UNDERGROUND CONSTRUCTION MANUAL

HV SWITCHGEAR
Back to MAIN INDEX Go to SECTION INDEX

CONSTRUCTION

DESCRIPTION

DWG 5229/1 5229/2 5229/3

CONSTRUCTION

DESCRIPTION ABB 11kV Safelink - HV switchgear schematic ABB 11kV Safelink - HV switchgear schematic ABB 11kV Safeplus / Safering - Material ABB 11kV Safeplus / Safering Construction

DWG 5237/1 5237/2 5238/1 5238/2

Construction code guide - 11kV Ring main unit Construction code guide - Foundation & site finish Construction code guide - 22kV Ring main unit

RING MAIN UNIT Ring main unit installation Ring main unit installation Ring main unit installation Ring main unit installation Location in council parklands Location in council parklands Location in residential allotments Site preperation sloping site Maximum cut & fill Outdoor RMU with precast concrete fdn Site finish concrete suround 11RMU/ASL Culvert Foundation details - Material Culvert Foundation details - Construction 11RMU/O/ASL2S1F ABB 11kV ring main unit Safelink - Material 11RMU/O/ASL2S2F ABB 11kV ring main unit Safelink 11RMU/O/ASL3S Construction 11RMU/O/ASL3S1F 11RMU/O/ASL4S 5255/1 5255/2 5255/3 5255/4 22RMU/O/FGA2S1F 5234/1 5234/2 5233 5230 22RMU/O/FGA2S2F 22RMU/O/FGA3S 22RMU/O/FGA3S1F 22RMU/O/FGA4S 22RMU/O/FGA1S1CB1F 22RMU/O/FGA1S1CB2F 22RMU/O/FGA2S1CB 5217

ABB 11kV Safeplus / Safering HV switchgear schematic F & G 22kV ring main unit - Material F & G 22kV ring main unit - Construction

5253/1

5243/1 5243/2

F & G 22kV ring main unit - Schematic F & G 22kV ring main unit - Schematic F & G 22kV ring main unit - Schematic

5252/1 5252/2 5252/3

5232/1 5232/2 5236/1 5236/2

ORIGINAL ISSUE

APPROVED

C. Noel 31/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR INDEX

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

FILE: 5 62 5254 1

Dwg

Sh

Alignment
F

Fall FOOTPATH Reinforced concrete surround slab cast around plinth

3000

Fall
F
F

A _
F

Fall
F

PLAN
Refer Note 7 B _ Pre-cast foundation

100 Min.

Ground Line

50

Backfill Cable Pit Refer note 1.

SECTION

A _

Earth grid under concrete edge beam SECTION B _

A B

ORIGINAL ISSUE 02.11.11

APPROVED

C. Noel 23/11/01 A. Bletchly C.Lindsay

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR OUTDOOR RMU WITH PRECAST CONCRETE FDN SITE FINISH CONCRETE SURROUND
FILE: 5 62 5217 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5217

Finished

Fall

Fall
F

R.P. Street

2800 Concrete Edge Beam


F
F

NOTES:
F

Site Boundary (Level Site)

1. Backfill Cable Pit with bedding sand and compact in place. Refer TRENCHING Drawing No. 5227. 2. Reinforced concrete surround slab: a) 100/125mm thick slab: b) 11 TM trench mesh reinforcement in centre of slab: c) 25 MPa grade concrete: d) Finish by wood float or by nylon broom. 3. The top face of the concrete surround slab shall be 100mm Min. above the final surface level (when turf is laid). 4. The concrete slab is to slope away from plinth falling at a slope of 1 in 25. 5. Cable apertures through the precast concrete plinth shall be backfilled to 50mm from the top of plinth. A 30mm deep layer of 1:16 ratio weak mix concrete shall be placed to seal aperture. 6. The surface of the surround slab may be finished with a stencil pattern surface to match the surrounding pavements of the development. (Use Textcrete or equivalent product. Construct to suppliers specifications). 7. Concrete slab to be cast in separate sections on side/s where cables enter/exit to allow future access. Provide Abelflex between sections and around plinth. Concrete edge beam to perimeter 150 wide x 150 deep below finished surface.
F

Abelflex sealant joint between plinth and concrete slab

Foundation Finish ground line

Construction Type

11RMUF/ASL

Sh

11kV RING MAIN UNIT CONSTRUCTION CODE

Code shown within dashed box appears on relevant construction detail drawings in this manual.

A 11 RMU/O/ASL 2S1F

VOLTAGE 11 = 11kV

CONSTRUCTIONS RMU = Ring Main Unit

LOCATION O = Outdoor

HV SWITCHGEAR ASL = ABB SafeLink ASP = ABB SafePlus ASR = ABB SafeRing

CONFIGURATION 2S1F = 2 switch + 1 fuse 2S2F = 2 switch + 2 fuse 3S = 3 switch 3S1F = 3 switch + 1 fuse 4S = 4 switch 1S1CB1F = 1 switch + 1 circuit breaker + 1 fuse 1S1CB2F = 1 switch + 1 circuit breaker + 2 fuse 2S1CB = 2 switch + 1 circuit breaker

EXAMPLE:-

11RMU/O/ASL2S1F = 11kV, Ring Main Unit, outdoor, ABB SafeLink, 2 switches + 1 fuse.
APPROVED

ORIGINAL ISSUE

C. Noel 9/9/10 A. Bletchly T.Borg

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR CONSTRUCTION CODE GUIDE 11kV RING MAIN UNIT
FILE: 5 62 5229 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5229

Sh

RING MAIN UNIT FOUNDATION & SITE FINISH CONSTRUCTION CODE

Code shown within dashed box appears on relevant construction detail drawings in this manual.

A 11 RMUF / ASL

Required only where foundation is not provided by others.

VOLTAGE 11 = 11kV

RMU FOUNDATION RMUF = Ring Main Unit Foundation

HV SWITCHGEAR ASL = ABB Safelink

EXAMPLE:-

11RMUF/ASL = 11kV, Ring main unit foundation, ABB Safelink


APPROVED

ORIGINAL ISSUE

C. Noel 3/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR CONSTRUCTION CODE GUIDE FOUNDATION AND SITE FINISH
FILE: 5 62 5229 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5229

Sh

22kV RING MAIN UNIT CONSTRUCTION CODE

Code shown within dashed box appears on relevant construction detail drawings in this manual.

A 22 RMU/O/FGA 3S1F

VOLTAGE 22 = 22kV

CONSTRUCTIONS RMU = Ring Main Unit

LOCATION O = Outdoor

HV SWITCHGEAR FGA = Felton & Guillaume (F&G)

CONFIGURATION 1S1CB1F = 1 switch + 1 circuit breaker + 1 fuse 1S1CB2F = 1 switch + 1 circuit breaker + 2 fuse 2S1CB = 2 switch + 1 circuit breaker 2S1F = 2 switch + 1 fuse 2S2F = 2 switch + 2 fuse 3S = 3 switch 3S1F = 3 switch + 1 fuse 4S = 4 switch

EXAMPLE:-

22RMU/O/FGA3S1F = 22kV, Ring Main Unit, outdoor, Felton and Guillaume (F&G), 3 switches + 1 fuse.
APPROVED

ORIGINAL ISSUE

C. Noel 9/9/10 A. Bletchly T.Borg

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR CONSTRUCTION CODE GUIDE 22kV RING MAIN UNIT
FILE: 5 62 5229 3

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5229

Sh

R.P. Street Alignment

Outline of RMU foundation over (shown dashed)

FOOTPATH

A _
F

3000

800 F = 2800 = 1. Refer drawing 5226 for installation requirements. 2. Ergon Energys 3000mm x 2800mm (minimum) site shall be levelled and surrounding area graded to ensure NO PONDING of water occurs. 3. No services other than the Ergon Energys electric cables shall pass through this RMU site. 4. Clear access to the RMU shall be maintained for Ergon Energys personnel & heavy equipment. CUT 5. After installation is complete the site surface is to be finished with a concrete slab. (Refer drawing 5217). 6. Mature landscaping (including trees, sprinklers etc) shall not encroach onto the RMU site. 7. The finished surface of the adjacent footpath, in front of the RMU cabinet, shall be level to ensure that the cabinet doors will swing into the fully open position.

PLAN
R.P. Street Alignment 100 MAX FILL
F

150 MAX

SECTION

A _

ORIGINAL ISSUE

HARD COPY UNCONTROLLED

Ergon Energy Corporation Ltd ABN 50 087 646 062

Site Boundary

NOTES:

F F

APPROVED

C.Noel 8.3.11 A.Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR SITE PREPARATION SLOPING SITE MAXIMUM CUT & FILL
FILE: 5 62 5230 1

DATE

PASSED

DRAWN

Dwg

5230

Sh

MATERIAL ASSY 583-2


Culvert

DESCRIPTION

QTY
1

NOTES: 1. Foundation design details are as follows: Unstable soils are soft clay to sandy gravel with a soil strength 50-150 kPa. Stable soils are very stiff clay to shale/rock with soil strength of 150kPa or higher. 2. Lift the culvert separately with 4 x 1.3 tonnes Reid Swiftlift lifting eyes. 3. Position the top face of the culvert at the finished ground level of the site, as detailed on the Projects Civil Construction drawings. 4. Do NOT remove the culvert end wall knockouts. 5. The culvert shall be constructed level. Under no circumstances shall it be allowed to tilt forward towards the footpath. 7. Refer drawing No. 5217 for site finish concrete surround.

ORIGINAL ISSUE

APPROVED

C. Noel 4/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR CULVERT FOUNDATION DETAILS MATERIAL
FILE: 5 62 5232 1
B 1/2 DISC

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5232

Sh

Cable entry Precast concrete plinth supplied with RMU


F

2800 Site
F F F F

Footpath

=
F

SECTION =

A _

3000 Site

A _

Site Boundary
F

1280 Unstable

B _

1180 Stable

R.P. Street Alignment

PLAN

50 Stable 100 Un-stable

SECTION

B _

ORIGINAL ISSUE

APPROVED

C. Noel 8.3.11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR CULVERT FOUNDATION DETAILS CONSTRUCTION
FILE: 5 62 5232 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

F F

HV cables
F

Assy 583-2

Backfill with approved suitable material and compact in place

=
F F

Finished Ground Line (Site)

Compact pit sand Construction Type

11RMU/ASL

Dwg

5232

Sh

R.P. Street Alignment Dwelling

NOTE: A reduction in dwelling setback of 6000mm from the R.P. Street Alignment will require relocation of the ring main unit to an alternative site to achieve the acceptable separation.

Real Property Boundary


F

As Reqd FOOTPATH 3000 Ring main units may be in 1 or 2 allotments


F

2800
F

6000

As Reqd Dwelling
F F F

F F F

ORIGINAL ISSUE

APPROVED

C. Noel 8/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR LOCATION IN RESIDENTIAL ALLOTMENTS

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

FILE: 5

62 5233 1

Dwg

5233

Sh

NOTES: 1. A ring main unit in parkland shall be located: Away from residential dwellings and surrounding properties to minimise visual and sound impact; As close as possible to the road kerb to allow 24 hour all weather access for personnel, a coventional crane and heavy equipment. 2. When planting vegetation in parklands, ensure vegetation does not encroach on the ring main unit site. Take into consideration the fully matured size of vegetation to allow continuing access to the site. 3. A 3.0m wide cable and access easement or road reserve shall be provided between the ring main unit site and the R.P. Street Alignment. 4. The location of ring main unit sites is based on acceptable separation to adjacent dwellings located as shown. Any reduction in the 1.5m minimum dimension shown on the drawings requires a corresponding relocation of the ring main unit site to maintain the acceptable separation. Parklands Dwelling Refer Note 4
F

2.5m

Min.

1.5m Min.

Real Property Boundary

Dwelling

Site Boundary
F
F

2.0m

3.0m
F

FOOTPATH Kerb ROAD

PLAN
RMU SET BACK FROM R.P. STREET ALIGNMENT

ORIGINAL ISSUE

APPROVED

C. Noel 10.3.11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR LOCATION IN COUNCIL PARKLANDS

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

FILE: 5

62 5234 1

Dwg

5234

Apron

1.5m Min.
F

As Reqd

Refer Note 4
F

R.P. Street Alignment

Sh

2.5m Min.

Real Property Boundary

Real Property Boundary

Dwelling

Dwelling Parklands
F

Parklands

1.5m Min. 6.0m Min. Site Boundary


F
F

FOOTPATH Kerb ROAD

R.P. Street Alignment

FOOTPATH Kerb ROAD

PLAN

PLAN

RMU ADJOINING R.P. STREET ALIGNMENT

ORIGINAL ISSUE

APPROVED

C. Noel 10.3.11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR LOCATION IN COUNCIL PARKLANDS

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

FILE: 5

62 5234 2

Dwg

5234

Sh

Site Boundary

As Reqd

2.5m Min.
F

Less than 6.0m Refer Note 4 Sheet 1.

R.P. Street Alignment

F F

MATERIAL - FREESTANDING RING MAIN UNIT ASSY 567-1 567-3 567-5 567-7 567-9 DESCRIPTION
2S1F 2S2F 11kV ABB safelink 2 switch 1 fuse c/w cubical and plinth 11kV ABB safelink 2 switch 2 fuse c/w cubical and plinth 11kV ABB safelink 3 switch c/w cubical and plinth 11kV ABB safelink 3 switch 1 fuse c/w cubical and plinth 11kV ABB safelink 4 switch c/w cubical and plinth 1 1 1 1 1

QTY
3S 3S1F 4S

MATERIAL - HV FUSE - EACH CIRCUIT ASSY 555-2 555-4 555-5 555-7 555-8 555-9 DESCRIPTION
Cartridge fuse link 10A HRC Cartridge fuse link 20A HRC Cartridge fuse link 25A HRC Cartridge fuse link 40A HRC Cartridge fuse link 50A HRC Cartridge fuse link 63A HRC Refer note 1 3

QTY
NOTES: 1. Designer to nominate HV fuse link current rating 2. Designer to nominate the position(s) of the outgoing cable circuits (Refer dwg 5237 for schematic) as follows: * Radial feeders - switch disconnector(s) provided with CFI unit(s) * Ring feeders - determine the circuit arrangement in consultation with system operations staff. 3. The gland plates supplied with the units are not required to be fitted on the ground mounted RMU 4. The HV cables must be clamped to the unistrut provided as per construction standards and the opening on the plinth for cable entry must be filled with a weak concrete mix and compacted

555-10 Cartridge fuse link 80A HRC

CONTRACT No. 2008 / 024 / T

A B

ORIGINAL ISSUE 24.11.11

APPROVED

C. Noel 10/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV RING MAIN UNIT SAFELINK MATERIAL
FILE: 5 62 5236 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5236

Sh

Assy Selection 567-1 to 9 and 555-2 to 10


F

Lifting points 4 x M12 ferrules


F

Concrete plinth

Lifting points 4 x M12 ferrules

Refer HV CONSTRUCTION drawing no. 5244 or 5245 for feeder cable connections

Side View

Plan CONTRACT No. 2008 / 024 / T

ORIGINAL ISSUE

APPROVED

C. Noel 10/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV RING MAIN UNIT SAFELINK CONSTRUCTION
FILE: 5 62 5236 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

Construction Type

11RMU/O/ASL2S1F 11RMU/O/ASL2S2F 11RMU/O/ASL3S 11RMU/O/ASL3S1F 11RMU/O/ASL4S

5236

Sh

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

2S1F 11kV ABB safelink RMU 2 switch 1 fuse

2S2F 11kV ABB safelink RMU 2 switch 2 fuse

3S1F 11kV ABB safelink RMU 3 switch 1 fuse

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 10/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV SAFELINK - HV SWITCHGEAR SCHEMATIC
FILE: 5 62 5237 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5237

Sh

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

4S 11kV ABB safelink RMU 4 switch

3S 11kV ABB safelink RMU 3 switch

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 10/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV SAFELINK - HV SWITCHGEAR SCHEMATIC
FILE: 5 62 5237 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5237

Sh

MATERIAL - FREESTANDING RING MAIN UNIT ASSY 578-1 578-3 578-5 DESCRIPTION
11kV ABB safeplus RMU 1 switch 1 circuit breaker 1 fuse c/w cubical and plinth 11kV ABB safeplus RMU 1 switch 1 circuit breaker 2 fuse c/w cubical and plinth 11kV ABB safering 2 switch 1 curcuit breaker c/w cubical and plinth 1 1 1

QTY
1S1CB1F 1S1CB2F 2S1CB

NOTES: 1. For circuit breaker setting refer to protection. 2. Designer to nominate the position(s) of the outgoing cable circuits (Refer dwg 5253 for schematic) as follows: * Radial feeders - switch disconnector(s) provided with CFI unit(s) * Ring feeders - determine the circuit arrangement in consultation with system operations staff.

A B

ORIGINAL ISSUE 24.11.11

APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV SAFEPLUS / SAFERING MATERIAL
FILE: 5 62 5238 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5238

Sh

Assy Selection 578-1, 3 or 5


F

Lifting point

Lifting point

Lifting point

ORIGINAL ISSUE

APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV SAFEPLUS / SAFERING CONSTRUCTION
FILE: 5 62 5238 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5238

Sh

MATERIAL - FREESTANDING RING MAIN UNIT ASSY 579-1 579-3 579-5 579-7 579-9 DESCRIPTION
2S1F 22kV F&G 2 switch 1 fuse c/w cubical & plinth 22kV F&G 2 switch 2 fuse c/w cubical & plinth 22kV F&G 3 switch c/w cubical & plinth 22kV F&G 3 switch 1 fuse c/w cubical & plinth 22kV F&G 4 switch 1 1 1 1 1 1 1 1 2S2F 3S

QTY
3S1F 4S 1S1CB1F 1S1CB2F 2S1CB

579-11 22kV F&G 1 switch 1 circuit breaker 1 fuse c/w cubical & plinth 579-13 22kV F&G 1 switch 1 circuit breaker 2 fuse c/w cubical & plinth 579-15 22kV F&G 2 switch 1 circuit breaker c/w cubical & plinth

MATERIAL - HV FUSE - EACH CIRCUIT ASSY 556-3 556-4 556-7


NOTE: 1. Designer to nominate HV fuse links 2. For circuit breakers refer to protection for setting 3. Designer to nominate the position(s) of the outgoing cable circuits (Refer dwg 5252 for schematic) as follows: * Radial feeders - switch disconnector(s) provided with CFI unit(s) * Ring feeders - determine the circuit arrangement in consultation with system operations staff.

DESCRIPTION
2S1F Cartridge fuse link 16A Cartridge fuse link 20A Cartridge fuse link 40A 3 6 3 2S2F 3S

QTY
3S1F 4S 1S1CB1F 1S1CB2F 2S1CB

CONTRACT No. 2008 / 024 / T


APPROVED

A B

ORIGINAL ISSUE 24.11.11

C. Noel 16/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR F&G 22kV CONSTRUCTION
FILE: 5 62 5243 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5243

Sh

Assy Selection 579-1 to 15 and 556-3 to 7


F
F

Lifting point
F

Construction Type

22RMU/O/FGA2S1F 22RMU/O/FGA2S2F

Lifting point

Lifting point Refer HV CONSTRUCTION drawing no. 5044 for feeder cable connection

CONTRACT No. 2008 / 024 / T A


ORIGINAL ISSUE APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

22RMU/O/FGA3S 22RMU/O/FGA3S1F 22RMU/O/FGA4S 22RMU/O/FGA1S1CB1F 22RMU/O/FGA1S1CB2F 22RMU/O/FGA2S1CB UNDERGROUND DISTRIBUTION


HV SWITCHGEAR F&G 22kV RING MAIN UNIT CONSTRUCTION
FILE: 5 62 5243 2

Dwg

5243

Sh

F FEEDER CABLE FEEDER CABLE FEEDER CABLE

F FEEDER CABLE FEEDER CABLE FEEDER CABLE FEEDER CABLE

F FEEDER CABLE FEEDER CABLE

F FEEDER CABLE FEEDER CABLE

2S1F 22kV F & G ring main unit 2 switch, 1 fuse

2S2F 22kV F & G ring main unit 2 switch, 2 fuse

3S1F 22kV F & G ring main unit 3 switch, 1 fuse

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR F & G 22kV RING MAIN UNIT SCHEMATIC
FILE: 5 62 5252 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5252

Sh

F FEEDER CABLE FEEDER CABLE

F FEEDER CABLE FEEDER CABLE

F FEEDER CABLE FEEDER CABLE

F FEEDER CABLE

4S 22kV F & G ring main unit 4 switch

3S 22kV F & G ring main unit 3 switch

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 10/3/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR F & G 22kV RING MAIN UNIT SCHEMATIC
FILE: 5 62 5252 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5252

Sh

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

1S1CB1F 22kV F & G ring main unit 1 switch, 1 circuit breaker, 1 fuse

1S1CB2F 22kV F & G ring main unit 1 switch, 1 circuit breaker, 2 fuse

2S1CB 22kV F & G ring main unit 2 switch, 1 circuit breaker

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR F & G 22kV HV SWITCHGEAR SCHEMATIC
FILE: 5 62 5252 3

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5252

Sh

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

FEEDER CABLE

1S1CB1F 11kV ABB Safeplus ring main unit 1 switch, 1 circuit breaker, 1 fuse

1S1CB2F 11kV ABB Safeplus ring main unit 1 switch, 1 circuit breaker, 2 fuse

2S1CB 11kV ABB Safering ring main unit 2 switch, 1 circuit breaker

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

Note: F Represents circuit fault indicator (CFI) on this switch disconnector unit

ORIGINAL ISSUE

APPROVED

C. Noel 9/5/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR ABB 11kV SAFEPLUS / SAFERING HV SWITCHGEAR - SCHEMATIC
FILE: 5 62 5253 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5253

Sh

RING MAIN UNIT INSTALLATION


1 SITE 1.1 General The site shall be to the satisfaction of Ergon Energy, including Stable (soil conditions) Flood free Level (topography) where possible Free from steep batters Free from other services Along coastal areas the site must be located as far as possible from the shoreline and sheltered from salt spray. A site should not be located where impact by traffic is likely and, if at a truncated section of the street alignment or other non-regular shaped site the following shall apply: The front edge of the ring main unit shall be as near to parallel as possible to the R.P. Street Alignment. The specified rectangular size of the site shall not be reduced. 1.2 Site Size The minimum area required to accommodate a ring main unit shall be: Common earthing sites Level sites - 3000mm width x 2800mm depth. Retaining wall sites - 3400mm width x 3000mm depth. 1.3 Ring Main Unit Orientation Ring main units shall be oriented such that the HV panels are easily accessible from the dedicated footpath. Where the developer required the ring main unit to be included: a) In the Road Reserve:The Developer shall obtain all necessary approvals from the Department of Transport or the Local Authority. b) On Freehold property (including residential or parkland):The Developer shall provide Ergon Energy with a registered easement at no cost to Ergon Energy. Acceptable separation of ring main unit to adjacent dwellings is provided if the front of dwellings are set back 6.0m from the R.P. Street Alignment and the padmount is located as shown in drawings No. 5233, 5234 Sheets 1 or 2. Developments including streets where the allowable dwelling set back is less than 6.0m will require ring main unit siting on either an alternative street, where the dwelling set back is 6.0m, or in Parklands. The developer shall provide a ring main unit site(s) as required by Ergon Energy at no cost to Ergon Energy. The site shall be included in the road reserve, or located on freehold property. No ring main units are to be located in Trustee Reserves. 1.4 URD

ORIGINAL ISSUE

APPROVED

C. Noel 1/6/11 A. Bletchly L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR RING MAIN UNIT INSTALLATION
FILE: 5 62 5255 1

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5255

Sh

1 SITE 1.5

(CONTD)

2 SITE PREPARATION Sites shall be prepared in accordance with the included construction drawings. 3 CONSTRUCTION OF RETAINING WALLS Retaining walls shall be constructed around the perimeter of a ring main unit site where: A change in ground level of 300mm or more occurs within 2.0m of the boundary of the ring main unit site. 4 RING MAIN UNIT FOUNDATION 4.1 Uniculvert Uniculvert foundations shall not be constructed where site and ground conditions do not provide an even or equal bearing capacity for the ring main unit. Uniculvert foundations for stable soil conditions shall be constructed in accordance with Drawing No. 5232.

Commercial and Industrial or Landscaped Areas Whether the ring main unit is for the sole use of that complex, or is required as part of the distribution network, the owner is required to grant Ergon Energy an easement for the ring main unit site, access and cabling. Separation of 5.0m between ring main unit and the nearest room or habitable area should be provided where possible.

1.6

Parklands - for other than URD Obtain the necessary approval for an easement to accommodate the ring main unit, cabling and access to site. Acceptable separation of ring main unit to adjacent dwellings is shown in drawings No. 5234 Sheets 1 & 2.

1.7

Cabling and Access Requirement Cabling and Access A 3.0m wide easement, or road reserve, from the front of the site is required for cabling and access. Cabling Only Should the cabling route not be available in conjunction with access, a 1.0m wide cable easement is required to the front of the ring main unit. Additionally 2.0m x 3.0m (ring main unit site width) is required immediately in front to allow spreading of cables for entry to the ring main unit and also include the buried earth cable.

ORIGINAL ISSUE

APPROVED

C. Noel A. Bletchly 1/6/11 L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR RING MAIN UNIT INSTALLATION
FILE: 5 62 5255 2

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5255

Sh

4 RING MAIN UNIT FOUNDATION

(CONTD)

4.2 Unstable Sites Where sites are very unstable, and conventional foundation construction techniques as described in this document cannot be applied, a special design shall be required. In such circumstances, the developer shall obtain a certified design from a Civil Engineer (RPEQ) for Ergon Energys consideration. No special designs for ring main unit foundation construction shall be used without the approval of Ergon Energy. 5 BACKFILLING AND FINAL SITE FINISH All backfill of the site must be compacted before final site finish in accordance with the applicable drawing. 5.1 Common Earthing Sites Sealing of the cable apertures in the precast concrete plinth and construction of the concrete surround slab over the ground surface shall be in accordance with drawing No. 5217.

Ring main units shall be located on the development in areas where clear, all weather access is provided for personnel and heavy equipment at all times. Easy access for a mobile crane must be available for the purpose of installation or replacement. Ergon Energy cable conduits for the development may be placed in the substation site and shall pass down the sides of the uniculvert foundation. No conduits shall pass through or under the uniculvert foundation. Conduits shall be 750mm minimum depth below the finished surface level. The substation site surface is to be finished with a concrete slab (refer to drawing No. 5004). The 2.0m apron in front of the substation cabinet shall be finished with a concrete slab sectioned with construction joints for ease of future removal. 6.2 Ring Main Units in Landscaped Areas Where the ring main unit is located in a landscaped area (gardens) the following shall apply: An additional 2.0m apron shall be provided in front of, and for the full width of the site (ie 4.8m depth). This will provide a safe working platform and access around latched open doors for emergency operations. The ring main unit site surface is to be finished with a concrete slab (refer to drawing No. 5217). The 2.0m apron in front of the ring main unit site shall be finished with a concrete slab sectioned with construction joints for ease of future removal.

6 ADDITIONAL REQUIREMENTS 6.1 Commercial and Industrial Installation The preferred location of ring main unit sites at commercial and industrial developments is at the real property street alignment. Switchgear cabinet doors shall face the adjoining footpath. Should the site be located in restricted areas such as carparks and between buildings, an additional minimum 2.0m of clear access shall be provided in front of, and for the full width of the site (ie 4.8m depth). This will provide a safe working platform and access around latched open doors for emergency operations.

ORIGINAL ISSUE

APPROVED

C. Noel A. Bletchly 1/6/11 L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR RING MAIN UNIT INSTALLATION
FILE: 5 26 5255 3

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5255

Sh

6.2

Ring Main Unit in Landscaped Areas (CONTD) When planting vegetation in landscaped areas and gardens, ensure vegetation does not encroach on the ring main unit site. Take into consideration the fully matured size of vegetation to allow continuing access to the site. Ergon Energy cable conduits for the development may be placed in the ring main unit site and shall pass down the sides of the uniculvert foundation. No conduits shall pass through or under the uniculvert foundation. Conduits shall be 750mm minimum depth below the finished surface level.

6.3

Ring Main Units Installation in Parklands Where the ring main unit is located in Council Parklands, the installation shall be in accordance with the requirements of drawing No. 5234 Sheets 1 or 2. A 2.0m apron as specified in Clause 6.2 shall be provided.

7 SPACING BETWEEN RING MAIN UNIT AND OTHER METAL OBJECTS No buildings/residences, fences, including their foundations, LV switchboard earths, or metalic objects are permitted within the clearance zone around the RING MAIN UNIT. Clearance to Telstra assets shall be as noted on EARTHING drawing No. 5221 Sheet 1.

ORIGINAL ISSUE

APPROVED

C. Noel A. Bletchly 1/6/11 L. Burton

UNDERGROUND DISTRIBUTION
HV SWITCHGEAR RING MAIN UNIT INSTALLATION
FILE: 5 62 5255 4

HARD COPY UNCONTROLLED

DATE

PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062

DRAWN

Dwg

5255

Sh