DESCRIPTION OF PROBLEM

43,200 lb/hr of 35 API distillate is cooled from 250 to 120 F using cooling water from 85 to 120oF. Available for service is a 19.25 in. ID 1-2 exchanger having 204 tubes 3/4in. OD, 16 BWG, 16'0" long on 1-in square . Baffles are spaced at 5in. Apart, and the bundle is arranged for 4 passes. Calculate pressure drop & dirt Factor. What is the optimum outlet water temperature? (Allowable Pressure Drop is 10.0 psi)
o

DATA AVAILABLE

HOT FLUID

COLD FLUID

UNIT

Inlet Temperature Outlet Temperature Thermal Conductivity Specific Heat Capacity Viscosity Mass Flow Rate specific Gravity

Tin Tout k Cp m s

250 120 0.077 0.52 5.268 43000 0.815

85 120 0.3615 1 1.815 83051.42857 1

F F Btu/(hr)(ft2)(F/ft) Btu/(lb)(F) lb/(ft)(hr) lb/hr -

PARAMETERS

Heat Transfer

UNIT Btu/hr

NOTATION

HOT FLUID

COLD FLUID

2906800

2906800

Calorific Temperature

TC

156.4

94.8

SHELL SIDE CALCULATION


PARAMETERS

Flow area Mass Velocity Reynolds Number Factor for Heat Transfer Prandtl Number ho/t at wall temperature Viscosity Ratio Heat Transfer Coefficient

UNIT ft2 lb/(hr)(ft ) lb/(ft)(hr) Btu/hr


2

NOTATION as GS Re JH Pr w s ho

VALUES

0.167100694 257329.8701 3858.971097 35 35.5761039 112.1978341 7.26 0.956091111 107.2713518

CLEAN OVERALL HEAT TRANSFER COEFFICIENT

UC

94.12363295

CLEAN OVERALL HEAT TRANSFER COEFFICIENT DIRT FACTOR OPTIMUM OUTLET WATER TEMPERATURE

UD RD to

72.02733936 0.003259293 130.7371768

Pressure Drop Calculation


SHELL SIDE
Friction factor Number of Crosses Pressure Drop (psi) f N+1 Ps 0.0026 38.4 3.300501834 Friction factor
Tube side Prssure Drop Return Pressure Drop Total Pressure Drop

f Pt Pr PT

THE HEAT EXCHANGER IS SATISFACTORY FOR THE SERVICE

ADDITIONAL DATA ( 1-2 exchanger)


UNIT

Shell ID Baffle Spacing passes No. of Tubes OD of Tubes ID of Tubes Length BWG / Pitch Tube Pitch Clearence between Tubes Eq. Diameter Flow Area per Tube External Surface Per lin. ft Velocity through Tubes Acceleration of Gravity

Di B n NT do di L PT C' De at a'' V g

19.25 5 4 204 0.75 0.0517 16 16/1-in sq. 1 0.25 0.079 0.302 0.1963 2.8 32.2

inch inch ft ft inch inch ft in2 ft2 ft/sec ft/sec2

Log Mean Temperature Difference


Temperature Difference at Hot End Temperature Difference at Cold End LMTD T 1 T2 TLM

130 35 72.39825135

CORRECTION FACTOR (F)


R S 3.714285714 0.212121212

0.87 (FROM GRAPH)

Corrected LMTD

62.98647867

CALORIFIC TEMPERATURE

Tc/TH
FC WALL TEMPERATURE

0.269230769 0.28

102.7908355 640.7232

HEAT TRANSFER SURFACE

TUBE SIDE CALCULATION


PARAMETERS

Flow area Mass Velocity Reynolds Number Factor for Heat Transfer Prandtl Number hi/t hio/t at wall temperature Viscosity Ratio Heat Transfer Coefficient

UNIT ft2 lb/(hr)(ft ) lb/(ft)(hr) Btu/hr


2

NOTATION at GT Re JH Pr w t hio

VALUES

0.106958333 776483.9446 22118.02751 76 5.020746888 909.956839 752.7162972 1.573 1.020236148 767.9483756

TUBE SIDE
0.00027 3.783963561 1.947826087 5.731789648