You are on page 1of 9

REVIEWED WITH COMMENTS

DATA SHEET

M006-NN-SE-0-BAT-001

1
Item 1.1 1.2 1.3 1.4

RATED CHARACTERISTICS
Description Equipment Construction type Number of phases Rated power (Continuous load) At ambient temperature of 33,8C and solar radiation of 1000W/m2 K MVA ONAN 255 AT Nominal tap Lower tap Higher tap Tap changer Type Tapping range kV kV kV 230 218,5 241,5 No-load (off-circuit) 2 x 2,5% YN HV kV kV peak kV peak kV peak kV rms 245 850 1050 1155 460 70 Neutral 36 170 70 d1 LV 36 170 187 70 70 19 Unit Generator Step-up Transformer Shell type 3 ONAF1 340 BT ONAF2 425

1.5

Rated voltages at no load

1.6 1.7

Vector group Insulation levels Highest voltage for equipment Switching impulse withstand voltage Lightning impulse withstand voltage (1.2 / 50 s) Chopped wave impulse withstand voltage Short duration induced AC withstand voltage (60Hz, 1min) Separate source AC withstand voltage Rated frequency Standards

REVIEWED WITH COMMENTS


kV rms Hz 70 60 IEC 60076

1.8 1.9

CONNECTIONS DIAGRAM

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 2 of 7

DATA SHEET

M006-NN-SE-0-BAT-001

3
3.1 Item

GUARANTEES No load losses and excitation current


Description Unit Percent voltage 100 110 339 0,55

3.1.1 3.1.2

No load losses (a) Excitation current (a)

kW %

237 0,25

3.2 Item 3.2.1

Load losses
Description Load losses (At 425 MVA base, corrected to 75C) (a) Connection (Tap voltage) Unit

HV

230 218,5 241,5

KW KW kW kW kW

930 948 914 10,5 21

3.2.2

Auxiliary losses

ONAF1 ONAF2

3.3 Item 3.3.1

Impedance voltages
Description (At 425 MVA base, corrected to 75C) (a) Connection (Tap voltage) Unit

REVIEWED WITH COMMENTS


HV 230 218,5 241,5 % % % 13,0 13,0 13,0

3.4 Item 3.4.1

Temperature rise and noise level


Description Temperature rise Top oil (by thermometer) Average winding (by resistance) Unit C C dB(A) 55 60 < 85

3.4.2

Sound pressure level at maximum power rating and rated voltages

at 1m from prescribed contour

(a) - Tolerances according to IEC 600076-1.

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 3 of 7

DATA SHEET

M006-NN-SE-0-BAT-001

4
Item 4.1 4.2 4.3

OIL AND OIL PRESERVATION SYSTEM


Description Oil type Oil preservation system Accessories Nynas: Nytro Taurus Conservator equipped with rubber cell One dial type oil level gauge with low and very-low level alarm and trip contacts One silica-gel dehydrating breather

5
Item

COOLING SYSTEM
Description Cooling stages Unit ONAN ONAF1 ONAF2 Type Number Mounting Hot-dip galvanized plate radiators 36 Attached to tank though disc valves by groups of 6 72 EFAFLU / VTTF 454/6/27 m3/h rpm kW V 4400 1030 0.29 460 ( 3 ph - 60 Hz ) Hot-dip galvanized mesh Under radiators

5.1

Radiators

5.2

Motor-fan groups

Number Manufacturer / reference Flow (free air) Speed Input power Voltage Protection Mounting

REVIEWED WITH COMMENTS


V 125 (cc)

5.3

Control Voltage

Top oil temperature and thermal image system

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 4 of 7

DATA SHEET

M006-NN-SE-0-BAT-001

6
Item 6.1

ACCESSORIES
Description Tap changer Manufacturer Manufacturer reference Type Rated current Insulation level (lightning impulse) Number of positions Operation Additional features A kV Unit M. Reinhausen DU III 1222 72,5 06.05.0Y Three-phase no-load (off-circuit) linear switch 1200 350 5 Manual operation by wheel, from ground level Padlock Electrical switch for tap position indication HV Neutral TRENCH COT 250-1600 Condenser IEC 1600 30 250 1300 Brown Tank cover LV ABB GOH 170/25 Condenser IEC 25000 36 200 760 Brown Tank cover N.A. -

6.2

Bushings

Manufacturer Manufacturer reference Type Standard Rated current Rated voltage (line to ground) Lightning impulse test voltage (BIL) Minimum creepage distance Porcelain colour Location A kV kV mm

TRENCH COT 1050-1600 Condenser IEC 1600 142 1050 7595 Brown Tank cover

REVIEWED WITH COMMENTS


Level indicator Eleq A 3x1800:1 30VA 5P20 ABB EXLIM P192-GV245 kV kV kV kA mm 192 154 222 20 7717 1800:1 30VA Cl 0,2 Level indicator Eleq 2 x 1800:1 30VA 5P20 -

Oil level indication 6.3 Bushing current Manufacturer transformers (per Quantity x Current ratio phase) Burden Accuracy class 6.4 Surge arresters Manufacturer Manufacturer reference Rated voltage Max. cont. operating voltage Temporary overvoltage (1s) Nominal discharge current Creepage distance

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 5 of 7

DATA SHEET

M006-NN-SE-0-BAT-001
Accessories (Continued)
6.5 6.6 05 6.7 6.8 6.9 6.10 Gas detection relay Sudden pressure relay Pressure relieve device Top oil temperature gauge Thermal image system Other accessories and features EMB Buchholz relay Qualitrol, ref. 900-003-02 Qualitrol, provided with visual indicator and alarm contacts, ref. XPRD AKM, with contacts for alarm and trip AKM, provided with temperature gauge and contacts for alarm, tripping and cooler plant control Weather-proof (IP-55W) control cabinet with all the devices for operation, protection and control of the cooling system, provided with heater, lighting and socket. Draining, filtering and sampling valves Lifting, untanking and pulling lugs Grounding pads External cabling installed in flexible metallic conduits

7
Item 7.1

TESTS
Description Factory tests according to IEC 60076: Routine tests Measurement of winding resistance Measurement of voltage ratio and check of phase displacement Measurement of short-circuit impedance and load loss Measurement of no-load loss and current Switching impulse test on line terminals

REVIEWED WITH COMMENTS


Lightning impulse test on line terminals Accessories functional tests Physical-chemical oil tests Vacuum and oil leakage tests Type and special tests Lightning impulse test on neutral terminal Short duration induced voltage test

Separate source AC withstand voltage test (applied potential test) Long duration induced voltage test with PD measurement by radio frequency interference voltage (RIV) method

Measurement of zero-phase sequence impedance Temperature rise test Dissolved gas in oil analysis (chromatographic analysis) Audible sound level Auxiliary cooling losses measurement

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 6 of 7

DATA SHEET

M006-NN-SE-0-BAT-001

8
Item 8.1

MASS AND OVERALL DIMENSIONS


Description Mass (approx.) Complete transformer without oil Total oil Complete transformer with oil Untanking Heaviest part for transport Largest part for transport Unit ton ton ton ton ton ton m m m m m m m m m m 405 67 472 20 115 16 14,0 8,8 8,8 11,4 4,0 3,3 4,5 12,4 4,0 2,5

8.2

Overall dimensions of the complete transformer (approx.)

Length Width Height Untanking height

8.3

Shipping dimensions Length of the heaviest part Width (approx.)

Height 8.4
Shipping dimensions Length of the largest part Width (approx.)

Height

REVIEWED WITH COMMENTS

M006-NN-SE-0-BAT-001 Rev 05.doc Calc.: S. Ricca Verif.: P. Pedro Date: 2009-09-10 Page 7 of 7

DATA SHEET

M006-NN-SE-0-BAT-001
9 ANEX NYNAS OIL DATA SHEET

REVIEWED WITH COMMENTS

M006-NN-SE-0-BAT-001 Rev 03 - Data Sheet Calc.: S. Ricca Verif.: P. Pedro Date: 2009-04-09 Page 8 of 9

DATA SHEET

M006-NN-SE-0-BAT-001

REVIEWED WITH COMMENTS

M006-NN-SE-0-BAT-001 Rev 03 - Data Sheet Calc.: S. Ricca Verif.: P. Pedro Date: 2009-04-09 Page 9 of 9