1- SHUNT CAPACITOR 2- AIR CORE SERIES REACTOR 3- CURRENT TRANSFORMERS (C.T) 4- POTENTIAL TRANSFORMER (P.T) 5- SURGE ATTESTERS
(43-TMSS-01, Rev. 0) (58-TMSS-01, Rev. 0) (50-TMSS-01, Rev. 0) (50-TMSS-03, Rev. 0) (35-TMSS-01, Rev. 0)
58-TMSS-02, Rev. 0
SCHEDULE
AIR CORE SERIES REACTOR 13.8 KV THROUGH 380kV DESCRIPTION 'A' Damping/ Tuning Copper/ Aluminum * * * * 250V * * * * * * * Yes/No 'B' 'C'
4.2.1 Design and Construction Application Coil conductor Magnetic clearance (Minimum) Reactor coil Center to center (mm) Edge to edge (mm) Edge of reactor to metallic parts not forming closed loops (mm) Noise Level (dB) Maximum RIV at maximum line to ground value of system voltage (applicable for 230kV and 380kV only) Complete dimension with drawing details provided Reactor weight (kg) Design Ambient Temperature Class of Insulation Maximum temperature rise (C) Hot spot temperature (C) Supporting Insulator (Manufacturer shall fill up column B of 15-TMSS-01 data schedule) 4.2.2 Damping Reactors Nominal System Voltage UN (kVrms) Inductance per phase (mH) Inductance tolerance Rated continuous current IN (A) Overload current rating (A) (suitable for capacitor bank overloading) High frequency in-rush current IIN (kApeak) In-rush current frequency fib (Hz)
* * * *
58TMSS02R0/KSB
PAGE NO. 9 OF 12
58-TMSS-02, Rev. 0
6.0 DATA
SCHEDULE
AIR CORE SERIES REACTOR 13.8 KV THROUGH 380kV REFERENCE SECTION NO. DESCRIPTION 4.2.2 (continued) High frequency out-rush current IOUT (kApeak) Out-rush current frequency fob (Hz) Rated short circuit withstand current (kA) for 1 second Thermal short-time overcurrent (kApeak) Harmonic voltage distortion factor FhU BIL (kVpeak) Power frequency withstand voltage (kVrms) Switching Impulse Withstand Voltage (BSL) if applicable (kVpeak) Total Losses at 75C and 110% rated voltage (kW) at in-rush frequency Q-factor at in-rush frequency Impedance at rated frequency (ohm) Thermal class of insulation Temperature rise C Voltage drop (V) 4.2.3 Tuning (Filter) Reactors Nominal System Voltage UN (kVrms) Rated inductance LA (mH) at tuning frequency Inductance tolerance for principal tap Tapping Range (%) (if applicable) Inductance Step (%) Number of steps Inductance tolerance at other taps Fundamental current rating IN (A) Rated tuning frequency current IA (A) Rated tuning frequency fA (Hz) 'A' * * 'B' 'C'
* * * * * * * * * *
13.8kV
Max 5%
500A
279Hz
58TMSS02R0/KSB
PAGE NO. 10 OF 12
58-TMSS-02, Rev. 0
6.0 DATA
SCHEDULE
AIR CORE SERIES REACTOR 13.8 KV THROUGH 380kV REFERENCE SECTION NO. DESCRIPTION Rated short time current IKN (kA) and duration Mechanical peak current (kApeak) Type of filter (band-pass/high pass) BIL (kVpeak) Power frequency withstand voltage (kV rms) Switching Impulse Withstand Voltage (BSL) if applicable (kVpeak) Total Losses at 75C and 110% rated voltage (kW) at tuning frequency Q-factor at tuning frequency Impedance at rated frequency (ohm) Thermal class of insulation Temperature rise C Voltage drop (V) (for each tap and principal tap) Power Network Single line Diagram enclosed 4.4 Terminals (applicable for outdoor reactors) Type Material No. of holes For Conductor Size (mm2) For Conductor Material (Al or Cu) Incoming conductor take-off (vertical, horizontal, angle to horizontal) ADDITIONAL INFORMATION Approximate shipping Dimensions (mm) Approximate shipping weight (kg) 'A' */* * 'B' / 'C'
50kV
* * * * * Yes/No
* Copper/ Aluminum *
* *
58TMSS02R0/KSB
PAGE NO. 11 OF 12
58-TMSS-02, Rev. 0
6.0 DATA
SCHEDULE
AIR CORE SERIES REACTOR 13.8 KV THROUGH 380kV A. ADDITIONAL TECHNICAL INFORMATION OR SEC: FEATURES TO BE FURNISHED BY
B.
C.
Vendor/Supplier/ Contractor
Name and Signature of authorized representative and date Official Seal/Stamp of the Company & Date
58TMSS02R0/KSB
PAGE NO. 12 OF 12
50-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
CURRENT TRANSFORMERS, 11KV THROUGH 380 KV SEC Enquiry No. SEC Purchase Order No. or Contract No. SEC PTS No./Project Title with J.O. No. REFERENCE SECTION NO. DESCRIPTION Nominal System Voltage ( kV) System short circuit current (kA sym.) at rated voltage Type of System Grounding Installation (Outdoor/Indoor) 'A' 'B' 'C' Date: Date:
'A'- SEC SPECIFIED DATA/PARAMETER. 'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'. (*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR/CONTRACTOR IN COLUMN 'B'.
50TMSS01R0/JSG
PAGE NO. 10 OF 15
50-TMSS-01, Rev. 0
DATA SCHEDULE
'B'
'C'
4.0 4.1
DESIGN AND CONSTRUCTION REQUIREMENTS Ratings Rated Primary Current (A) Rated Secondary Current (A)
10A 1A
4.1.1
Continous Thermal Current Rating Factor Multi ratio CTs Single ratio CTs Rated Short Time Thermal Current-Ith (kA rms) (21, 25,31.5, 40, 50, 63 kA rms) Short time thermal current duration (sec.) Rated Dynamic Current (kA peak) Fault current duration (sec.) Rated primary short circuit current -IPSC (kA) Temperature Rise (C) Nunber of Metering Cores Number of Protection Corers
2.6xIth
* *
4.2
Construction Type of CT (Ring continuous/split core type,bushing type, cast resin type, free standingoil filled/fluid filled type )
50TMSS01R0/JSG
PAGE NO. 11 OF 15
50-TMSS-01, Rev. 0
DATA SCHEDULE
Construction (Continued) Free standing CT core location (top or bottom) Type of Insulation (Mineral Oil filled / Fluid / Cast Resin) Manufacturers type Designation
4.2.2
Insulating Oil /Fluid [Refer to Data Schedule of 54-TMSS-01 for insulating oil.Vendor to fill in column B of the same] High Voltage Insulator Housing Name of Manufacturer Type (Porcelain/Cast Resin) Make Designation Creepage Distance (mm) Color Cantilever Strength (kN)
4.2.3
* *
4.2.4
Terminals Primary Terminal Connector: Conductor Material (Al or Cu) Size (mm) Number of Conductors/phase Degree of protection of enclosure for secondary terminal box
50TMSS01R0/JSG
PAGE NO. 12 OF 15
50-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
CURRENT TRANSFORMERS, 11KV THROUGH 380 KV REFERENCE SECTION NO. DESCRIPTION 4.3 Primary Winding for Free Standing Type CTs Bar Primary Wound Primary Material Winding Insulation and Class Rated Maximum Voltage (kV) BIL (kV peak) Power Frequency Withstand Voltage (kV rms) -Indoor CTs Power Frequency Withstand Voltage (kV rms) -Outdoor CTs 1 minute dry (kV rms) 10 sec. Wet (kV rms) BSL for 380kV (kV peak) 4.4 Secondary Winding Core No Purpose ( Relaying / Metering) Winding No. 1: Purpose Type of Protection(back up/differential/distance protection etc) Current Ratio at specified tap Accuracy Class Burden (VA)/Resistive burden -Rb (ohms) */*/* Relaying/ Metering / / 1/2/3 'A' 'B' 'C'
Al / Cu * * * * *
* * *
50TMSS01R0/JSG
PAGE NO. 13 OF 15
50-TMSS-01, Rev. 0
6.0 REFERENCE SECTION NO. DESCRIPTION 4.4 (Continued) Secondary winding Resistance at 20C -Rct (ohms) Specified Tap For class TPS CTs per IEC
DATA SCHEDULE
Rated symmetrical short circuit current factor -KSSC Dimensioning parameter K Excitation limiting secondary Voltage -Ual (Volts) Accuracy limiting secondary exciting current Ial (mA) Secondary excitation current-Imag at half excitation limiting secondary Secondary winding resistance Rct (ohm) 5.1.3 Special tests Special tests required Class P CTs Chopped Lightning Impulse Measurement of capacitance and dielectric dissipation factor Multiple Chopped Impulse test on Primary Winding Mechanical Tests Measurement of Transmitted OverVoltages Special tests required Class TPS CTs Verification of Low Leakage Flux
50TMSS01R0/JSG Date of Approval: May 30, 2006
* * *
PAGE NO. 14 OF 15
50-TMSS-01, Rev. 0
6.0
DATA SCHEDULE
CURRENT TRANSFORMERS, 11KV THROUGH 380 KV A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY SEC:
B.
FEATURES
PROPOSED
BY
C.
Vendor/Supplier/ Contractor
Name and Signature of authorized representative and date Official Seal/Stamp of the Company & Date
50TMSS01R0/JSG
PAGE NO. 15 OF 15
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV SEC Enquiry No. SEC Purchase Order No. or Contract No. SEC PTS No./Project Title with J.O. No. REFERENCE SECTION NO. 3.0 4.0 DESCRIPTION 'A' 'B' 'C' Date: Date:
IEC/TMSS/PTS
DESIGN AND CONSTRUCTION REQUIREMENTS Mean Altitude from Sea Level (m)
1000 M
4.1
Design Criteria Type of connection of Capacitor Bank (Single star or Double star with grounded neutral) Type of capacitor bank neutral Grounding Type of application (Reactive power compensation or Harmonic filtering) Type of Bank Switching (Isolated or backto-back) Capacitors (internally or externally fused)
DOUBLE STAR
UNDERGROUND
BACK TO BACK
INTERNALLY
4.2
'A'- SEC SPECIFIED DATA/PARAMETER. 'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'. (*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR/CONTRACTOR IN COLUMN 'B'.
43TMSS01R01/KSB
PAGE NO. 10 OF 16
50-TMSS-03, Rev. 0
6.0
DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV REFERENCE SECTION NO. 3.0 DESCRIPTION 'A' 'B' 'C'
4.0 4.1
DESIGN AND CONSTRUCTION REQUIREMENTS Ratings Maximum Rated Primary Voltage (kV rms) (Phase to Ground) Rated Voltage Factor Rated Secondary Voltage ( V rms) ( Nominal) Secondary 1 Secondary 2 Any tap required on Secondary -1 or Secondary -2 winding If Yes, What is the tap voltage? Secondary -1 ( V rms) Secondary -2 ( V rms) Rated burden ( VA ) Secondary 1 Secondary 2
13.8kVrms
110Vrms
Yes /No
Continous Thermal Burden ( VA ) Type of insulation (Liquid/Solid) Maximum Partial Discharge Level Phase to earth (pc) @ maximum rated voltage @1.2 x max.rated voltage / 3 * *
50TMSS03R0/JSG
PAGE NO. 9 OF 13
50-TMSS-03, Rev. 0
6.0
DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV REFERENCE SECTION NO. 4.1 DESCRIPTION 'A' 'B' 'C'
Ratings (Continued) Maximum Radio Influence Voltage(RIV) (applicable only for 115 & 132 kV outdoor PTs) at 1.1 x maximum rated voltage/3 Winding Insulation and class Winding Material (Al or Cu) BIL of Winding (kV peak) Power Frequency Withstand Voltage of Winding (kV rms) Accuracy class: Secondary 1 Secondary 2 2500 V * * * *
4.2
Construction Type of PT ( Mineral Oil filled/silicone liquid filled) 3-phase type or Single Phase type Manufacturers type designation Country of Manufacture * *
4.2.2. Insulating Oil (c) [Refer to Data Schedule of 54-TMSS-01. Vendor to fill in column B of the same] 4.2.2. Silicone Liquid (d) Applicable Standard Color (Max.)
50TMSS03R0/JSG
IEC 60836 35
ASTM D4652 15
PAGE NO. 10 OF 13
50-TMSS-03, Rev. 0
6.0
DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV REFERENCE SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.2. Silicone Liquid (Continued) (d) Applicable Standard Appearance Viscosity Max. at 400 C (mm2 /s) Flash point, Min .(0C) Pour point, Max (0C) Density at 20 (0C) ( kg/dm3 ) IEC 60836 * 40+ 4 240 - 50 0.955 to 0.970 ASTM D4652 * 39 300 -50 *
Dissipation Factor tan at 60 Hz @ * 25 C 0.0012 90 C Dielectric breakdown voltage at 60 Hz,Min.(kV) Neutralization value max (mg KOH/g) Water content (ppm) PCB content 4.2.3 40
0.01 * 35
0.02 50 *
0.01 50 *
High Voltage Insulator Housing Name of Manufacturer Type (Porcelain/Silicon Rubber) Rated Voltage (Nominal, kV rms)
13.8kVrms
50TMSS03R0/JSG
PAGE NO. 11 OF 13
50-TMSS-03, Rev. 0
6.0
DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV REFERENCE SECTION NO. 4.2.3 DESCRIPTION 'A' 'B' 'C'
High Voltage Insulator Housing (Cont.) BIL (kV peak) Power frequency Withstand Voltage: (Wet Withstand applicable for Outdoor Housings only) 1 minute dry (kV rms) 10 sec. wet (kV rms) Creepage Distance (mm) Color Cantilever Strength(kg)
125kV peak
50kVrms
* * * *
4.2.4
Terminals Primary Terminal Connector: For Conductor Material (Al or Cu) Size (mm2) Number of Conductor/phase Degree of protection of enclosure for secondary terminal box *
4.2.5
4.4
5.0
50TMSS03R0/JSG
PAGE NO. 12 OF 13
50-TMSS-03, Rev. 0
6.0
DATA SCHEDULE
POTENTIAL TRANSFORMER (PT) 33KV THROUGH 380KV A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY SEC:
B.
FEATURES
PROPOSED
BY
B.
Vendor/Supplier/ Contractor
Name and Signature of authorized Representative and date Official Seal/Stamp of the Company & Date
50TMSS03R0/JSG
PAGE NO. 13 OF 13
35-TMSS-01, Rev. 0
4.4
Nameplate 4.4.1 Each surge arrester shall bear a na meplate permanently and legibly marked in English with the inform ation listed per IEC 60099-4 or ANSI / IEEE C62.11 as applicable and the following additional information: a. b. c. 4.4.2 The words: " kV Surge Arresters"
The nameplate material shall be stainl ess steel and shall be f astened to the equipment by stainless steel screws or rivets. The m arkings shall be engraved.
5.0 TESTS All test results shall be provided for review and acceptance by SEC. 5.1 Type (Design) Tests All type tests prescribed in the la test revision IEC 60099- 4 or ANSI/IEEE C62.11 standard shall be perform ed on the repres entative unit or on the f irst unit of every new design or rating to be supplied to SEC. In lieu of the actual type tests, certif ied test reports of type (design) tests perform ed on an identical unit m ay be subm itted to SEC f or review and approval during bidding stage. 5.2 Routine (Production) Tests All routine tests prescribed in the latest revision IE C 60099-4 or ANSI/IEEE C62.11 standard shall be performed on all surge arresters. 5.3 Acceptance Tests Acceptance Tests per the latest revi sion IEC 60099-4 or Conform ance Tests per ANSI/IEEE C62.11, as applicable, shall be perform ed on the nearest lower whole number to the cube root of the number of surge arresters to be supplied. 5.4 Special Thermal Stability Test. Special Thermal Stability Test per latest revision of IEC 60099-4 shall be conducted on the appropriate sample taken from the production lot if this test is mentioned in the Data Schedule or SOW/ PTS.
35TMSS01R0/MSO
PAGE NO. 7 OF 13
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL SEC Enquiry No. SEC Purchase Order No. or Contract No. SEC PTS No./Project Title with J.O. No. REFERENCE SECTION NO. DESCRIPTION SYSTEM DATA 'A ' 'B' 'C' Date:
Date:
Nominal System Voltage (kV) (11kV, 13.8kV ,33 kV, 34.5kV , 69kV , 110kV , 115kV , 132kV , 230kV or 380kV) System Fault Current Level at Rated System Voltage (kA) Max. Duration of Ground Fault (ms) System Neutral Grounding at Arrester Point of Installation (Effectively, Non-Effectively grounded)
13.8kV
25kA 3sec
'A'- SEC SPECIFIED DATA/PARAMETER. 'B'- BIDDER/S UPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'. (*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR/CONTRACTOR IN COLUMN 'B'.
35TMSS01R0/MSO
PAGE NO. 8 OF 13
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION 'A ' 'B' 'C'
*
125kVpeak) IEC/TMSS/PTS
4.0
4.1
Designation (Indoor/Outdoor)
*
OUTDOOR
4.2
Performance Characteristics and Ratings Rated Voltage (kVrms) Line Discharge Class Dielectric Withstand for Housing Lightning impulse withstand voltage, with 1.2/50 s Waveform (kVpeak) Switching impulse withstand voltage with 250/2500s Waveform (for arresters with rated voltage of 200kV and above) (kVpeak) * One minute power frequency withstand Voltage. (kVrms)
18kVrms 4
* *
35TMSS01R0/MSO
PAGE NO. 9 OF 13
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION 'A ' 'B' 'C'
Nominal Discharge Current (Lightning Impulse Classifying Current) With 8/20 s Waveform (kA) High Current Impulse Capability With 4/10 s Waveform ( kA peak) Long Duration Wave Withstand Capability Current (A) Duration (ms) Maximum Lightning Impulse Residual Voltage with 8/20 s Waveform (kVpeak) at a Discharge (classifying) Current of : - 5 kA - 10 kA - 20 kA - 30 kA Maximum Switching Surge Residual Voltage (kVpeak) at a Discharge Current of: - 0.5 kA - 1 kA - 2 kA - 3 kA Maximum Steep Current/Front-of-Wave Residual Voltage Based on 1/> 2 or 0.5 s Waveform, as Applicable (kVpeak) at a Discharge Current of : - 10 kA - 20 kA Temporary over voltage capability(kVrms) for: - 1 second - 10 second Maxim um R.I.V (v) Maximum External Insulation Levels Power frequency Dry Withstand Voltage (kVrms) *
35TMSS01R0/MSO
20kA
* *
* * * *
* * * *
* *
* * *
*
PAGE NO. 10 OF 13
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL REFERENCE 'A SECTION NO. DESCRIPTION Power frequency Wet Withstand Voltage (kVrms) Lightning Impulse Withstand Level (kVpeak) * Switching Impulse Withstand Level (kVpeak) Leakage Current Through Arrester at MCOV (mA) Maximum Energy Absorption Capability i) kj/kV of Arrester Rating ii) kj/kV of MCOV 4.3 ' * 'B' 'C'
* * * *
Construction
Pressure Relief Capability (rms symmetrical) High current, short duration (kA) Low current, long duration (A)
600 * * * * * * * *
Porcelain Housing Color Creepage Distance (mm) Bending Failing Load (kN) Cantilever Strength min. (kN) Torsional Strength (kN) Com pression Strength (kNm) No. of stacks in each unit Height (mm) Internal Pressure Required to Operate Pressure Relief Device as a Percent of Pressure Required to Burst Porcelain (%) Mounting Arrangement Mode of mounting(Self supporting/bracket mounting) Bolt circle diameter (mm) No. of holes Size of bolts (mm) Accessories Scale range of the leakage Ammeter (mA) *
35TMSS01R0/MSO
* * * *
PAGE NO. 11 OF 13
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV REFERENCE SECTION NO. DESCRIPTION 'A' 'B' 4.2 Contd. Capacitor Bank Rated Voltage (kVrms) 3-phase Bank Reactive Power Rating at Rated Voltage (MVAR) Bank Insulation Level (BIL) (kVpeak) Rated power frequency withstand voltage(kVrms) Design Ambient temperature of the capacitor bank (C) Temperature range of operation (C) Harmonic filter: Tuned harmonic frequency (Hz) Type of filter (band-pass/high-pass) Rated Continuous Current (Arms) System fault level (kArms) Capacitor tolerance (%) Power Network Single Line Diagram provided? 4.3 Capacitor Bank Assembly Model designation of the Capacitor Bank Expected lifetime of the Bank (Years) Maximum Terminals Voltage Rating including harmonics (kVrms) Maximum Continuous Current Rating including harmonics (Arms)
INTERNALLY FUSED 279Hz
'C'
125kVpeak
50kVrms
55C
-10C + 55C
0.05%
Yes/No
30 YEARS
17.5kVrms
500Arms
43TMSS01R01/KSB
PAGE NO. 11 OF 16
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION 'A * * Pad * ' 'B' 'C'
Dia of the grading ring, if applicable (mm) Material of the grading ring, if applicable Term Type Size inals (mm2) * Material (Al or CU) (mm2) *
MISCELLANEOUS
Minimum Clearance, Between Live Parts and Earth Parts (mm) Minimum Permissible Centre to Centre Distance Between Arresters (mm) Overall Height of Arrester (mm) Weight of Arrester (kg) * * * *
35TMSS01R0/MSO
PAGE NO. 12 OF 13
35-TMSS-01, Rev. 0
6.0 DATA
SCHEDULE
SURGE ARRESTERS FROM 11 kV THROUGH 380kV NOMINAL A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY SEC:
B.
B.
Vendor/Supplier/ Contractor
35TMSS01R0/MSO
PAGE NO. 13 OF 13
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV REFERENCE SECTION NO. 4.3 Contd. Number of Parallel Capacitors per group Number of Parallel groups in series/phase Total number of capacitors/phase Air-core series reactor (if any) inductance per phase (mH) Peak maximum inrush current (kApeak) Peak maximum outrush current (kApeak) Frequency of inrush current (Hz) Frequency of outrush current (Hz) Rate of change of inrush/outrush current (kA/s) Capacitance per phase(F) Base and spacing insulators (Furnish detail dimensions and mechanical ratings) Capacitor bank assembly drawing provided? 4.4 Capacitor Unit Model designation of the Capacitor Unit Capacitance (F) Capacitor Unit Rated Voltage (kVrms) Capacitor Unit Power Rating (kVAR) Maximum Continuous Operating Current (Arms)
43TMSS01R01/KSB
DESCRIPTION
'A'
'B'
'C'
XX@279mH
* * * * * * * * Yes/No
* *
*
PAGE NO. 12 OF 16
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV REFERENCE SECTION NO. 4.4 DESCRIPTION 'A' 'B' 'C'
Contd. BIL of Capacitor Unit (kVpeak) Rated power frequency withstand voltage (kVrms) Tank material of Capacitor Unit Whether the tank is to be painted? Internal Discharge resistance (ohm) Standard for capacitor dielectric fluid (Furnish complete data of the dielectric fluid) Capacitor tank rupture curve provided? Temperature coefficient of the capacitor (F/C)
125kVpeak
50kVrms
*
YES
* * * Yes/No
4.5
Capacitor Bushing Number of bushings per capacitor unit Maximum Voltage Rating (kVrms) Wet (10 sec.) Power Frequency withstand voltage (kVrms) Dry (1 min.) Power Frequency withstand voltage (kVrms) Basic Impulse Withstand voltage (BIL) (kVpeak) Color of Porcelain Creepage Distance (mm) Striking Distance (mm)
DOUBLE 23kVrms
50kVrms
55kVrms
125kVpeak
Brown/Grey
55mm
*
Date of Approval: January 31, 2012 PAGE NO. 13 OF 16
43TMSS01R01/KSB
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV REFERENCE SECTION NO. 4.5 Contd. Permissible safe cantilever loading at external terminal (Kg) Facilities required for making capacitance measurement and Power factor test? 4.6 Terminals Type (parallel groove clamp or threaded studs) For Conductor Size (mm2) For Conductor Material (Al or Cu) Bird-proof terminal caps required? Type for neutral and mid-point 4.8 Capacitor Rack Complete dimensional details and weight to be provided? 4.9.1 Individual Capacitor Unit Protection Fuse: Type & designation Fuse element, fuse-bus & fuse element supporting assembly material Maximum Voltage Rating including harmonics (kVrms) Maximum Continuous Current Rating including harmonics (Arms)
INTERNALLY FUSED
DESCRIPTION
'A'
'B'
'C'
Yes/No
Yes/No *
Yes/No
* * *
43TMSS01R01/KSB
PAGE NO. 14 OF 16
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV REFERENCE SECTION NO. 4.9.1 Contd. Current Rating of the fuse-bus/base (Arms) Cold resistance of the fuse-link () & percentage tolerance of resistance value External creepage distance along the fuselink (for current limiting fuse) (mm) Interrupting assymetrical current (A) Discharge energy interrupting rating (Joule) Time-current characteristics provided? Capacitor bank protection data provided? Other General Information: Approximate shipping dimensions of capacitor bank/unit (mm) Approximate shipping weight of capacitor bank/unit (Kg) List parts that will be dismantled and shipped separately 5.1 Capacitor loss (tan ) value at elevator temperature during measuremtn of the tangent of of the loss angle type test Capacitor loss (tan ) value during measurment of tangent of loss angle routine test * * * * * * * * * Yes/No Yes/No DESCRIPTION 'A' 'B' 'C'
5.3
43TMSS01R01/KSB
PAGE NO. 15 OF 16
43-TMSS-01, Rev. 01
6.0
DATA SCHEDULE
SHUNT CAPACITOR BANK, SUBSTATION TYPE, 13.8kV THROUGH 380kV A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY SEC:
B.
FEATURES
PROPOSED
BY
C.
Vendor/Supplier/ Contractor
Name and Signature of authorized epresentative and date Official Seal/Stamp of the Company & Date
43TMSS01R01/KSB
PAGE NO. 16 OF 16
58-TMSS-02, Rev. 0
6.0 DATA
SCHEDULE
AIR CORE SERIES REACTOR 13.8 KV THROUGH 380kV SEC Enquiry No. SEC Purchase Order No. or Contract No. SEC PTS No./Project Title with J.O. No. REFERENCE SECTION NO. 3.0 DESCRIPTION 'A' 'B' 'C' Date: Date:
4.0 4.1
DESIGN AND CONSTRUCTION REQUIREMENTS DRY TYPE AIR CORE Model Designation No. of phases Type of mounting Reactor Arrangement (side by side or vertically stacked) 3/1 Outdoor/Inside Weather proof enclosure
A'- SEC SPECIFIED DATA/PARAMETER. 'B'- BIDDER/S UPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'. (*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR/CONTRACTOR IN COLUMN 'B'.
58TMSS02R0/KSB
PAGE NO. 8 OF 12