For Future Energy & Environment KTL KITECH

Absorption Chiller Heat Pump


CONTENT
Features / Control Sytstem / Absorption Cycle

World Energy

02 12 18 26 28 42 46 50 52 54

1 2 3 4 5 6 7 8 9

Double Effect Exhaust Gas Driven Absorption Machine Single Effect Double Lift Hot water Driven Absorption Machine Waste Heat Recovery Absorption Machine Single Effect Hot Water Driven Absorption Machine

Double Effect Direct Fired Absorption Chiller & Heater Double Effect Steam Fired Absorption Chiller Single Effect Steam Fired Absorption Chiller Absorption Heat Pump Installation Records

Hot water

Waste heat ->> Recycle energy


Exhaust gas

Steam

Welcome to World Energy


World Energy Co., Ltd. was founded for the purpose of developing and providing various types of wasteheat recovered and energy saving Absorption Machines such as Single Effect Double Lift Hot Water Driven Absorption Chiller, Single-Effect Hot Water Driven Absorption Machine, DoubleEffect Exhaust Gas Driven Absorption Machine and Absorption Heat Pump. Thanks to an accumulated and international grade technologies of R&D and manufacturing, a highly-qualified engineers and also a cooperation with well-known world-class partners, the company is introducing high efficient chillers to the world market. World Energy Co., Ltd. is playing a key role in Korean District Cooling and Heating industry. In cooperation with KDHC(Korea District Heating Corporation) and KARSE(Korean Association of Air Conditioning, Refrigerating and Sanitary Engineers), the company introduced a new technology in Absorption Chiller and developed Certification Program for Absorption Chiller. World Energy Co., Ltd. makes every effort to satisfy worldwide customers with high performing, reliable and international standard products. World Energy Co., Ltd. will continue to improve customers business interests by offering energysaving products in the age of high energy cost, and furthermore, to contribute to environmental protection.
Thank you.

Quality Management System Certificate

Environmental Management System Certificate

Declaration of Conformity

R&D Center Certificate

Underwriters Laboratories

World Energy Milestone

02. 2004. Cooperate company starts 05. 2006. 1st commercial operation of Single Effect 2-Lift Hot Water Driven Absorption Chiller (300RT, KDHC office, Korea) 09. 2006. 1st Shipment to USA market (130RT, USA market) 12. 2006. Complete Development of 1st Generation Single Effect 2-Lift Hot Water Driven Absorption Chiller (75~1125RT) 02. 2007. 1st Development of Exhaust Gas Driven Simultaneous Absorption Chiller/Heater (UTC Power, USA) 03. 2007. UL Listed 08. 2007. Ethylene Glycol Chemical Plant application chillers delivered (HWAR-L 1000RT*3Units S Model*5 Units) 12. 2007. Development of Heating Cycle with 2-Lift Absorption Chiller 06. 2008. Shipment of Exhaust Heat of MethyleneChloride Driven Absorption Chiller to Chemical Plant (Korea) 09. 2008. Shipment of Large capacity (4708kW) Hot Water Driven Chiller to Chemical Plant(Korea)

10. 2008. 1st Shipment to EU market (Italy, 2Units/Hot Water Chiller) 08. 2009. 1st Shipment of 2-Lift Hot Water Chiller to EU market (Germany) 09. 2009. 1st Shipment of Waste Heat Recovery Absorption Chiller (2AA240, ZINC Factory, Korea) 09. 2009. Complete Development of 2nd Generation Single Effect 2-Lift Hot Water Driven Absorption Chiller (75~1300RT) 05. 2010. 1st Shipment of Single Effect 2 Lift Hot Water Chiller to Taiwan (2AB825, Nanya Plastic)) 06. 2010. 1st Shipment of Exhaust Gas Driven Chiller to EU market (IBM R&D Center, Germany) 06. 2010. Shipment of 3,883kW MVR(Evaporating Condenser for Mechanical Vapor Compression System) to Chemical Plant (Korea) 07. 2010. Shipment of Heat Exchanger for Fuel Cell to UTC Power, USA 09. 2010. Shipment of the largest capacity(1025RT) Hot Water Driven Chillers to Commercial/ Residential complex district cooling application (Korea)

World Energy Co.

01

For ForFuture FutureEnergy Energy& &Environment Environment

Absorption Machines
Provide the best solution for CHP and CCHP application by utilizing waste heat more efficiently through various Absorption Machine technology.
No CFC's and Environmentally safe Cost-Effective Direct Cooling & Heating Low Noise & Low Vibration operation Precise & Optimized Control by Microprocessor-based Controller Saving of Initial Investment High Reliability

Safe

Easy

both of cooling & heating directly from exhaust gas from reciprocating engine or gas turbine without additional heat recovery systems. And Hot water Driven type Machine produces cooling from engine jacket water or the other hot water. Specially, in Double-lift type Machine, hot water energy can be utilized by 55C.

Exhaust-Energy Recovery season Exhaust Gas Driven Absorption Machine produces Safe ONE

Safe

Microprocessor-based control system allows stable, part load operation at cooling water temperatures as low as 18 [64] without a cooling water bypass. For maximum efficiency, a variable frequency drive pump automatically maintains optimum solution flow to Low-Temp. season Generator and also High-Temp Generator during whole operation. Easy

Excellent Part Load Performance Easy

ONE

Low Noise and Low Vibration


The overall sound level of The Worldenergy machine is typically 65dbA. This allows the machines to be installed near occupies spaces or in area with strict sound requirements. Low vibration levels also make it possible to install the chiller on upper floors without special consideration for vibration dampening systems.

Easy

season Hermetically-designed refrigerant and solution pumps which are only moving parts provide reliability and they are field serviceable through pump isolation valves. Also marine-type water box cover on both of the absorber and condenser allows easy tube-cleaning and water-box inspection. And factory performance test, which is provided as an optional season basis, ensure the performance and function of chiller before shipment.

Safe Reliability & Easy Maintenance

Factory mounted, wired and tested microprocessorbased controller monitors and controls the machine operation continuously and automatically. A touch screen display identifies operational status and fault indication. All components meet internally acceptable codes like UL or CE or KS or equivalents. During the start-up sequence, the controller initiates a self-diagnostic system check to verify that all sensors are in range. Remote start/stop switch and a key-locked control panel door protect against unauthorized access.

Preciseseason & Optimized Operation

ONE

Easy

Easy

ONE

ONE

Non-condensable gases are periodically exhausted from the storage tank by a simple procedure performed while the machine is running. Evacuation is performed by a unit mounted vacuum pump that is connected to the purge evacuation valve.

ONE

season

Reliable Purge System

02

World Energy Co.

WORLD ENERGY

Control System
Microprocessor-based Unit Controller is factory mounted, wired and tested to ensure a protection of the Machine and efficient capacity control. The program logic provides proper Start/Stop of the Machine and also enables a communication interface with others.
Component Test and Diagnostic Check Touch Screen Interface for Status Display, Set-point Control, and System Configuration Primary and Secondary Status Messages Individual Start/Stop Schedules for Local Mode Recall of Up to 999 Alarm and Alert Messages with Diagnostic Help Extensive Diagnostic and Service Capabilities Advanced Crystallization Protection Low Chilled Water Temperature Alarm Low Cooling Water Temperature Alarm Low Chilled Water Flow Alarm

Overrides

Hot Water High Temperature (Low Temp. Hot Water Driven type only) Generator Solution High Temperature High Concentration

Safety Cutouts

Solution Pump Motor Overload/High Temperature Refrigerant Pump Motor Overload/High Temperature Low Chilled Water Temperature Cutout Low Refrigerant Temperature Cutout Low Cooling Temperature Cutout Low Chilled Water Flow Cutout Low Cooling Water Flow Cutout (Option) Generator High Temperature Cutout Hot Water High Temperature Cutout (Low Temp. Hot Water Driven type only) High Temperature Generator High Pressure Cutout (Exhaust Gas Driven type only) High Temperature Generator Low Level Cutout (Exhaust Gas Driven type only)

Temperature Sensor Faults

Leaving Chilled Water Temperature Cooling Water Temperature Entering Absorber Refrigerant Condensate Temperature from Condenser Refrigerant Evaporating Temperature Strong Solution Temperature Leaving Generator Entering Hot Water Temperature (Low Temp. Hot Water Driven type only) Exhaust Gas Temperature Cutout (Exhaust Gas Driven type only)

World Energy Absorption Machines / Control System

Capacity Control

Leaving Chilled Water Control Running Travel Limit (Control Valve Opening Limit)

Indications

Protective Limits

Strong Solution Leaving High Temperature Generator Alarm Hot Water High Temperature Alarm (Low Temp. Hot Water Driven type only) Refrigerant Pump Overload/High Temperature Alarm Solution Pump Motor Overload/High Temperature Alarm Low Refrigerant Temperature Alarm

Chiller Operating Status Message Absorption Cycle State Points Dilution Cycle Power-On Alarm Safety Shutdown Message Run Hours Control Valve Position

Microprocessor

Touch Screen

Control Panel
World Energy Co.

03

For Future Future Energy Energy & & Environment Environment For

Absorption Cycle
1 Double Effect Exhaust Gas Driven Absorption Machine _ CHP series
Low Temp. Generator

Cooling Cycle [Cooling Mode]


37

Condenser

Cooling Water Outlet

Exhaust Gas Outlet Chilled Water Outlet


7 12 165

Change Valve (close) Evaporator Absorber Change Valve (close) High Temp. Generator
32

Bypass Exhaust Gas Inlet

Chilled Water Inlet

M
Diverter Valve

450

Cooling Water Inlet

Refrigerant Pump

Solution Pump

Low Temp. Heat Exchanger

High Temp. Heat Exchanger

The double-effect, exhaust-gas driven absorption machine consists of an

evaporator, absorber, condenser, high-temperature and lowtemperature generators, solution heat exchangers, refrigerant and solution pumps , purge system, controls and accessories. During the cooling mode, the machine operates at the condition that under vacuum, water boils at a low temperature. Under typical operating conditions, this occurs at approximately 4.4oC (40oF), thereby cooling the chilled water that circulates through the evaporator tubes. A refrigerant pump is used to spray the refrigerant(water) over the evaporator tubes to improve heat transfer. To make the cooling process continuous, the refrigerant (water) vapor must be removed as it is produced. To accomplish this, a lithium bromide solution (which has a high affinity for water) is used to absorb the water vapor. As this process continues, the lithium bromide becomes diluted, reducing its absorption capacity. A solution pump then transfers this diluted solution to the generators where it is re-concentrated in two stages (double-effect) to boil off the previously absorbed water. A variable frequency drive on the solution pump automatically maintains optimum solution flow to the generators at all operating conditions for maximum efficiency. The diluted solution is pumped to the high-temperature generator where it is heated and re-concentrated to a medium concentration solution by the exhaust heat from the gas turbine or reciprocating engine exhaust gas. The medium concentration solution from the high-temperature generator flows to the low-temperature

generator where it is heated and re-concentrated to a strong solution by the high temperature water vapor released from the solution in the hightemperature generator. Since the low-stage generator acts as the condenser for the high-stage generator, the heat energy first applied in the high-stage generator is used again in the low-stage generator, thus reducing the heat input by approximately 45% as compared to an absorption chiller with a single-stage of re-concentration. The water vapor released in the shell side of the low-stage generator, in addition to the now condensed water vapor from the tube side of the low-stage generator, enters the condenser to be cooled and returned to a liquid state. The refrigerant water then returns to the evaporator to begin a new cycle. To remove heat from the machine, cooling water from a cooling tower is first circulated through the tubes of the absorber to remove the heat of vaporization. The water is then circulated through the tubes of the condenser. The re-concentrated (strong) solution from the low-stage generator flows back to the absorber to begin a new cycle. For efficiency purposes, the medium concentration solution from the high-stage generator is passed through the high-temperature solution heat exchanger to pre-heat the diluted (weak) solution, while pre-cooling the medium concentration solution. The re-concentrated (strong) solution from the low-stage generator is passed through the lowtemperature solution heat exchanger to pre-heat/pre-cool the solution before being returned to the absorber.

04

World Energy Co.

WORLD ENERGY
Absorption Cycle

Heating Cycle [Heating Mode]


Hot water temperature at 60oC (140oF)
Condenser Cooling Water Outlet Low Temp. Generator

Exhaust Gas Outlet Chilled Water Outlet Change Valve (open) Chilled Water Inlet Evaporator Absorber Change Valve (open) High Temp. Generator Cooling Water Inlet

Bypass

Absorption Cycle - CHP Cooling & Heating Mode

Exhaust Gas Inlet

M
Diverter Valve

Refrigerant Pump

Solution Pump

Low Temp. Heat Exchanger

High Temp. Heat Exchanger

Hot water temperature at 79oC (175oF)


Condenser Cooling Water Outlet Low Temp. Generator Change Valve (close) Hot water Outlet

Hot water Inlet

Change Valve (close) Exhaust Gas Outlet

Chilled Water Outlet Chilled Water Inlet Absorber

Bypass Evaporator Exhaust Gas Inlet High Temp. Generator

Change Valve (close) Cooling Water Inlet Refrigerant Pump Solution Pump Low Temp. Heat Exchanger High Temp. Heat Exchanger

M
Diverter Valve

During the heating mode, the cycle follows a different vapor flow path

than that undertaken for cooling and does not use the typical absorption process. In addition, the absorber-condenser cooling water circuit is drained and thus not operated, since all heat rejection from the machine is designed to take place through the evaporator (now the heating bundle) in a classic two-pipe system that utilizes only the evaporator nozzles. High temperature water vapor produced in the high-temperature generator section is passed directly to the evaporator via the absorber where it condenses and transfers its heat to the water circulating through the evaporator tubes.

This condensed water then flows to the absorber section where it mixes with the concentrated solution returning from the high-temperature generator. The diluted solution is then pumped back to the hightemperature generator to repeat the vapor generation phase for the heating function. Quick changeover from cooling to heating is accomplished by switching the positions of two hand valves, draining the absorber-condenser water circuit and putting the machine into heating mode by changing the position of a switch in the control panel. The hot water temperatures is 60oC (140oF) as a standard without additional components and 79oC (175oF) as an option with the additional heat exchanger. World Energy Co.

05

ForFuture FutureEnergy Energy& &Environment Environment For

Double Effect Exhaust Gas Absorption Driven Absorption Cycle Chiller and Heater

2 Single Effect Double Lift Hot Water Driven Absorption Machine _ 2AB series

Hot Water Outlet


55

51.2

52.2 mmHg
Condenser

Cooling Water Outlet


36.5 38.9 74.5 73.1

Aux. Generator

45.2% 56.2

Hot Water Inlet


95

Intermediate Solution Pump

58.3% 80.0

Aux. Heat Exchanger


63.5

Chilled Water Outlet


8 13

6.8 mmHg

37.8 33.5

60.2 C

21.2 mmHg

Chilled Water Inlet

Evaporator

Absorber

40.1 34.3
Aux. Absorber

57.1 54.6% 34.5 Solution Pump


Low Temp. Heat Exchanger High Temp. Heat Exchanger

5.5 Refrigerant Pump

42.9% 36.5 Aux. Solution Pump 59.9% 65.2

31

Cooling Water Inlet


Refrigerant Diluted Solution Intermidiate Soution Concentrated Solution Aux. Intermidiate Soution Aux. Concentrated Solution Chilled Water Cooling Water Hot Water

Concentrated Solution Pump

Double Lift Hot water driven absorption chiller has main cycle and aux.

cycle The chilled water is cooled down in evaporator and the vaporized refrigerant is absorbed into concentrated solution which is coming from 2nd generator. The concentrated solution becomes diluted solution and the heat is absorbed into cooling water. The diluted solution in absorber flows to 1st generator through low temp. heat exchanger and high temp. heat exchanger, and 95oC of driving hot water heats up the diluted solution and refrigerant vapor is generated. The absorbent solution in 1st generator becomes intermediate solution and it flows to 2nd generator through high temp. heat exchanger. World Energy Co.

The intermediated solution in 2nd generator is heated up by driving hot water and the refrigerant vapor is generated. The vaporized refrigerant from 2nd generator is absorbed into absorbent solution in aux. absorber and it becomes aux. diluted solution. The aux. diluted solution is delivered to aux. generator through aux. heat exchanger, and the solution is heated up by driving hot water return from 2nd generator and becomes aux. concentrated solution. The aux. concentrated solution is delivered to aux. absorber through aux. heat exchanger. The refrigerant vapors which are generated 1st generator and aux. generator are condensed in condenser and then flow into evaporator, and the heat in condenser is absorbed by cooling water.

06

WORLD ENERGY
Absorption Cycle

3 Waste Heat Recovery Absorption Machine _ 2AA series


Cooling Water Outlet
36
Refrigerant Diluted Solution Chilled Water Cooling Water Hot water

Condenser

Concentrated Solution Aux. Intermediate Solution Aux. Concentrated Solution

Hot Water Outlet Aux. Generator


Aux. Concentrated Solution Pump 60

Chilled Water Outlet


8 13

Generator

Hot Water Inlet


70

Chilled Water Inlet

Evaporator

Absorber

Absorption Cycle - 2AB / 2AA / HWAR-L

Aux. Absorber

Refrigerant Pump

Solution Pump

31

Cooling Water Inlet

Solution Heat Exchanger

Aux. Solution Pump

Aux.Solution Heat Exchanger


Concentrated Solution Pump

4 Single Effect Hot Water Driven Absorption Machine _ HWAR - L series


36.5 Cooling Water Outlet Condedenser

80 95 Hot Water Outlet Generator Hot Water Outlet

8 Chilled Water Outlet

13 Chilled Water Inlet Evaporator Absorber

Refrigerant Diluted Solution Concentrated Solution Chilled Water Cooling Water Hot Water

31 Cooling Water Inlet

Refrigerant Pump

Solution Pump

Exchanger

World Energy Co.

07

ForFuture FutureEnergy Energy& &Environment Environment For

Double Effect Exhaust Gas Absorption Driven Absorption Cycle Chiller and Heater

5 Double Effect Direct Fired Absorption Chiller & Heater _ DW series


Cooling Cycle [Cooling Mode]
Cooling Water Outlet
37.5

Condenser

Low Temp. Generator

High Temp. Generator

Exhaust Gas

Chilled Water Outlet


7 Change Valve (Close)

12

Chilled Water Inlet

Evaporator

Absorber

Change Valve (Close)

Refrigerant Refrigerant Vator Diluted Solution Intermediate Solution Concentrated Solution Chilled Water Cooling Water

Gas Inlet

Refrigerant Pump

Solution Pump

Low Temp. High Temp. Heat Exchanger Heat Exchanger

Cooling Water Inlet 32

Heating Cycle [Heating Mode]


Condenser Cooling Water Outlet Low Temp. Generator High Temp. Generator

Exhaust Gas

Hot Water Outlet


60 Change Valve (Open)

55

Evaporator

Absorber

Hot Water Inlet

Change Valve (Open)

Refrigerant Refrigerant Vator Diluted Solution

Gas Inlet

Intermediate Solution
Concentrated Solution Hot Water

Refrigerant Pump

Solution Pump

Low Temp. Heat Exchanger

High Temp. Heat Exchanger

Cooling Water Inlet

08

World Energy Co.

WORLD ENERGY
Absorption Cycle

Double Effect Steam Fired Absorption Chiller _ SW Series


Cooling Water Outlet Condenser Low Temp. Generator High Temp. Generator Steam Inlet

Chilled Water Outlet

Chilled Water Inlet Evaporator Absorber

Absorption Cycle - DW Cooling & Heating Mode / SW / S

Steam Trap
Refrigerant Refrigerant Vator
Diluted Solution
Intermediate Solution Concentrated Solution

Drain Outlet

Chilled Water Cooling Water Steam

Refrigerant Pump

Solution Pump Cooling Water Inlet

Low Temp. Heat Exchanger

Steam Drain Reclaimer

High Temp. Heat Exchanger

Single Effect Steam Fired Absorption Chiller _ S Series


Steam Inlet

Cooling Outlet

Condenser

Generator

Chilled Outlet

Steam Drain Reclaimer

Drain Outlet

Chilled Inlet Evaporator Absorber

Refrgerant Refrgerant Vator Diluted Solution Concentrated Solution Chilled Water Cooling Water Steam

Cooling Water Inlet

Refrigerant Pump

Solution Pump

Heat Exchanger

World Energy Co.

09

For Future Energy && Environment For Future Energy Environment

Double Effect Exhaust Gas Driven Absorption Absorption Cycle Chiller and Heater

Absorption Heat Pump Cycle


Condenser Hot Water Outlet Generator Steam Inlet

Steam Fired Type _ HPS series

Drain Outlet

Waste Hot water Outlet

Waste Hot water Inlet

Evaporator

Absorber

Refrigerant Refrigerant Vator Diluted Solution Concentrated Solution Hot Water Waste Hot water Steam

Refrigerant Solution Pump Pump

Hot Water Inlet

Solution Heat Exchanger

Direct Fired Type _ HPD series


Hot Water Outlet Condenser

Exhaust Gas

Waste Hot water Outlet Waste Hot water Inlet


Evaporator Absorber Generator

Refrigerant Refrigerant Vator Diluted Solution Concentrated Solution Hot Water Waste Hot water

Gas Inlet
Refrigerant Pump Hot Water Pump

Hot Water Inlet

Solution Heat Exchanger

10

World Energy Co.

WORLD ENERGY
Absorption Cycle

Steam Generation Type _ AHT series


Evaporator Absorber Waste Heat Inlet
(Heat source : Hot Water or Drain)

Hot Water Outlet

Hot Water Inlet

Refrigrant Cirlculration Pump

Cooling Water Outlet

Waste Heat Outlet


(Heat source : Hot Water or Drain)

Absorption Cycle - HPS / HPD / AHT Heat Pump

Cooling Water Inlet Generator Condenser

Refrigerant Refrigerant Vator

Diluted Slution

Concentrated Solution
Hot Water Cooling Water Waste Heat

Refrigerant Pump

Heat Exchanger DUEHRING DIAGRAM

Solution Pump

Solution

Duhring Diagram _ 2AB Series


100
COOLING WATER OUTLET 36.5C HOT WATER OUTLET 55C

0% 40%

50%

60%
HOT WATER INLET 95C

59.4

50
44 .9

.2 %

40

34.3C

14

.3 %

69.7C

81.6C

70%

PRESSURE [mmHg]

30
23.6

56

33.3C

10
6.6

5 4 3 2 1 -20

8C 13C CHILLED WATER

COOLING WATER INLET 31C

-10

10

20

30

40

50

61

.5

20

58

.9

60

70

80

90

100

SOLUTION TEMPERATURE [C]


World Energy Co.

11

For Future Future Energy Energy & & Environment Environment For

Double Effect Exhaust Gas Driven Absorption Machine


Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Heating Capacity Inlet Temp./Outlet Temp. Hot Water Flow rate P. Drop Connection Flow rate Temp. Exhaust Gas Cooling Heating Unit
usRT kW m3/h mAq mm m /h mAq mm Mcal/h kW ton/h mAq mm kg/sec mmAq
3

Double Effect Exhaust Gas Driven Type (50~400RT)


CHP010 CHP012 CHP015 CHP018 100 351 60.5 4.8 120 422 72.6 5.1 100 32 / 37.5 70 10.2 100 80 9.6 100 11.1 125 198 230 42 6.2 80 227 263 48 5.6 283 329 60.5 4.8 340 395 72.6 5.1 100 0.615 0.703 0.88 1.05 1.32 1.58 1.84 425 494 90.7 6.6 510 592 109 7.0 120 11.3 150 11.5 180 11.8 150 595 691 127 6.4 125 2.11 2.46 2.81 680 790 145 6.3 793 922 169 4.6 906 1053 194 4.5 150 3.16 3.51 210 11.8 150 527 90.7 6.6 180 633 12 / 7 109 7.0 CHP021 210 738 127 6.4 125 240 12.1 280 11.2 CHP024 CHP028 CHP032 240 844 145 6.3 280 984 169 4.6 320 1125 194 4.5 150 CHP036 CHP040 360 1265 218 5.0 400 1406 242 5.1 60 211 36.3 3.7 80 70 246 42.3 6.2 80 281 48.4 5.6

CHP005 CHP006 CHP007 CHP008 50 176 30.2 4.0

50 7.0

60 6.1

320 10.7 200

360 11.1

400 10.8

142 165 30 4.0

170 197 36 3.7

1019 1185 218 5.0

1133 1317 242 5.1

55.3 / 60

0.439

0.527

450 / 165 450 / 125 58 58 300 300 1.5 (5.5) 0.2 (1.0) 74 71 77 82 400 400 3, 400V, 50Hz 2.0 (6.4) 0.3 (1.2) 0.4 (1.4) 0.4 (2.5) 0.2 (0.5) 10.8 2100 1,683 3.0 3.2 1,722 3.2 3.5 2600 1,761 3.7 4.0 1,800 3.9 4.3 2,638 1,857 5.0 5.4 1,935 5.3 5.8 11.9 3,680 2,052 6.4 7.0 2,091 6.8 7.4 3,717 2,194 7.9 8.6 2,194 8.5 9.3 12.6 4,742 2,310 9.8 10.7 2,349 10.3 11.3 14.7 4,872 2,349 12.8 14.0 2,349 13.2 14.6 2.4 (6.9) 0.4 (1.4) 3.2 (9.0) 79 92 97 113 500 500 129 131 123 600 600 131

Pressure Drop Inlet Conn. Outlet Conn Diverter Valve Power source Abs. Pump Ref. Pump

mm*mm 782*291 782*330 782*369 782*408 922*408 922*486 922*603 922*642 922*681 922*681 922*798 922*876 1376*720 1376*759 mm mm kW kW [A] kW [A] kW [A] kW [A] kW [A] A mm mm mm ton ton

Electric

Purge Pump Sealing Blower Control Panel Amp.(400Vac) Lenght (L)

Size

Width (W) Height (H)

1800

2,090

2,147

2,399

Weight

Rigging Operation

Note
1. Working pressure of each water side is based on 1.0MPa (150psig). 2. Lowest outlet temperature of chilled water is 5oC and 18oC for cooling water. 3. Controllable cooling capacity range shall be 25~100% as a standard condition and 0~100% as an option. 4. Each water flow can be adjusted within 50~120%. 5. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator and Generator. 6. 79oC of hot-water temperature is possible as an option.

12

World Energy Co.

WORLD ENERGY

CHP Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Heating Capacity Inlet Temp./Outlet Temp. Hot Water Flow rate P. Drop Connection Flow rate Temp. Exhaust Gas Cooling Heating Unit
usRT kW m3/h mAq mm m /h mAq mm Mcal/h kW ton/h mAq mm kg/sec mmAq
3

Double Effect Exhaust Gas Driven Absorption Machine

Double Effect Exhaust Gas Driven Type (450~1500RT)


CHP050 500 1757 302 3.9 CHP056 560 1968 339 3.6 200 CHP063 630 2214 381 5.0 CHP070 700 2460 423 6.6 CHP080 800 2812 484 4.7 CHP090 900 3163 12 / 7 544 6.4 250 32 / 37.5 630 10.6 300 1416 1646 302 3.9 4.39 1586 1843 339 3.6 200 4.92 1784 2074 381 5.0 5.53 1982 2304 423 6.6 6.15 2266 2633 484 4.7 7.03 700 14.0 800 8.7 900 11.8 350 2549 2962 55.3 / 60 544 6.4 250 7.91 450 / 165 450 / 125 8.78 9.66 2832 3291 605 8.5 3115 3621 665 7.2 3398 3950 726 9.2 300 10.54 11.42 12.30 1000 15.6 1100 3.0 CHP100 1000 3515 605 8.5 CHP110 1100 3866 665 7.2 CHP120 1200 4218 726 9.2 300 1200 3.8 1300 4.8 400 3682 4279 786 11.5 3965 4608 847 8.3 350 13.18 4248 4937 907 10.2 CHP130 1300 4569 786 11.5 CHP140 1400 4921 847 8.3 350 1400 4.0 1500 4.8 CHP150 1500 5272 907 10.2

1
CHP Performance Data

CHP045 450 1582 272 4.4

450 10.7 250 1274 1481 272 4.4 3.95

500 10.8

560 7.7

Pressure Drop Inlet Conn. Outlet Conn Diverter Valve Power source Abs. Pump Ref. Pump

133 600 600

134

143

133

146 750 750

155

153

176

213

221

212 1000 1000

206

184

mm*mm 1376*837 1376*915 1376*1008 1376*1143 1376*1233 1376*1218 1376*1368 1376*1418 1376*1418 1376*1518 1376*1668 1376*1818 1376*2068 mm mm kW kW [A] kW [A] kW [A] kW [A] kW [A] A mm mm mm ton ton

3, 400V, 50Hz 3.2 (9.0) 0.3 (1.2) 0.4 (1.4) 0.4 (2.5) 0.2 (0.5) 14.7 4,954 2,491 15.7 17.2 2,569 16.5 18.1 2,633 21.2 23.7 4,998 2,934 20.7 5,540 3,069 2,962 23.1 25.8 24.6 27.5 31.0 34.8 6,038 3,159 5,644 3,330 23.3 6,142 3,480 3,380 33.6 37.6 35.6 39.9 41.1 46.2 6,667 3,530 6,293 4,348 6,818 4,448 3,500 43.4 48.8 46.4 52.1 50.2 56.5 33.1 7,318 4,598 6,974 4,932 7,475 5,182 54.1 60.8 5.5 (15.0) 1.5 (4.0) 0.75 (2.2) 7.5 (24.0)

Electric

Purge Pump Sealing Blower Control Panel Amp.(400Vac) Lenght (L)

Size

Width (W) Height (H)

3,700

Weight

Rigging Operation

Note
1. Working pressure of each water side is based on 1.0MPa (150psig). 2. Lowest outlet temperature of chilled water is 5oC and 18oC for cooling water. 3. Controllable cooling capacity range shall be 25~100% as a standard condition and 0~100% as an option. 4. Each water flow can be adjusted within 50~120%. 5. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator and Generator. 6. 79oC of hot-water temperature is possible as an option.

World Energy Co.

13

ForFuture FutureEnergy Energy& &Environment Environment For

Double Double Effect Effect Exhaust Exhaust Gas Driven Gas Driven Absorption Absorption Chiller Machine and Heater
Foundation
K/2 A

Anchor Bolt Nut Steel Plate Machine Feet

F Absorber, Evaporator, Condenser & Low Temperature Generator Shell Assembly

F B

Welding

J/2 J K

Example of Anchoring

Note 1. Drain ditch should be prepared around foundation. 2. Horizontal level of foundaton surface should be maintained less than 1mm per 1m. 3. indicates the location of anchor bolts. (Anchor bolt, nut and steel plates are not supplied)

G High Temperature Generator Assemply

G
Drain Ditch

Foundation 50

Model
CHP005 CHP006 CHP007 CHP008 CHP010 CHP012 CHP015 CHP018 CHP021 CHP024 CHP028 CHP032 CHP036 CHP040 CHP045 CHP050 CHP056 CHP063 CHP070 CHP080 CHP090 CHP100 CHP110 CHP120 CHP130 CHP140 CHP150

A (mm) 1,421

B (mm) 800

C (mm) 973 1,033

1,921 1,941 700 2,961 2,936 1,010 3,956 900 3,906 3,856 4,398 4,896 4,348 4,846 5,371 4,896 5,421 5,921 5,371 5,871 990

1,194 1,307 1,453 1,386 1,404 1,567 1,370 1,600

1,150

1,210

2,400

1,290 2,500 1,500

D (mm) 322 322 400 400 400 500 600 600 641 641 800 800 816 816 800 900 1,000 1,100 1,200 1,200 1,400 1,400 1,400 1,500 1,700 1,800 2,100

E (mm) 236 236 236 236 382 371 292 292 289 289 267 287 342 342 352 341 445 463 458 486 461 486 1,171 1,171 1,146 1,131 1,106

H (mm) 100 50 100

I (mm) 200 150 200

J (mm)

K (mm)

125

325

125

325

115

215

150

350

105

205 200 400

105

205 300 500

F (ton) 1.0 1.1 1.2 1.3 2.0 2.1 2.5 2.6 3.1 3.4 3.9 4.1 5.1 5.3 6.2 6.4 8.8 9.6 10.3 12.4 13.4 14.4 17.3 18.3 19.4 21.1 22.4

G (ton) 0.5 0.6 0.7 0.8 0.7 0.8 1.0 1.1 1.2 1.3 1.4 1.5 1.9 2.0 2.4 2.6 3.0 3.3 3.5 4.9 5.4 5.6 5.8 6.1 6.6 7.1 8.0

14

World Energy Co.

CHP Series
System Pipings

WORLD ENERGY
Double Effect Exhaust Gas Driven Absorption Machine

1
CHP Foundation / System Pipings

Exhaust Gas Bypass Air Handling Unit Expansion Tank

Air

Fuel Supply water Air vent


AV

Cooling Tower

Diverter V alve

Engine P T

Drain line Exhaust gas Inlet Chilled / Hot water Pump (1st) Exhaust gas Outlet Bleed off

Cooling water Outlet P T P T Chilled water Outlet Chilled water Inlet Cooling water Inlet D
P T

Thermostat Pressure gauge Temperature Gauge Damper valve Bypass valve Strainer Valve

Chilled / Hot water Pump (2nd)

Flow meter F

Bypass valve

ABSORPTION CHILLER
P T Supply Header Return Header

Cooling water Pump

1) All external equipment out of dotted line is scope of customer's. 2) Refer to outline drawing and specification data sheet for the external dimensions of the machine, the location & the diameter of water pipe connection and the dimensions & the size of Exhaust gas line connections. 3) The locations of chilled water pumps, cooling water pumps and expansion tanks shall be determined in consideration of the hydrostatic head of pumps and the height of building. And the Machine shall not be subject to a pressure higher than the designed pressure at any water header. 4) For cooling water quality control, it is recommended to install cooling water bleed-off device on the inlet pipe line of cooling towers. 5) Around 10 meshes of strainers are recommended to be installed in the cooling water line. 6) For the maintenance and the inspection of the Machine, the following equipment shall be installed on each chilled water and cooling water inlet/outlet lines as well as stop valve. Thermometers and pressure gauges shall be installed at chilled and cooling water inlet/outlet. Air relief valves shall be installed on each chilled and cooling water lines at higher points than each water headers. Drain valves shall be installed at the lowest position between the stop valves of chilled and cooling water and the Machine and the drain valve shall be piped to the drain ditch. 7) There shall be a sufficient clearance for access to the absorber, evaporator, condenser, and generator to facilitate inspection and cleaning work.

Diverter Valve & Exhaust Gas Duct

For Diverter Valve; 1) Install the diverter valve at the exhaust gas duct end of gas turbine or reciprocating engine and level the diverter valve horizontally by using the level gauge. 2) Install the transient duct between high-stage generator and diverter valve. Bypass 3) Connect the wiring in accordance with Exhaust wiring diagram of the manufacturer.
Exhaust Duct Exhaust Gas Diverter Valve Vertical Duct High Stage Generator

For Exhaust Gas Duct; 1) Sharp bend and restrictions should be avoided to allow smooth gas flow. 2) The exhaust gas duct outlet should be arranged to prevent the rain water from entering into the machine and the drain connection should be provided to remove the condensate from the exhaust gas outlet side. World Energy Co.

15

For Future Energy & Environment


B B B

Insulated parts on pipes : Colored galvanized steel with 0.30mm thickness or over 6. For insulation area for each model, please refer to the picture below. 7. The water box sections should be worked to be disassembled for the repair. 8. If necessary, please perform the finish painting in the field after completing the insulation work.

Double Effect Exhaust Gas Driven Absorption Machine


INSULATION FOR HOT SURFACES 75mm(3inch) : High Temperature Generator

Thermal Insulation
Hot Surface FOR HOT SURFACES INSULATION
75mm : High Temp. Generator 75mm(3inch) : High Temperature Generator

50mm(2inch) : High Heat Exchanger Box and It's High Te

19mm(3/4inch) : Heat Exchanger Body It's Low temperatu Low Temperature Generator Body and It's Outle 10mm(3/8inch) : Low Temperature Piping

Cold SurfaceFOR COLD SURFACES INSULATION


19mm(3/4inch) : Evaporator Body and It's Water Box 19mm : Evaporator Body with Water Box

C C C

50mm(2inch) : High Heat Exchanger Box and It's High Temperoture Piping, Steam Box 50mm : HighFOR Heat Exchanger Box INSULATION HOT SURFACES 19mm(3/4inch) :Temperature Heat Exchanger Body It's Low temperature Box(Inlet, Outlet) 75mm(3inch) : High Temperature Generator with High Piping, Low Temperature Generator Body and It's Outlet(ABSO, Refrigerant) Box 50mm(2inch) : High Heat Exchanger Box and It's High Temperoture Piping, Steam Box Steam box 10mm(3/8inch) : Low Temperature Piping INSULATION SURFACES 19mm(3/4inch) :HOT Heat Exchanger Body It's Low temperature Box(Inlet, Outlet) 19mm : HeatFOR Exchanger Body 75mm(3inch) High Temperature Generator Low :Temperature Generator Body and It's Outlet(ABSO, Refrigerant) Box INSULATION COLD SURFACES with FOR Low Temperature Box, 10mm(3/8inch) : Evaporator Low Temperature Piping 50mm(2inch) : High Heat Exchanger Box It'sBox High Temperoture Piping, Steam Box 19mm(3/4inch) : Body and It's and Water 10mm(3/8inch) Inlet Outlet Piping of Refrigerant Pump Box(Inlet, Outlet) 19mm(3/4inch) :COLD Heat and Exchanger Body It's Low temperature INSULATION FOR: SURFACES with Outlet Box Low Temperature Generator Body and It's Outlet(ABSO, Refrigerant) Box 19mm(3/4inch) : Evaporator Body and It's Water Box 10mm(3/8inch) : Low Temperature Piping 10mm : Low temperature Piping 10mm(3/8inch) : Inlet and Outlet Piping of Refrigerant Pump INSULATION FOR COLD SURFACES 19mm(3/4inch) : Evaporator Body and It's Water Box 10mm(3/8inch) : Inlet and Outlet Piping of Refrigerant Pump

10mm(3/8inch) : InletPiping and Outlet Piping of Refrigerant Pum 10mm : Inlet and Outlet of

Refrigerant Pump

Low temperature Generator Body

D D D E

E E E

Note
1. Use only Non-inflammable or Incombustible insulation materials. 2. Do not insulate motor of refrigerant pump. 3. Total insulation area includes piping. 4. Do not cover components such as service valves, dampers, diaphragm valves, sight glass, control valves or thermometers or sensor wells. 5. The standard Material and Thickness as the recommendation : HOT Surface insulation Material of insulation : Glass wool, Thermal Conductivity 0.04kcal/m h Thickness of insulation : 50mm (2 inch), 75mm (3 inch) Material of insulation : Closed cell type Non-inflammable polymer sponge Thickness of insulation : 10mm (3/8inch), 19mm (3/4inch) COLD Surface insulation Material of insulation : Closed cell type Non-inflammable polymer sponge Thickness of insulation : 10mm (3/8 inch), 19mm (3/4 inch) Wrapping Material when Glass wool is used. Insulated parts on body : Colored galvanized steel with 0.45mm thickness or over Insulated parts on pipes : Colored galvanized steel with 0.30mm thickness or over F 6. For insulation area for each model, please refer to the picture below. 7. The water box sections should be worked to be disassembled for the repair. 8. If necessary, please perform the finish painting in the field after DWG NAME completing the insulation work. World Energy Co.,LTD. INSULATION
TIT.PRJ SCALE : UNIT : CHP-SERIES DATE : 2011.02.10.

F F F

1 DWG NO.
7

L90605
A2 (594x420 95g/m )
2

6
Model (mm) 3 CHP045 3 CHP050 CHP056 3 CHP063 CHP070 CHP080 CHP090 CHP100 CHP110 CHP120 CHP130 CHP140 CHP150 75mm 20.6 21.3 23.4 24.7 25.3 32.1 33.7 34.2 36.5 37.6 39.3 41.1 43.9

Model (mm) CHP005 CHP006 CHP007 CHP008 CHP010 CHP012 CHP015 CHP018 CHP021 CHP024 CHP028 CHP032 CHP036 CHP040

75mm 1 8.2 1 8.2 8.2 1 8.2 9.5 10.4 11.2 11.4 12.8 13.6 14.1 18.2 18.4 18.4

Hot Surface (m ) 50mm 19mm 3.9 0.9 3.9 0.9 3.9 0.9 4.2 1.1 5.1 1.8 5.2 1.8 7.5 2.2 7.5 2.2 8.5 2.2 8.5 22.2 10.2 2.5 10.2 2.5 11.3 3.0 11.3 3.0
2

10mm 2 0.4 2 0.4 0.4 2 0.3 0.7 0.7 0.7 0.7 0.7 0.9 1.1 1.1 1.2 1.2

Cold Surface (m ) 19mm 10mm 2.6 0.3 2.6 0.3 2.6 0.3 2.6 0.3 3.6 0.3 3.6 0.3 4.8 0.3 4.8 0.3 5.8 0.3 5.8 0.4 7.1 0.4 7.1 0.4 7.9 0.4 7.9 0.4
2

Hot Surface (m ) 50mm 19mm 4 12.4 3.1 4 12.4 3.1 9.5 7.5 4 9.5 8.3 9.5 9.2 11.0 10.5 11.4 11.5 11.8 13.0 13.7 15.5 14.0 16.8 14.3 18.2 14.6 18.1 15.1 19.6
2

10mm 1.2 1.2 1.4 1.4 1.5 1.6 1.6 1.7 1.7 1.7 1.8 1.8 1.8

Cold Surface (m ) 19mm 10mm 5 7.9 0.4 11 0.4 5 13.5 0.6 15 0.7 5 16 0.7 17 1.1 18.5 1.2 20 1.2 22.5 1.4 22.2 1.4 23.4 1.4 26.6 1.5 27.6 1.5
2

16

World Energy Co.

CHP Series
Start-up Sequence

WORLD ENERGY
Double Effect Exhaust Gas Driven Absorption Machine

1
Start Request No
CHP Thermal Insulation / Start-up Sequence

Verify All sensors in range In Prestart safties

No

Sensor Fault / Prestart Alerts

Yes Start Chilled Water Pump Cooling Mode 60 deg C Heating Start Water Verify Timer No A B 79 deg C Heating

Verify Chilled Water Flow

No

Verify timer elapsed

Yes

Chilled Water Fault

Yes

Start-Stop Condition

Yes

Monitor for Start-Stop

Start 3 min Refrigerant Pump Delay Timer No

No Start Cooling Water Pump

Ref Pump Timer elapsed

Start Water Verify Timer No

Yes Start Refrigerant Pump

Verify Cooling Water Flow Yes Start Tower Control

No

Water timer Elapsed

Yes

Cooling Water Fault

Start Solution Pump

Machine Running

World Energy Co.

17

For Future Energy & Environment

Single Effect Double Lift Hot Water Driven Absorption Machine


Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Water Pressure Drop Control Valve Connection Control Valve Power source Abs. Pumps Ref. Pump Electric Purge Pump Control Panel Total kW Total Ampere Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Shell Unit
kW usRT m3/h mH20 mm m3/h mH20 mm ton/h m /h mH20 mH20 mm mm kW (A) kW (A) kW (A) kW (A) kW A mm mm mm ton ton mm
3

Single Effect Double Lift Hot water Driven Type (75~375RT)


2AB090 316 90 54.4 3.8 80 107 10.3 125 9.0 9.4 3.1 2.2 10.8 11.2 3.3 3.2 65 40 2.3 (8.8) 0.2 (1.1) 0.3 (1.5) 50 3, 400V, 50Hz 2.6 (9.8) 3.2 (10.8) 13.2 13.7 2.9 4.7 16.2 16.8 3.5 3.0 129 10.8 157 5.2 2AB110 387 110 66.5 4.6 100 193 5.8 150 95 / 55 18.6 19.3 3.1 3.9 21.6 22.4 3.3 5.2 80 65 25.2 26.2 6.7 2.9 28.8 29.9 6.9 3.7 32.4 33.7 6.3 4.7 36.0 37.4 6.3 2.3 100 80 40.8 42.4 6.2 3.0 45.0 46.8 6.2 3.6 222 5.9 257 6.3 2AB135 475 135 81.6 4.8 2AB155 545 155 93.7 4.1 2AB180 633 180 12 / 7 45.4 3.7 109 4.6 125 31 / 36.5 300 11.4 200 343 11.3 386 10.8 429 10.6 250 486 11.0 536 11.3 127 3.2 145 3.4 163 3.4 150 181 3.5 206 3.1 200 227 3.2 2AB210 738 210 2AB240 844 240 2AB270 949 270 2AB300 1,055 300 2AB340 1,196 340 2AB375 1,319 375 264 75

2AB075

0.4 (1.5) 0.4 (1.5)


0.2 (0.5)

3.1 11.9 2,658 1,834 2,084 4.4 5.1 2,400 116 425 241 130 466 263 152 548 316 4.6 5.3 5.7 6.6

3.2 12.3 3,678

3.5 13.3 3,720 2,109 2,257 6.0 7.0 3,400 174 610 350 234 779 423 252 852 466 286 910 519 7.2 8.4 7.5 8.9 8.8 10.4

3.6 4,740 4,872 2,248 2,519 9.2 10.9 310 1,008 576 11.3 13.4 356 1,353 695 11.8 14.1 4,500 381 1,460 758

4.2 14.3 4,882 2,430 2,787 13.5 16.2 509 1,729 895 14.0 16.9 536 1,827 968

Space for Tube Replacement Chilled Water Side Water Volume of Cooling Water Side Machine Hot Water Side

Note
1. Working pressure of chilled/cooling water circuits are based on 1.0Mpa (150psig) and 1.6MPa (230psig) for driving hot water circuit. 2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.42m3/h for cooling water and 0.1187ton/h for hot water. 3. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator and Generator.

2AB180 (Korea)

18

World Energy Co.

2AB Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Water Shell Pressure Drop Control Valve Connection Control Valve Power source Abs. Pumps Ref. Pump Electric Purge Pump Control Panel Total kW Total Ampere Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Chilled Water Side Cooling Water Side Hot Water Side Unit
kW usRT m3/h mH20 mm m3/h mH20 mm ton/h m3/h mH20 mH20 mm mm kW (A) kW (A) kW (A) kW (A) kW A mm mm mm ton ton mm

WORLD ENERGY
Single Effect Double Lift Hot Water Driven Absorption Machine

Single Effect Double Lift Hot water Driven Type (420~1,300RT)


2AB470 1,653 470 284 4.3 200 601 9.9 672 13.5 300 50.4 52.4 5.6 1.8 56.4 58.6 7.6 2.2 100 100 3, 400V, 50Hz 5.6 (18.6) 0.4 (1.6) 63.0 65.5 8.0 2.8 72.0 74.8 5.3 3.6 751 12.7 858 9.5 2AB525 1,846 525 318 5.7 2AB600 2,110 600 363 4.1 2AB675 2,373 675 408 5.5 250 31 / 36.5 965 12.9 350 95 / 55 81.0 84.2 3.4 4.6 90.0 93.5 4.4 2.2 125 125 99.0 103 3.7 2.6 108 112 4.6 3.2 117 122 5.6 3.7 126 131 4 4.3 135 140 4.8 2.2 150 150 12.7 (45.0) 156 162 7 2.9 1,073 16.9 1,180 10.1 1,287 12.9 400 1,394 16.1 1,502 12.5 1,609 15.3 450 1,859 14.5 2AB750 2,637 750 12 / 7 2AB Performance Data 254 3.1 454 7.2 499 4.0 544 5.1 590 6.3 300 635 5.2 680 6.3 786 8.8 2AB825 2,901 825 2AB900 3,165 900 2AB975 2AB1050 2AB1125 2AB1300 3,428 975 3,692 1,050 3,956 1,125 4,571 1,300 1,477 420

2AB420

7.7 (25.0)

9.4 (31.5)

1.5 (4.0A) 0.75 (2.3)


0.2 (0.5) 9.8 31.0 6,038 5,654 6,152 3,140 3,471 22.2 26.9 5,700 724 2,788 1,247 26.7 31.6 5,200 970 3,567 1,561 28.7 34.0 5,700 1,037 3,776 1,684 30.7 36.3 6,200 1,106 3,996 1,813 36.4 43.1 5,700 1,373 4,938 2,040 6,677 6,258 11.9 38.3 6,783 3,531 3,837 38.4 45.5 6,200 1,459 5,206 2,201 40.8 48.3 6,700 1,541 5,461 2,354 43.4 52.5 7,200 1,970 7,867 2,810 7,283 7,010 15.2 51.8 7,510 4,430 4,000 46.1 55.7 7,700 2,083 8,193 2,994 53.1 64.1 8,200 2,309 8,844 3,363 8,510

0.4 (1.5)
6.6 22.1 4,998 5,540 2,788 3,036 19.0 23.0 4,500 619 2,448 1,050 20.7 25.0 5,200 674 2,625 1,153

Space for Tube Replacement Water Volume of Machine

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

19

For Future Energy & Environment

Single Effect Double Lift Hot Water Driven Absorption Machine

Outline_Foudation
2AB 075 / 090

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m
325 125 REAR 80 552 372 0 150 50

1326

1547

FRONT 100 1941 0

3200

R6

Clearance for tube removal at either side

50

2658(L) Cooling water Outlet(125A) 1928

1834(W)

Condenser

Aux. Generator 1'st Generator

1957

Hot water Outlet(65A)

1452

2'nd Generator Control Panel 680 2084(H) Aux. Absorber

Absorber

Evaporator

Hot water Inlet(65A) 1230 Chilled water Outlet(80A) 882 Chilled water Inlet(80A) 653 Cooling water Inlet(125A)

63

2113 2004 1941

1309

1376

80 168

2AB 110 / 135


0
1326 REAR 80 552 372 100 325 125

2074 2114

781

904 854

1456 1656

100

1547

R6 50

Clearance for tube removal at either side

3678(L)
Cooling water Outlet(150A)

1834(W)

1928

Condenser

Aux. Generator 1'st Generator

1957 Outlet(65A) 1452 Inlet(65A)


Hot water

2084(H)

2'nd Generator

Control Panel

Absorber
Aux. Absorber

Evaporator

1217 Chilled water Outlet(100A) 895 Chilled water


Inlet(100A) Inlet(150A)

680

627 Cooling water

0
3134 3024 2961 1376 63 1474 80 3094 3134
1978

0
904 854
168

20

World Energy Co.

2961

Hot water

100

4200

0 150

FRONT

50

1456 1656

2AB Series
Outline_Foudation
2AB 155 / 180

WORLD ENERGY
Single Effect Double Lift Hot Water Driven Absorption Machine
1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

80

1594

REAR

100

350 150

2
2AB Outline_Foudation

660 480 0 150 0

4200 Clearance tube removal Clearance for for tube removal 50 at side R6 ateither either side
3720(L)
Cooling water Outlet(150A) 2081

2109(W)

Condenser

Aux. Generator 1'st Generator

2125 Hot water Outlet(80A)

2257(H)

2'nd Generator Absorber Aux. Absorber

Control Panel

Evaporator

Hot water Inlet(80A) 1370 Chilled water Outlet(125A)


1620 1018 Chilled water Inlet(125A) 705 Cooling water Inlet(150A)

830

0
3146 3011 2936 1985 1481 1644 1064 1014 175

0
80

75

2AB 210 / 240


1594 REAR 80 FRONT 100 100 50 0 150 1724 1924 350 150

660 480

5200
Clearance for tube removal at either side
50

R6

4740(L)
Cooling water Outlet(200A) 2082

2109(W)
Hot water Outlet(80A) 2125 Chilled water Outlet(125A) Hot water Inlet(80A) 1620 Chilled water Inlet(125A) 1018

Condenser

Aux. Generator 1'st Generator

2257(H)

2'nd Generator Absorber Aux. Absorber

1370
Evaporator

Control Panel

830

0
75

0 0 0 0

210

4166 4031 3956

2506

2003

4111 4166

1644

1064 1014

80 168

3956

1815

3091 3146

2936

654 Cooling water Inlet(200A)

100

1815

FRONT

50

1724 1924

World Energy Co.

21

For Future Energy & Environment

Single Effect Double Lift Hot Water Driven Absorption Machine

Outline_Foudation
2AB 270 / 300

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m
400 200

729 514

5300
Clearance for tube removal at either side
50

R6

4872(L)
Cooling water Outlet(250A) 2319

2248(W)
Hot water Outlet(100A) 2389 Hot water Inlet(100A) 1773 Chilled water Inlet(150A) 1052 Cooling water Inlet(250A) 576

Condenser

Aux. Generator 1'st Generator

Control Panel

2519(H)

2'nd Generator Absorber Aux. Absorber Evaporator

Chilled water Outlet(150A) 1489

980

0
1699 4171 4006 3906 1045 1005 100 105 190 2520 2016

0 0 0 0

2AB 340 / 375


0
1813 REAR 105 FRONT 3906 100 0
R6 50
Hot water Outlet(100A) 2657 Hot water Inlet(100A) 1971 Chilled water Inlet(200A) 1122 Cooling water Inlet(250A) 609

4096 4164 4171

258

833 618

2049

0 170

5300

Clearance for tube removal at either side

4882(L)
Cooling water Outlet(250A) 2587

2430(W)

Condenser

Aux. Generator 1'st Generator

Control Panel

2787(H)

2'nd Generator Absorber Aux. Absorber Evaporator

Chilled water Outlet(200A) 1660

1100

0 0 0 0

1125 1085

265

4171 4006 3906

1926

22

World Energy Co.

1883

4096 4171

2430

100

105 190

70

1988 2188

100

400 200

3906

100

1865

0 170

FRONT

70

1804 2004

105

1629

REAR

100

2AB Series
Outline_Foudation
2AB 420 / 470 / 525

WORLD ENERGY
Single Effect Double Lift Hot Water Driven Absorption Machine
1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m
450 250

2
105 100

A B C D E F G H I

2330

I
Clearance for tube removal at either side
50

2AB420 4998 3856 3981 4171 2405 1901 4151 4071 4500

2AB470 5540 4398 4523 4713 2647 2143 4693 4613 5200

2AB525 6038 4896 5021 5211 2895 2391 5191 5111 5800

2069

REAR

2AB Outline_Foudation

2274 FRONT 0

921 686

0 200

R6

A
Cooling water Outlet(300A)

2788(W)

Hot water Outlet(100A)

2811

2903
Condenser Aux. Generator

1'st Generator

2085 1769

Hot water Inlet(100A)

3036(H)

2'nd Generator Absorber Aux. Absorber Evaporator

Chilled water Outlet(200A) Chilled water Inlet(200A)

Control Panel

1150

1149
Cooling water Inlet(300A)

634

1283 1253

2169

D CB

0 125

105

215

HG D

2AB 600 / 675 / 750


0

A B C D E F G H I J

2518

2AB600 5654 4348 4498 4708 5011 2755 2183 4708 4598 5200

2AB675 6152 4846 4996 5206 5509 2938 2366 5206 5096 5700

2AB750 6677 5371 5521 5731 6034 3163 2591 5731 5621 6200

2323

REAR 105 2528 FRONT 0

100 100 100 2728

500 300

1015 780

0 200

J
Clearance for tube removal at either side
50

R6

A
Cooling water Outlet(350A)

3140(W)

Hot water Outlet(125A)

3200

3330
Condenser Aux. Generator

1'st Generator

Hot water Inlet(125A) Chilled water Outlet(250A)

2356 1993

3471(H)

2'nd Generator Absorber Aux. Absorber Evaporator

Control Panel

Chilled water Inlet(250A)

1299
Cooling water Inlet(350A)

1000

657

0
643

0
250

0 0

150

2831

2423

1443 1413

E D CB

105 309

IH

100

100

2474

World Energy Co.

23

For Future Energy & Environment

Single Effect Double Lift Hot Water Driven Absorption Machine

Outline_Foudation
2AB 825 / 900 / 975

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m
500 300 2613 REAR 105 FRONT 0

A B C D E F G

Clearance for tube removal at either side

R6

50

A
Cooling water Outlet(400A)

3531(W)
Hot water Outlet(125A)

3541

3671
Condenser Aux. Generator

1'st Generator

Hot water Inlet(125A)

2612

3837(H)

2'nd Generator Absorber Aux. Absorber Evaporator

2199 1427

Chilled water Outlet(300A) Chilled water Inlet(300A)

Control Panel

1000

Cooling water Inlet(400A)

667
0
0

3173

2713

1603 1573

2AB 1050 / 1125 / 1300


A B
0

150

699

D CB

105 358

250

IH

C D E F G H I

2AB1050 2AB1125 2AB1300 7010 7510 8475 5371 5871 6871 5521 6021 7021 5781 6281 7281 6144 6644 7644 2643 2893 3393 1921 2171 2671 5881 5706 7200 6281 6206 7700 7282 7206 8200

500 100 105 3420 1285 1030 0 200 0 FRONT 100 100 3620 300 3215 REAR

3410

J
Clearance for tube removal at either side
R8 00

A
Cooling water Outlet(500A) 3631

4430(W)
Hot water Outlet(150A) 3834
Condenser Aux. Generator

1'st Generator

Control Panel

Chilled water Outlet(350A) 2154 Chilledwater Inlet(350A) 1565

Hot water Inlet(150A) 2662

4000(H)

2'nd Generator Absorber Evaporator

Aux. Absorber

850

Cooling water Inlet(500A) 808

0
150 866

0
3835 3315 2085 2035 965 105

E D CB

595

IH

24

World Energy Co.

100

2808

H I

5231 5096 5700

5756 5621 6200

6256 6121 6700

0 200

100

2AB825 6258 4846 4996 5231 5559 2918 2351

2AB900 6783 5371 5521 5756 6084 3158 2591

2AB975 7283 5871 6021 6256 6584 3408 2841

1145 910

2818 3018

100

(mm) 2AB75 2AB90 2AB110 2AB135 2AB155 2AB180 2AB210 2AB240 2AB270 2AB300 2AB340 2AB375 2AB420 2AB470 2AB525 2AB600 2AB675 2AB750 2AB825 2AB900 2AB975 2AB1050 2AB1125 2AB1300

(m )

(m )

2AB Series

Thermal Insulation

Hot Surface

19 7.3 7.3 9.8 9.8 11.4 11.4 14.3 14.3 16.0 16.0 18.7 18.7 21.7 23.6 25.4 28.4 30.3 32.1 35.1 37.0 38.8 40.7 42.8 44.9

10 19 10 4.0 0.4 2.2 4.0 0.4 2.2 5.4 0.4 2.2 5.4 0.4 2.2 2.5 6.1 0.5 6.1 0.5 2.5 7.4 0.6 2.5 7.6 0.6 2.5 8.2 0.6 3.3 19 mm : 1 , 2, 8.2 0.6 3.3 , 9.8 0.6 3.9 9.8 0.6 3.9 10 mm : 13.5 0.7 4.6 15.0 0.8 4.6 16.0 0.8 4.6 16.3 1.3 5.4 19 mm : 17.8 1.3 5.4 19.4 1.3 5.4 10 mm : 19.5 1.4 5.9 21.2 1.4 5.9 25.7 1.4 5.9 st Generator nd 19mm : 1 6.2 27.0 1.5 with water box, 2 Generator with water box, 6.2 28.4 Generator 1.5 Aux. with water box, Heat Exchanger body 6.2 29.8 1.5

Single Effect Double Lift Hot Water Driven Absorption Machine


(2) : : 10mm( 3 8 inch), 19mm(

NOTES 1. . 2. . 3. . 4. , , , , , , 5. (1) : 120C 3 inch) : : 10mm( 3 8 inch), 19mm( 4

WORLD ENERGY

inch)

6. . 7. . 8. .

10mm : Pipes of High temperatures parts

Cold Surface

19mm : Evaporator with water box 10mm : Inlet and outlet pipes of refrigerant pump

2
2AB Outline_Foundation / Thermal Insulation

Condenser

Aux. Generator 1'st Generator

2'nd Generator Control Panel Aux. Absorber

Absorber

Evaporator

Note
1. Use only Non-inflammable or Incombustible insulation materials. 2. Do not insulate motor of refrigerant pump. 3. Total insulation area includes piping. 4. Do not cover components such as service valves, dampers, diaphragm valves, sight glass, control valves or thermometers or sensor wells. 5. The standard Material and Thickness as the recommendation : HOT Surface insulation Material of insulation : Non-inflammable polymer sponge usable at 120C Thickness of insulation : 19mm (3/4 inch), 10mm (3/8 inch) when polymer sponge is used COLD Surface insulation Material of insulation : Closed cell type Non-inflammable polymer sponge Thickness of insulation : 10mm (3/8 inch), 19mm (3/4 inch) 6. For insulation area for each model, please refer to the table below. 7. The water box sections should be worked to be disassembled for the repair. 8. If necessary, please perform the finish painting in the field after completing the insulation work.

Model (mm) 2AB075 2AB090 2AB110 2AB135 2AB155 2AB180 2AB210 2AB240 2AB270 2AB300 2AB340 2AB375

Hot Surface(m2) 19mm 7.3 7.3 9.8 9.8 11.4 11.4 14.3 14.3 16.0 16.0 18.7 18.7 10mm 2.2 2.2 2.2 2.2 2.5 2.5 2.5 2.5 3.3 3.3 3.9 3.9

Cold Surface(m2) 19mm 4.0 4.0 5.4 5.4 6.1 6.1 7.4 7.6 8.2 8.2 9.8 9.8 10mm 0.4 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6

Model (mm) 2AB420 2AB470 2AB525 2AB600 2AB675 2AB750 2AB825 2AB900 2AB975 2AB1050 2AB1125 2AB1300

Hot Surface(m2) 19mm 21.7 23.6 25.4 28.4 30.3 32.1 35.1 37.0 38.3 40.7 42.8 44.9 10mm 4.6 4.6 4.6 5.4 5.4 5.4 5.9 5.9 5.9 6.2 6.2 6.2

Cold Surface(m2) 19mm 13.5 15.0 16.0 16.3 17.8 19.4 19.5 21.2 25.7 27.0 28.4 29.8
World Energy Co.

10mm 0.7 0.8 0.8 1.3 1.3 1.3 1.4 1.4 1.4 1.5 1.5 1.5

25

For Future Energy & Environment

Waste Heat Recovery Absorption Machine


Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chillrd Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Water Pressure Drop Shell Control Valve Unit
kW usRT m /h mH20 mm m /h mH20 mm ton/h m /h mH20 mH20 mm mm kW (A) kW (A) kW (A) kW (A) kW A mm mm mm ton ton mm
3 3 3

Waste Heat Recovery (Single Effect Hot Water) Driven Type (75~375RT)
2AA090 316 90 2AA110 387 110 2AA135 475 135 2AA155 545 155 2AA180 633 180 13 / 8 2AA210 738 210 2AA240 844 240 2AA270 949 270 2AA300 1,055 300 2AA340 1,196 340 2AA375 1,319 375

2AA075 264 75

45.4 3.7 80

54.4 3.8

66.5 4.6 100

81.6 4.8

93.7 4.3

109 4.6 125 31 / 36

127 3.2

145 3.4

163 3.4 150

181 3.5

206 3.1 200

227 3.2

156 4.7 150

188 5.0

229 12.0

281 13.0 200

323 13.0

375 13.4

438 7.1

500 7.1 250

563 7.3

625 7.2

709 7.1 300

782 7.2

70 /60 55.1 56.3 5.8 1.9 100 100 66.1 67.6 6.5 2.7 80.7 82.6 5.3 4.0 99.1 101.4 6.1 2.9 125 125 3, 400V, 50Hz 3.0 (11.0) 0.2 (1.1) 0.3 (1.5) 0.4 (1.5) 0.2 (0.5) 3.8 14.1 2,658 2,281 2,084 4.8 5.6 2,400 5.1 5.8 6.3 7.3 6.6 7.7 3,400 7.9 9.2 8.3 9.8 3.8 14.1 3.9 14.5 3,678 3.9 14.5 4.8 16.2 3,720 2,623 2,257 9.7 11.4 10.1 12.0 12.4 14.7 4,500 4.8 16.2 4.8 16.2 4,740 4.8 16.2 5.8 18.8 4,776 2,795 2,540 13.0 15.5 14.9 17.8 5.8 18.8 5.8 18.8 4,880 3,022 2,838 15.4 18.6 5.8 18.8 3.8 (12.6) 0.4 (1.6) 4.8 (15.2) 113.8 116.4 6.7 3.8 132.1 135.2 7.1 5.2 154.1 157.7 5.9 3.1 150 150 176.2 180.2 6.2 4.1 198.2 202.8 5.6 5.1 220.2 225.3 5.7 1.4 200 200 249.6 255.3 5.5 1.8 275.3 281.6 5.7 2.2

Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Ampere Length (L) Size Width (W) Height (H) Weight Rigging Operation

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

2AA240 (Zinc Factory, Korea)

26

World Energy Co.

2AA Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chillrd Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Pressure Water Drop Shell Control Valve Unit
kW usRT m /h mH20 mm m /h mH20 mm ton/h m /h mH20 mH20 mm mm kW (A) kW (A) kW (A) kW (A) kW A mm mm mm ton ton mm
3 3 3

WORLD ENERGY
Waste Heat Recovery Absorption Machine

Waste Heat Recovery (Single Effect Hot Water) Driven Type (420~1300RT)
2AA470 1,653 470 2AA525 1,846 525 2AA600 2,110 600 2AA675 2,373 675 2AA750 2,637 750 13 / 8 2AA825 2,901 825 2AA900 3,165 900 2AA975 3,428 975 2AA1050 2AA1125 2AA1300 3,692 1,050 3,956 1,125 4,571 1,300

2AA420 1,477 420

254 3.1

284 4.3 200

318 5.7

363 4.1

408 5.5 250

454 7.2

499 5.4

544 6.9

590 8.6 300

635 5.2

680 6.3

786 9.4

3
2AA Performance Data

31 / 36 875 5.6 979 7.6 350 1,094 6.8 1,250 5.1 1,407 6.9 400 70 / 60 308.3 315.4 6.3 2.8 345.0 353.0 7.6 3.5 385.4 394.3 4.1 4.4 250 200 250 3, 400V, 50Hz 9.2 (27.0) 0.4 (1.6) 0.4 (1.5) 0.2 (0.5) 10.2 30.6 4,998 10.2 30.6 5,540 3,467 3,222 20.9 25.3 4,500 22.8 27.5 5,200 24.4 29.6 5,700 29.4 34.8 5,200 10.2 30.6 6,038 11.3 33.0 5,654 11.3 33.0 6,158 3,905 3,600 31.6 37.4 5,700 33.8 39.9 6,200 40.0 47.4 5,700 11.3 33.0 6,683 12.9 41.8 6,293 12.9 41.8 6,818 4,477 3,850 42.2 50.1 6,200 44.9 53.1 6,700 47.4 57.7 7,200 12.9 41.8 7,318 20.5 70.8 7,008 20.5 70.8 7,508 5,202 4,000 50.7 61.7 7,700 58.4 70.5 8,200 20.5 70.8 8,475 10.4 (35.0) 1.5 (4.0) 0.75 (2.3) 18.0 (64.0) 440.4 450.6 3.3 2.5 495.5 5.609 4.4 3.1 550.5 563.3 5.8 3.9 606 620 4.0 4.7 661 676 5.1 1.8 300 300 716 732 6.3 2.1 771 789 4.8 2.4 826 845 5.8 2.8 400 954 976 8.5 3.7 1,563 9.0 1,719 6.7 1,876 8.6 450 2,032 10.7 2,188 6.6 2,345 8.1 500 2,709 10.8

Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Ampere Length (L) Size Width (W) Height (H) Weight Rigging Operation

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

World Energy Co.

27

For Future Energy & Environment

Single Effect Low Temperature Hot Water Absorption Chiller

Single Effect Hot Water Driven Absorption Machine


Unit
kW usRT m3/h mH20 mm m /h mH20 mm ton/h mH20 mH20 mm mm kW (A) kW (A) kW (A) kW (A) A mm mm mm ton ton mm
3

Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Water Shell Pressure Drop Control Valve Connection Control Valve Power source Abs. Pumps Electric Ref. Pump Purge Pump Control Panel Total Ampere Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Chilled Water Side Cooling Water Side Hot Water Side L030 105 30 18.1 4.9 L040 141 40 24.2 5.1 65 39.6 6.3 52.8 6.6 100 8.4 0.8 2.1 40 1.2 (4.0) 0.2 (1.1) 11.2 1.1 3.8 50 50 14 1.9 2.2 16.8 2.2 3.2 21 1.5 5.0 65 65 66.1 12.6 79.3 14.0 99.1 10.9 125 L050 176 50 30.2 9.7 L060 211 60 36.3 10.6 L075 264 75 45.4 10.4 80 119 7.2 L090 316 90 54.4 11.0

Single Effect Hot Water Driven Type (30~300RT)


L110 387 110 66.5 9.6 100 31 / 36.5 145 10.8 178 11.6 150 95 / 80 25.2 1.6 7.1 30.8 0.7 4.3 37.8 0.8 2.5 80 80 3, 380V, 50Hz 1.5 (4.0) 0.3 (1.5) 0.4 (1.5) 0.2 (0.5) 7.1 2,095 1,077 1,880 2,598 1,095 2.2 2.5 1,900 61 161 69 2.6 2.9 2,400 73 187 80 77 198 90 117 312 112 2.7 3.1 3.6 4.1 3.7 4.2 2,400 129 344 124 155 432 148 2,597 1,244 2,255 4.6 5.2 4.8 5.5 3,400 173 480 166 234 644 198 252 698 221 286 715 252 5.5 6.4 5.8 6.8 7.5 3,680 9.6 3,708 1,472 2,257 6.8 7.9 7.1 8.4 310 786 283 327 4,500 356 381 993 359 8.8 10.4 4,734 10.6 4,776 1,495 2,540 9.2 10.9 2.0 (6.0) 0.4 (1.6) 2.4 (7.0) 43.4 0.9 3.3 50.4 1.0 4.5 58.8 1.6 2.4 67.2 1.6 3.2 100 100 75.6 1.6 4.0 84 1.6 5.0 205 11.3 238 11.9 277 11.0 317 10.5 200 357 10.9 396 10.6 L135 475 135 81.6 10.6 L155 545 155 93.7 9.6 L180 633 180 109 9.7 125 L210 738 210 127 9.8 L240 844 240 145 9.6 L270 949 270 163 10.3 150 L300 1,055 300 181 10.6

13 / 8

2.1 2.3 54 140 57

Space for Tube Replacement Water Volume of Machine

Note
1. Working pressure of chilled/cooling water circuits are based on 1.0MPa (150psig) and 1.6MPa (230psig) for driving hot water circuit. 2. Standard flow rate of chilled water per usRT is 0.6048m3/h, 1.321m3/h for cooling water and 0.280ton/h for hot water. 3. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator and Generator. 4. High temperature (100 ~ 150 degree C) Hot Water Driving type is available as additional model. Followings are the standard capacity range and the standard operational condition for the model selection; - Cooling capacity range as Standard model : 100 ~ 1300RT - Hot water Inlet / Outlet temperature : 138 / 108 degree C - Chilled water Inlet / Outlet temperature : 12 / 7 degree C - Cooling water Inlet / Outlet temperature : 32 / 39 degree C

28

World Energy Co.

HWAR - L Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate P. Drop Connection Inlet Temp./Outlet Temp. Flow rate Hot Water Unit
kW usRT m3/h mH20 mm m /h mH20 m ton/h
3

WORLD ENERGY
Single Effect Hot Water Driven Absorption Machine

Single Effect Hot Water Driven Type (340~1300RT)


L375 1,319 375 227 9.8 L420 1,477 420 254 7.5 200 L470 1,653 470 284 10.3 L525 1,846 525 318 4.6 L600 2,110 600 363 3.4 L675 2,373 675 408 4.6 250 31 / 36.5 621 8.5 300 105 1.6 3.0 118 1.6 3.7 125 125 132 2.2 4.7 147 3.0 2.6 168 1.8 3.4 694 11.4 793 7.2 892 9.7 350 95 / 80 189 2.5 4.3 150 150 3, 380V, 50Hz 3.0 (11.0) 0.4 (1.6) 0.4 (1.5) 0.2 (0.5) 1.5 (4.0) 0.75 (2.3) 22.8 6,667 6,293 6,818 2,329 4,000 23.9 29.0 6,200 1,110 3,311 791 26.2 31.8 5,700 1,439 4,001 905 28.5 34.6 6,200 1,525 4,223 970 30.8 37.5 6,700 1,607 4,435 1,045 33.1 40.3 6,200 1,688 5,426 1,146 35.4 43.2 6,700 1,783 5,675 1,217 37.7 46.0 7,200 1,980 6,172 1,360 7,318 6,860 7,360 2,929 7,860 210 3.3 5.3 231 2.6 1.9 252 3.3 2.3 273 4.1 2.7 200 200 4.5 (16.0) 991 12.7 1,090 10.9 L750 2,637 750 454 6.1 L825 2,901 825 499 4.0 L900 3,165 900 544 5.2 300 1,189 13.9 1,288 17.3 400 294 3.4 3.1 315 4.2 3.6 364 6.1 2.0 250 250 1,387 13.8 L975 3,428 975 590 6.4 L1050 L1125 L1300 3,692 1,050 635 5.2 3,956 1,125 680 6.4 350 1,486 14.0 1,717 14.4 4,571 1,300 786 9.5

L340 1,196 340 206 9.4

13 / 8

449 10.7 250 95.2 1.6 2.4

495 10.7

555 6.2

4
L-Performance Data

mH20 Shell Pressure Drop Control Valve mH20

Connection Control Valve Power source Abs. Pumps Electric Ref. Pump Purge Pump Control Panel Total Ampere Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Chilled Water Side Cooling Water Side Hot Water Side

mm mm kW (A) kW (A) kW (A) kW (A) A mm mm mm ton ton mm

2.4 (7.0)

10.6 4,880 1,575 2,838 10.5 12.5 463 1,296 347 10.9 13.1 4,500 486 1,405 388 580 1,865 423 14.7 17.8 4,998

14.6 5,540 1,830 3,222 16.0 19.4 5,200 626 2,001 463 17.2 20.8 5,700 669 2,125 504 19.3 23.3 5,200 982 2,963 672 6,038 5,644

17.0 6,142 2,206 3,600 21.6 26.1 5,700 1,045 3,132 725

Space for Tube Replacement Water Volume of Machine

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

29

For Future Energy & Environment

Single Effect Hot Water Driven Absorption Machine

Outline_Foudation
HWAR-L030 / 040

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

125

800

0 50
R6

163

00

1076(W) Cooling Water Outlet (100A) 1760

2095(L)

Condenser
Hot water Inlet (65A)
1394

Generator

1488

Hot water Outlet (65A)

1169 1880(H)
Control Panel

Absorber

Evaporator

Chilled water Outlet (65A)

Cooling Water Inlet (100A) 575

762 675

Chilled water Inlet (65A)

216

1421

670

10

387.5

162.5

860 800

Clearance for tube removal at either side

2400

HWAR-L050 / 060
125

1583.5

1707.5

800

0 32

R6

00

0 50 150

216.5

1077(W)

2600(L)

Condenser
Hot water Inlet (65A)
1394

1772

Cooling Water Outlet (100A)

Generator

1508

Hot water Outlet(65A)

1169 1880(H)

Chilled water Outlet (65A)

Control Panel

Absorber

Evaporator Chilled water Inlet (65A)

Cooling Water Inlet (100A)


549

762 610

63

1418

1921 1984

2084

2213

387

162

973

10

860 800

217

2500

Clearance for tube removal at either side

30

World Energy Co.

860

1921

163

163

860

1421

163

163

0 0

HWAR - L Series
Outline_Foudation
HWAR-L075 / 090

WORLD ENERGY
Single Effect Hot Water Driven Absorption Machine
1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

125

700

243
0 100 200

R6 00

1244(W)

2597(L)

4
L- Outline Foundation

Cooling Water Outlet (125A)


2125

Condenser
Hot water Inlet (65A)
1641

Generator

2255(H)

Control Panel

Absorber

Evaporator

Cooling Water Inlet (125A)


639

750

882 800

700

878

1331

1941

2068 2115 2210

362

182

700

100

387

Clearance for tube removal at either side

2400

HWAR-L110 / 135
125

162 62.5

700

0
0 100 200 2961 163 163

243

R600

3680(L)

1242(W)

842 882
2109 Colling water Outlet (150A) 1825 Hot water Outlet (80A)

Condenser
Hot water Inlet (80A)
1641

Generator

1941

163

163

1825

Hot water Outlet (65A)

Chilled water Outlet (80A)


1410

Chilled water Inlet (80A)


950

1402 Outlet (100A) 2255(H)

Chilled water

Control Panel

Absorber

Evaporator
958

Chilled water Inlet (100A) Cooling water


Inlet (150A)

677

614

0 337.3

800

700

2961 3098 3130 3135 3292

100

1331

62.5

Clearance for tube removal at either side

3400

1783

700 842 882

387

182

World Energy Co.

31

For Future Energy & Environment

Single Effect Hot Water Driven Absorption Machine

Outline_Foudation
HWAR-L155 / 180

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m
150

1010

0 213
0 105 205

R6

00

3708(L) 1472(W) Cooling water Outlet (200A) 2081 Hot water Outlet (80A) 1801 Chilled water Outlet (125A) 1370 Chilled water Inlet (125A) 1018 Cooling water Inlet (200A) 654

Condenser Hot water Inlet (80A) 1620 Generator

2257(H)

Control Panel

Absorber

Evaporator

780

0 0 0 0

105

210 75

392

2936 3011 3091 3146

1291

3328

332

130

1115 1010

4000

Clearance for tube removal at either side

HWAR-L210 / 240
150

1768

1010

213
R6 0 0

0 105 205 0 3956 175 175

1472(W)

4734(L)

1010

1140

Condenser

Cooling water Outlet(200A) 2081 Hot water Outlet(80A) 1801 Chilled water Outlet(125A) 1370

Hot water Inlet(80A) 1620

Generator

2257(H)

Chilled water Inlet(125A) 1018 Cooling water Inlet(200A) 654

Control Panel

Absorber

Evaporator

780

105

392

210

75

3956 4031 4111 4166

4342

332

1140 1115 1010

1826

130

5000

Clearance for tube removal at either side

32

World Energy Co.

2278

1140

2936

175

175

HWAR - L Series
Outline_Foudation
HWAR-L270 / 300

WORLD ENERGY
Single Effect Hot Water Driven Absorption Machine
1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

200

990

0 241

0 105 205 200 200


R6 00

3906

1495(W)

4776(L)

4
Condenser
Cooling water Outlet (200A) 2364 Hot water Outlet (100A) 2018

L-Outline_Foudation

Hot water Inlet (100A) 1798

Generator
Chilled water Outlet (150A) 1511

2540(H)

Control Panel

Chilled water Inlet (150A) 1074

Absorber

Evaporator

852 652 Cooling water Inlet (200A)

0 441 260 240 100 2480 1135 1095 990 3906 4098 4146 4166 4335 2028 105 0 0

0 360 1135 145 0

4600

Clearance for tube removal at either side

HWAR-L340 / 375
200

990

0 345
0 105 205 200 200

R6
1575(W) 4880(L)

00

Condenser
Hot water Inlet (125A) 1956

Cooling water Outlet (250A) 2616 Hot water Outlet (125A) 2175

Generator
Chilled water Outlet (200A) 1640

2838(H)

Chilled water Inlet (200A) 1102 Cooling water Outlet (250A) 589

Control Panel

Absorber

Evaporator

852

0 495 267 265 100 1175 1095 990 2480 105 3906 4106 4172 2028 4385 0 0

0 450 1175 145 0

4600

Clearance for tube removal at either side

World Energy Co.

3906

33

For Future Energy & Environment

Single Effect Hot Water Driven Absorption Machine

Outline_Foudation
HWAR-L420 / 470 / 525
A B C D E F G H I

1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

225

4600

5200

5700
A

R6

00

1830(W)

225

L420 4998 3856 4081 4150 4171 4420 2028 2480

L470 5540 4398 4623 4692 4713 4962 2028 2480

L525 6038 4896 5121 5190 5211 5460 2400 2853

250 1150

0 321

0 105 205

Condenser
Hot water Inlet (125A) 2284

Cooling water Outlet (300A) 3001 Hot water Outlet (125A) 2503

Generator
Chilled water Outlet (200A) 1955

3222(H)

Control Panel

Absorber

Evaporator

Chilled water Inlet (200A) 1220

Cooling water Inlet (300A) 761

1030

0 578 491 315 105 125 1339 1255 1150 0 0

0 189 1339

0 399 0

B CDE F

Clearance for tube removal at either side

HWAR-L600 / 675 / 750


A B C D E F G H I

250

5200

5700

6200
A

250

R6

L600 5644 4328 4488 4603 4695 4971 2000 2477

L675 6142 4826 4986 5101 5193 5469 2400 2852

L750 6667 5351 5511 5626 5718 5994 2663 3116

300 1210

0
0 105 205

376
00

2206(W)

Cooling water Outlet (350A) Condenser


3302

Hot water Inlet (150A)


2494

Hot water Outlet (150A) Generator


2753

Chilled water Outlet (250A)


2130

3600(H)

Absorber
Control Panel

Evaporator

Chilled water Inlet (250A)


1462

Cooling water Inlet (350A) 762

1000

1210

1543

1315 1210

Clearance for tube removal at either side

34

World Energy Co.

1543

105

673

370

160

665 495 399

B CDE F

HWAR - L Series
Outline_Foudation
HWAR-L825 / 900 / 975
A B C D E F G H

WORLD ENERGY
Single Effect Hot Water Driven Absorption Machine
1. Indicates the position of anchor bolt holes. 2. All external water piping are to be provided by the customer. 3. Indicates the position of the power supply wiring connections to control panel. 4. Installation and service clearance : Longitudinal Distance : 1m Top : 0.2m Control Panel : 1.2m Others : 0.5m

L825 6293 4826 5146 5207 5221 2755 3208 5700

L900 6818 5351 5671 5732 5746 3280 3733 6200

L975 7318 5851 6171 6232 6246 3280 3733 6700

300 1210

0 430
R600

0 105 205 0

250

250

2329(W)

4
Condenser 3761 Cooling water Outlet (400A) 3093 Hot water Outlet (200A) 2386 Chilled water Outlet (300A)

Condenser

L- Outline_Foudation

Generator 2796 Hot water Inlet (200A)

Generator

4000(H)

Evaporator

Absorber

Absorber

Evaporator

1534 Chilled water Inlet (300A) 859 Cooling water Inlet (400A)
AMP. CAP. VOLT OUTPUT HEAD TYPE

Control Panel

1000

0 1576 1330 1210 120 395 381 0 0

415

Clearance for tube removal at either side

B CDE

HWAR-L1050 / 1125 / 1300


A B C D E F G H

L1025 6860 4200 5146 5163 5460 2361 2814 6800

L1125 7360 4700 5646 5663 5960 2561 3014 7300

L1300 8475 5725 6670 6688 6985 2561 3014 8000


0 27

300 2400

1576

0 105 205 250 250 0

2929(W)

A
Cooling water Outlet (400A) 3681 Hot water Outlet (200A) 2887

R6

00

Condenser

Hot water Inlet (200A) 2835 Chilled water Outlet (300A) 2154 Chilled water Inlet (300A) 1565 Cooling water Inlet (400A) 888

Generator

4000(H)

Absorber
Control Panel

Evaporator

Absorber

1150

1402

2672 2550 2400

1386 1200

Clearance for tube removal at either side

2400 2550

257

146

CD E

World Energy Co.

100

CHUN IN

DO NOT TURN POWER SWITCH ON WITHOUT LIQUID

CHUN IN CO., LTD.KOREA .


/ min PHASE Kw FREQ. m LOCK AMP. A DATE V

TEL.(032)812-4191

MOTOR PUMP

Ser.No.
60 3 A

Hz

ROTATION

0 0

100

300

100

35

For Future Energy & Environment


MODEL Approximate Insulation Approximate Insulation 2 2 for Hot Surfaces(ft ) for Cold Surfaces(ft ) Thickness (inch) L30 L40 L50 L60 L75 L90 L110 L135 L155 L180 L210 L240 L270 L300 L340 L375 L420 L470 L525 L600 L675 L750 L820 L900 L975

Approximate Insulation Approximate Insulation MODEL for Hot Surfaces(m 2 ) for Cold Surfaces(m 2 ) Thickness (mm) L30 L40 L50 L60 L75 L90 L110 L135 L155 L180 L210 L240 L270 L300 L340 L375 L420 L470 L525 L600 L675 L750 L820 L900 L975

Thermal Insulation

2 25 25 29 29 30 30 41 41 43 43 55 56 65 65 72 72 81 89 99 135 145 157 160 172 183

1 15 15 17 17 16 16 18 23 26 26 32 34 38 38 39 40 50 54 57 59 61 65 71 75 80

3/4 36 36 42 42 43 43 58 58 66 66 80 82 88 88 106 106 145 162 172 175 192 209 210 228 277

3/8 2 2 3 3 3 3 3 3 4 4 5 5 5 5 5 5 6 8 8 13 13 13 14 14 14

Single Effect Hot Water Driven Absorption Machine

50 2.3 2.3 2.7 2.7 2.8 2.8 3.8 3.8 4.0 4.0 5.1 5.2 6.0 6.0 6.7 6.7 7.5 8.3 9.2 12.5 13.5 14.6 14.9 16.0 17.0

25 1.4 1.4 1.6 1.6 1.5 1.5 1.7 2.1 2.4 2.4 3.0 3.2 3.5 3.5 3.6 3.7 4.6 5.0 5.3 5.5 5.7 6.0 6.6 7.0 7.4

19 3.3 3.3 3.9 3.9 4.0 4.0 5.4 5.4 6.1 6.1 7.4 7.6 8.2 8.2 9.8 9.8 13.5 15.0 16.0 16.3 17.8 19.4 19.5 21.2 25.7

10 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.6 0.7 0.7 1.2 1.2 1.2 1.3 1.3 1.3

NOTES 1. Use only Non-inflammable or Incombustible insulation materials. 2. Do not insulate motor of refrigerant pump. 3. Total insulation area includes piping. 4. Do not cover components such as service valves, dampers, diaphragm valves, sight-glass, control valves or thermometers or sensor wells. 5. The standard Material and Thickness as the recommendation : (1) HOT Surface insulation Material of insulation : Non-inflammable polymer sponge usable at 120 or Glass wool 3 1 4 inch), 38mm (1 2 inch) when polymer sponge is used Thickness of insulation : 19mm ( Thickness of insulation : 25mm (1 inch), 50mm (2 inch) when Glass wool is used (2) COLD Surface insulation Material of insulation : Closed cell type Non-inflammable polymer sponge 3 3 Thickness of insulation : 10mm ( 8 inch), 19mm ( 4 inch) (3) Wrapping Material when Glass wool is used. Insulated parts on body : Colored galvanized steel with 0.45mm thickness or over Insulated parts on pipes : Colored galvanized steel with 0.30mm thickness or over 6. For insulation area for each model, please refer to the picture below. 7. The water box sections should be worked to be disassembled for the repair. 8. If necessary, please perform the finish painting in the field after completing the insulation work.

19mm (3/4 in) : Generator with Water Box Hot INSULATION FOR HOT SURFACES INSULATION FOR COLD SURFACES Cold 3/4 in : Evaporator Body and It's Water Box 2 in(1 in) : Generator and It's Water Box Surfaces 10mm (3/8 in)Piping : Heat Exchanger Body Piping Surfaces 3/8 in : with Inlet and Outlet Piping of Refrigerant Pump 1 in( in) : Heat Exchanger Body and It's
1 2 4 3

19mm (3/4 in) : Evaporator Body with Water Box 10mm (3/8 in) : Inlet and Outlet Piping of Refrigerant Pump

* ( ) is Thickness of polymer sponge

Condenser

Generator

Control Panel

Absorber

Evapo rator

Note
1. Use only Non-inflammable or Incombustible insulation materials. 2. Do not insulate motor of refrigerant pump. 3. Total insulation area includes piping. 4. Do not cover components such as service valves, dampers, diaphragm valves, sight glass, control valves or thermometers or sensor wells. 5. The standard Material and Thickness as the recommendation : HOT Surface insulation Material of insulation : Non-inflammable polymer sponge usable at 120C Thickness of insulation : 19mm (3/4 inch), 10mm (3/8 inch) when polymer sponge is used COLD Surface insulation Material of insulation : Closed cell type Non-inflammable polymer sponge Thickness of insulation : 10mm (3/8 inch), 19mm (3/4 inch) 6. For insulation area for each model, please refer to the picture below. 7. The water box sections should be worked to be disassembled for the repair. 8. If necessary, please perform the finish painting in the field after completing the insulation work.

Model (mm) HWAR-L030 HWAR-L040 HWAR-L050 HWAR-L060 HWAR-L075 HWAR-L090 HWAR-L110 HWAR-L135 HWAR-L155 HWAR-L180 HWAR-L210 HWAR-L240 HWAR-L270 HWAR-L300

Hot Surface(m2) 19mm 10mm 2.3 2.3 2.7 2.7 2.8 2.8 3.8 3.8 4.0 4.0 5.1 5.2 6.0 6.0 1.4 1.4 1.6 1.6 1.5 1.5 1.7 2.1 2.4 2.4 3.0 3.2 3.5 3.5

Cold Surface(m2) 19mm 10mm 3.3 3.3 3.9 3.9 4.0 4.0 5.4 5.4 6.1 6.1 7.4 7.6 8.2 8.2 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.5 0.5 0.5 0.5

Model (mm) HWAR-L340 HWAR-L375 HWAR-L420 HWAR-L470 HWAR-L525 HWAR-L600 HWAR-L675 HWAR-L750 HWAR-L825 HWAR-L900 HWAR-L975 HWAR-L1050 HWAR-L1125

Hot Surface(m2) 19mm 10mm 6.7 6.7 7.5 8.3 9.2 12.5 13.5 14.6 14.9 16.0 17.0 22.0 23.1 3.6 3.7 4.6 5.0 5.3 5.5 5.7 6.0 6.6 7.0 7.4 7.5 7.6

Cold Surface(m2) 19mm 9.8 9.8 13.5 15.0 16.0 16.3 17.8 19.4 19.5 21.2 25.7 11.5 12.1 10mm 0.5 0.5 0.6 0.7 0.7 1.2 1.2 1.2 1.3 1.3 1.3 1.4 1.4

36

World Energy Co.

WORLD ENERGY
Absorption Machines
Supply Scope (Standard)
Item Description
1) Evaporator, Absorber, Condenser, Generators 2) Solution Heat Exchanger 3) Pumps - Solution pumps with isolation valves - Refrigerant pump with isolation valves - Purge pump 4) Control panel - Panel unit, circuit Breakers - Switches ( Operation, emergency, man/auto selector) - Relays, controller, touch screen 5) Locally mounted control instruments - Chilled water flow switch - temperature sensors 6) Purge device - Purge storage tank, Eductor, Liquid trap, Manometer, piping and manual valves 7) Interconnecting piping and wiring - Refrigerant and absorbent piping for internal mechanical components - Control & Power wiring for Internal electrical components Absorbent (Lithium bromide) with inhibitor Refrigerant Painting for chiller assembly and control panel Insulation of hot surface and cold surface for Absorption chiller 1) Check of external dimensions 2) Hydraulic Pressure test for water Boxes 3) Leak Test (Vacuum side) 4) Function test for electric circuit and safety device Factory test or start-up at site

Scope

Chiller Assembly

Vendor

L-Thermal Insulation / Supply Scope for Absorption Machines

Initial charge Painting Insulation

Vendor Vendor Option

Test & Inspection Performance Test

Vendor Option

Out of supply and work scope for Vendor 1. Foundation of chiller 2. Installation of chiller 3. Piping and wiring connections out of Chillers 4. Interlock wiring of chilled water pump and cooling water pump. 5. Installation and wiring of control valve.

Installation & wiring work

Buyer

Painting
Painting type : Epoxy Prime and Epoxy Finish painting Color : Chiller body - Blue (Munsell No. 4.0 PB3.4/6.7) Control Panel - Grey (Munsell No.5Y 7/1)

2AB1125 Installation (Korea)

World Energy Co.

37

For Future Energy & Environment

Single Effect Double Lift Hot Water Driven Absorption Machine

System Piping
P T Hot water control valve P T Hot water Inlet Air handling unit Supply water Bleed off Drain line Expansion tank Hot Water Diff. Pressure Control Valve Hot water Outlet Cooling tower

Hot water Outlet

Absorption chiller Cooling water Outlet P T

Flow meter F Chilled / Hot water Pump(2nd)

Chilled / Hot water Pump(1st)

Hot water Inlet P P T T Chilled water Outlet Chilled water Inlet P T

Thermostat Pressure Gauge Temperature Gauge Valve Cooling water pump Drain Valve Air Vent

Bypass valve

Cooling water Inlet Supply header Return header

1) All external equipment out of dotted line is scope of customer's. 2) Refer to outline drawing and specification data sheet for the external dimensions of the machine, the location & the diameter of water pipe connection and etc. 3) Driving hot water must be maintained as design temperature. 4) It is strongly recommended to install stop valves at hot water inlet and outlet pipe. 5) The locations of chilled water pumps, cooling water pumps and expansion tanks shall be determined in consideration of the hydrostatic head of pumps and the height of building. And the Machine shall not be subject to a pressure higher than the designed pressure at any water header. 6) For cooling water quality control, it is recommended to install cooling water bleed-off device on the inlet pipe line of cooling towers. 7) Around 10 meshes of strainers are recommended to be installed in the cooling water line.

8) For the maintenance and the inspection of the Machine, the following equipment shall be installed on each chilled water and cooling water inlet/outlet lines as well as stop valve. Thermometers and pressure gauges shall be installed at chilled and cooling water inlet/outlet. Air relief valves shall be installed on each chilled and cooling water lines at higher points than each water header. Drain valves shall be installed at the lowest position between the stop valves of chilled and cooling water and the Machine and the drain valve shall be piped to the drain ditch. 9) There shall be a sufficient clearance for access to the absorber, evaporator, condenser, and generator to facilitate inspection and cleaning work.

Cooling Water Quality Control


The cooling water which is recycled by cooling tower is exposed into atmosphere and polluted as it is vaporized. If the cooling water gets polluted, it develops corrosion and also scale inside the tubes and Absorption Machine performance drops.
Items
PH (25C) Conductivity (25C, s/cm) Chloride ion CI (mg / cI / ) Sulfuric acid ion SO42-(mg CaCo3 / ) Alkalinity pH4.8 (mg CaCo3 / ) Total hardness (mg CaCO3 / ) Iron Fe (25C) Sulfides S2- ion (ms S2-/ ) Ammonium ion NH4+ (mg NH4+/ ) Silica SiO (mg SiO2 / )

Therefore, it is recommended to control the water quality; the following table shows guideline for cooling water and make-up water. The tube cleaning method and interval depends on each water quality.
Tendency Corrosion Scale

Cooling Water
6.5 ~ 8.0 Max. 800 Max. 200 Max. 200 Max. 100 Max. 200 Max. 1.0 No trace Max. 1.0 Max. 50

Make-up Water
6.5 ~ 8.0 Max. 200 Max. 50 Max. 50 Max. 50 Max. 50 Max. 0.3 No trace Max. 0.2 Max. 30

Standard

Reference

38

World Energy Co.

PUMP INTERLOCK

K4

WIRING

G*1.5*8L
COOLING TOWER FAN RUN SIGNAL

K5

START SIGNAL ALARM SIGNAL

CHILLED WATER TEMP. SET SIGNAL

IN05
K1

CHILLED WATER TEMP SIGNAL

No.

K2

CHILLED WATER PUMP RUN SIGNAL

Note

Note

TB3
K3
COOLING WATER TEMP SIGNAL
COOLING WATER PUMP RUN SIGNAL

AIR SEAL BLAWER POWER

R S T
Lamps Buzzer

R S T

Outline

Buzzer stop

Wiring
K4

CHP

Power switch

Touch screen

2AB & HWAR-L


Description
PURGE PUMP OPERATING SIGNAL
COOLING TOWER FAN RUN SIGNAL CHILLED WATER TEMP. SET SIGNAL

is field wiring at the site after completion of chiller installation

is field wiring at the site after completion of chiller installation

Control Panel

Emergency stop switch

Purge pump start/stop switch

229A 228
IN05
CHILLED WATER TEMP SIGNAL COOLING WATER TEMP SIGNAL
1

220 221

508 509 512 513 514 515 516 517 518 519
AL06 AL073G*1.5*8L 88VP

2G*1.5*2L

DIVERTER VALVE

4G*1.5
AIR SEAL BLAWER POWER

G G0

725A 726 507 220 508 221

246 247 272 273

TB3

CHP

TB3

R S T
2AB&HWAR-L
250

R S T 220 221
800

AL06 AL07 88VP

HOT WATER CONTROL VALVE

4G*1.5
2G*1.5*2L
PURGE PUMP OPERATING SIGNAL

246 247 248

REMOTE START STOP START SIGNAL


4 2

CHILLED WATER PUMP INTERLOCK ALARM SIGNAL


S2

Y O U M

229A 228
1

407 500 501 502 503 504 505 506 507 508 509 512 513 514 515 516 517 518 519
CHP

250

TB4

DIVERTER VALVE

4G*1.5

REMOTE START STOP


4

7 2

CHILLED WATER PUMP INTERLOCK


1000(800)

725A 726 507 508


5

246 247 272 273

S1
1

3G*1.5*3L
7

600

TOUCH S2

250

COOLING WATER PUMP INTERLOCK

S3

G G0

TB3

2AB&HWAR-L

TB4
HOT WATER
K5
S1

800

TB4

4G*1.5
TOUCH

REMOTE START STOP


6
S3

650(600)

K1

3G*1.5*3L CONTROL VALVE USER'S WIRING

3G*1.5*3L
3

Y O U M

COOLING WATER PUMP INTERLOCK CHILLED WATER

CHILLED WATER PUMP INTERLOCK COOLING WATER PUMP INTERLOCK

220 221 246 400 247 401 403 248

S1

K2

PUMP RUN SIGNAL


K5

600

S2

START SIGNAL

1
6

K3

USER'S WIRING

COOLING WATER PUMP RUN SIGNAL


K1

S3

250

USER'S WIRING

ALARM SIGNAL

K5

CHILLED WATER TEMP. SET SIGNAL COOLING WATER

2AB & HWAR-L

PUMP RUN SIGNAL

TEMP SIGNAL COOLING TOWER FAN RUN SIGNAL


K4
COOLING WATER PUMP RUN SIGNAL REMOTE START STOP COOLING TOWER FAN RUN SIGNAL

3G*1.5*8L
START SIGNAL ALARM SIGNAL CHILLED WATER PUMP RUN SIGNAL

K4

CHILLED WATER PUMP RUN SIGNAL

COOLING TOWER FAN RUN SIGNAL


K2

K1
1000(800)

IN05

K3

K2

CHILLED WATER

(
4

TB4 K3

3G*1.5*8L
AL06 AL07 88VP
IN05

S1

COOLING WATER CHILLED WATER SIGNAL TEMP. SET TEMP SIGNAL

K4

TOUCH
S2

650(600)

3G*1.5*8L
CHILLED WATER PUMP INTERLOCK CHILLED WATER

3G*1.5*3L

PURGE PUMP CHILLED WATER OPERATING SIGNAL TEMP SIGNAL

400 401 403 404 406 407 500 501 502 503 504 505 506 507 508 509 512 513 514 515 516 517 518 519
IN05
TEMP. SET SIGNAL

S3

TB3
3

R S T

COOLING WATER TEMP SIGNAL

COOLING WATER CHILLED WATER PUMP INTERLOCK

TEMP SIGNAL

K5

AL06 AL07 88VP

World Energy Co.


TEMP SIGNAL PURGE PUMP ALARM SIGNAL
1

)dimension for HWAR - L series

USER'S WIRING

220 221

PURGE PUMP OPERATING SIGNAL

400 401 403 404 406 407 500 501 502 503 504 505 506 507 508 509 512 513 514 515 516 517 518 519
START SIGNAL COOLING WATER

K1

WORLD ENERGY

Double Effect Exhaust Gas Driven / Single Effect Double Lift Hot Water Absorption Machine TOUCH

AL06 AL07 88VP

OPERATING SIGNAL

404 406 407 500 501 502 503 504 505 506 400 507 401 508 509 403 512 404 513 406 514 407 515 500 516 501 517 502 518 519 503
K2
CHILLED WATER PUMP RUN SIGNAL
250

39

COOLING WATER PUMP RUN SIGNAL

2AB - L Piping Diagram / CHP - 2AB - L Control Panel


K3

246 247 272 273

504 505 506

CHP

For Future Energy & Environment

Absorption Machines
Communication Protocol
(1) RS-485 (3) MODBUS (5) INTERNET (2) RS-232 (4) PROFIBUS

Wiring
1) RS-485
Type 15Pin Female
9 15

Pin No. 11 12 13

Signal RDA(RD+) RDB(RD-) SDA(SD+) SDB(SD-) SG

Drection input input output output

Contents data receive(+) data receive(-) data send(+) data send(-) signal ground

14 15 1~9

(COM2)

Serial interface for RS232

2) RS-232
6 4 2 1 5 3
Body side(6Pin Male) 1 2 3 4 5 6 RD SG (9Pin Male) 1 2 3 4 5 6 7 8 9 RD SD SG

SD

3) MODBUS
Body side(6Pin Male) 1 2 3 4 5 6 RD SG (MODBUS) 1 2 3 4 5 6 7 8 9 RD SD SG

RS-485 wiring(MODBUS Chiller side) Outside(3Pin) 1 2 RD SG Chiller side(9Pin) 1 2 3 4 5 RD SD SG

SD

6 4 2

5 3 1

connet No 1, 4, 5, 6, 9 for 9Pin type, No 11~15 for 15Pin type

40

World Energy Co.

WORLD ENERGY
Absorption Machines
4) PROFIBUS
5 1 2 3 9 6

No

Description

Pin 1 2 3 4 5 6 7 8 9 B line RTS GND

Signal -

Content

+ RxD / TxD, RS485 level Request to send Isolated ground Isolated +5V - RxD / TxD, RS485 level Communication Protocol / Wiring

+5V Bus output A line -

5) INTERNET
Monitoring Chillers equipped with internet-enabled controller
Ethernet User

INTERNET

Ethernet WEB Server

RS-485

Controller

Controller

Controller

World Energy Co.

41

For Future Energy & Environment

Double Effect Direct Fired Absorption Chiller & Heater


Performance Data
Model Cooling Capacity Heating Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Hot Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection High Heating Value Flow rate Gas Inlet Pressure Connection Exhaust gas Power source Ref. Pump Abs. Pump Electric Purge Pump Burner Control Panel Total kW Total Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT kW kcal/h m3/h mH20 mm m /h mH20 mm m3/h mH20 m kcal/Nm3 Nm3/h mmAq mm mm kW kW kW kW kW kW A mm mm mm ton ton mm
3

Double Effect Dierct Fierd Type (50~400RT)


DW60 211 60 176 151 36 3.7 80 DW70 246 70 205 177 42 6.2 DW80 281 80 235 202 48 6.9 DW100 352 100 293 252 60 5.6 DW120 DW150 422 120 352 303 73 5.9 100 55.8 / 60 42 6.2 80 48 6.9 60 5.6 73 5.9 100 32 / 37.5 70 10.2 100 80 10.0 100 8.9 125 10,550 20.1 200 50(200mmAq) 40(4,000mmAq) 280 X 210 3PH, 400V, 50Hz 0.2 1.5 0.4 2.7 8.8 2,095 1,477 1760 3.0 10.1 2,598 1,615 2.7 3.0 1,900 3.2 3.5 3.3 3.7 2,400 4.6 5.0 0.7 3.6 11.8 2,597 1,810 2,090 4.9 5.3 5.8 6.3 6..2 6.8 3,400 7.3 8.0 7.7 8.5 4.0 14.1 3,680 1,920 0.3 2.0 0.4 1.1 0.2 4.5 15.2 3,708 2,100 2,122 8.9 9.8 9.4 10.4 5.6 16.6 4,734 2,200 8.2 22.4 4,776 2,290 2,385 11.6 12.8 4,500 12.2 13.5 2.2 3.2 2.4 0.4 4.0 310 X 310 23.0 28.7 34.4 43.1 51.7 120 9.1 150 10.4 180 10.8 150 60.3 68.9 80.4 91.8 210 10.7 91 7.6 109 8.1 127 7.5 125 240 11.2 280 8.9 320 8.6 200 103 115 527 150 440 378 12 / 7 91 7.6 DW180 633 180 528 454 109 8.1 DW210 938 210 616 530 127 7.5 125 145 169 5.4 194 5.3 150 360 8.8 400 8.7 DW240 844 240 704 606 145 7.4 DW280 985 280 822 706 169 5.4 DW320 DW360 1,125 320 939 807 194 5.3 150 218 5.8 242 6.0 1,266 360 1,056 908 218 5.8 DW400 1,407 400 1,174 1,009 242 6.0

DW50 176 50 147 126 30 4.0

30 4.0

36 3.7

50 7.0

60 6.1

14.4

17.2

4,000 50(4,000mmAq) 360 X 310 270 X 150

190 X 110

2.6 2.8

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

42

World Energy Co.

DW Series
Performance Data
Model Cooling Capacity Heating Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Hot Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Flow rate Gas Inlet Pressure Connection Exhaust gas Power source Ref. Pump Abs. Pump Electric Purge Pump Burner Control Panel Total kW Tatal Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT kW kcal/h m3/h mH20 mm m /h mH20 mm m3/h mH20 m
3

WORLD ENERGY
Double Effect Direct Fired Absorption Chiller & Heater

Double Effect Dierct Fierd Type (450~1500RT)


DW500 1,758 500 1,467 1,262 302 5.4 DW560 1,969 560 1,643 1,413 339 4.2 200 DW630 2,215 630 1,848 1,590 381 5.8 DW700 2,461 700 2,054 1,766 423 7.7 DW800 2,813 800 2,347 2,019 484 5.7 DW900 3,165 900 2,641 2,523 12 / 7 544 7.7 250 56.3 / 60 381 5.8 423 7.7 484 5.7 544 7.7 250 32 / 37.5 630 9.3 300 144 161 181 201 230 700 12.4 800 8.8 900 12.0 350 10,550 258 4,000 50(4,000mmAq) 65(4,000mmAq) 400 X 620 3PH, 400V, 50Hz 0.4 3.2 0.4 4.0 8.2 22.4 4,880 2,490 2,633 10.5 28.4 4,998 5,540 3,055 2,962 19.5 22.2 21.1 24.0 5,200 22.7 25.7 5,700 27.9 32.0 5,200 14.0 34.6 6,038 5,644 7.5 0.2 15.1 37.0 6,142 3,330 3,310 30.4 34.4 5,700 32.8 37.1 6,200 40.0 45.1 5,700 18.6 43.7 6,667 6,293 21.0 53.5 6,818 3,738 3,500 43.0 48.5 6,200 45.8 51.5 6,700 49.7 26.1 6,200 7,318 25.0 60.4 6,860 7,360 4,460 3,700 52.3 59.1 6,700 11.0 5.5 1.5 7.5 0.75 15.0 400 X 900 287 316 1,000 15.8 1,100 11.1 605 10.1 665 6.7 DW1000 DW1100 DW1200 DW1300 DW1400 DW1500 3,516 1,000 2,934 2,271 605 10.1 3,868 1,100 3,227 2,523 665 6.7 4,220 1,200 3,521 2,776 726 8.6 300 726 8.6 300 1,200 14.1 400 344 373 402 1,300 17.6 1,400 14.0 450 431 786 10.7 847 8.7 350 1,500 16.8 4,571 1,300 3,814 3,280 786 10.7 4,923 1,400 4,108 3,532 847 8.7 350 907 10.6 5,274 1,500 4,401 3,785 907 10.6

DW450 1,582 400 1,320 1,135 272 5.1

272 5.1

302 5.4

339 4.2 200

5
DW Performance Data

450 8.4 250 129

500 8.6

560 6.8

3 High Heating Value kcal/Nm

Nm3/h mmAq mm mm kW kW kW kW kW kW A mm mm mm ton ton mm

410 X 310

350 X 500

14.2 15.8

14.9 16.6 4,500

Space for Tube Replacement

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

43

For Future Energy & Environment

Double Effect Direct Fired Absorption Chiller & Heater

Performance Data
Model Cooling Capacity Heating Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Hot Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Flow rate Gas Inlet Pressure Connection Exhaust gas Power source Ref. Pump Abs. Pump1 Electric Abs. Pump2 Purge Pump Burner Control Panel Total kW Tatal Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT kW kcal/h m3/h mH20 mm m3/h mH20 mm m3/h mH20 m

High Efficiency Double Effect Direct Fired Type (50~400RT)


DWH60 211 60 145 125 36.3 3.7 80 DWH70 246 70 170 146 42.3 6.2 DWH80 281 80 194 167 48.4 6.9 DWH100 DWH120 DWH150 DWH180 DWH210 DWH240 DWH280 DWH320 DWH360 DWH400 352 100 242 208 60.5 5.6 422 120 291 250 72.6 5.9 100 56.3 / 60 42.3 6.2 80 48.4 6.9 60.5 5.6 72.6 5.9 100 32 / 37.2 70 10.2 100 80 10.0 100 8.9 125 10,550 16.6 200 50(200mmAq) 40(4,000mmAq) 280 x 210 3PH, 400V, 50Hz 0.2 1.5 0.2 0.4 2.9 9.9 0.7 0.2 3.9 13.4 2,598 1,615 1,760 2.9 3.1 3.4 3.7 3.6 3.9 2,400 4.5 5.0 2,597 1,810 2,090 4.8 5.3 5.7 6.3 6.2 6.8 3,400 7.2 8.0 7.6 8.5 4.3 15.7 3,680 1,920 4.9 16.8 3,708 2,1 2,122 8.8 9.8 9.3 10.4 6.0 18.2 4,734 2,137 6.8 20.2 4,776 2,270 2,385 11.5 12.8 4,500 12.1 13.5 8.6 24.0 0.3 2.0 0.3 0.4 1.1 2.2 4.0 2.4 0.4 0.4 3.2 310 x 310 19.0 23.7 28.4 35.6 42.7 120 9.1 150 10.4 180 10.8 150 49.8 56.9 66.4 75.8 210 10.7 90.7 7.6 109 8.1 127 7.5 125 240 11.2 280 8.9 320 8.6 200 85.3 94.8 527 150 363 313 90.7 7.6 633 180 436 375 12 / 7 109 8.1 738 210 509 438 127 7.5 125 145 7.4 169 5.4 194 5.3 150 360 8.8 400 8.7 844 240 581 500 145 7.4 985 280 678 583 169 5.4 1,125 320 775 667 194 5.3 150 218 5.8 242 6.0 1,266 360 872 750 218 5.8 1,407 400 969 833 242 6.0

DWH50 176 50 121 104 30.2 4.0

30.2 4.0

36.3 3.7

50 7.0

60 6.1

3 High Heating Value kcal/Nm

Nm3/h mmAq mm mm -

11.9

14.2

4,000 50(4,000mmAq) 360 x 310 270 x 150

180 x 110

kW kW kW kW kW kW kW
A mm mm mm ton ton mm

2,095 1,477 2.7 2.9 1,900

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

44

World Energy Co.

DWH Series
Performance Data
Model Cooling Capacity Heating Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Hot Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection High Heating Value Flow rate Gas Inlet Pressure Connection Exhaust gas Power source Ref. Pump Abs. Pump1 Electric Abs. Pump2 Purge Pump Burner Control Panel Total kW Tatal Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT kW kcal/h m3/h mH20 mm m3/h mH20 mm m /h mH20 m kcal/Nm3 Nm3/h mmAq mm mm kW kW kW kW kW kW kW A mm mm mm ton ton mm
3

WORLD ENERGY
Double Effect Direct Fired Absorption Chiller & Heater

High Efficiency Double Effect Direct Fired Type (450~1500RT)


DWH500 1,758 500 1,211 1,042 302 5.4 DWH560 1,969 560 1,357 1,167 339 4.2 200 DWH630 2,215 630 1,526 1,313 381 5.8 DWH700 2,461 700 1,696 1,459 423 7.7 DWH800 2,813 800 1,938 1,667 484 5.7 DWH900 DWH1000 DWH1100 DWH1200 DWH1300 DWH1400 DWH1500 3,165 900 2,181 1,875 12 / 7 544 7.7 250 56.3 / 60 381 5.8 423 7.7 484 5.7 544 7.7 250 32 / 37.2 630 9.3 300 119 133 149 166 190 700 12.4 800 8.8 900 12.0 350 10,550 213 4,000 50 (4,000mmAq) 65 (4,000mmAq) 400 x 620 3PH, 400V, 50Hz 0.4 3.2 0.4 0.4 4.0 8.6 24.0 4,880 2,469 2,633 4,998 12.7 34.9 5,540 2,935 2,962 19.6 22.2 21.2 24.0 5,200 22.7 25.7 5,700 28.7 32.0 5,200 16.2 41.1 6,038 5,644 7.5 0.2 17.3 43.5 6,142 3,330 3,310 30.6 34.4 5,700 32.9 37.1 6,200 40.4 45.1 5,700 6,667 19.7 53.3 6,293 23.2 60.0 6,818 3,929 3,500 43.4 48.5 6,200 46.0 51.5 6,700 50.1 56.1 6,200 7,318 6,860 25.5 69.5 7,360 4,460 3,700 52.7 59.1 6,700 5.5 2.2 0.75 11.0 1.5 7.5 4.5 400 x 900 237 261 1,000 15.8 1,100 11.1 605 10.1 665 6.7 3,516 1,000 2,423 2,084 605 10.1 3,868 1,100 2,665 2,292 665 6.7 4,220 1,200 2,907 2,500 726 8.6 300 726 8.6 300 1,200 14.1 400 284 308 332 1,300 17.6 1,400 14.0 450 356 786 10.7 847 8.7 350 1,500 16.8 4,571 1,300 3,510 2,709 786 10.7 4,923 1,400 3,392 2,917 847 8.7 350 907 10.6 5,274 1,500 3,634 3,125 907 10.6

DWH450 1,582 450 1,090 938 272 5.1

272 5.1

302 5.4

339 4.2 200

450 8.4 250 107

500 8.6

560 6.8

5
DWH Performance Data

410 x 310

350 x 500

14.1 15.8

14.8 16.6 4,500

Space for Tube Replacement

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

45

For Future Energy & Environment

Double Effect Exhaust Gas Driven Absorption Chiller and Heater

02

WORLD ENERGY CO.

For Future Energy & Environment

WORLD ENERGY WORLD ENERGY

Single Effect Double Lift Low Temperature Hot Water Absorption Chiller

Double Effect Steam Fired Absorption chiller


SW120 422 120 SW150 527 150 SW180 633 180 SW210 738 210 SW240 844 240 12 / 7 SW280 985 280 SW320 1,125 320

Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m3/h mH20 mm m3/h mH20 mm MPa kg/h mm mm mm kW kW kW kW kW A mm mm mm ton ton mm

Cooling Cycle (Cooling Mode)


Double Effect Steam Fired Type (100~500RT)
SW360 1,266 360 SW400 1,407 400 SW450 1,582 450 SW500 1,758 500 SW100 352 100

1
Single Effect Double Lift Low Temperature Hot Water Absorption Chiller - Product Feature / Cycle block diagram

60 5.6

73 5.9 100

91 7.6

109 8.1

127 7.5 125

145 7.4

169 5.4

194 5.3 150

218 5.8

242 6.0

272 5.1 200

302 5.4

32 / 37.5 100 8.9 125 120 9.1 150 10.4 180 10.8 150 0.8 440 528 50 25 40 50 3PH, 400V, 50Hz 0.3 2.0 2.4 0.4 0.2 2.9 9.5 2,597 1,389 2,200 3.8 4.2 2,400 3.9 4.4 4.9 5.5 5.2 5.8 3,400 5.9 6.7 6.4 7.2 3,680 3,708 1,652 2,250 7.4 8.4 7.8 8.9 9.6 10.9 4,500 3.4 10.6 4,734 4,776 1,735 2,450 10.1 11.5 11.6 13.3 4.2 12.6 4,880 1,954 2,600 12.0 13.8 0.4 3.2 660 792 924 1,056 65 1,232 1,408 1,584 1,760 80 40 65 1,980 2,200 210 10.7 240 11.2 280 8.9 320 8.6 200 360 8.8 400 8.7 450 8.4 250 500 8.6

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

46

World Energy Co.

WORLD ENERGY CO.

01

For Future Energy & Environment

Single Effect Double Lift Low Temperature Hot Water Absorption Chiller

Exhaust-Energy Recovery_Available exhaust gas from reciprocating engine, gas turbine engine or processor of Factory without additional heat recovery systems.

Cost effective cooling and heating_ CHP Series is design to to double-effect cycle providing more efficient usage of the same energy input.
Excellent part load performance_ a variable frequency drive pump automatically maintains optimum solution flow to low temp. generator and HTG during whole operation High Efficient heat transfer tubes_Newly designed high performance tube enable of heat transfer rate increase. Smaller installation space and saved operation cost

RELIABILITY & EASY MAINTENANCE


Hermetically-designed refrigerant and solution pumps which are only moving parts provide reliability and they are field serviceable through pump isolation valves. Also marine-type water box cover on both of the absorber and condenser allows easy tube-cleaning and water-box inspection. And factory performance test, which is provided as an optional basis, ensure the performance and function of chiller before shipment.

PRECISE & OPTIMIZED OPERATION


Factory mounted, wired and tested microprocessor-based controller monitors and controls the machine operation continuously and automatically. A touch screen display identifies operational status and fault indication. All components meet internally acceptable codes like UL or CE or KS or equivalents. During the start-up sequence, the controller initiates a self-diagnostic system check to verify that all sensors are in range. Remote start/stop switch and a key-locked control panel door protect a against unauthorized access.

RELIABLE PURGE SYSTEM


Non-condensable gases are periodically exhausted from the storage tank by a simple procedure performed while the machine is running. Evacuation is performed by a unit mounted vacuum pump that is connected to the purge evacuation valve.

LOW MAINTENANCE
Worldenergy absorption machines has numerous standard design features that provide for convenient and simple Maintenance. Hinged water box cover on the absorber, and condenser facilitate tube and water box inspection. Epoxy coating of the waterboxes and covers, standard on all machines, protects against corrosion and extend machine life. All moving parts are easily accessible for inspection or replacement, as required.

Low Noise and Low Vibration


Low sound and vibration levels are characteristic of absorption chillers, primarily due to the fact that the only rotating parts are the refrigerant and solution pumps. The overall sound level of The Worldenergy machine is typically 65dbA. This allows the machines to be installed near occupies spaces or in area with strict sound requirements. Low vibration levels also make it possible to install the chiller on upper floors without special consideration for vibration dampening systems.

02

WORLD ENERGY CO.

SW Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m3/h mH20 mm m3/h mH20 mm MPa kg/h mm mm mm kW kW kW kW kW

WORLD ENERGY
Double Effect Steam Fired Absorption chiller

Double Effect Steam Fired Type (560~1500RT)


SW630 2,215 630 SW700 2,461 700 SW800 2,813 800 SW900 3,165 900 SW1000 3,516 1,000 12 / 7 SW1100 3,868 1,100 SW1200 4,220 1,200 SW1300 4,571 1,300 SW1400 4,923 1,400 SW1500 5,274 1,500

SW560 1,969 560

339 4.2

381 5.8 200

423 7.7

484 5.7

544 7.7 250

605 10.1

665 6.7

726 8.6 300

786 10.7

847 8.7 350

907 10.6

32 / 37.5 560 6.8 630 9.3 300 700 12.4 800 8.8 900 12.0 350 0.8 2,464 2,772 100 50 80 3PH, 400V, 50Hz 0.4 5.5 0.4 0.2 6.5 18.6 4,998 5,540 2,180 2,900 16.1 18.7 4,500 17.5 20.3 5,200 18.9 21.8 5,700 21.1 24.5 5,200 6,038 5,644 7.6 21.0 6.142 2,606 3,350 23.7 27.4 5,700 26.2 30.4 6,200 28.7 33.4 5,700 6,667 6,293 6,818 2,829 3,450 31.3 36.4 6,200 33.8 39.4 6,700 36.4 42.3 6,200 10.0 30.8 7,318 6,860 3,250 3,650 38.9 45.3 6,700 7,360 1.5 7.5 0.75 3,080 3,520 3,960 125 65 100 4,400 4,840 5,280 5,720 150 80 125 6,610 6,600 1,000 15.8 1,100 11.1 1,200 14.1 400 1,300 17.6 1,400 14.0 450 1,500 16.8

6
SW Performance Data

A
mm mm mm ton ton mm

Space for Tube Replacement

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

47

For Future Energy & Environment

Double Effect Steam Fired Absorption chiller

Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump1 Electric Abs. Pump2 Purge Pump Control Panel Total kW Tatal Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m /h mH20 mm m /h mH20 mm MPa kg/h mm mm mm kW kW kW kW kW kW A mm mm mm ton ton mm
3 3

High Efficiency Double Effect Steam Fired Type (100~500RT)


SWH120 422 120 SWH150 527 150 SWH180 633 180 SWH210 738 210 SWH240 844 240 12 / 7 SWH280 985 280 SWH320 1,125 320 SWH360 1,266 360 SWH400 1,407 400 SWH450 1,582 450 SWH500 1,758 500

SWH100 352 100

60 5.6

73 5.9 100

91 7.6

109 8.1

127 7.5 125

145 7.4

169 5.4

194 5.3 150

218 5.8

242 6.0

272 5.1 200

302 5.4

32 / 37.2 100 8.9 125 120 9.1 150 10.4 180 10.8 150 0.8 390 468 50 25 40 3PH / 400V / 50Hz 0.3 2.0 0.3 0.4 0.2 3.2 11.1 2,597 1,420 2,200 4.0 4.4 2,400 4.1 4.6 5.1 5.7 5.2 5.8 3,400 5.9 6.7 6.1 7.0 3,680 3,708 1,652 2,250 7.3 8.3 7.6 8.7 9.6 10.9 4,500 3.8 12.2 4,734 4,776 1,735 2,450 9.9 11.3 11.5 13.2 4.6 14.2 4,880 1,954 2,600 11.9 13.7 2.4 0.4 0.4 3.2 50 585 702 819 936 65 1,092 1,248 1,404 1,560 80 40 65 1,755 1,950 210 10.7 240 11.2 280 8.9 320 8.6 200 360 8.8 400 8.7 450 8.4 250 500 8.6

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

48

World Energy Co.

SWH Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Inlet Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump1 Electric Abs. Pump2 Purge Pump Control Panel Total kW Tatal Amp. Lenght (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m /h mH20 mm m /h mH20 m MPa kg/h mm mm mm kW kW kW kW kW kW A mm mm mm ton ton mm
3 3

WORLD ENERGY
Double Effect Steam Fired Absorption chiller

High Efficiency Double Effect Steam Fired Type (560~1500RT)


SWH630 2,215 630 SWH700 2,461 700 SWH800 2,813 800 SWH900 3,465 900 SWH1000 3,516 1,000 12 / 7 SWH1100 3,868 1,100 SWH1200 4,220 1,200 SWH1300 4,571 1,300 SWH1400 4,923 1,400 SWH1500 5,274 1,500

SWH560 1,969 560

339 4.2

381 5.8 200

423 7.7

484 5.7

544 7.7 250

605 10.1

665 6.7

726 8.6 300

786 10.7

847 8.7 350

907 10.6

32 / 37.2 560 6.8 630 9.3 300 700 12.4 800 8.8 900 12.0 350 0.8 2,184 2,457 100 50 65 80 3PH / 400V / 50Hz 0.4 5.5 2.2 0.4 0.2 8.7 25.1 4,998 5,540 2,180 2,900 16.1 18.7 4,500 17.5 20.3 5,200 18.9 21.8 5,700 21.1 24.5 5,200 6,038 5,644 9.8 27.5 6,142 2,606 3,350 23.7 27.4 5,700 26.2 30.4 6,200 28.7 33.4 5,700 6,667 6,293 12.2 37.3 6,818 3,000 3,450 31.3 36.4 6,200 33.8 39.4 6,700 36.4 42.3 6,200 7,318 6,860 3,250 3,650 38.9 45.3 6,700 14.5 46.8 7,360 0.75 1.5 7.5 4.5 2,730 3,120 3,510 125 65 100 3,900 4,290 4,680 5,070 150 80 5,460 5,850 1,000 15.8 1,100 11.1 1,200 14.1 400 1,300 17.6 1,400 14.0 450 1,500 16.8

6
SWH Performance Data

Space for Tube Replacement

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

49

For Future Energy & Environment

Single Effect Steam Fired Absorption Chiller


Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Ampere Length (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m3/h mH20 mm m3/h mH20 mm MPa kg/h mm mm mm kW kW kW kW kW A mm mm mm ton ton mm

Single Effect Steam Fired Type (50~400RT)


S060 211 60 S070 246 70 S080 281 80 S100 352 100 S120 422 120 S150 527 150 12 / 7 S180 633 180 S210 738 210 S240 844 240 S280 985 280 S320 1,125 320 S360 1,265 360 S400 1,407 400

S050 176 50

30.2 4.0

36.3 3.7 80

42.3 6.2

48.4 5.6

60.5 5.6

72.6 5.9 100

90.7 7.6

109 8.1

127 7.5 125

145 7.4

169 5.4

194 5.3 150

218 5.8

242 6.0

32 / 39.4 50 7.0 60 6.1 100 70 10.2 80 9.6 100 8.9 125 0.15 390 468 100 25 40 50 65 3PH / 400V / 50Hz 0.2 1.2 0.3 1.5 0.4 0.2 2.0 7.1 2,095 1,077 1,880 2.1 2.3 1,800 2.2 2.5 2.6 2.9 2.7 3.1 2,400 3.6 4.1 3.7 4.2 2,598 1,095 2,597 1,244 2,236 4.6 5.2 4.8 5.5 3,400 5.5 6.4 5.8 6.8 2.4 8.2 3,680 3.0 9.6 3,708 1,472 2,238 6.8 7.9 7.1 8.4 8.6 10.4 4,500 4,734 3.4 10.6 4,776 1,495 2,521 9.2 10.9 2.0 0.4 2.4 546 624 780 936 1,170 125 40 80 100 1,404 1,638 1,872 150 2,184 2,496 2,808 200 50 125 3,120 120 9.1 150 10.4 180 10.8 150 210 10.7 240 11.2 280 8.9 320 8.6 200 360 8.8 400 8.7

Space for Tube Replacement

Note
1. Working pressure of chilled water/cooling water circuit are based on 1.0Mpa [150psig]. 2. Fouling factor 0.0001m2.h.oC/kcal for Absorber and Condenser, 0.0001m2.h.oC/kcal for Evaporator. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Catalogue specifications are subject to change without prior notice.

50

World Energy Co.

S Series
Performance Data
Model Cooling Capacity Inlet Temp./Outlet Temp. Chilled Water Flow rate Pressure Drop Connection Inlet Temp./Outlet Temp. Cooling Water Flow rate Pressure Drop Connection Pressure Flow rate Steam Inlet Connection Drain Connection Control Valve Power source Ref. Pump Abs. Pump Electric Purge Pump Control Panel Total kW Total Ampere Length (L) Size Width (W) Height (H) Weight Rigging Operation Unit
kW usRT m3/h mH20 mm m3/h mH20 m MPa kg/h mm mm mm kW kW kW kW kW A mm mm mm ton ton mm

WORLD ENERGY
Single Effect Steam Fired Absorption Chiller

Single Effect Steam Fired Type (450~1500RT)


S500 1,758 500 S560 1,969 560 S630 2,215 630 S700 2,461 700 S800 2,813 800 S900 3,165 900 12 / 7 S1000 3,516 1,000 S1100 3,868 1,100 S1200 4,220 1,200 S1300 4,571 1,300 S1400 4,923 1,400 S1500 5,274 1,500

S450 1,582 450

272 5.1

302 5.4

339 4.2 200

381 5.8

423 7.7

484 5.7

544 7.7 250 32 / 39.4

605 10.1

665 6.7

726 8.6 300

786 10.7

847 8.7 350

907 10.6

450 8.4 250

500 8.6

560 6.8

630 9.3 300

700 12.4

800 8.8

900 12.0 350 0.15

1,000 15.8

1,100 11.1

1,200 14.1 400

1,300 17.6

1,400 14.0 450

1,500 16.8

3,510

3,900 200

4,368

4,914 250

5,460

6,240

7,020 300 80

7,800

8,580

9,360 350

10,140

10,920 400

11,700

65 125 150

100 200

3PH / 400V / 50Hz 0.4 2.4 0.4 0.2 3.4 10.6 4,880 1,594 2,799 10.5 12.5 10.9 13.1 4,500 14.7 17.8 4,998 4.0 14.6 5,540 1,830 3,244 16.0 19.4 5,200 17.2 20.8 5,700 19.3 23.3 5,200 6,038 5,644 5.1 17.0 6,142 2,206 3,522 21.6 26.1 5,700 23.9 29.0 6,200 26.2 31.8 5,700 6,667 6,293 6,818 2,329 3,900 28.5 34.6 6,200 30.8 37.5 6,700 33.1 40.3 6,200 7.0 22.8 7,318 6,860 7,360 3.0 1.5 4.5 0.75

7
S Performance Data

2,929 3,950 35.4 43.2 6,700

Space for Tube Replacement

Options
1. High Pressure water Boxes Water boxes rated for 250psig or 300psig working pressure shall be furnished when specified on the equipment specification data. 2. Special Tubes Tubes of non-standard materials and/or wall thickness shall be provided when specified on the equipment specification data. 3. Special operation temperature conditions Special operation temperature shall be provided when specified on the equipment specification data.

World Energy Co.

51

For Future Energy & Environment

Absorption Heat Pump


Performance Data
HPS Series
Model Heating capacity Inlet Temp./Outlet Temp. Flow rate Hot Water P. Drop Connection Recovery Heat Capacity Waste Hot Water Inlet Temp./Outlet Temp. Flow rate P. Drop Connection Flow rate Inlet Connection Drain Connection Valve Connection Power source Absb. Pump Ref. Pump Purge Pump Control Panel Total Ampare Lenght (L) Width (W) Height (H) Rigging Operation Unit Mcal/h ton/h mAq mm Mcal/h m3/h mAq A kg/h mm mm mm kW (A) kW (A) kW (A) kW (A) A mm mm mm ton ton ton mm HPS010 576 9.6 3.6 227 22.7 10.7 622.5 HPS012 691 11.5 3.7 272 27.2 10.8 80A 747.0 80 25 40 1.5 (5.4) 0.3 (1.5) 0.4 (1.0) 0.3 (0.5) 8.4 2,436 1,335 1,980 3.3 4.5 3.3 2,400 3.4 4.8 3.4 4.1 5.8 4.1 4.3 6.2 4.3 3,400 5.2 7.5 5.2 10.5 3,456 3,506 1,495 2,370 6.2 5.5 9.0 8.0 6.2 5.5 One Body 6.6 9.7 6.6 7.9 11.5 7.9 4,526 1,558 2,700 8.5 12.3 8.5 4,500 10.0 14.5 10.0 10.4 15.2 10.4 14.4 20.0 12.4 13.3 4,606 1,689 4,666 20.5 5,208 1,861 3,100 15.6 21.8 13.4 Two Body 5,200 5,706 40 3.0 (7.5) 933.8 1120.5 1307.3 HPS015 864 14.4 9.8 65A 340 34.0 10.7 408 40.8 11.3 476 47.6 9.9 544 54.4 10.6 635 63.5 10.5 HPS018 1036 17.3 10.0 HPS021 1209 20.2 9.4 HPS024 1382 23.0 9.9

Steam Fired Type Absorption Heat Pump (670 ~ 4686kW)


HPS028 1612 26.9 8.9 HPS032 HPS036 2073 1842 20 / 80 34.5 30.7 9.4 9.4 80A 816 726 30 / 20 81.6 72.6 11.1 11.0 1992.0 2241.0 125 50 65 3, 400V, 50Hz 3.4 (10.2) 0.4 (1.6) 5.5 (15.0) 1.5 (4) 80 HPS040 2303 38.4 9.0 907 90.7 12.0 HPS045 2591 43.2 9.4 1,021 102.1 10.6 HPS050 2879 48.0 9.3 1,134 113.4 11.0 3112.5 HPS056 3224 53.7 3.0 100A 1,270 127.0 10.3 3486.0 150 HPS063 3627 60.5 4.1 1,429 142.9 13.9 150A 3921.8 65 100 HPS070 4030 67.2 5.4 1,588 158.8 14.8 4357.5

Steam side

100A 1743.0 1494.0 100 40 50

125A 2801.3 2490.0

Electric

Size

Weight

Max. Shipping Shipment Type Space for Tube Replacement

16.4 23.1 14.0 5,700

HPD Series
Model Hot Water Outlet capacity Inlet Temp./Outlet Temp. Flow rate Hot Water P. Drop Connection Waste Heat Capacity Inlet Temp./Outlet Temp. Waste Water Flow rate P. Drop Connection LNG(10,500kcal/Nm2) LPG(12,000kcal/kg) Supply pressure Gas connection Kerosene(10,960kcal/) Diesel(11,100kcal/) Oil Connection Power source Absb. Pump Ref. Pump Gas Burner Oil Burner Purge Pump Control Panel Total Ampare Lenght (L) Width (W) Height (H) Rigging Operation Max. Shipping Shipment Type Exhaust Duct Unit Mcal/h ton/h mAq mm Mcal/h m3/h mAq mm Nm2/h kg/h mmAq A /h /h A kW (A) kW (A) kW (A) kW (A) kW (A) KVA A mm mm mm ton ton ton mm mm HPD010 576 9.6 3.6 227 22.7 10.7 40.0 35.0 HPD012 691 11.5 3.7 272 27.2 10.8 80A 48.0 42.0 40A 47.2 46.6 60.1 52.5 72.1 63.1 84.1 73.6 96.1 84.1 HPD015 864 14.4 9.8 65A 340 34.0 10.7 408 40.8 11.3 476 47.6 9.9 544 54.4 10.6 100A 635 63.5 10.5 HPD018 1036 17.3 10.0 HPD021 1209 20.2 9.4 HPD024 1382 23.0 9.9

Direct Fired Type Absorption Heat Pump (670 ~ 4686kW)


HPD028 1612 26.9 8.9 HPD032 1842 20 / 80 30.7 9.4 80A 726 30 / 20 72.6 11.0 128.1 112.1 4,000 125.8 124.2 3, 400V, 50HZ 1.5 (5.4) 0.3 (1.5) 1.5 (3.5) 1.5 (3.5) 2.2 (5.0) 2.2 (5.0) 3.7 (8.1) 3.7 (8.1) 6.3 (13.1) 0.4 (1.0) 0.3 (0.5) 21.4/26.4 4,526 2,557 8.6 11.7 8.6 2,590 10.3 13.9 10.3 3.0 (7.5) 3.4 (10.2) 0.4 (1.6) 4.0 (10.5) 5.5 (15.0) 1.5 (4) 7.5 (18.6) 8.6 (21.9) 816 81.6 11.1 144.1 126.1 50A 59.0 58.2 70.7 69.9 82.5 81.5 15A x 2 94.3 93.1 110.1 106.7 141.5 139.7 157.2 155.2 176.9 174.6 196.5 220.1 194.0 217.3 20A x 2 247.6 244.5 275.1 271.7 907 90.7 12.0 125A 112.1 96.1 160.1 140.1 180.2 157.6 200.2 175.2 224.2 196.2 1,021 102.1 10.6 1,134 113.4 11.0 HPD036 2073 34.5 9.4 HPD040 2303 38.4 9.0 HPD045 2591 43.2 9.4 HPD050 2879 48.0 9.3 HPD056 3224 53.7 3.0 100A 1,270 127.0 10.3 HPD063 3627 60.5 4.1 1,429 142.9 13.9 150A 252.2 220.7 HPD070 4030 67.2 5.4 1,588 158.8 14.8 280.3 245.2

fuel consumption

39.3 38.8

1.5 (4)
Electric

11.9/11.9 2,643

Size

Weight

11.9/13.4 14.0/15.5 15.5/23.1 15.5/23.1 3,456 2,843 3,645 1,980 2,370 2,315 2,461 0 1,930 2,370 4.0 4.9 5.3 6.5 7.9 4.1 6.9 5.2 6.6 7.3 8.7 10.7 9.3 5.5 4.0 4.9 5.3 6.5 7.9 6.9 4.1 One Body 280*210 2,400 310*310 3,400 360*310

31.9/35.2 23.8/26.4 4,606 2,819 2,965 2,700 13.3 10.8 12.6 18.1 14.6 17.1 13.3 10.8 12.6 350*350 4,500

39.1/42.4 4,666 5,206 3,263 3,100 20.6 26.8 13.4 Two Body 400*620 5,200 5,706

19.0 24.6 12.4

21.8 28.5 14.0

410*310

Space for Tube Replacement

5,700

52

World Energy Co.

HPS, HPD, AHT Series


Performance Data
AHT Series
Model Heating Capacity flow rate Inlet Temp. Hot Water Outlet Temp. Pre. Drop Connection Waste Heat Capacity Temp. Waste Steam Connection Drain Connection Max. Working Pre Flow rate Inlet Temp. Outlet Temp. Cooling Water Pre. Drop Connection Condition Max. Working Power source Abs. Pump Electric Ref. Pump-1 Ref. Pump-2 Purge Pump Control Panel Lenght (L) Size Width (W) Height (H) Operation Unit
kcal/h ton mAq A
2

WORLD ENERGY
Absorption Heat Pump

Steam Generation Absorption Heat Pump


AHT-560 300,000 50 127 133 5 100 3.5 625,000 88 150 50
2

AHT-1100 600,000 100 127 133 5 125 3.5 1,250,000 88 200 80 2 108 26 32 7 125

AHT-1650 900,000 150 127 133 5 150 3.5 1,875,000 88 200 100 2 162 26 32 7 150

AHT-2200 1,200,000 200 127 133 5 200 3.5 2,500,000 88 250 125 2 216 26 32 7 200 Indurstrial Water

AHT-2250 1,500,000 250 127 133 5 200 3.5 3,125,000 88 250 125 2 270 26 32 7 200

AHT-3300 1,800,000 300 127 133 5 200 3.5 3,750,000 88 300 125 2 324 26 32 7 250

AHT-3800 2,100,000 350 127 133 5 250 3.5 4,375,000 88 300 150 2 378 26 32 7 250

Max. Working Pressure kg/cm G kcal/h A A kg/cm G ton/h mAq A kg/cm G kW kW kW kW VA mm mm mm ton
2

2 54 26 32 7 100

4.5

4.5

4.5

4.5 3, 400V, 50Hz

4.5

4.5

4.5

8
HPS - HPD - AHT Performance Data

1.5 0.75 0.75 0.4 300 4,470 2,405 4,300 16

2.2 0.75 0.75 0.4 300 4,645 3,005 4,615 27

3.7 0.75 0.75 0.4 300 4,680 3,260 5,010 36

3.7 0.75 0.75 0.75 300 6,870 3,240 5,120 48

5.5 0.75 0.75 0.75 300 6,870 3,310 5,370 52

5.5 0.75 1.5 0.75 300 7,150 3,585 5,770 59

5.5 0.75 1.5 0.75 300 7,735 4,000 5,430 63

Note
1. Available model will be selected as Temperature condition of Waste water and Hot water. 2. Waste water side tube material is 90/10 Cupro Nickel. Tube material may be changed as the waste water and hot water condition. 3. Standard power source is 3ph, 400V, 50Hz. Available 220, 380, 440V and 460V Power source. 4. Please consult with sale person in case of the other fuel condition. Do not available Buncker C oil. 10ton/h Absorption Heat Pump Installation [Korea]

World Energy Co.

53

Installation Records

Single Effect Double Lift Hot water Driven Type

2AB470, 2AB420, Total 2023 usRT Location : Korea

Single Effect Double Lift Hot water Driven Type

2AB470, Total 910 usRT Location : Korea

Single Effect Double Lift Hot water Driven Type

2AB135, Total 260 usRT Location : Korea

Single Effect Double Lift Hot water Driven Type

2AB75, 75 usRT Location : Korea

Single Effect Hot Water Driven Type

HWAR-L110, 110 usRT Location : U.S.A.

Single Effect Double Lift Hot water Driven Type

2AB155, 156 usRT Location : Germany

Double Effect Exhaust Gas Driven Type

CHP024, 240 usRT Location : Germany

Heat Exchanger for Fuel Cell

HEX920, Capacity 400 kW Location : U.S.A.

54

World Energy Co.

WORLD ENERGY
Absorption Chiller Heat Pump

Single Effect Steam Fired Absorption Chiller

S1300, S560, L750, Total 7,800 usRT (Explotion Protection) Location : Korea

Evaporating Condenser for MVR (Mecanical Vapor Recompression System)

Steam Generating Capacity 5 ton/h Location : Korea

Single Effect Steam Fired Absorption Chiller

S500, 500 usRT (Explotion Protection) Location : Korea

Single Effect Double Lift Hot water Driven Type

2AB, 240, 220 usRT Location : Korea

9
Installation Records

Single Effect Hot Water Driven Type

HWAR-L1125, 1422 usRT (Explotion Protection) Location : Korea

Single Effect Double Lift Hot water Driven Type

2AB975, 2AB240, Total 1,036 usRT Location : Taiwan

Single Effect Double Lift Hot water Driven Type

2AB825, 2AB270, 1,001 usRT Location : Taiwan

Single Effect Double Lift Hot water Driven Type

2AB240, 240 usRT Location : Korea

World Energy Co.

55

For Future Energy & Environment -

We-Abs-Gen-1102-00 2011. 02. Print

Office
388-1(34B-5L), Daeyami-dong, Gunpo-si, Gyeonggi-do, 435-060, Korea www.worldenergy.co.kr Tel. 82-31-501-2704 Fax. 82-31-501-2705
EUROPE International Sales Representative

World Energy Absorption PROMORE Corporation Ltd.Chillers Europe Ltd Sky Business Center - Bldg., Unit 21, Port Seosho-Dong, Tunnel Business Park - Dublin 17 - Ireland TAHOE 206B, Illkwang 1656-2 Secho-Gu, Seoul, Korea 137-070 Telephone: +353 1 894 1469 - Fax: +353 1 894 1401 Tel. 82-2-3471-4127 / Fax. 82-2-6280-4127, E-mail charles @ promorecorp.com