Daikin products are manufactured for export to numerous countries throughout the world. Prior to purchase, please confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation. Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer.

PCV1131

VRV indoor units combine with residential indoor units, all in one system

Single outdoor unit series


suitable for homes, offices, shops, and middle-sized buildings
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Organization: DAIKIN INDUSTRIES, LTD. AIR CONDITIONING MANUFACTURING DIVISION Scope of Registration: THE DESIGN/DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING, HEATING, COOLING, REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, COMPRESSORS AND VALVES. Organization: DAIKIN INDUSTRIES (THAILAND) LTD. Scope of Registration: THE DESIGN/DEVELOPMENT AND MANUFACTURE OF AIR CONDITIONERS AND THE COMPONENTS INCLUDING COMPRESSORS USED FOR THEM

All of the Daikin Group s business facilities and subsidiaries in Japan are certified under the ISO 14001 international standard for environment management.

JMI-0107

JQA-1452

Dealer
Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/
c All rights reserved Printed in Japan12/11/005 Y.K.

Specifications, designs and other content appearing in this brochure are current as of December 2011 but subject to change without notice.

Cooling Only 50 Hz

Contents
Main Features................................page 3 Option List....................................page 35 Indoor units.............................page 35
VRV.....................................page 35 Residential..........................page 37

Meet the new single outdoor unit series, connectable to both VRV and residential indoor units

Outdoor Unit Lineup......................page 4 Indoor Unit Lineup.........................page 9


VRV.....................................page 9 Residential........................page 19

BP units...................................page 38 Outdoor units...........................page 38 Control Systems...........................page 39

Specifications...............................page 24 Indoor units.............................page 24


VRV.....................................page 24 Residential..........................page 31

BP units...................................page 33 Outdoor units...........................page 34

First launched in Japan in 1982, the Daikin VRV system has been embraced by world markets for nearly 30 years. Now, Daikin proudly introduces the new VRVIII single outdoor unit series which enables a mixed combination of VRV indoor units and residential indoor units all in one system, opening the door to stylish and quiet indoor units.

OFFICES

SHOPS

HOMES

Main Features

Wide range of choices


Indoor units
Indoor units can be selected from 2 lineups, both VRV and residential indoor units, to match rooms and preferences.

BP unit Connection unit

BP unit

VRV indoor units

Residential indoor units


15 types 73 models

VRV indoor units


20 Type
Ceiling Mounted Cassette (Round Flow) Ceiling Mounted Cassette (Compact Multi Flow) Ceiling Mounted Cassette (Double Flow) Ceiling Mounted Cassette Corner

Residential indoor units with connection to BP units


25 Type Model Name Rated Capacity Capacity Index
Ceiling Mounted Cassette Ceiling Mounted Cassette (Compact Multi Flow) Ceiling Mounted Built-in

7 types 21 models
50 5.0 kW 50 60 6.0 kW 60 71 7.1 kW 71

25 25

32 31.25

40 40

50 50

63 62.5

80 80

100 100

125 5 HP 125

140 6 HP 140

200 8 HP 200

250 10 HP 250

35 3.5 kW 35

Model Name

Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP Capacity Index 20

2.5 kW 25

FXFQ-PVE FXZQ-MVE FXCQ-MVE FXKQ-MAVE FXDQ-PBVE


(with drain pump)

FCQ-BVE FFQ-BV1B FBQ-BV1 FDKS-EAVMB

Slim Ceiling Mounted Duct

(700 mm width type)

FDKS-C(A)VMB
(900/1,100 mm width type) (700 mm width type)

FXDQ-PBVET
Slim Ceiling Mounted Duct
(without drain pump)

FTKS-DVM
Wall Mounted

FXDQ-NBVE
(with drain pump)

FTKS-FVM
Note: BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.
(900/1,100 mm width type)

FXDQ-NBVET
(without drain pump)

FXMQ-PVE
Ceiling Mounted Duct

Outdoor units
The new VRVIII single outdoor unit series offers 6 models to select from, providing the power that suits your needs.

FXMQ-MAVE
Ceiling Suspended

single outdoor unit series

FXHQ-MAVE FXAQ-MAVE FXLQ-MAVE FXNQ-MAVE

Wall Mounted

Floor Standing Concealed Floor Standing

8, 10 HP

12, 14, 16, 18 HP

Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system.

Outdoor unit lineup


100 4 HP 100
BEVQ100MAVE

VRV indoor units connection unit series


71 Type Model Name Capacity Range Capacity Index Connection Unit
Ceiling Note: Suspended Cassette

125 5 HP 125
BEVQ125MAVE

Model Name HP kW

RSXQ8PY1 8 HP 22.4 kW 200

RSXQ10PY1 10 HP 28.0 kW 250

RSXQ12PY1 RSXQ14PY1 12 HP 33.5 kW 300 14 HP 40.0 kW 350

RSXQ16PY1 16 HP 45.0 kW 400

RSXQ18PY1 18 HP 49.0 kW 450


4

3 HP 71
BEVQ71MAVE

Capacity Range

FXUQ-MAV1

Capacity Index

Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.

Main Features

Energy efficiency and quiet operation


Outdoor units use Daikins unique scroll compressor to realise energy saving performance and quiet operation.

A collection of cutting-edge technologies realises efficient and quiet operation


1

High efficiency compressor

High COPs
It has become essential for air conditioning manufacturers to develop systems that provide high energy savings. We at Daikin have made great efforts in this field, and the VRVIII delivers highly efficient performance, contributing to high energy savings.

Reluctance DC scroll compressor Daikins unique scroll compressor reduces heat loss, and is driven by a high efficiency motor to achieve significant energy savings.
High torque and efficiency is attained with the adoption of neodymium magnets.

Achieving a high COP


We have reached a high level of efficiency, thanks to advanced features such as the heat exchanger, the grille and the dual DC fans.
4 3 2 1

4.27 3.54 3.75


Powerful magnets
Use of neodymium magnets in the motor enables efficient generation of high torque.
Neodymium magnets are well known for their powerfulness compared to commonly used ferrite magnets.

8 HP

10 HP

12 HP

Reluctance DC motor

Cooling operating conditions: Indoor temp. of 27CDB, 19.0 CWB, and outdoor temp. of 35CDB.

High-performance, low-noise scroll compressor operates at a fast rate. The speed increase has been achieved through advanced stress analysis for increased strength and utilisation of the advantages (oil film control) of the high thrust mechanism.*

*High thrust mechanism

Nighttime quiet operation function


Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode

By introducing high pressure oil, the reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. This results in improved efficiency and suppressed sound levels.

Operation sound dB(A) Load % Capacity %

Set on the outdoor PCB. Time of maximum temperature is memorised. The low operating mode will initiate 8 hours*1 after the peak temperature in the daytime, and normal operation will resume 10 hours*2 after that. The operation sound level for the night mode can be selected from 55 dB(A) (Step 1), 50 dB(A) (Step 2) and 45 dB(A) (Step 3).

2 Heat exchanger
Mode 1. Automatic mode

Compact aero box

Thanks to an optimised e-Pass heat exchanger, heat change effectiveness has been increased, thus contributing to a high COP.

Peak in outdoor temperature (For 10 HP outdoor unit)


100

Realises a compact casing by stacking the Inverter and control PCBs plus optimising the internal design to suit airflow speed. This achieves low noise and reduces the power required by the large-diameter fanned outdoor unit.

8 hrs
50

(Initial setting)

10 hrs

Smooth sine wave DC Inverter

DC fan motor

(Initial setting)

Mode 2. Manual mode

By adoption of the Sine Wave, which smoothes the rotation of the motor, operation efficiency is improved sharply.
Night Mode

Efficiency improvement by approximately 40% especially at low speed.


DC fan motor structure
100

50 45 8:00

Step 2 max. - 8dB(A) Step 3 max. - 13dB(A)

Step 2: 50 dB(A) Step 3: 45 dB(A)

Efficiency (%)

Starting time and ending time can be input. (An external control adaptor for outdoor unit, DTA104A53/61/62, and a locally obtained timer are necessary.)
Mode 3. Combined mode

DC motor efficiency
(comparison with AC motor)

0 58 55

Step 1 max. - 3dB(A)

Step 1: 55 dB(A)
80 60 40

DC motor
Approx. increase

40%

AC motor
20 0 200 300

Combinations of modes 1 and 2 can be used depending on your needs.


*1. Initial setting. Can be selected from 6, 8 and 10 hours. *2. Initial setting. Can be selected from 8, 9 and 10 hours.

Night mode starts


12:00 16:00 20:00

Night mode ends


0:00 4:00 8:00

400 500

600

700 800

900 1000

Notes: This function is available in setting at site. The relationship of outdoor temperature (load) and time shown in the graph is just an example. The capacity reduction rate differs depending on the operation sound level step selected.

Motor speed (rpm)

Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.

Main Features

Design flexibility
Long piping length
Long piping length offers flexibility during installation.
Actual piping length Total piping length

As many as 29 indoor units can be connected


VRVIII single outdoor unit series enables a mixed combination of VRV and residential indoor units by connecting BP units. As many as 29 indoor units can be connected, making this series a highly versatile system.
BP unit BP unit

Max.

100

Max.

250

m Max.

When only VRV indoor units are connected

Colours in the diagram below are merely for identifying pipes referenced with symbols such as a .

29
i

Indoor units

Residential indoor units

a b
First indoor branch

c f

d g h
VRV indoor units
Note: Total capacity index of connectable indoor units must be 50%130% of the capacity index of the outdoor unit. Refer to page 34 for the maximum number of connectable indoor units.

Max.

50 m k
j
Max.

15 m

When only VRV indoor units are connected


Refrigerant piping length Maximum allowable piping length Total piping length Between the first indoor branch and the farthest indoor unit

Actual piping length

Example

Equivalent piping length

100 m 250 m 40 m
Level Difference

a+b+c+d+i a+b+c+d+e+f+g+h+i b+c+d+i

125 m
Example

High external static pressure of 78.4 Pa


High external static pressure has been achieved thanks to the fan grilles and the dual DC fans that reduce internal pressure loss. Daikin offers 78.4 Pa (8 mm H2O) external static pressure by field setting to meet the requirements for installation on each floor.

78.4 Pa

Between the indoor units Maximum allowable level difference Between the outdoor unit and the indoor unit If the outdoor unit is above. If the outdoor unit is below.

15 m 50 m 40 m

j k k

When a mixed combination of VRV and residential indoor units is connected

Colours in the diagram below are merely for identifying pipes referenced with symbols such as a .

VRV: VRV indoor unit RA: Residential indoor unit BP: BP unit

a
First indoor branch
BP

b e i f

d g
o
Max. Max.

Easy Installation
40 m

High reliability
Backup operation
If one of the multiple compressors malfunctions, the other compressors take over for emergency operation.*1 If one compressor malfunctions...

Max.

50 m

h
RA RA

j
VRV RA

BP

15 m
k

Small and light, significantly reducing constraints during carry-in


Carry-in possible using ordinary elevators Easy belt suspension

Max.

15 m

VRV

RA

When a mixed combination of VRV and residential indoor units is connected or when only residential indoor units are connected
Refrigerant piping length Total piping length Maximum allowable piping length If indoor unit capacity index < 60. Between BP unit and indoor unit If indoor unit capacity index is 60. If indoor unit capacity index is 71. Between the first indoor branch and the farthest BP unit or between the first indoor branch and the farthest VRV indoor unit Minimum allowable piping length Between outdoor unit and the first indoor branch

Actual piping length

Example

100 m 250 m 2 m15 m 2 m12 m 2 m8 m 50 m*1 5m

a+b+c+g+k, a+b+c+d a+b+c+d+e+f+g+h+i+j+k

h, i, j, k

Emergency operation occurs.*1


b+c+g, b+c+d a

Can be carried on a fork-lift without a pallet

*1. Possible only with single outdoor unit systems that are equipped with two or more compressors. Local setting of the outdoor unit is necessary.

Level Difference

Example

Between the indoor units Between BP units Maximum allowable level difference Between the outdoor unit and the indoor unit If the outdoor unit is above. If the outdoor unit is below.

15 m 15 m 50 m 40 m 40 m

l m n n o

Automatic test operation


Simply press the test operation button and the unit performs an automatic system check, including wiring, shutoff valves, and sensors. The results are returned automatically after the check finishes.

Less chances of refrigerant leakage


The shutoff valve connections for outdoor unit are brazed, meaning less chance of refrigerant leakage compared with flanged or flared connections.
8

Between the outdoor unit and the BP unit

*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering Data Book for details.

Indoor Unit Lineup VRV Indoor Units


Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type

FXFQ25P/FXFQ32P/ FXFQ40P FXFQ50P/FXFQ63P/ FXFQ80P FXFQ100P/FXFQ125P


* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

FXZQ20M / FXZQ25M / FXZQ32M FXZQ40M / FXZQ50M

360 airflow improves temperature distribution and offers a comfortable living environment.
The industrys first* Round Flow Ceiling Mounted Cassette type offers 360 airflow with improved temperature distribution.
4-way flow

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Quiet, compact, and designed for user comfort


Dimensions correspond with 600 mm X 600 mm architectural module ceiling design specifications. Low operation sound level
FXZQ-M Sound level 230 V (H/L) 240 V 20/25 30/25 32/26 32 32/26 34/28 40 36/28 37/29
(dB(A))

Round Flow

50 41/33 42/35

There are areas of uneven temperature.

There are much fewer areas of uneven temperature.

* As of April 2004, the release date for Japan.

All models are lighter than the conventional ones. Ex: Models FXFQ25P-50P are 4.5 kg lighter (reduced from 24 kg to 19.5 kg). Drain pump is equipped as standard accessory, and the 850 mm lift height has been improved from 750 mm to 850 mm. A modern sophisticated decoration panel has been applied, with a panel surface that has been treated with a dirt-repellant coating.
Treated surface Untreated surface
Dirt and grime Condition after exposure to the smoke of 600 3 cigarettes in 1 m enclosed space.

Comfortable airflow
1

Wide discharge angle: 0 to 60


Auto swing Fixed angles: 5 levels

0 60 60

0 60 60

An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours. The horizontal louvres prevent dew condensation. Their non-flocking surfaces, which repel dirt, are easy to clean. The air filter has an anti-mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter.
4-way flow 3-way flow L-shaped 2-way flow

Angles can be also set on site to prevent drafts (0-35) or soiling of the ceiling (25-60), other than standard setting (0-60).

Resists soiling

2-, 3-, and 4-way airflow patterns are available, enabling installation in the corner of a room. Drain pump is equipped as standard accessory with 750 mm lift.

Control of the airflow rate has been improved from 2-step to 3-step control. Low operation sound level
FXFQ-P 25/32 40 50 63 80 100 (dB(A)) 125

Sound level 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34 (HH/H/L)

4-way flow

3-way flow

L-shaped 2-way flow

750 mm

Example of airflow patterns:


360 airflow is available, as well as 2- to 4-way flows, so you can choose the most suitable airflow pattern depending on location or room layout.

All-round flow

For 3-way or 2-way flow installation, the sealing member for air discharge outlet (option) must be used to close each unused outlet.

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.

10

Indoor Unit Lineup VRV Indoor Units


Ceiling Mounted Cassette (Double Flow) Type Ceiling Mounted Cassette Corner Type

FXCQ20M/FXCQ25M/FXCQ32M FXCQ40M/FXCQ50M/FXCQ63M FXCQ80M/FXCQ125M


* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

FXKQ25MA / FXKQ32MA FXKQ40MA / FXKQ63MA

Thin, lightweight, and easy to install in narrow ceiling spaces


The thin unit (only 305 mm high) can be installed in a ceiling space as narrow as 350 mm. All models feature a compact design with a depth of only 600 mm.

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Slim design for flexible installation


Slim body needs only 220 mm space above the ceiling. If you use a panel spacer (option), the unit can be installed in the minimum space of 195 mm.
Min.195 mm

Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even distribution of airflow and room temperature.
(m) 3 28C 32C 30C 26C 24C 22C 20C 1 2 3 4 5 6 (m)

305 mm 20 mm

Panel spacer

2 1 0

(When a high-efficiency filter is attached, the unit's height is 400 mm.)

Low operation sound level


FXCQ-M 20 25/32 40/50 63 80

(dB(A)) 125

Single-flow type allows effective air discharge from corner or from drop-ceiling. Drain pump is equipped as standard accessory with 500 mm lift.

Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.
Main body

Sound level 220 V 32/27 34/28 34/29 37/32 39/34 44/38 (H/L) 240 V 34/29 36/30 37/32 39/34 41/36 46/40

Designed with higher airflow suitable for high ceiling application up to 3 metres. Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism realises even distribution of airflow and room temperature. Drain pump is equipped as standard accessory with 600 mm lift.

500 mm

Downward discharge

Air discharge grille (Option)

Set for front discharge using a suspended ceiling.

Two types of optional high-efficiency filter are available (65% and 95%, colourimetric method). A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m
3

Main body

Air discharge grille (Option)

600 mm

Major maintenance work can be performed by removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.

Downward discharge is shut off and air is blown straight out (front discharge).

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.


* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

11

12

Indoor Unit Lineup VRV Indoor Units


Slim Ceiling Mounted Duct Type Ceiling Mounted Duct Type

Slim design, quietness and static pressure switching


* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

FXMQ20P/ FXMQ25P/FXMQ32P FXMQ40P/ FXMQ50P/FXMQ63P FXMQ80P/FXMQ100P/ FXMQ125P FXMQ140P


* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Suited to use in drop-ceilings!


FXDQ20PB/FXDQ25PB/FXDQ32PB
Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels. Great for hotel use!

FXDQ40NB/FXDQ50NB/ FXDQ63NB

Middle and high static pressure allows for flexible duct design
A DC fan motor increases the external static pressure capacity range to include middle to high static pressures, increasing design flexibility.
30 Pa100 Pa for FXMQ20P-32P 30 Pa160 Pa for FXMQ40P 50 Pa200 Pa for FXMQ50P-125P 50 Pa140 Pa for FXMQ140P

Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.

200 mm
Only

900 mm

200 mm
1,100 mm in width for the FXDQ63NB model.

All models are only 300 mm in height, an improvement over the 390 mm height of conventional models. The weight of the FXMQ40P has been reduced from 44 kg to 28 kg. Drain pump is equipped as standard accessory with 700 mm lift.
700 mm
Ceiling

700 mm

Suspension bolt*

Air filter

AIR

240 mm
Suction grille* AIR

Control of the airflow rate has been improved from 2-step to 3-step control. Low operation sound level
FXMQ-P 20/25 32 40 50 63 80/100 125 (dB(A)) 140

Discharge grille*

* To be obtained locally

External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models. 15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.

Sound level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43 (HH/H/L)

Improved ease of installation The airflow rate can be controlled using a remote controller during test operation. With the conventional model, the airflow rate was controlled from the PC board. It is automatically adjusted to the range between approximately 10% of the rated HH tap airflow for FXMQ20P125P. Improved ease of maintenance The drain pan can be detached for easy cleaning. An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.

Energy-efficient The adopted DC fan motor is much more efficient than the conventional AC motor, yielding an approximate 20% decrease in energy consumption (FXMQ125P).

FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift) as a standard accessory FXDQ-PB/NBVET: without a drain pump

FXMQ200MA/FXMQ250MA

Built-in Drain Pump (Option)


Housing the drain pump inside the unit reduces the space required for installation.

Control of the airflow rate has been improved from 2-step to 3-step control. Low operation sound level
FXDQ-PB/NB Sound level (HH/H/L) 20/25/32 33/31/29 40 34/32/30 50 35/33/31 (dB(A)) 63 36/34/32

Without drain pump


750 mm

With drain pump


0250
mm

Simplified Static Pressure Control


Ceiling

470 mm
25 mm

470 mm
222 mm

The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.

External static pressure can be easily adjusted using a change-over switch inside the electrical box to meet the resistance in the duct system.

Indoor unit

Indoor unit

13

14

Indoor Unit Lineup VRV Indoor Units


Ceiling Suspended Type Wall Mounted Type

FXHQ32MA/FXHQ63MA FXHQ100MA
* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

FXAQ20MA / FXAQ25MA FXAQ32MA/FXAQ40MA FXAQ50MA / FXAQ63MA


* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Slim body with quiet and wide airflow


Adoption of QUIET STREAM FAN
Uses the quiet stream fan and many more advanced technologies.
Sound absorption member

Sophisticated design and compact casing harmonised with your interior dcor
Compact and stylish design that does not detract from the dcor of the room. Low operation sound level
FXAQ-MA Sound level (H/L) 20 35/29 25 36/29 32 37/29 40 39/34 50 42/36 (dB(A)) 63 46/39

Turbulent flow is produced

Quiet stream fan Straightening vane

Drain pan and air filter can be kept clean by mildew-proof polystyrene.
(dB(A))

Low operation sound level


FXHQ-MA Sound level (H/L) 32 36/31 63 39/34

100 45/37

Washable grille, the front grille can be easily removed for washing. Auto-swing realises efficiency of air distribution. The louvre closes automatically when the unit stops. 5 steps of discharge angle can be set by remote controller. Maintenance is easy Non-dew Flap with no implanted bristles
Bristle-free Flap minimises contamination and makes cleaning simpler.

Installation is easy Drain pump kit (option) can be easily incorporated.


600 mm

Drain pump kit (built inside main unit)

Discharge angle is automatically set at the same angle as the previous operation when restarting. (Initial setting: 10 for cooling) Flexible installation Drain pipe can be fitted to from either left or right sides.

Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.
Height of drain-up

Wide air discharge openings produce a spreading 100 airflow.

Easy-to-clean flat design

Non-dew Flap

Maintenance is easier because everything can be performed from below the unit. A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
100
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

1,000 mm

Indoor unit Drain pump kit

15

16

Indoor Unit Lineup VRV Indoor Units


Connection unit series indoor units
Floor Standing Type Ceiling Suspended Cassette Type

FXLQ20MA/FXLQ25MA FXLQ32MA/FXLQ40MA FXLQ50MA/FXLQ63MA

FXUQ71MA/FXUQ100MA FXUQ125MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details. * Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Suitable for perimeter zone air conditioning


Floor Standing types can be hung on the wall for easier cleaning. Running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier. The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier. A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

This thin indoor unit achieves optimum air distribution, and can be installed without the need for ceiling cavity.
Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.

4-way airflow from the centre of the store.

The 3-way airflow can distribute comfortable air throughout the room.

Wall hanging

Floor installation

Concealed Floor Standing Type

Only one unit is needed to distribute comfortable air throughout an L-shaped store.

FXNQ20MA/FXNQ25MA FXNQ32MA/FXNQ40MA FXNQ50MA/FXNQ63MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Designed to be concealed in the perimeter skirting-wall


The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design. The connecting port faces downward, greatly facilitating on-site piping work. A long-life filter (maintenance free up to one year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Connection unit is the device for connecting above indoor unit to VRV III. Connection unit BEVQ71MA/BEVQ100MA/BEVQ125MA
Refrigerant piping layout
Connection unit for indoor unit

External wiring layout

*1 Model FXUQ-MA

Maximum piping length between the BEV unit and the indoor unit. 5m

VRV series outdoor unit Liquid pipe Gas pipe


BEVQ-MA

Super wiring (DIII-NET ) Single-phase 220-240 V power supply Indoor unit

Connecting port Refrigerant piping

Piping length*1

Indoor unit Remote controller

Applies also to Floor Standing type (FXLQ-MA).

Notes: When connecting centralised-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52). Connection unit BEVQ-MA is necessary for each indoor unit. The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m. The BEV unit must be installed within a maximum height difference between indoor units of 15 m. Branching of the refrigerant piping is not possible downstream of the BEV unit.

17

18

Indoor Unit Lineup Residential Indoor Units with connection to BP units


Ceiling Mounted Cassette Type FCQ35B/FCQ50B/FCQ60B/FCQ71B Ceiling Mounted Cassette (Compact Multi Flow) Type FFQ25B/FFQ35B/FFQ50B/FFQ60B

Option Note: Remote controller cables not included. Cables should be obtained locally.

Option

Signal receiver unit Note: Wireless remote controllers and signal receiver units are sold as a set.

Option Note: Remote controller cables not included. Cables should be obtained locally.

Option

Signal receiver unit Note: Wireless remote controllers and signal receiver units are sold as a set.

Specially designed for false ceilings for a smooth, modern interior finish
All models feature a decoration panel with the same size and simple design in consideration of harmonised interior dcor. Three convenient patterns for auto-swing operation
Standard

Quiet, compact, and designed for user comfort


Designed to fit 600 mm wide ceiling grids
575 mm 575 mm
Less draught

Low draft performance is designed for your comfort.

Horizontal Flow

286

950 mm

mm
act Comp e panel orativ dec

Same for all models

Draft prevention

Comfortable across all areas


Conditioned air is distributed Adjustable airflow angle to evenly by Auto-swing operation. suit all room conditions.

700 mm
Decoration panel is optional

950 mm

Soiling prevention

700 mm

AUTO-SWING
Standard setting
0 60
0

5 direction
Settable to 5 different levels between 0 and 60

T-bar grid does not need to be cut. The indoor units weigh only 24 kg and require an installation space with a height of just 245 mm.
Min. 245 mm

Auto-swing between 0 and 60

60

Ceiling panel

Drain pump is equipped as standard with 750 mm.

T-bar
750 mm

Draft prevention setting


(Set on site)

0 35

Auto-swing between 0 and 35

35

Settable to 5 different levels between 0 and 35

600 mm 600 mm

Setting to prevent soiling of ceiling


(Set on site)

25 60

Auto-swing between 25 and 60

25 60

Settable to 5 different levels between 25 and 60

Low operation sound level

(H/L)

Note: Angles shown above are provided as a guide. They may differ depending on the installation site.

FCQ35B 33/29 dB (A)

FCQ50B 33/29 dB (A)

FCQ60B 35/30 dB (A)

FCQ71B 35/30 dB (A)

These models have the power to provide a comfortable airflow even with a ceiling height of up to 3.8 m.

Low operation sound level


Max. 3.8 m

(H/L)

FFQ25B 29.5/24.5 dB (A)

FFQ35B 32/25 dB (A)

FFQ50B 36/27 dB (A)

FFQ60B 41/32 dB (A)

Drain pump is equipped as standard accessory with 750 mm lift.

750 mm
20

19

Indoor Unit Lineup Residential Indoor Units with connection to BP units


Ceiling Mounted Built-in Type
700 mm width type

Slim Ceiling Mounted Duct Type

FBQ60B/FBQ71B

FDKS25EA/FDKS35EA
900/1,100 mm width type

FDKS25CA/FDKS35CA/FDKS50C/FDKS60C

Option
Note: Remote controller cables not included. Cables should be obtained locally.

Standard accessory
Note: Remote controllers other than the standard accessory wireless remote controller cannot be used.

Flexible air discharge unit to fit various forms of space


The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab. It also works with both flexible and ordinary ducts.
Options
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3

Slim and smooth design suits your shallow ceiling


Models in the FDKS-EA series are only 700 mm in width and 21 kg in weight, so are easily installed in limited spaces. Just 200 mm in height, all models can be installed in rooms with as little as 240 mm depth between the drop ceiling and ceiling slab, making them ideal for even shallow ceilings. Great for hotel use! Low operation sound level
(H/L/SL)

Decorative panel Air discharge opening adaptor Canvas bellows and air intake panel Flexible duct Air discharge grille Air discharge chamber

High-performance filter Inspection panel Rear intake blocking pad Air discharge opening flange Rear intake filter chamber Branch duct Low-draft filter chamber

FDKS25

FDKS35

FDKS50

FDKS60

35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)

Standard installation examples In crawl space


6 4 5 2 Air conditioner

With high-efficiency filter With canvas bellows and air intake panel (sold separately)
2 Air conditioner 4 1 3 7 3 5 5 1 1

350 mm or more
6 1

2 Air conditioner 4

540 mm or more

FDKS-EA

425 mm or more Long-life filter Air intake


3

Air blow

Air intake

Long-life filter

Air blow

Air blow

Air intake

45 mm

Ceiling return
2 Air conditioner 6 4

Ceiling return with high-efficiency filter


2 Air conditioner

With ordinary ducts


Ordinary duct (procured locally)

Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home. This means that an air-conditioned welcome awaits when you wake or return. It also means that the indoor temperature can quickly return to your favourite comfort setting.
* Home Leave Operation can be selected for any temperature from 18 to 32C for cooling operation and 10 to 30C for heating operation. * Home Leave Operation function must be set using the remote controller when going to sleep or leaving the house, and after waking up or returning home.

450 mm or more Long-life filter Air intake


8

540 mm or more Air intake


7 1 1

Air conditioner
9 8

Ordinary duct (procured locally)

1 0

460 mm or more

200 mm Only 700 mm


FDKS25EA FDKS35EA FDKS25CA FDKS35CA 200 x 900 x 620 mm 200 x 700 x 620 mm 25 kg 21 kg 3 3 3 8.7 m /min 9.5 m /min 10 m /min 30 Pa 40 Pa

Air blow

Air blow

Air intake

Air blow

To cope with the challenges of L-shaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit. This extends the possibilities for coping with human gathering patterns or sun lighting. At the same time, different types of architectural space can be kept comfortable.

Drain pump is equipped as standard accessory with 250 mm lift.

Dimensions (H x W x D) Weight Airflow rate (H) External static pressure

Air discharge duct* Air discharge grille*

Suspension bolt*

Suction duct*

Air filter

AIR
250 mm

240 mm
Signal receiver wire Length = 1,900 mm

Chamber Signal receiver Air suction grille*

AIR

* Locally obtained parts

Option

Low operation sound level

(H/L)

FBQ60B
L-shaped room U-shaped room Long room

FBQ71B 41/35 dB (A)


Signals from the wireless remote controller are transmitted to the signal receiver.

Suction grille (KDGF19A45)

41/35 dB (A)

Notes: 1. To prevent an increase in operation noise, avoid installing the air suction grille directly below the suction chamber. 2. Grilles, piping connections, ducts, and installation parts should be obtained locally. Slim Ceiling Mounted Duct type FDKS models do not have drain-up pumps. 3. The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature.

21

22

Indoor Unit Lineup Residential Indoor Units with connection to BP units


Wall Mounted Type FTKS25D/FTKS35D

Specifications VRV Indoor Units


Ceiling Mounted Cassette (Round Flow) Type
MODEL
Power supply kcal/h (*1) Cooling capacity Btu/h (*1) kW Power consumption Casing (*1) (*2) 2,500 9,900 2.9 2.8 0.033 3,200 12,600 3.7 3.6 0.033

FXFQ25PVE FXFQ32PVE FXFQ40PVE FXFQ50PVE FXFQ63PVE FXFQ80PVE FXFQ100PVE FXFQ125PVE


1-phase, 220 - 240 V/220 V, 50/60 Hz 4,000 16,000 4.7 4.5 0.047 5,000 19,800 5.8 5.6 0.052 6,300 24,900 7.3 7.1 0.066 8,000 31,700 9.3 9.0 0.093 10,000 39,600 11.6 11.2 0.187 12,500 49,500 14.5 14.0 0.209

kW

Galvanised steel plate m3/min cfm 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5

Standard accessory*

Airflow rate (HH/H/L) Sound level (HH/H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Model

459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1,130/918/706 1,165/989/794 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34

FTKS50F/FTKS60F/FTKS71F

dB(A) mm kg

246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 288X840X840 288X840X840 19.5 6.4 19.5 6.4 12.7 19.5 6.4 12.7 19.5 6.4 12.7 22 9.5 15.9 22 9.5 15.9 25 9.5 15.9 25 9.5 15.9

mm

12.7

VP25 (External Dia, 32/Internal Dia, 25) BYCP125K-W1 Fresh white mm kg 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Standard accessory* * Remote controllers other than the standard accessory wireless remote controller cannot be used.

Panel (Option)

Colour Dimensions (HXWXD) Weight

Stylish flat panel harmonises with your interior dcor


Wall Mounted indoor units achieve quiet sound levels of 22 dB (A). (H/L/SL) Titanium apatite is a photocatalytic material with high adsorption power. Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface. The photocatalyst is activated simply by exposure to light.

Ceiling Mounted Cassette (Compact Multi Flow) Type


MODEL
Power supply kcal/h (*1) Cooling capacity Btu/h (*1) kW Power consumption (*1) (*2) 2,000 7,800 2.3 2.2 0.073

FTKS25D FTKS35D FTKS50F FTKS60F FTKS71F 37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A)
Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room. When there is no movement, it adjusts the temperature by 2C for energy savings.

FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE


1-phase, 220 - 240 V/220 V, 50/60 Hz 2,500 9,900 2.9 2.8 0.073 3,200 12,600 3.7 3.6 0.076 Galvanised steel plate m3/min cfm 9/7 318/247 30/25-32/26 9/7 318/247 30/25-32/26 9.5/7.5 335/265 32/26-34/28 286X575X575 18 6.4 mm 12.7 6.4 12.7 6.4 12.7 6.4 12.7 6.4 12.7 11/8 388/282 36/28-37/29 14/10 493/353 41/33-42/35 4,000 16,000 4.7 4.5 0.089 5,000 19,800 5.8 5.6 0.115

kW

Air filter catches dust

Casing Airflow rate (H/L) Sound level 230 V-240 V (H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Model Panel (Option) Colour Dimensions (HXWXD) Weight mm kg 55X700X700 2.7 55X700X700 2.7

dB(A) mm kg

Titanium Apatite Photocatalytic Air-purifying Filter

When you are in the room

When you go out

These filters are not medical devices. Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter. Bacteria Removal Test Testing method: dropping method Result certificate: No. 012553-1 and 012553-2 Testing organisation: Japan Spinners Inspecting Foundation

VP20 (External Dia, 26/Internal Dia, 20) BYFQ60B8W1 White (6.5Y9.5/0.5) 55X700X700 2.7 55X700X700 2.7 55X700X700 2.7

3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.
* This function is available for FTKS50/60/71F.
A uniform temperature is achieved throughout the entire room.

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

23

24

Specifications VRV Indoor Units


Ceiling Mounted Cassette (Double Flow) Type
MODEL
Power supply kcal/h(*1) Cooling capacity Btu/h(*1) kW Power consumption Casing Airflow rate (H/L) 220 V 240 V m3/min cfm Sound level (H/L) dB(A) mm kg 7/5 247/177 32/27 34/29 9/6.5 318/230 34/28 36/30 9/6.5 318/230 34/28 36/30 (*1) (*2) 2,000 7,800 2.3 2.2 0.077 2,500 9,900 2.9 2.8 0.092

Slim Ceiling Mounted Duct Type (700 mm width type)


MODEL
Power supply kcal/h (*1) Cooling capacity Btu/h (*1) kW Power consumption (FXDQ-PBVE) Power consumption (FXDQ-PBVET) Casing Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) 2 3 Dimensions (HXWXD) BYBC125G-W1 Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm m3/min cfm Pa dB(A) mm kg 33/31/29 200X700X620 23.0 6.4 12.7 8.0/7.2/6.4 282/254/226 (*1) (*2) 16.5/13 582/459 37/32 39/34 26/21 918/741 39/34 41/36 33/25 1,165/883 44/38 46/40 kW kW 2,000 7,800 2.3 2.2 0.086 0.067 with drain pump without drain pump

FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE


1-phase, 220-240 V/220 V, 50/60 Hz 3,200 12,600 3.7 3.6 0.092 4,000 16,000 4.7 4.5 0.130 5,000 19,800 5.8 5.6 0.130 6,300 24,900 7.3 7.1 0.161 8,000 31,700 9.3 9.0 0.209 12,500 49,500 14.5 14.0 0.256

FXDQ20PBVE FXDQ20PBVET

FXDQ25PBVE FXDQ25PBVET
1-phase, 220 -240 V/220 V, 50/60 Hz 2,500 9,900 2.9 2.8 0.086 0.067 Galvanised steel plate 8.0/7.2/6.4 282/254/226 30-10 1 33/31/29 200X700X620 23.0 6.4 12.7 VP20 (External Dia, 26/Internal Dia, 20)

FXDQ32PBVE FXDQ32PBVET
3,200 12,600 3.7 3.6 0.089 0.070

kW

Galvanised steel plate 12/9 424/318 34/29 37/32 12/9 424/318 34/29 37/32

Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Model Panel (Option) Colour Dimensions (HXWXD) Weight

305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 26.0 6.4 26.0 6.4 12.7 26.0 6.4 12.7 31.0 6.4 12.7 32.0 6.4 12.7 35.0 9.5 15.9 47.0 9.5 15.9 48.0 9.5 15.9

8.0/7.2/6.4 282/254/226

mm

12.7

33/31/29 200X700X620 23.0 6.4 12.7

VP25 (External Dia, 32/Internal Dia, 25) BYBC32G-W1 BYBC50G-W1 White (10Y9/0.5) mm kg 53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680 8.0 8.0 8.0 8.5 8.5 9.5 12.0 12.0 BYBC63G-W1

Ceiling Mounted Cassette Corner Type


MODEL
Power supply kcal/h(*1) Cooling capacity Btu/h(*1) kW Power consumption Casing Airflow rate (H/L) Sound level (H/L) 220 V 240 V m3/min cfm dB(A) mm kg mm 11/9 388/318 38/33 40/35 215X1,110X710 31.0 6.4 12.7 (*1) (*2) 2,500 9,900 2.9 2.8 0.066

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


FXKQ32MAVE
3,200 12,600 3.7 3.6 0.066 11/9 388/318 38/33 40/35 215X1,110X710 31.0 6.4 12.7 BYK45FJW1 White (10Y9/0.5)

FXKQ25MAVE

FXKQ40MAVE
4,000 16,000 4.7 4.5 0.076 13/10 459/353 40/34 42/36 215X1,110X710 31.0 6.4 12.7

FXKQ63MAVE

1-phase, 220-240 V/220 V, 50/60 Hz 6,300 24,900 7.3 7.1 0.105 18/15 635/530 42/37 44/39 215X1,310X710 34.0 9.5 15.9 BYK71FJW1 70X1,240X800 8.5 70X1,440X800 9.5

MODEL
Power supply

with drain pump without drain pump kcal/h (*1)

FXDQ40NBVE FXDQ40NBVET
4,000 16,000 4.7 4.5 0.160 0.147

FXDQ50NBVE FXDQ50NBVET
1-phase, 220 -240 V/220 V, 50/60 Hz 5,000 19,800 5.8 5.6 0.165 0.152 Galvanised steel plate

FXDQ63NBVE FXDQ63NBVET
6,300 24,900 7.3 7.1 0.181 0.168

kW

Cooling capacity

Btu/h (*1) kW (*1) (*2)

Galvanised steel plate Power consumption (FXDQ-NBVE) Power consumption (FXDQ-NBVET) Casing Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) 2 3 Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain

kW kW

Dimensions (HXWXD) Machine weight Liquid (Flare) Piping Gas (Flare) connections Drain Model Panel (Option) Colour Dimensions (HXWXD) Weight

m3/min cfm Pa dB(A) mm kg

10.5/9.5/8.5 371/335/300

12.5/11.0/10.0 441/388/353 44-15 1

16.5/14.5/13.0 583/512/459

VP25 (External Dia, 32/Internal Dia, 25)

34/32/30 200X900X620 27.0 6.4

35/33/31 200X900X620 28.0 6.4 12.7 VP20 (External Dia, 26/Internal Dia, 20)

36/34/32 200X1,100X620 31.0 9.5 15.9

mm kg

70X1,240X800 8.5

70X1,240X800 8.5

mm

12.7

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. (FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. 1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.) 2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). 3: Values are based on the following conditions: external static pressure of 10 Pa. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

25

26

Specifications VRV Indoor Units


Ceiling Mounted Duct Type
MODEL
Power supply kcal/h(*1) Cooling capacity Btu/h(*1) kW Power consumption Casing Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm m3/min cfm Pa dB(A) mm kg 9/7.5/6.5 318/265/230
30-100
1

Ceiling Mounted Duct Type


FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
1-phase, 220-240 V/220 V, 50/60 Hz 2,000 7,800 2.3 2.2 0.081 2,500 9,900 2.9 2.8 0.081 3,200 12,600 3.7 3.6 0.085 Galvanised steel plate 9/7.5/6.5 318/265/230
30-100
1

MODEL
Power supply kcal/h (*1) Cooling capacity Btu/h (*1) kW Power consumption Casing (*1) (*2) kW

FXMQ200MAVE
19,800 78,500 23.0 22.4 1.294 Galvanised steel plate m3/min cfm 58/50 2,047/1,765
132-221
1

FXMQ250MAVE
24,800 98,300 28.8 28.0 1.465

1-phase, 220-240 V/220 V, 50/60 Hz

4,000 16,000 4.7 4.5 0.194

5,000 19,800 5.8 5.6 0.215

(*1) (*2)

kW

9.5/8/7 335/282/247
30-100
1

16/13/11 565/459/388
30-160
1

18/16.5/15 635/582/530
50-200
1

Airflow rate (H/L) External static pressure Sound level (H/L) 220 V 240 V

72/62 2,542/2,189
191-270
1

Pa dB(A) mm kg

33/31/29 300X550X700 25.0 6.4 12.7

33/31/29 300X550X700 25.0 6.4 12.7

34/32/30 300X550X700 25.0 6.4 12.7

39/37/35 300X700X700 28.0 6.4 12.7

41/39/37 300X1,000X700 36.0 6.4 12.7

48/45 49/46 470X1,380X1,100 137.0 9.5

48/45 49/46 470X1,380X1,100 137.0 9.5 22.2 PS1B

Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Brazing) Drain

VP25 (External Dia, 32/Internal Dia, 25)

mm

19.1

MODEL
Power supply kcal/h(*1) Cooling capacity Btu/h(*1) kW Power consumption Casing Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm m3/min cfm Pa dB(A) mm kg (*1) (*2) kW

FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE


1-phase, 220-240 V/220 V, 50/60 Hz 6,300 24,900 7.3 7.1 0.230 8,000 31,700 9.3 9.0 0.298/ 10,000 39,600 11.6 11.2 0.376 Galvanised steel plate 19.5/17.5/16 688/618/565
50-200
1

12,500 49,500 14.5 14.0 0.461

14,300 57,000 16.7 16.0 0.461

Ceiling Suspended Type


MODEL
Power supply kcal/h (*1) Cooling capacity Btu/h (*1) kW Power consumption Casing Airflow rate (H/L) Sound level (H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm m3/min cfm dB(A) mm kg 12 /10 424/353 36/31 195X960X680 24.0 6.4 12.7 (*1) (*2) kW 3,200 12,600 3.7 3.6 0.111

FXHQ32MAVE

FXHQ63MAVE
1-phase, 220-240 V/220 V, 50/60 Hz 6,300 24,900 7.3 7.1 0.115 White (10Y9/0.5) 17.5 /14 618/494 39/34 195X1,160X680 28.0 9.5 15.9 VP20 (External Dia, 26/Internal Dia, 20)

FXHQ100MAVE
10,000 39,600 11.6 11.2 0.135

25/22.5/20 883/794/706
50-200
1

32/27/23 1,130/953/812
50-200
1

39/33/28
1

46/39/32
1

1,377/1,165/988 1,624/1,377/1,130
50-200 50-140

42/40/38 300X1,000X700 36.0 9.5 15.9

43/41/39 300X1,000X700 36.0 9.5 15.9

43/41/39 300X1,400X700 46.0 9.5 15.9

44/42/40 300X1,400X700 46.0 9.5 15.9

46/45/43 300X1,400X700 47.0 9.5 15.9

25/19.5 883/688 45/37 195X1,400X680 33.0 9.5 15.9

VP25 (External Dia, 32/Internal Dia, 25)

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. 1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. 1: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure". Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. (FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

27

28

Specifications VRV Indoor Units


Wall Mounted Type
MODEL
Power supply kcal/h(*1) Cooling capacity Btu/h(*1) kW Power consumption Casing Airflow rate (H/L) Sound level (H/L) Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm m /min cfm dB(A) mm kg
3

Connection unit series indoor units


FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVE
1-phase, 220-240 V/220 V, 50/60 Hz 2,000 7,800 2.3 2.2 0.016 2,500 9,900 2.9 2.8 0.022 3,200 12,600 3.7 3.6 0.027 4,000 16,000 4.7 4.5 0.020 5,000 19,800 5.8 5.6 0.027 6,300 24,900 7.3 7.1 0.050

* A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details. * Group control between Connection Unit series equipment within one system is possible. However, group control with the other VRV indoor units is not possible.

(*1) (*2)

Ceiling Suspended Cassette Type


MODEL
Indoor unit Connection unit
Power supply Kcal/h(*1) Cooling capacity Btu/h(*1) (*1) kW Power consumption Casing Indoor unit Airflow rate (H/L) Sound level (H/L) 230 V m /min cfm dB(A) mm kg Liquid Piping connections Gas Drain mm
3

kW

White (3.0Y8.5/0.5) 7.5/4.5 265/159 35/29 290X795X230 11.0 6.4 12.7 8/5 282/177 36/29 290X795X230 11.0 6.4 12.7 9/5.5 318/194 37/29 12/9 424/318 39/34 15/12 530/424 42/36 19/14 671/494 46/39

FXUQ71MAV1 BEVQ71MAVE
7,100 28,300 8.3 8.0 0.189

FXUQ100MAV1 BEVQ100MAVE
1-phase, 220-240 V, 50 Hz 10,000 39,600 11.6 11.2 0.298 White (10Y9/0.5)

FXUQ125MAV1 BEVQ125MAVE
12,500 49,500 14.5 14.0 0.298

290X795X230 290X1,050X230 290X1,050X230 290X1,050X230 11.0 6.4 12.7 14.0 6.4 12.7 14.0 6.4 12.7 14.0 9.5 15.9

(*2)

kW

VP13 (External Dia, 18/Internal Dia, 13)

19/14 671/494 40/35 165X895X895 25

29/21 1,024/741 43/38 230X895X895 31 9.5 (Flare) 15.9 (Flare) VP 20 (External Dia. 26/Internal Dia. 20)

32/23 1,130/812 44/39 230X895X895 31

Floor Standing Type/Concealed Floor Standing Type


MODEL
Power supply kcal/h(*1) 2,000 7,800 2.3 2.2 0.049 2,500 9,900 2.9 2.8 0.049

Dimensions (HXWXD) Machine weight

FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
1-phase, 220-240 V/220 V, 50/60 Hz 3,200 12,600 3.7 3.6 0.090 4,000 16,000 4.7 4.5 0.090 5,000 19,800 5.8 5.6 0.110 6,300 24,900 7.3 7.1 0.110

FXLQ
Cooling capacity

Btu/h(*1) kW (*1) (*2)

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Power consumption Casing

kW

FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate m3/min cfm 7/6 247/212 35/32 37/34 mm 7/6 247/212 35/32 37/34 8/6 282/212 35/32 37/34 11/8.5 388/300 38/33 40/35 14/11 494/388 39/34 41/36 16/12 565/424 40/35 42/37

FXNQ

Airflow rate (H/L) 220 V 240 V Dimensions (HXWXD) Machine weight FXLQ FXNQ FXLQ FXNQ Liquid (Flare) Piping connections Gas (Flare) Drain

Sound level (H/L)

dB(A)

600X1,000X222 600X1,000X222 600X1,140X222 600X1,140X222 600X1,420X222 600X1,420X222 610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220 25.0 19.0 6.4 12.7 30.0 23.0 6.4 12.7 21O.D. 30.0 23.0 6.4 12.7 36.0 27.0 6.4 12.7 36.0 27.0 9.5 15.9

kg

25.0 19.0 6.4

mm

12.7

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Equivalent piping length: 7.5 m Level difference: 0 m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) Sound level: (FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. (FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

29

30

Specifications Residential Indoor Units with connection to BP units


Residential indoor units with connection to BP units
Residential indoor units can be connected to the VRVIII single outdoor unit series by BP units.

Ceiling Mounted Built-in Type


MODEL
Power supply Airflow rates (H) Sound levels (H/L)* m3/min (cfm) dB (A)

FBQ60BV1
1-phase, 220 -240 V, 50 Hz 17.0 (600) 41/35 2 steps Microcomputer control mm kg 6.4 mm 12.7 I.D 25XO.D 32 Both liquid and gas pipes BYBS71DJW1 White mm kg 55X1,100X500 4.5 300X1,000X800 41

FBQ71BV1
19.0 (670)

Ceiling Mounted Cassette Type


MODEL
Power supply Airflow rates (H) Sound levels (H/L)* Fan speed Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Heat insulation Model Panel (Option) Colour Dimensions (HXWXD) Weight
Note: * For 220 V operation.

FCQ35BVE
m3/min (cfm) dB (A) 14.0 (494) 33/29

FCQ50BVE
15.0 (530)

FCQ60BVE

FCQ71BVE

Fan speed Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Heat insulation

1-phase, 220-240 V/220 V, 50/60 Hz 19.0 (671) 35/30 2 steps Microcomputer control mm kg 6.4 mm 9.5 12.7 I.D 25XO.D 32 Both liquid and gas pipes BYC125K-W1 White mm kg 40X950X950 5 230X840X840 24 9.5 15.9

9.5 15.9

Model Panel (Option) Colour Dimensions (HXWXD) Weight


Note: * For 220 V operation.

Slim Ceiling Mounted Duct Type


MODEL
Power supply Airflow rates (H) m3/min (cfm) dB (A) 8.7 (307)

FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB


1-phase, 220-240 V/220 V, 50/60 Hz 9.5 (335) 35/31/29 5 steps, quiet and automatic Microcomputer control mm kg 200X700X620 21 200X900X620 25 6.4 mm 9.5 VP20 (External Dia. 26/Internal Dia. 20) Both liquid and gas pipes Pa 30 40 12.7 15.9 27 200X1,100X620 30 10.0 (353) 12.0 (424) 37/33/31 16.0 (565) 38/34/32

Ceiling Mounted Cassette (Compact Multi Flow) Type


600 x 600

Sound levels (H/L/SL)* Fan speed

MODEL
Power supply Airflow rates (H) Sound levels (H/L)* Fan speed Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Heat insulation Model Panel (Option) Colour Dimensions (HXWXD) Weight mm kg mm mm kg m3/min (cfm) dB (A)

FFQ25BV1B
9.0 (318) 29.5/24.5

FFQ35BV1B
10.0 (353) 32/25 2 steps

FFQ50BV1B
12.0 (424) 36/27

FFQ60BV1B
15.0 (530) 41/32

Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Heat insulation External static pressure

1-phase, 220-240 V, 50 Hz

Microcomputer control 286X575X575 17.5 6.4 9.5 VP20 (External Dia. 26/Internal Dia. 20) Both liquid and gas pipes BYFQ60B8W1 White 55X700X700 2.7 12.7

Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.

Wall Mounted Type


MODEL
Power supply Front panel colour Airflow rates (H) Sound levels (H/L/SL) Fan speed Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Heat insulation mm 9.5 18.0 Both liquid and gas pipes mm kg 283X800X195 9 6.4 12.7 15.9 m3/min (cfm) dB (A) 8.7 (307) 37/25/22 8.9 (314) 39/26/23

FTKS25DVM FTKS35DVM FTKS50FVM


White 14.7 (519) 43/34/31

FTKS60FVM

FTKS71FVM

1-phase, 220 -240 V/220 V, 50/60 Hz

Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

16.2 (572) 45/36/33

17.4 (614) 46/37/34

5 steps, quiet and automatic Microcomputer control 290X1,050X238 12

31

32

Specifications BP Units for connection to units residential indoor


BP units for connection to residential indoor units
A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to residential indoor units. A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room spaces. A BP unit is easy to disassemble, making repairing and recycling simple.

Specifications SpecificationsIndoor Units Outdoor Units


single outdoor unit series

MODEL
Power supply kcal/h(*1)

RSXQ8PY1
19,400 76,800 22.5 22.4 5.24 20-100

RSXQ10PY1
24,300 96,200 28.2 28.0 7.90 14-100

RSXQ12PY1
29,000 115,000 33.7 33.5 8.93 14-100

RSXQ14PY1
34,600 137,000 40.2 40.0 12.4 10-100

RSXQ16PY1
39,000 155,000 45.3 45.0 14.2 10-100

RSXQ18PY1
42,400 168,000 49.3 49.0 16.4 9-100

3-phase 4-wire system, 380415 V, 50 Hz Btu/h(*1) kW (*1) (*2)

MODEL
Power supply Number of ports Power consumption Running current Dimensions (HXWXD) Machine weight W A mm kg

BPMKS967B3B
1-phase, 220-240 V/220 V, 50/60 Hz 3 (connectable to 1-3 indoor units) 10 0.05 180X294 (+356*)X350 8

BPMKS967B2B
2 (connectable to 1-2 indoor units)

Cooling capacity (*1)(*2)

Power consumption (*2) Capacity control Casing colour Compressor Type Motor output

kW %

Ivory white (5Y7.5/1) Hermetically sealed scroll type kW m3/min mm kg dB(A) CDB kg mm 4.7 9.5 (Brazing) 19.1 (Brazing) 4.9 9.5 (Brazing) 22.2 (Brazing) 6.0 12.7 (Brazing) 28.6 (Brazing) Type Charge Liquid Gas 188 57 3.6X1 180 1,680X930X765 232 58 268 60 5 to 43 R-410A 6.3 12.7 (Brazing) 28.6 (Brazing) 6.5 12.7 (Brazing) 28.6 (Brazing) 6.7 15.9 (Brazing) 28.6 (Brazing) 312 60 (1.4+4.5)X1 185 (1.8+4.5)X1 233 (1.4+4.5+4.5)X1 233 1,680X1,240X765 312 60 324 63 (2.7+4.5+4.5)X1 233 (2.8+4.5+4.5)X1 239

7.5

Airflow rate Dimensions (HXWXD) Machine weight Sound level Operation range Refrigerant

Number of wiring connections Piping connections (Brazing) Liquid Main Branch Gas Main Branch Heat insulation Connectable indoor units Min. rated capacity of connectable indoor units Max. rated capacity of connectable indoor units kW kW mm mm mm mm

3 for power supply (including earth wiring), 2 for interunit wiring (outdoor unit-BP, BP-BP), 4 for interunit wiring (BP-indoor unit) 9.5X1 6.4X3 19.1X1 15.9X3 Both liquid and gas pipes 2.5 kW class to 7.1 kW class residential indoor units 2.5 20.8 14.2 15.9X2 6.4X2

Piping connections

Note: Specifications are based on the following conditions; Cooling: (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB. (*2) Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Equivalent piping length: 7.5 m Level difference: 0 m

Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Note: * Total auxiliary piping length.

Outdoor unit combinations


Total capacity index of connectable indoor units* Model name

kW 22.4 28.0 33.5 40.0 45.0 49.0

HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP

Capacity index 50%

Combination (%)* 100% 130%

Maximum number of connectable indoor units

RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1

200 250 300 350 400 450

100 125 150 175 200 225

200 250 300 350 400 450

260 325 390 455 520 585

13 16 19 22 26 29

* Total capacity index of connectable indoor units must be 50%130% of the capacity index of the outdoor unit.

Combination ratio =

Total capacity index of the indoor units Capacity index of the outdoor unit

33

34

Option List VRV Indoor Units


Ceiling Mounted Cassette (Round Flow) Type
No.
1 2 3

Ceiling Mounted Duct Type


No. Item
1 KAFP556B160 KAFP557B160 KAFP552B160 KAFP553B160 2 3 4 5 6 7 KDJP55B160 KDTP55K160 Drain pump kit High efficiency filter Filter chamber Long life replacement filter Long life filter chamber kit White Service panel Air discharge adaptor Fresh white Brown 65% 90% KAF372AA36 KAF373AA36 KDDF37AA36 KAF371AA36 KAF375AA36 KTBJ25K36W KTBJ25K36F KTBJ25K36T KDAJ25K36A KAF372AA56 KAF373AA56 KDDF37AA56 KAF371AA56 KAF375AA56 KTB25KA56W KTBJ25K56F KTBJ25K56T KDAJ25K56A

Item

Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P


BYCP125K-W1 KDBH55K160F KDBP55H160FA KAFP556B80 KAFP557B80 KAFP552B80 KAFP553B80 KDDFP55B160 KAFP551K160 KAFP55B160 KAFP55H160H KDDP55B160 KDDP55B160K KDDP55X160 KDJP55B80 KKSJ55KA160 KDTP55K80

Type

5 6 7 8

Decoration panel Sealing member of air discharge outlet Panel spacer High efficiency filter unit 65% High efficiency filter unit 90% Replacement high efficiency filter 65% Replacement high efficiency filter 90% Filter related Filter chamber Long life replacement filter Non-woven type Ultra long-life filter Replacement ultra long-life filter Without T shape and fan Chamber type With T shape without fan Fresh air intake kit Direct installation type Branch duct chamber Chamber connection kit Insulation kit for high humidity

FXMQ20P FXMQ25P FXMQ32P

FXMQ40P

FXMQ50P FXMQ63P FXMQ80P


KAF372AA80 KAF373AA80 KDDF37AA80 KAF371AA80 KAF375AA80 KTB25KA80W KTBJ25K80F KTBJ25K80T KDAJ25K71A

FXMQ100P FXMQ125P FXMQ140P


KAF372AA160 KAF373AA160 KDDF37AA160 KAF371AA160 KAF375AA160 KTB25KA160W KTBJ25K160F KTBJ25K160T KDAJ25K140A

FXMQ200MA FXMQ250MA
KDU30L250VE KAFJ372L280 KAFJ373L280 KDJ3705L280 KAFJ371L280

Ceiling Suspended Type


No. Item
Drain pump kit Replacement long-life filter (Resin net) L-type piping kit (for upward direction)

Type

FXHQ32MA
KDU50N60VE KAF501DA56 KHFP5MA63

FXHQ63MA
KDU50N125VE KAF501DA80 KHFP5MA160

FXHQ100MA
KAF501DA112

Ceiling Mounted Cassette (Compact Multi Flow) Type


No.
1 2 3 4 5

Item

Type

FXZQ20M

FXZQ25M

FXZQ32M
BYFQ60B8W1 KDBH44BA60 KDBQ44BA60A KAFQ441BA60 KDDQ44XA60

FXZQ40M

FXZQ50M

2 3

Decoration panel Sealing member of air discharge outlet Panel spacer Replacement long-life filter Fresh air intake kit Direct installation type

Wall Mounted Type


No.
1

Item
Drain pump kit

Type FXAQ20MA

FXAQ25MA

FXAQ32MA

FXAQ40MA

FXAQ50MA

FXAQ63MA

K-KDU572EVE

Ceiling Mounted Cassette (Double Flow) Type


No.
1

Type FXCQ20M Item


Decoration panel

FXCQ25M FXCQ32M

FXCQ40M

FXCQ50M

FXCQ63M
BYBC63G-W1 KAFJ532G80 KAFJ533G80 KDDFJ53G80 KAFJ531G80

FXCQ80M FXCQ125M
BYBC125G-W1 KAFJ532G160 KAFJ533G160 KDDFJ53G160 KAFJ531G160

Floor Standing Type


No. Item
Long life replacement filter

Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA


KAFJ361K28 KAFJ361K45 KAFJ361K71

2
Note:

Filter related

BYBC32G-W1 High efficiency filter 65% 1 KAFJ532G36 High efficiency filter 90% 1 KAFJ533G36 Filter chamber bottom suction KDDFJ53G36 Long life replacement filter KAFJ531G36

BYBC50G-W1 KAFJ532G56 KAFJ533G56 KDDFJ53G56 KAFJ531G56

1 Filter chamber is required if installing high efficiency filter.

Concealed Floor Standing Type


No. Item
Long life replacement filter

Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA


KAFJ361K28 KAFJ361K45 KAFJ361K71

Ceiling Mounted Cassette Corner Type


No.
1

Item
Panel related Air inlet and air discharge outlet related

Type
Decoration panel Panel spacer Long life replacement filter Air discharge grille Air discharge blind panel Flexible duct (with shutter)

FXKQ25MA

FXKQ32MA
BYK45FJW1 KPBJ52F56W KAFJ521F56 K-HV7AW KDBJ52F56W KFDJ52FA56

FXKQ40MA

FXKQ63MA
BYK71FJW1 KPBJ52F80W KAFJ521F80 K-HV9AW KDBJ52F80W KFDJ52FA80

Ceiling Suspended Cassette Type


No. 1 2 3 4 5
Type Item Replacement long-life filter Sealing member of air discharge outlet Decoration panel for air discharge Vertical flap kit L-shape piping kit

FXUQ71MA
KDBH49FA80 KDBT49FA80 KDGJ49FA80

FXUQ100MA
KAF495FA140

FXUQ125MA

(*1)

KDBH49FA140 KDBT49FA140 KDGJ49FA140 KHFP49MA140

Slim Ceiling Mounted Duct Type (700 mm width type)


No.
1

Note: (*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.

Type Item
Insulation kit for high humidity

FXDQ20PB

FXDQ25PB
KDT25N32

FXDQ32PB

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


No.
1

Type Item
Insulation kit for high humidity

FXDQ40NB
KDT25N50

FXDQ50NB

FXDQ63NB
KDT25N63

35

36

Option List Residential Indoor Units with connection to BP units


Ceiling Mounted Cassette Type
No.
1 2 3 4 5 6 7 8

Wall Mounted Type


FCQ50BVE FCQ60BVE FCQ71BVE No.
1

Item
Decoration panel Panel spacer

Type

FCQ35BVE

Item
Titanium apatite photocatalytic air-purifying filter

Type FTKS25DVM

FTKS35DVM

FTKS50FVM

FTKS60FVM
KAF952B42

FTKS71FVM

Chamber Without T-shaped pipe and fan*1 type With T-shaped pipe, without fan*2 Direct installation type*3 (Colourimetric method 65%) High-efficiency filter (Colourimetric method 90%) (Colourimetric method 65%) Replacement high-efficiency filter (Colourimetric method 90%) High-efficiency filter chamber Replacement long-life filter Branch duct chamber Fresh air intake kit

BYC125K-W1 KDBP55H160WA KDDP55D160 KDDP55D160K KDDJ55X160 KAFP556D80 KAFP557D80 KAFP552H80 KAFP553H80 KDDF55DA160 KAF551KA160 KDJ55K80

KAF970A46

Note: Filter is a standard accessory. It should be replaced approximately 3 years.

Notes: *1. With a suction chamber. Fresh air intake is from 2 holes on the sides of the connection chamber. (This method should be selected if a wireless remote controller is used.) *2. Without a suction chamber. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. (A wireless remote controller cannot be used in this case.) *3. Without a suction chamber. Fresh air intake is directly from a hole on the main unit.

Ceiling Mounted Cassette (Compact Multi Flow) Type


No.
1 2 3 4 5

BP Units for connection to units residential indoor


FFQ60BV1B No.
1

Item
Decoration panel Replacement long-life filter Fresh air intake kit Direct installation type Sealing member for air discharge outlet Panel spacer

Type

FFQ25BV1B

FFQ35BV1B

FFQ50BV1B

BYFQ60B8W1 KAFQ441BA60 KDDQ44XA60 KDBH44BA60 KDBQ44BA60A

Item
REFNET joint

Type

BPMKS967B2B
KHRP26A22T

BPMKS967B3B

Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.

Ceiling Mounted Built-in Type


No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Item
Decoration panel Service access panel

Type

FBQ60BV1

FBQ71BV1

(Colourimetric method 65%) (Colourimetric method 90%) Replacement long-life filter Resin net Filter chamber for bottom suction Filter chamber for rear suction Canvas duct 150 Discharge grille 200 150 Discharge chamber 200 Branch duct 150 200 150 Flexible duct 200 Blind board Adaptor for discharge Flange for suction High-efficiency filter

BYBS71DJW1 KTBJ25L80W KAF252LA80 KAF253LA80 KAFJ251K80 KAJ25LA80D KAJ25LA80B KSAJ25K80 K-DG5DW K-DG9DW K-DGC5D K-DGC9D K-DDV20A K-FDS151C(1m)/K-FDS152C(2m)/K-FDS153C(3m)/K-FDS154C(4m)/K-FDS155C(5m)/K-FDS156C(6m) K-FDS201C(1m)/K-FDS202C(2m)/K-FDS203C(3m)/K-FDS204C(4m)/K-FDS205C(5m)/K-FDS206C(6m) KBBJ25KA80 KDAJ25K71 KDJ2507K80

SpecificationsIndoor Units Outdoor Units


Type Item
REFNET header Distributive piping REFNET joint

RSXQ8PY1

RSXQ10PY1

RSXQ12PY1

RSXQ14PY1

RSXQ16PY1

RSXQ18PY1

KHRP26M22H (Max. 4 branch) KHRP26M33H (Max. 8 branch) KHRP26A22T KHRP26A33T KHFP22B8P KHFP22B10P KHFP22B12P

KHRP26M22H (Max. 4 branch) KHRP26M33H (Max. 8 branch) KHRP26M72H (Max. 8 branch) KHRP26A22T KHRP26A33T KHRP26A72T KHFP22B16P KWC26C450 BHGP26A1 KHFP22B18P

Slim Ceiling Mounted Duct Type


No.
1 2

Auxiliary pipe set*1 Central drain pan kit Digital pressure gauge kit

Item
Suction grille Insulation kit for high humidity

Type FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB


KDGF19A45 KDT25N32 KDT25N50 KDT25N63

KWC26C280

Note: *1. Auxiliary pipe sets are not attached to the outdoor units. If neccesary, use the optional accessories.

37

38

Control Systems Individual Control Systems for VRV Indoor Units


Navigation remote controller (Wired remote controller) (Option)
Large buttons and arrow keys for easy operation. Guide on display gives an explanation of each setting. Backlight and dot matrix LCD display for easy viewing. Weekly schedule timer can be set up easily. 10 display languages are available. (English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian and Turkish)
Signal receiver unit
(Separate type)

Wireless remote controller (Option)


The same operation modes and settings as with wired remote controllers are possible. A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is included. A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow, Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted type is mounted into the indoor unit. Signal receiver unit can be installed on the panel
ex. Ceiling Mounted Cassette (Round Flow) type

BRC1E61

Wired remote controller (Option)


Displays current airflow, swing, temperature, operating mode and timer settings.

Wired remote controller with weekly schedule timer (Option)


Adds weekly schedule timer function.

Wireless remote controller *Wireless remote controller and signal receiver unit are sold as a set. *Refer to page 43 for the name of each model.

Signal receiver unit


(Installed type)

Simplified remote controller (Option)


The remote controller has centralised its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms. The exposed type remote controller is fitted with a thermostat sensor.

BRC1C62

BRC1D61 Notes: 1. Standard remote controllers (BRC1C62) not required. 2. If the BRC1D61 is connected to the centralised remote controllers (DCS303A51, DCS302CA61, DCS301BA61, DST301BA61), the schedule function is not available. Concealed type
(For hotel use) (BRC3A61)

Exposed type
(BRC2C51)

The concealed type remote controller smartly fits into a night table or console panel in a hotel room.

The wired remote controller supports a indoor units Wide variation of remote controllers for wide range of control functions Wide variation of remote controllers for VRV indoor units indoor units
Control by two remote controller

1
Group control
Outdoor unit

Equipment related to the central control

One remote controller can control the operation of max.16 indoor units at the same time.

The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely. (The last command has a priority.) Of course, the group control by two remote controller is also possible.

FXFQ Navigation remote controller


(Wired remote controller) (BRC1E61)

FXZQ

FXCQ

FXKQ

FXDQ

FXMQ

FXHQ

FXAQ

FXL(N)Q

FXUQ

Wired remote controller


Remote controller Remote controller Indoor unit

(BRC1C62)

Remote control

The wiring of remote controller can be extended to max. 500 m and it is possible to install the remote controllers for the different indoor units in one place.
Remote controller

Wired remote controller with weekly schedule timer


(BRC1D61)

Wireless remote controller*

3 Control for the combined operation


Forced OFF input Heat Reclaim Ventilator Remote controller Remote controller Remote controller Remote controller Remote controller

(Installed type signal receiver unit)

The operation of the Heat Reclaim Ventilator can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.

Wireless remote controller*


(Separate type signal receiver unit)

4 1 2 3 4

Expansion of system control

Simplified remote controller


(Exposed type) (BRC2C51)

The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.

Simplified remote controller


(Concealed type: for Hotel use) (BRC3A61)

*Refer to page 43 for the name of each model.

39

40

Control Systems Advanced Control Systems for VRV Indoor Units


PCMCIA Flash Memory
CSV output of power proportional distribution results (Option)

DCS601C51
Dio Unit DEC102A51 (Option) Di Unit DEC101A51 (Option)

Communication functions in the user-friendly icon-based multilingual controller simplify centralised control of the VRV system.
Function 5
Input (Lights) Set temperature change command Input (Key signal General purpose ADP) OFF command

Function 1
System
Remote monitoring and control

Colour LCD touch panel icon display Small manageable size Simplified engineering Multi language (English, French, Italian, German, Spanish, Dutch,
Portuguese, Chinese and Korean) Yearly schedule PPD (Power Proportional Distribution function) (Option) Auto heat/cool change-over Temperature limitation Enhanced history function Air Conditioning Network Service System (Optional Maintenance Service) Simple Interlock Function

Function 1 Function 2 Function 3 Function 4 Function 5 Function 6

Support for centralised control from elsewhere using a PC with a Web browser (Option) Sending of e-mail alerts to a specified address when malfunctions occur (Option) Built-in modem for connecting to Air Conditioning Network Service System (Option) Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option) Management of facilities/equipment other than A/C units (By adding Dio unit or Di unit)
Simple Interlock Function

Function 6

Function 2
Malfunction report by E-mail
Mobile Phone PC

Air Conditioning Network Service System modem for connections

Pi Port Connection to power consumption metre when using power proportional distribution function. (Option) RS-232C Heat Reclaim Ventilator

Function 3

Via internet

D -NET

System Components ACC centre


Air Conditioning Network Service System (Optional Maintenance Service)

Indoor Unit D -NET Plus Adaptor DCS601A52 (Option)

Function 4

Number of indoor units expanded from 64 to 128.

Centralised Control Systems for VRV Indoor Units


Up to 64 groups of indoor units (128 units) can be centrally controlled. Optional controllers for centralised control can be combined freely, and system can be designed in accordance with building scale and purpose. System integration with various air-conditioning peripheral equipment, such as a Heat Reclaim Ventilator, is easy. Wiring can be run up to a total length of 2 km, and adapts easily to large-scale system expansion.

Residential central remote controller* (Option) Max. 16 groups of indoor units can be easily controlled with the large LCD panel.
Max. 16 groups (128 indoor units) controllable Backlight and large LCD panel for easy readability ON/OFF, temperature settings and scheduling can
All indoor units can be turned on or off at once with ALL button. Each group has a dedicated button for convenience. Outside temperature display

Unified on/off controller (DCS301BA61) Connection of up to 8 units possible Address setting of central control can be performed from the remote controller.

DCS303A51

be controlled individually for indoor units.

* For residential use only. Cannot be used with other centralised control equipment.

Independent and centralised control of a Heat Reclaim Ventilator is possible.

Central remote controller (Option) Max. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
Max. 64 groups (128 indoor units) controllable Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers, which can control from 2 different places. Zone control Malfunction code display Max. wiring length 1,000 m (Total: 2,000 m) Connectable with Unified ON/OFF controller, schedule timer and BMS system Airflow volume and direction can be controlled individually for indoor units in each group operation. Ventilation volume and mode can be controlled for the Heat Reclaim Ventilator. Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.

Connectable number of centralised control equipment Central remote controller Unified on / off controller Schedule timer 2 units 8 units 1 unit Group control of up to 16 units is possible (group control via automatic address setting)

DCS302CA61

Unified ON/OFF controller (Option)


System without remote control is also available.

Max. 16 groups of indoor units can be operated simultaneously/individually.


Max. 16 groups (128 indoor units) controllable 2 remote controllers can be used to control from 2 different places. Operating status indication (Normal operation, Alarm) Centralised control indication

Forced shut-down input

Central control adaptor kit (DTA107A55)

Wiring adaptor for other airconditioners (DTA103A51)

Outdoor-air processing unit can be connected.

Max. wiring length 1,000 m (Total: 2,000 m) Compact size casing (Thickness: 16 mm) Connectable with Central Remote controller, Schedule timer and BMS system

DCS301BA61

Central remote controller (DCS302CA61) Up to 2 units connectable

Interface adaptor for SkyAir series (built-in indoor unit) (DTA102A52)

Schedule timer (Option) Max. 128 indoor units can be operated as programmed schedule.
Max. 128 indoor units controllable When used in combination with a central remote controller, a maximum of 8 weekly schedule patterns can be set, while the central controller can be used to select desired zones. Up to 2 ON/OFF pairs can be set per day. Max. 48 hours back up power supply Max. wiring length 1,000 m (Total: 2,000 m) Compact size casing (Thickness: 16 mm) Connectable with Central Remote controller, Unified ON/OFF controller and BMS system

6 cores Schedule timer (DST301BA61) 1 unit connection possible ; 8 weekly schedule control patterns possible

7 cores max.

Interlink Building Management System (host computer monitor panel) also possible

Unification adaptor for computerised control (DCS302A52)


Certain indoor units limit the functions of some control systems.

DST301BA61

For more details, please refer to the Engineering Data Book.

41

42

Option List Control Systems


Operation Control System Optional Accessories
For VRV indoor unit use
No.
1 2 3 4 5 6 7-1 7-2 8 9 10 11

System Configuration
No. Item
Residential central remote controller Central remote controller Electrical box with earth terminal (3 blocks) Unified ON/OFF controller Electrical box with earth terminal (2 blocks) Noise filter (for electromagnetic interface use only) Schedule timer 5-room centralised controller for residential indoor units Interface adaptor for residential indoor units Interface adaptor for SkyAir-series Central control adaptor kit
For FTKS-D/F, FDKS-EA/C(A) For FTKS-D/F, FDKS-EA/C(A) For FCQ-B, FFQ-B, FBQ-B For SkyAir, FD(Y)M-FA, FDY-KA FDYB-KA, FVY(P)J-A, FXUQ-MA For UAT(Y)-K(A),FD-K

Model No.
Note 3

Function
Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF, temperature settings and scheduling can be controlled individually for indoor units. Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system.

Type Item
Wireless type Remote controller Wired type

FXFQ-P

FXZQ-M

FXCQ-M FXKQ-MA FXDQ-PB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-MA FXLQ-MA FXUQ-MA FXDQ-NB FXNQ-MA
BRC4C63 BRC4C66 BRC4C66 BRC1C62 BRC1E61 BRC1D61 BRC2C51 BRC3A61 KRP1B61 KRP2A61 KRP1B61 KRP2A61 KRP1B56 KRP2A53 KRP4A54 KRP1C64 KRP2A61 KRP1B61 KRP2A61 KRP1BA54 KRP2A62 KRP4AA52 KRP2A61 BRC2C51 BRC3A61 KRP1B61 KRP2A61 KRP2A62 KRP4AA53 BRC4C64 BRC7EA66 BRC7EA619 BRC4C64 BRC7CA529W

DCS303A51
Note 2

2 2-1 3 3-1 3-2 4 5

DCS302CA61 KJB311AA
Note 2

BRC7F635F BRC7E531W BRC7C67

Navigation remote controller (Wired remote controller) Wired remote controller with weekly schedule timer Simplified remote controller (Exposed type) Remote controller for hotel use (Concealed type) Adaptor for wiring Wiring adaptor for electrical appendices (1) Wiring adaptor for electrical appendices (2) Remote sensor (for indoor temperature) Installation box for adaptor PCB External control adaptor for outdoor unit Adaptor for multi tenant KRP1C63 KRP2A62 KRP4AA53 KRCS01-4B
Notes 2, 3

DCS301BA61 KJB212AA KEK26-1A


Note 2

Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.

KRP1BA57 KRP2A62 KRP4AA53

DST301BA61
Note 4

Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day. Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.

KRP4AA51 KRP4AA51 KRCS01-1B

KRP4AA51 KRP4AA51 KRCS01-4B

KRP4AA51 KRP4AA51 KRCS01-1B

KRC72 KRP928BB2S DTA112BA51 DTA102A52 DTA107A55 DTA103A51

KRP1H98 DTA104A62 DTA114A61

Notes 4, 6

KRP1BA101 DTA104A62

Notes 2, 3

KRP1B96

Notes 4, 6

KRP1BA101 KRP4A96 DTA104A53

Notes 2, 3

Note 3

KRP1CA93 KRP4AA93 DTA104A62

Notes 2, 3

KRP1BA97

DTA104A61 DTA104A61

DTA104A61 DTA104A61 DTA114A61

DTA104A61 DTA104A61 DTA114A61

Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be controlled.

7 8 9

Notes: 1. Installation box is necessary for each adaptor marked . 2. Up to 2 adaptors can be fixed for each installation box. 3. Only one installation box can be installed for each indoor unit. 4. Up to 2 installation boxes can be installed for each indoor unit. 5. Installation box is necessary for second adaptor. 6. Installation box is necessary for each adaptor.

Wiring adaptor for other air-conditioner D -NET

Up to 1024 units can be centrally controlled in 64 different groups. DTA109A51 Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16) apply to each adaptor. Fixing plate for DTA109A51

10

Expander Adaptor Mounting plate

10-1

KRP4A92

For Residential indoor unit use


No.
1 2 3 4 5 6 7

Type Item
Remote controller Adaptor for wiring Wiring adaptor for electrical appendices Installation box for adaptor PCB Remote sensor (for indoor temperature) Wiring adaptor for time clock/remote controller Note 5 (Normal open pulse contact/normal open contact) Remote controller loss prevention chain Wired typeNote 1 Wireless type

FCQ-B

FFQ-B
BRC1C61 BRC7E531W
Note 4

FBQ-B

FDKS-EA FDKS-C(A)

Note 2

FTKS-D FTKS-F

Notes: 1. Installation box for adaptor must be obtained locally. 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary. For residential indoor units, an interface adaptor (KRP928BB2S or DTA112BA51) is required for each indoor unit. 3. For residential use only. Cannot be used with other centralised control equipment. 4. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.

BRC7C613W
Note 3

KRP1BA57
Note 3

KRP1BA57
Note 4

KRP1BA54 KRP4AA51

KRP4AA53 KRP1B98

KRP4AA53 KRP1BA101 KRCS01-1B


Building Management System


No.
KRP413AB1S KKF917A4
1 1-1 1-2 1-3 1-1 1-4 Electrical box with earth terminal (4 blocks) 128 units 2 Basic Number of Hardware units to be connected 256 units 512 units 768 units 1024 units PPD Option Software Web ECONO Optional DIII Ai unit Di unit Dio unit intelligent Touch Controller Basic Option Software

Item
Hardware intelligent Touch Controller Hardware DIII-NET plus adaptor PPD Web

Model No.
DCS601C51 DCS601A52 DCS002C51 DCS004A51 KJB411A DAM602B52 DAM602B51 DAM602B51x2 DAM602B51x3 DAM602B51x4 DAM002A51 DAM004A51 DAM003A51 DAM101A51 DEC101A51 DEC102A51 Power Proportional Distribution function

Function
Air-Conditioning management system that can be controlled by a compact all-in-one unit. Additional 64 groups (10 outdoor units) is possible. PPD: Power Proportional Distribution function Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC. Wall embedded switch box.

Notes: 1. Wiring for wired remote controller should be obtained locally. 2. A wireless remote controller is a standard accessory for FDKS and FTKS models. 3. Installation box for adaptor PCB (KRP1B98) is necessary. 4. Installation box for adaptor PCB (KRP1BA101) is necessary. 5. Time clock and other devices should be obtained locally.

Air conditioner management system that can be controlled by personal computers.

intelligent Manager III 2-1 2-2 2-3 2-4 2-5 2-6 3 3-1 3-2 4 5 6 7 8

Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC. ECONO (Energy saving functions.) External temperature sensor for intelligent Manager III. 8 pairs based on a pair of On/Off input and abnormality input. 4 pairs based on a pair of On/Off input and abnormality input. Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through BACnet communication.

Communication line

*1 Interface for use in BACnet

DMS502B51 DAM411B51 DAM412B51

Optional DIII board Optional Di board


*2 Interface for use in LONWORKS

Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable independently. Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable independently. Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through LONWORKS communication.

DMS504B51 DPF201A51 DPF201A52 DPF201A53 DCS302A52

Contact/analogue signal

Parallel interface Basic unit Temperature measurement units Temperature setting units Unification adaptor for computerised control

Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to 4 units. Enables temperature measurement output for 4 groups; 0-5VDC. Enables temperature setting input for 16 groups; 0-5VDC. Interface between the central monitoring board and central control units.

Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). *2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries. *3. Installation box for adaptor must be obtained locally.