Open ] ( Binary Input )

Status
C.B off ( Open ) + Carrier Receive ( Z1B Fault ) C.B on ( Closed ) + Carrier Receive ( Z1B Fault )

Relay action should be


Echo Signal Send Immediately ( CS )
Echo Signal Send (CS ) after time delay Address No: (2502A) : ( 40 m Sec.) Trip / Echo Delay After Carrier Receipt.

Relay action

11. 2.1.2.

( Echo & Trip )


Relay action should be
Echo Signal Send Immediately ( CS ) Without Local Trip

Status
C.B off ( Open ) + Carrier Receive ( Z1B Fault ) C.B on ( Closed ) + Carrier Receive ( Z1B Fault )

Relay action

Local Trip & Echo Signal Send ( CS )


after time delay Address No: (2502A) : ( 40 m Sec.)
Client: SEC - CSD Name: Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Signature: Date:
Page 21 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V S/S Trip / Echo Delay After Carrier Receipt.

11. 2.1.3. Under Voltage Pick Up for Local Trip ( Weak Infeed Voltage ) Settings: Address No: ( 2502A ) : Trip / Echo Delay After Carrier Receipt. = 5 Sec. ( 2505 ) : Under Voltage ( Phase Earth ) = 25.0 V ( 1130A ) : Pole Open Current Threshold = 0.1 A

If we apply one Phase Voltage Setting in Address No: (2505 ) : Under Voltage ( Phase Earth ) and we apply the other two Phases Voltage by Normal value and inject one phase

Setting in Address No: ( 1130A ) : Pole Open Current Threshold = 0.1 A and the other two phases by Normal value.
current
All this with Carrier Receive then the relay will send an Echo and weak in feed Local Trip after the time of Address No: ( 2502A ) But if the one phase voltage is more than the Address No: ( 2505 ) the relay will send Echo Only after time of Address No: ( 2502A ) : Trip / Echo Delay After Carrier Receipt. = 5 Sec. Under Voltage ( PhE) Setting Value = 25 V
Address No: ( 2505)

Measured Voltage = Measured Time =

V Sec. A

( V )

Trip Time Delay for Local Trip

Setting Value = 5 Sec.


Address No: ( 2502A)

( Sec. )

Pole Open Current Threshold ( A )


siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Measured Current = Setting Value = 0.1 A Address No: ( 1130A)


Client: SEC - CSD Name: Signature: Date:
Page 22 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.2.2. Current Reversal Logic

( with POTT Scheme )

0021

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 23 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.3. Blocking Scheme Send Logics ( CS )

:
Instantaneous Trip with Z1B Time + CS Block , Trip with Z2 Time Instantaneous Trip with Z1B Time

Z3 Fault ( Reverse ) Or ( Undefined Zones ) Z1B Fault + CR

Trip Logic

Z1B Fault W/O CR

( Local ) S / S Location of Fault

Relay action
Inst. Trip with Z1 Time + CS + CS Inst. Trip with Z1B Time + CS Inst. Trip with Z1 Time

( Remote ) S / S Location of Fault

Relay action
Inst. Trip with Z1 Time + CS Inst. Trip with Z1 Time + CS

Z1 Z1B Z1
Z1B W/O Z3(reverse) CR

+ CR

Z1 Z1 Z1B
Z3(reverse) Z1B W/O

Trip with Z2 Time


CR

+ CS

+ CR w/o CR
CR

Inst. Trip with Z1B Time + CS Inst. Trip with Z1B Time

w/o

Inst. Trip with Z1B Time Trip with each Zone Time +No CS

Trip with Z2 Time CR

+ CS

Z2 , Z3, Z4, Z5

Z3(reverse) W/O

Trip with each Zone Time

Note: If the Fault is in Z3 ( Reverse Zone ):


1- Z3 Fault ( Reverse ) W/O CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.,

The Trip will be Instantaneous . With Z1B Time

2- Z3 Fault ( Reverse ) + CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.,

The Trip will be with Z3( Reverse) Time.


3- Z3 Fault ( Reverse ) W/O CR , & the Time is the Time at Address : 2109A: Transient Block: Duration external fault = 400 m Sec.& Z3 time
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 24 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

The Trip will be with the Time at Address : 2110A : Transient Block: Block
Transient after external fault = 500 m Sec.

Settings Address No: 3850 BO for Distance Trip Z1B With Tele Protection Scheme 4006 4054 BI for Distance Teleprotection Carrier reception channel 1 ( Carrier Received ) LED 13 = Distance Teleprotection Carrier Signal Received ( Carrier Received ) { LED 14 = Distance Teleprotection Carrier Send Signal ( Carrier Send )

4056

# 0021Current reversal logic WITH BLOCKING SCHEME: -

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 25 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.4. Unblocking Scheme

This Scheme is not related to any CR , Z1B is Active only with Binary Input ( From : Masking I / O ( Configuration Matrix )), use the Address No: 4030 Distance Teleprotection Unblocking :UNBLOCK Channel 1
Send Logics ( CS ) A Z1 Fault Z1B Fault + CR Z2-----Z5 W/O CR Z1B Fault W/O CR Instantaneous Trip with Z1 Time + CS Block , Trip with Z2 Time Trip with each Zone Time W/O CS Instantaneous Trip with Z1B Time

Trip Logic

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 26 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

11.5. Direct

Transfer Trip ( DDT )


Z1 Fault Z1B Fault + CR Instantaneous Trip with Z1 Time + CS Trip with Z1B Time

Send Logics ( CS ) Trip Logic From DIGSI Program :

0122 : DDT Direct Transfer Trip Enabled Setting Group A : 0022 : DDT Direct Transfer Trip Address No: 2201 : Direct Transfer Trip ( DDT ) ON 2202 : Trip Time Delay Sec.
From : Masking I / O ( Configuration Matrix ) , Configure the following:

Settings Device Configuration , Choose the Scheme Address No: 0121 : Teleprotection for Distance protection Disabled

0.01

Address No: 4417 4435

: Direct Transfer Trip INPUT 3 Ph - L123 ( Binary Input Carrier Received) : DDT Trip Command L123
( Binary Output Trip )

Also PUTT Scheme To Be Selected To SEND Signal In ZONE - 1.

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 27 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

12. Power Swing Detection

Address No:0120

Enabled

Setting Group A : 0020 : Power Swing

Address No:2007 :Trip Delay after Power Swing Blocking 5 Sec. ( Raise the Time Setting of Trip Delay after Power Swing Blocking Address No:2007 to more than the longest time of the Distance Zones ) Relay Action
No trip with Trip with No trip with Trip with No trip with Trip with

Power Swing Operating Mode Address No:2002 All zones Blocked Z1 , Z1B , Z2 Blocked Z1 , Z1B Blocked Z2 to Z5 Blocked

** When the Fault comes to the line , the Voltage will decrease Or the Current increase , then the Impedance will decrease in very short time , then the relay will trip according to the setting of the fault case. ** In the Power Swing case , the Impedance will decrease but in very short time , it will be decrease related with proper time for that decreasing, so the Power Swing depend on changing the Impedance with Time ( dZ / dt ). However , the time has to be proper with this changing ( Not very short when the Impedance will decrease ) , then the relay will Block all the Zones ( in case of chosen All zones Blocked in Address No:2002 )
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 28 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Test Procedure with OMCRON

Using ( State Sequencer ):

. Inject Normal Current & Normal Voltage - 1 ,( Then Decrease the Voltage by constant ( d / dt 2 [ (i.e.) Decrease the Impedance by ( dZ / dt ).]
3 -The Power Swing depend on changing the Impedance with Time( dZ/dt ) 4 -The Power Swing Impedance starts before Z5 by 5 5 When the Impedance enter the Polygon ,the Timer in Address No: 2007 : :Trip Delay after Power Swing Blocking 5 Sec. , Will Operate . ( i ) If the changing of the Impedance in the Polygon is slowly ,

then the relay will be Blocked by The Power Swing Function. ( ii ) If the changing of the Impedance in the Polygon is fastly and the Impedance is go out from the Polygon , then any Fault will make Trip.

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 29 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

13. Switch On To Fault ( SOTF ) Function Check :


13.1. Instantaneous High Speed SOTF-O/C

[ SOTF Separate Function ]

From Device Configuration :


Setting Group A :

Address No: 2401: Instantaneous High Speed SOTF-O/C is 2404: Iph Pick Up

Address No:0124 Address No:0024

Enabled

ON 2.5A

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 30 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Also : Disable the Distance Protection

Address No:1201 Disable Back Up Over Current Protection Address No:2601

Address No: 1201 : Distance Protection is 1232 : Instantaneous Trip after SOTF for Distance 2601 : Operating Mode for BackUp O/C

OFF Inactive OFF NO NO NO

2615 : Instantaneous Trip after SOTF for O/C I 2625 : Instantaneous Trip after SOTF for O/C I 2671 : Inst. Trip after SOTF for O/C Inverse Type

Also , From Setting Group A : Address No:0011 : Power System Data 2 ( Line Status )
Address No:1130 : Pole Open Current Threshold :1131A: Pole Open Voltage Threshold 0.1A 30 V

1132A: Seal in Time after All Closures

0.05 Sec.

:1133A: Minimal Time for Line Open before SOTF 0.25Sec.

1134 : Recognition of Line Closures with


(i)
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Manual Close Bi Only


Client: SEC - CSD Name: Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Signature: Date:
Page 31 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

(ii) Current flow OR Manual Close Bi (iii) Current OR Voltage OR Manual Close Bi (iv) CB aux. OR Current OR Manual Close Bi :1135: Reset of Trip Command (i) PickUP Reset
(ii)

With CB aux. Open & IPole Open Current (iii) With Pole Open Current Threshold Only :1136: Open Pole Detector (i)OFF

1150A: Seal in Time after Manual Closures

(ii)With CB aux. Open & IPole Open Current (iii)With measurement ( U/I , Trip , PickUp, CB aux.)

0.30Sec.

For C.B Closure Recognition Address No: (1134) : by Binary Input Manual Close Only Raise the Setting of Address No: ( 1150A ): Seal- in Time after Manual Closures
( This Time Controls the Time for Activation of BI:Manual Close ) Test Procedure :
From : Masking I / O ( Configuration Matrix ) , SOTF over current Configure the following:

# Instantaneous High Speed SOTF O/C has a private Trip ,


siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 32 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

So you must Configure Binary Output and any LED for it. Address No: (4295) :SOTF- O/C Trip Command L123 , # Also you can Configure Binary Output for SOTF-O/C Picked Up Address No: (4281): SOTF- O/C Picked Up for detecting Pick Up value ,but it is not important because the operation of SOTF is instantaneous. # Configure Binary Input for Manual Close Address No:00356 :Manual Close Signal # Configure Binary Input for C.B off Address No:00380:CB. Aux. Contact 3 Pole Open # Case No.( i ):
Inject Current more than the Setting in Address No: 2404: Iph Pick Up = 2.5A With activation of the Binary Inputs of C.B off & Manual Close .

The relay will Trip

Case No.( ii ): Inject Current more than the Setting in Address No: 2404:

Iph Pick Up = 2.5A Without activation of the Binary Inputs of C.B off & Manual Close .

The relay will Not Trip


Client: SEC - CSD Name: Signature: Date:
Page 33 of 55

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Case No.( iii ): Inject Current Less than the Setting in Address No: 2404:

Iph Pick Up = 2.5A With activation of the Binary Inputs of C.B off & Manual Close .

The relay will Not Trip


Setting in Address No: 2404 ( A )

Injected Current ( A ) 2.7 2.7 2.0

Measured Trip Time (m Sec)

Case No.( i ) Case No.( ii ) Case No.( iii )

2.5 2.5 2.5

No Trip No Trip

Note :
Address No: 1130 : Pole Open Current Threshold 1133A: Minimal Time for Line Open before SOTF 0.1A 0.25Sec.

1132A: Seal in Time after All Closures

2 Sec.

Instead of using Binary Input : CB. Manual Close , we can Inject Current Less Than the Current in Address No: 1130 for a period of time =250 mSec ,

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 34 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

So , the relay will know that the CB. of the Feeder as it is Opened ( OFF ), also the Time in Address No: 1132A , helping in Monitoring the Increase in Current after CB. is Closed ( ON ), If During that time 250 mSec , the Current Increased More than the Current in Address No: 1130 , Then the relay will be Tripe By SOTF Function. Hence , we can make this Test as following :
1134 : Recognition of Line Closures with(Current flow OR Manual Close Bi)

Using State Sequencer in OMICRON as following :


( 1 )1st State , Inject Normal Current (1 A ) & Voltage (57.73 V ) & Voltage Values for a period of time more than 250 mSec. ( 2 ) 2nd State , Inject Normal Current(1 A ) & Voltage (57.73 V ) Values for a period of time less than 2 Sec. ( 3 )3rd State , Inject a Current higher than the Current in Address No:

2404 : Iph Pick Up = 2.5A ,

& Normal Voltage Value( 57.73 V ) for a period of time less than 2 Sec. Then

The relay will Trip by SOTF Function

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 35 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

A 2 s 2 ms 250 *

A 2 s 2 ms 250 *

A 2 s 2 ms 250 * 9.1- SOTF associated with distance protection


B) SOTF WITH DISTANCE PROTECTION: (1232 = ZONE PICK UP )

ADDRESS NO1232 Dis. = ON ADDRESS NO1201 SOTF WITH Dis. = ON SOTF WITH Z1 T W/O SOTF = (Manual close)T WITH SOTF = (Current flow )T WITH SOTF SOTF WITH Z1B T W/O SOTF = (Manual close)T WITH SOTF = (Current flow )T WITH SOTF= SOTF WITH Z2 T W/O SOTF = (Manual close)T WITH SOTF = (Current flow )T WITH SOTF= SOTF WITH Z3 T W/O SOTF = (Manual close)T WITH SOTF = (Current flow )T WITH SOTF SOTF WITH Z4 T W/O SOTF = (Manual close)T WITH SOTF = (Current flow )T WITH SOTF
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Sec Sec = Sec Sec Sec Sec Sec Sec Sec Sec = Sec Sec = Sec
Consultant: Saudconsult Name: Signature: Date:

Sec

Sec

Client: SEC - CSD Name: Signature: Date:


Page 36 of 55

ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Note:-LED: SOTF P/U. -BI: MANUAL CLOSED -BO: GENERAL TRIP OR SOTF. -MAKE FAULT WITH ALL -NO SOTF TRIP LED WILL GLOW . BUT ZONE TRIP TIME WILL BE BYPASSED) Disable the back up over current protection add ( 2601 ) Disable the instantaneous high speed SOTF O/C add ( 2404 ) According to the specified zone that with instantaneous trip after SOTF is active add (1232 ) For with zone Z1B Inject Z in this zone twice one with the activation of the binary inputs of C.B off and manual close and the other without them Applied fault in zone Z1B Z1B Z2 Z3 Z4 Z5 measured time (s)

with the activation of the binary inputs of C.B off and manual close without the activation of the binary inputs of C.B off and manual close with the activation of the binary inputs of C.B off and manual close

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 37 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

9.2- SOTF associated with back up over current 2) SWITCH ON TO FAULT (SOTF)
A) SOTF WITH BACKUP O/C:

ADDRESS NO2615 O/C I> = ON ADDRESS NO2625 O/C I>> = ON ADDRESS NO2671 O/C Ip = ON ADDRESS NO2601 SOTF WITH O/C = ON AD 2625 SOTF WITH ( I >>) T W/O SOTF = = Sec Sec Sec Sec Sec Sec = Sec Sec Sec

I set = .

(Manual close)T WITH SOTF =

T set = (Current flow )T WITH SOTF AD 2615 SOTF WITH ( I >)

T W/O SOTF = =

I set = . T set = AD 2617

(Manual close)T WITH SOTF (Current flow )T WITH SOTF =

SOTF WITH ( Ip)

T W/O SOTF = =

I set = (Manual close)T WITH SOTF TMS =

(Current flow )T WITH SOTF

Note:-LED: SOTF P/U. -BI: MANUAL CLOSED. -MAKE FAULT WITH ALL TYPE OF O/C. -CHECK THE SEAL-IN TIME SETTING FOR MANUAL CLOSE Disable the distance protection add ( 1201 )
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 38 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S Disable the instantaneous high speed SOTF O/C add ( 2404 ) Inject current more than the setting {Iph >> pick up add ( 2610 )} twice one with the activation of the binary inputs of C.B off and manual close and the other without them. Repeat that with {Iph > pick up add ( 2620)} and {Iph > pick up add ( 2640)} Setting of all definite stages is 1A and 0.5 sec Setting of inverse stage is 0.5 A and 0.1 sec long inverse address Iph >> pickup add ( 2610) Iph > pick up add ( 2620) Ip > pick up add ( 2640) with the activation of the binary inputs of C.B off and manual close without the activation of the binary inputs of C.B off and manual close with the activation of the binary inputs of C.B off and manual close without the activation of the binary inputs of C.B off and manual close with the activation of the binary inputs of C.B off and manual close without the activation of the binary inputs of C.B off and manual close Setting (A) 1 1 1 1 1 1 Injected current (A) 1.5 1.5 1.5 1.5 2 2 measured time (msec)

Note : when you test any one of current stages you should raise the pick up setting of the others stages

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 39 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

10- Fuse failure monitoring


9. FUSE FAIL MONITOR:( 2910) . .. .. .. (A)FUSE FAILURE MONITORING FUNCTION (3Io & 3Vo (B)VOLTAGE ABSENT MONITORING FUNCTION (3 phase voltages ( C)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & I D)BROKEN CONDUCTOR

Note:- LED 14 = FUSE FAILURE=169, -LED: DISTANCE BLOCK. -INJECTION VOLTAGE LESS THAN(2913A)-MAX. VOLTAGE THRESHOLD V)>3PHASES) -DISTANCE WILL BLOCK AFTER TIME (2916A) DELAY TIME VOLTAGE FAILURE SUPERVISION. -APPLY FAULT AT ANY ZONE (Z1.Z5)BEFORE TIME (2916A)THE RELAY SHOULD OPERATE. -2916A=0 SECS. -A) 1 PHASE SETTING = 30V, Vrn = 31v,Vyn=Vbn=60V, 3 PHASE CURRENT = 0.5A. SLOWLY DECREASE RN VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS 406 * 3( . Vo>(AD2911A 3( Io<(AD2912A * .3 Vo 3Io

= 0 3 Io 1- S 10
Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 40 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S . 3 Io 3 Vo 2- S 10 B) 3 PHASE SETTING = 5V, DISTANCE BLOCKED SPONTANEOUS INDICATION APPEARS ON FUSE FAILURE OPERATION. LED 14 = FUSE FAILURE=168, 2916A=0 SECS, Vrn = Vyn=Vbn=6V, 3 PHASE CURRENT = 0.5A. SLOWLYDECREASE 3 PHASE VOLTAGE & CHECK AT WHICH VOLTAGE FUSE FAIL LED APPEARS 408 * CB (( AD1130A * 3(( V=5 )AD1130A ( . AD1135) . 9. FUSE FAIL MONITOR:( 2910) C)FUSE FAILURE MONITORING FUNCTION (3 phase voltages & I) 407 * ( AD2913A)( AD2915= OFF) * (AD2914A) . V * (AD2913A=5V) STAT1 . (AD2914A=0.2A) STAT2 L1 I=0.9 L2 I=0.9 L3 I=0.9 V=5 V=5 V=5

L1 I=1 L2 I=1 L3 I=1

V=30 V=30 V=30

*
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 41 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S For voltage fail supervision add (2915) is with current supervision Note: before starting the test you must specify Leds to failure voltage absent add (168) And V.T fuse failure alarm instantaneous add (170) and V.T fuse failure alarm> 10sec add (169) and distance is blocked add (3652) also you may specify a binary output for V.T fuse failure alarm> 10sec add (169) and distance is blocked add (3652) to be able measuring the time all of that can be done from the Masking in distance general and measurement supervision. 10.1- For balanced load If the current is balanced in the 3 phase and its amplitude is more than the setting {maximum current threshold I< add (2912A)} and the voltage difference in between any two phases is more than the setting {minimum voltage threshold U> add (2911A)}, the fuse failure monitor FFM will appear instantaneously with distance blocking. 10.1- Fuse failure measurement add (2911A) Injected current in 3- phase = .2 A minimum voltage threshold U> add (2911A) setting 30 V Pick up voltage (V) R S T 57.73 57.73 57.73 57.73 57.73 57.73 FFM and distance block appear inst.

10-2- For current less than the setting of Maximum current threshold I< add (2912A) and zero voltage appear for more than the setting (add.2911) FFM will appear after 10 sec with distance blocking.

10.3- maximum voltage threshold U< ( 3 phase ) add (2913A)

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 42 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S -You can check that with applying the normal voltage 3 phase and 3- phase current above the setting of {open pole threshold add ( 1130A ) } and the voltage is reduced in the 3- phase to less than the setting { maximum voltage threshold U< ( 3 phase ) add (2913A)} a voltage absent will appear after a time delay setting {delay voltage failure supervision add (2916A)}. Injected current = .2 A

10.4 When VT mcb is off distance is blocked


8. ZONE 1:
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

VT MCB TRIP :(00361) power syst.Data2:WITH OUT VT MCB TRIP : Distance trip .
Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Client: SEC - CSD Name: Signature: Date:


Page 43 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : Contract No.:

AL- BAWADI WITH VT MCB TRIP


:

110 / 13.8 K.V S/S : Distance blocked (O/C trip) : Distance trip : Distance blocked (O/C trip) : Distance trip : Distance blocked (O/C trip) : Distance trip : Distance blocked (O/C trip) : Distance trip : Distance blocked (O/C trip) : Distance trip : Distance blocked (O/C trip)

.. . .. . .. . .. . .. . ..

ZONE 1B ZONE 2: ZONE 3: ZONE 4: ZONE 5:

WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP WITH OUT VT MCB TRIP WITH VT MCB TRIP

Note:-LED: FAILURE FEEDER VT MCB TRIP.(AD3615) -BI: FAILURE FEEDER VT MCB TRIP.(AD3615) -LED: Distance Blook (AD3652) - MAKE FAULT WITH ALL ZONES WITH AND WITHOUT (BI) -DISTANCE PROTECTION WILL BLOCK. - MAKE O/C = ON

11- Fault locator


Line length = 6 Km Injected impedance
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

x = 0.1526 / km R-N 1.526 Y-N 1.526 B-N 1.526

Q=900 R-Y 1.526 Y-B 1.526 B-R 1.526

Client: SEC - CSD Name: Signature: Date:


Page 44 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

Relay reading (Km)

AL- BAWADI km

110 / 13.8 K.V S/S km km

km

km

km

12- Memory test 12.1 Memory time measurement test


Sequence-1 Time =2sec Va 57.73 180 Vb 57.73 60 Vc 57.73 300 Ia 0.2 0 Ib 0.2 -120 Ic 0.2 12 0 Sequence-2 Time was changed Va 0 --Vb 0 ---Vc 0 -Ia 0 -Ib 0 -Ic 0 --Va 0 --Sequence-3 Time =0.5sec Vb 0 --Vc 0 --Ia 1 0 Ib 1 -120 Ic 1 120

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 45 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant : SEC WRB : Contract No.:

Substation : AL- BAWADI Memory time measurement = sec

110 / 13.8 K.V

S/S

12.2 Memory voltage measurement test


Sequence-1
Voltage for this fault was changed Va 57.73 180 Vb 57.73 60 Vc 57.73 300 Ia 0.2 0 Ib 0.2 -120 V Ic 0.2 12 0 Va 0 ---

Sequence-2
Time =1sec Vb 0 ---Vc 0 -Ia 0 -Ib 0 -Ic 0 ---

Sequence-3
Time =0.5sec Va 0 --Vb 0 --Vc 0 --Ia 1 0 Ib 1 -120 Ic 1 120

Memory voltage measurement =

8- Back Up Over Current Protection: (Emergency)


Note: while testing any stage of over current you have to raise the setting of the other stages. 8.1- Inverse over current 8.1.1- For IEC curve add (2660) is normal curve
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 46 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Setting: Time

Ip > pick up add (2640) = 0.5 A R-Y Y-B 1A 2 A 2 B-R 1A A Calculated time ( sec ) 2.0 sec for T= 0.2 0.5 sec for T= 0.1 0.2 sec for T= 0.05

Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec

1A 2 A

3 A

3 A

3 A

T = 0.14TP / {( I/IP )0.02 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

Setting: 3I0p pick up add (2650) = 0.5 A R-N Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Y-N 1A 2 A

B-N 1A 2 A

1A 2 A

Calculated time ( sec ) 2.0 sec for T= 0.2 0.5 sec for

Client: SEC - CSD Name: Signature: Date:


Page 47 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI 110 / 13.8 K.V S/S Measured time sec Inj. Current = 6 Ip = 3 A 3 A 3 A Measured time sec T = 0.14TP / {( I/IP )0.02 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

3 A

T= 0.1 0.2 sec for T= 0.05

8.1.2-For IEC curve add (2660) is very inverse curve Setting: Ip > pick up add (2640) = 0.5 A R-Y 1A 2 A Y-B 1A 2 A 2 B-R 1A A Calculated time sec 2.7 sec for T= 0.2 0.43 sec for T= 0.1 0.135 sec for T= 0.05

Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec

3 A

3 A

3 A

T = 13.5 TP / {( I/IP ) 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT Setting: 3I0p pick up add (2650) = 0.5 A R-N Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Y-N 1A 2 A

B-N 1A 2 A

1A 2 A

3 A

3 A

3 A

Calculated time sec 2.7 sec for T= 0.2 0.43 sec for T= 0.1 0.135 sec for

Client: SEC - CSD Name: Signature: Date:


Page 48 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

Measured time

AL- BAWADI sec

110 / 13.8 K.V

S/S T= 0.05

T = 13.5 TP / {( I/IP ) 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT 8.1.3- For IEC curve add (2660) is extremely curve Setting: Time Ip > pick up add (2640) = 0.5 A R-Y Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec 1A 2 A Y-B 1A 2 A 2 B-R 1A A Calculated time sec 5.3 sec for T= 0.2 0.53 sec for T= 0.1 0.114 sec for T= 0.05

3 A

3 A

3 A

T = 80 TP / {( I/IP )2 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT Setting: 3I0p pick up add (2650) = 0.5 A Time R-N Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Y-N 1A 2 A

B-N 1A 2 A

1A 2 A

3 A

3 A

3 A

Calculated time sec 5.3 sec for T= 0.2 0.53 sec for T= 0.1 0.114 sec for T= 0.05

Client: SEC - CSD Name: Signature: Date:


Page 49 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

T = 80 TP / {( I/IP )2 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT 8.1.4- For IEC curve add (2660) is long inverse Setting: Ip > pick up add (2640) = 0.5 A Time R-Y Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec 1A 2 A

Y-B 1A 2 A

B-R 1A 2 A

3 A

3 A

3 A

Calculated time sec 24sec for T= 0.2 4 sec for T= 0.1 1.2 sec for T= 0.05

T = 120TP / {( I/IP ) 1} (SEC), WHERE: T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT Setting: 3I0p pick up add (2650) = 0.5 A Time R-N Inj. Current = 2 Ip = 1A Measured time sec Inj. Current = 4 Ip = 2 A Measured time sec Inj. Current = 6 Ip = 3 A Measured time sec T = 120TP / {( I/IP ) 1}
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Y-N 1A 2 A

B-N 1A 2 A

1A 2 A

3 A WHERE:

3 A

3 A

Calculated time sec 24sec for T= 0.2 4 sec for T= 0.1 1.2 sec for T= 0.05

(SEC),

Client: SEC - CSD Name: Signature: Date:


Page 50 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

T : TRIP TIME TP : SETTING VALUE TIME MULTPLIER IP : SETTING VALUE CURRENT I : FAULT CURRENT

8.2- low set stage I > Setting: Iph > pick up add (2620) = 1 A, Iph > Phase R-Y Y-B B-R Pick Up Setting Measured 1 1 1

T Iph > time delay add(2621) = 0.5 sec Drop Off Calculated Measured Operating Time (s) for 1.5 A Setting Measured 0.5 T 3I0 > time delay add(2623) = 0.5 Time sec Setting Measured
Consultant: Saudconsult Name: Signature: Date:
ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

Setting : 3I0 > pick up add (2622) = 1 A, Injected current A R-N


siemens Y-N Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

sec

B-N

1.5 1.5 1.5

Client: SEC - CSD 0.5 Name: Signature: Date:


Page 51 of 55

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

8.3- high set stage I >> Setting: Iph >> pick up add (2610) = 1 A, Injected current A Setting R-Y Y-B B-R 1.5 1.5 1.5 0.5 T Iph >> time delay add(2611) = 0.5 sec Time sec Measured

Setting : 3I0 >> pick up add (2612) = 1 A, Injected current A

T 3I0 >> time delay add(2613) = 0.5 sec Time sec Measured

Setting R-N Y-N B-N 1.5 1.5 1.5 0.5

2.4- I- STUB
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 52 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

Note: you must specify a binary input active low for { Enable I- STUB bus function add (7131)} and binary output and led for { O/C I- STUB TRIP add (7235)}. Setting: Iph > STUB pick up add (2630) = 1 A, T Iph time delay add (2631) = 0.5 sec

Injected current A Setting R-Y Y-B B-R 1.5 1.5 1.5 0.5

Time sec Measured

Setting : 3I0 > STUB pick up add (2632) = 1 A, T 3I0 STUB time delay add(2633) = 0.5 sec Injected current A Setting R-N Y-N B-N 1.5 1.5 1.5 0.5 Time sec Measured

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 53 of 55

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

. Annunciation
.1. LEDs

LEDS
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11 LED12 LED13 LED14 Pickup Pickup Pickup Pickup

Description
Distance Distance Distance Distance Zone 1 Trip Zone 1B Trip Zone 2 Trip Phase L1 ( Phase L2 ( Phase L3 ( Neutral ( ( Forward ) ( Forward ) ( Forward ) Start ) Start ) Start ) Start )

Checked

Zone 3 Trip ( Reverse ) Zone 4 Trip ( Forward ) Zone 5 Trip ( Forward )

5.2. Binary Out Puts


Annunciation Contact R1 R2 R3 R4 R5 R6 R7 R8 R9
siemens Name: Signature: Date:
CSD DAR ENGINEERING AL FANAR

Description Trip Trip Start Start Trip Trip Trip Start Watchdog
Client: SEC - CSD Name: Signature: Date:
Page 54 of 55

Checked

Consultant: Saudconsult Name: Signature: Date:


ENGR. / SAFWAT SAAD AHMED ( 0563683052 )

ARABIA ELECTRIC LTD. Equipment

Distance Protection Relay Type 7SA522 Installation, Testing and Commissioning Site Report
Customer Consultant Substation : SEC WRB : : Contract No.:

AL- BAWADI

110 / 13.8 K.V

S/S

5.3. All Binary Inputs Checked.

siemens Name: Signature: Date:


CSD DAR ENGINEERING AL FANAR

Client: SEC - CSD Name: Signature: Date:


Page 55 of 55

Consultant: Saudconsult Name: Signature: Date: