You are on page 1of 2

Flatpack2 48/3000

Rectifier Module

Versatile and powerful solution for any application


The combination of cost-effective design, power density and reliability makes the Flatpack2 a product family that truly stands outs and provides unparalleled network availability. The versatility of the Flatpack2 rectifier means that it can be used in a wide variety of 48VDC and 24VDC applications across the globe.

Applications
Wireless, fiber and fixed line communication Todays communications demand state of the art, cost effective and compact DC power systems. Flatpack2 delivers an industry leading power density and superb reliability at lowest lifetime cost Broadband and network access Increasing network speed demands flexible and expandable DC power solutions. The Flatpack2 rectifiers are your key building blocks for future needs. Small and large Due to the high power density, cost competitive design and a highly flexible system communication interface, Flatpack2 rectifiers are used in system solutions from 5kW to 96kW.

Flexibility and reliability Extensive use of digital control has enabled advanced functionality meeting most customers requirements with no added cost. It also provides intelligent self-protective features like reduced output power at high temperatures or low mains. Even the dual fan solution is designed to be redundant: If one fan fails, the unit continues to deliver full power, but temperature derating will begin at a lower ambient temperature. Plug and play Plug a new rectifier into the system, and it automatically logs on, gets an assigned ID, downloads the system set parameters from the control system and starts up with a minimum of installation time, and without interrupting the system or attached equipment. Global compliance Eltek Valere is among the market leaders in all regions of the world, and designs the core products to be compliant with all relevant standards and customer requirements. All Flatpack2 rectifiers are CE marked, UL recognized and NEBS compliant.

Product Features and Advantages


Industry leading efficiency and power density With a typical efficiency of more than 93%, Flatpack2 48/3000 is one of the most efficient rectifiers on the market. State-of-the-art soft switching and resonant technology combined with efficient thermal design and advanced digital control result in an industry leading power density of 33W/in3.

See reverse side for specifications

www.eltekvalere.com

Flatpack2 48/3000
Additional Technical Specifications
AC Input
Voltage Frequency Maximum Current Power Factor Input Protection 85-300 VAC (Nominal 176 275 VAC) 45 to 66Hz 19.2 Arms maximum at nominal input and full load > 0.99 at 50% load or more o Varistors for transient protection o Mains fuse in both lines o Disconnect above 300 VAC Alarms:

Other Specifications
Efficiency Isolation Typical 93%, min. 92% at 25-100% load o 3.0 KVAC input and output o 1.5 KVAC input earth o 0.5 KVDC output earth o o o o o o o o o o o Low mains shutdown High temperature shutdown Rectifier Failure Over-voltage shutdown on output Fan failure, one or two fans. Low voltage alarm at 43.5V CAN bus failure

Warnings:

DC Output
Voltage Output Power 53.5 VDC (adj. range: 43.5-58.0 VDC) 3000 W within nominal input range, linear derating to 1380 W at 85 VAC 62.5 Amps at 48 VDC and nominal input 5% of maximum current from 10% to 100% load 0.5% from 10% to 100% load Storage temp 5.0% for 10-90% or 90-10% load variation, regulation time < 50ms > 10ms; output voltage> 43.5 VDC at full load o < 100 mV peak to peak, 30 MHz bandwidth o < 2.0 mVrms psophometric o o o o Over-voltage shutdown Output fuse Short circuit proof High temperature protection Cooling Fan Speed MTBF

Low temperature shutdown Rectifier in power derate mode Remote battery current limit activated Input voltage out of range, flashing at over-voltage o Loss of CAN communication with control unit, stand alone mode o Green LED: o Red LED: o Yellow LED: ON, no faults Rectifier failure Rectifier warning

Maximum Current Current Sharing Static voltage regulation Dynamic voltage regulation Hold up time Ripple and Noise

Visual indications Operating temp

-40 to +75C (-40 to +158F), linear derating from +45C to 2130W at +75C -40 to +85C (-40 to +185F) 2 fans (front to back airflow) Temperature and current regulated > 300, 000 hours Telcordia SR-332 Issue I, method III (a) (Tambient : 25C) < 65dBA at nominal input and full load (Tambient < 30C) Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing Conformal coating on PCB 109 x 41.5 x 327mm (wxhxd) (4.25 x 1.69 x 13) 1.9 kg (4.19lbs)

Acoustic Noise Humidity

Output Protection

Dimensions Weight

Applicable Standards
Electrical safety IEC 60950-1 UL 60950-1 CSA 22.2 EN61000-6-1 EN61000-6-2 EN61000-6-3 EN61000-6-4 EN61000-3-2 EMC, Immunity, Light industry EMC, Immunity, Industry EMC, Emission, Light industry (with additional filtering in power shelf) EMC, Emission, Industry

EMC

Mains Harmonics Environment

ETSI EN 300 019-2 ETSI EN 300 132-2 RoHS


241119.100.DS3 2

Specifications are subject to change without notice

Ordering Information

Part no.

Description

241119.100 Flatpack2 48/3000

www.eltekvalere.com
Headquarters: Eltek Valere 1303 E. Arapaho Rd, Richardson, TX. 75081, USA Phone: +1 (469) 330-9100 Fax: +1 (469) 330-9101 Eltek Valere Grterudv. 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Fax: +47 32 20 32 10