You are on page 1of 57

Mustafa Lahloub, ABB INC April 16, 2013

ABB Red TIE Series Transformer Failure Modes


ABB Inc. 2013

Transformer Failure Modes Agenda


Primary Causes of Transformer Failure Balancing the three leg stool Thermal degradation Dielectric withstand Mechanical performance Causes of insulation system degradation Identification of failure vulnerabilities including key transformer components

ABB Inc. 2013

Transformer Failure Modes Core Form Transformer

ABB Inc. 2012

Transformer Failure Modes Stresses Acting on Power Transformers

Mechanical Stresses

Between conductors, leads and windings due to overcurrents or fault currents caused by short circuits and inrush currents Due to local overheating, overload currents and leakage fluxes when loading above nameplate ratings; malfunction of cooling equipment Due to system overvoltages, transient impulse conditions or internal resonance of windings

Thermal Stresses

Dielectric Stresses

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers


The fault current is governed by:

Open-circuit voltage Source impedance Instant of fault onset

Displacement of current
ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers

A short circuit gives rise to: Mechanical forces Temperature rise The transformer must be designed so that permanent damage does not take place Electromagnetic forces tend to increase the volume of high flux Inner winding to reduced radius Outer winding towards increased radius Winding height reduction

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers Effect of the radial forces on windings

Fmean

Inner winding

Outer winding

Radial forces inwards compressive stress

Radial forces outwards tensile stress

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers

Radial forces result in: Buckling for inner windings Increased radius for outer windings Spiraling of end turns in helical winding

Inner winding
ABB Inc. 2012

Outer winding

Transformer Failure Modes Mechanical Stresses in Power Transformers Effect of the axial forces on windings

The radial component of the leakage flux creates forces in axial direction

Axial short circuit forces accumulate towards winding mid-height


ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers Axial


B B Fax Fax

Axial imbalance will create extra axial forces

Fax

Fax

The forces tend to increase the imbalance

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers - Radial


Failure mode Buckling: Characteristic failure mode for inner winding Failure mode Spiraling: Characteristic failure mode for inner and outer winding

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers Two examples showing buckling of inner windings

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers


Axial force failure modes: Collapse of winding end support Tilting of winding conductors Telescoping of windings Bending of cables between spacers Damage of conductor insulation

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers


Failure mode Collapse of end support

Failure mode Bending of cables Failure mode Conductor tilting

ABB Inc. 2012

Transformer Failure Modes Mechanical Stresses in Power Transformers

Axial forces cause: Mechanical stress on insulation material Risk for conductor tilting

ABB Inc. 2012

Transformer Failure Modes Short-Circuit Failure

Unit Auxiliary Test Transformer Failure Internal High Speed Film Camera Footage

ABB Inc. Originally taken by The General Electric Company at Pittsfield, Massachusetts

ABB Inc. 2012

Movies should be screened in the grey area as featured here, size proportion 4:3. No titles should be used.

ABB Inc. 2012

Transformer Failure Modes Risk: Short Circuit Forces & Stresses


Through faults are often the cause of transformer failures Many older designs have insufficient margin for todays fault currents Loose coils due to aging can cause failures Normal aging can cause brittle insulation and increased failures Even brief overloading may cause significant aging Oxygen in the oil can double the aging rate Moisture in the insulation increases aging rate 2-5 times depending on the amount of moisture

ABB Inc. 2012

Transformer Failure Modes Mechanical Risk: Short Circuit Forces & Stresses
Little Risk of Failure

Design Margin

Slight Risk of Failure

Design #1 Design #2
High Risk of Failure

Design #3 Design #4

HV Radial HV Axial LV Radial LV Axial (Hoop) (tipping or (Buckling) (tipping or crushing) crushing)

LTC Winding Radial (Buckling)

LTC Winding Axial (tipping)

Figure 3. Results of the Short-Circuit Strength Design Analysis used in a Life Assessment Study
ABB Inc. 2012

Transformer Failure Modes Thermal Stresses in Power Transformers


Loading is primarily limited by highest permissible temperatures in the transformer, especially within the windings Temperature limits are based on: Expected lifetime The risk for oil vaporization Permissible temperatures are generally expressed as temperature rises above ambient Ambient temperature is in turn defined by current standards 24 hour ambient temperature average 30 C Maximum ambient 40 C In accordance to Standards: Winding temperature rise 65 K Top oil temperature rise 65 K Hot spot temperature rise 80 K

ABB Inc. 2012

Transformer Failure Modes Winding Temperature Rise and HS Calculation


Winding hot spot Top oil rise

hot spot factor

Winding average rise

Copper over tank oil gradient

Copper over winding oil gradient

Winding

Ambient

Bottom oil

Temperature
ABB Inc. 2012

Transformer Failure Modes Thermal Risk: Intensive aging

ABB Inc. 2012

Transformer Failure Modes Thermal Risk: Intensive aging

ABB Inc. 2012

Transformer Failure Modes Cellulose Insulation


Cellulose insulation is a polymer of glucose molecules. The glucose molecules are joined together to form a long chain. These chains form the fiber used to make insulation. Natural chains may be up to 1400 elements long. Reduction of this Polymerization number occurs during manufacture of the insulation material and the transformer.

Cellulose Fiber Chain

ABB Inc. 2012

Transformer Failure Modes Degree of Polymerization - DP


Degree of polymerization is a measure of the number of intact chains in a cellulose fiber. It provides an indication of the ability of the transformer insulation to withstand mechanical force (due to through-faults, etc). New transformer insulation is about 1200 -1000 DP.

ABB Inc. 2012

Transformer Failure Modes Factors affecting DP

Chemical reactions cause de-polymerization (breaking of polymer chains): Hydrolysis due to water. (Moisture in transformer) Pyrolysis due to heat. (Hot spots, overloads,etc.) Oxidation due to Oxygen. (Oxygen in oil) Acidity of the oil also accelerates this process. Aging occurs at normal load and ambient temperature but it is accelerated by high insulation temperature, humidity and oxygen. This reduces the insulation mechanical strength and the windings become more vulnerable to physical damage or dielectric failure during through-faults. Windings hot spots are more affected than the insulation between the windings as the host spot areas age faster. Insulation between windings may however loose some dielectric strength due to absorbing moisture.

ABB Inc. 2012

Transformer Failure Modes Life Expectancy Based on DP and Other Factors


It is assumed that the DP of transformer insulation is approx. 1,000 at the start of life and approx. 200 at the end of life. This graph shows the expected life of thermally upgraded insulation (Insuldur) under various conditions:
10000.0 Dry & Clean (Insuldur) Acidic Oil (Insuldur) 1000.0 L ife E x p e c ta n c y (y e a rs ) 1% Water Content (Insuldur) 3-4% Water Content (Insuldur) 100.0

10.0

1.0

0.1 50 60 70 80 90 100 110 120 130 140 150 Temperature [o C]

For long insulation life expectancy, it is important to keep the insulation dry, keep acidity and oxygen concentration of oil low and provide good cooling for insulation
ABB Inc. 2012

Transformer Failure Modes Thermal Stresses in Power Transformers Life Expectancy Based on DP and Other Factors

ABB Inc. 2012

Transformer Failure Modes DP Measurement Method

The DP is measured by viscosity measurements according an ASTM method after dissolving the paper samples in cupriethylene diamine solvent.

Paper samples must be taken from enough different areas in a transformer in order to get a profile of deterioration of the cellulose When combined with detailed design knowledge, measurements in one area of the transformer can give information on the condition of paper in inaccessible areas of the windings.

ABB Inc. 2012

Transformer Failure Modes Dielectric Stresses in Power Transformers


Overvoltage integrity Overvoltages can be divided into two classes: Continuous Transitory

Continuous overvoltage is related to the core and its magnetization (normal 50Hz or 60 Hz stresses) Transitory overvoltage refers to intermittent stresses placed on the insulation system, usually at much higher levels than the power frequency stresses

ABB Inc. 2012

Transformer Failure Modes Dielectric Stresses in Power Transformers Transient Voltages


Lightning and switching impulse surges are called Transients because their duration is short. The frequencies are much higher than the power frequency (60 Hz here) operation frequency. Transient calculations are used to find the time dependent distribution of transient voltages, applied on the line terminals, over the windings.

ABB Inc. 2012

Transformer Failure Modes Dielectric Stresses in Power Transformers


Winding oscillation
0,8
u

Voltage
0,2 0 0 0,1 0,2

0,4

0,6

1,0

0,3

Winding

Winding length

0,4

2 4

0,5 0,6 0,7 0,8 0,9 1,0

h/H

ABB Inc. 2012

Transformer Failure Modes Dielectric Stresses - Main Insulation Design


2 D Field Plot

2 D field plots can be used to check the design of the main insulation

ABB Inc. 2012

Transformer Failure Modes Analysis of Bushing Failure


525 kV unit assumed bushing failure Simulation showed electric stress was greatest on the paper insulation around the shield ring Used simulation to redesign insulation barriers
FLC evaluation

CAD-model
ABB Inc. 2012

Field distribution over the barriers and HV-LV windings

Transformer Failure Modes

Top transformer failures (78%) from Doble: 43% winding insulation 19% bushings 16% tap changers Other areas of concern: Pollution, dust & debris affecting bushings & cooling systems Cooling System inefficiency COPS Tank elevation Blocking or Wedging In 1998, Hartford Steam Boiler projected: 2% annual failure rate of existing installed base in 2008 5% annual failure rate of existing installed base by 2013

ABB Inc. 2012

Transformer Failure Modes / Diagnostic Techniques Highly Effective On-line Actions are Best
PROBLEMS DIAGNOSTIC TECHNIQUES SERVICE CONDITIONS OF THE EQUIPMENT[1] OFF-S OFF-S OFF-S OFF-S OFF-S ON ON ON ON ON ON ON OFF-S ON ON OFF-S OFF-S PROVEN EFFECTIVENESS[2] M L H M/H H H M M/H M/H L H M L M/H M/H H H 1. Excitation Current 2. Low-voltage impulse 3. Frequency response analysis 4. Leakage inductance measurement 5. Capacitance GAS-IN-OIL ANALYSIS 6. Gas chromatography 7. Equivalent Hydrogen method THERMAL OIL-PAPER DETERIORATION 8. Liquid chromatography-DP method 9. Furan Analysis HOTSPOT DETECTION 10. Invasive sensors 11. Infrared thermography OIL ANALYSIS 12. Moisture, electric strength, resistivity, etc. 13. Turns ratio DIELECTRIC PD MEASUREMENT 14. Ultrasonic method 15. Electrical method 16. Power Factor and Capacitance 17. Dielectric Frequency Response

MECHANICAL

ABB Service Handbook for Transformers, Table 3-1, Page 72


[1] OFF-S = equipment out of service at site, OFF-L = equipment out of service in laboratory, ON = equipment in service [2] H=High, M=Medium, L=Low
ABB Inc. 2012

ABB Inc. 2012

Transformer Failure Modes Solutions to Common Problems Exist


Upgrade and retrofit solutions to alleviate a number of know and unknown operating risks including:

Streaming Electrification Nitrogen Gas Bubble Evolution COPS System Elevation GE Mark II Clamping Shell Form Rewedging GE Type U Bushings Cooling Problems LTC Problems

ABB Inc. 2012

Transformer Failure Modes Case #1 Floating Shield between HV and LV

FRA tests were performed on a 42-MVA transformer, 115/46 kV (delta-wye), to investigate high acetylene level in the DGA End-to-end measurements on HV windings and capacitive interwinding tests between HV and LV showed a problem on phase B

ABB Inc. 2012

Transformer Failure Modes Case #1 Floating Shield between HV and LV

The fault was a loose electric contact of the copper bonding braid on the aluminum shield strips which caused the strips to float electrically

ABB Inc. 2012

Transformer Failure Modes Case #2 Shorted Core Laminations


The measurements were performed on a three-phase transformer rated 250 MVA, 212 kV/ 110 kV/ 10.5 kV, before and after the repair of the core. The first core-related resonance is clearly modified by the fault: the shorted laminations caused a decrease in the core magnetizing inductance (increase in resonance frequency) and an increase in the eddy currents in the core (increased damping).

ABB Inc. 2012

Transformer Failure Modes Case #2 Shorted Core Laminations

The core fault is shown below

ABB Inc. 2012

Transformer Failure Modes Case #3 Shorted Turns


FRA responses of the series windings of a 140-MVA autotransformer (220/69 kV with tertiary winding). The fault was located on phase C of the tertiary winding. In this condition, the low-frequency measurement on the HV winding of the same phase was influenced because of the lower inductance due to the shorted turns on a winding of the same phase (increased first resonance frequency).

ABB Inc. 2012

Transformer Failure Modes FRA Diagnostic Example More Shorted Turns


Shorted turns in transformers are produced by turn-to-turn faults and may have the following characteristics: Adjacent turns lose paper and braze/weld together They result in a solid loop around the core

ABB Inc. 2012

Transformer Failure Modes FRA Diagnostic Example Axial Collapse


Axial winding collapse is likely to have the following characteristics:

Produced within a transformer winding due to excessive axial forces during a fault Windings shift relative to each other Gassing may result Transformer integrity is compromised Failure likely to be catastrophic if transformer continues in service

ABB Inc. 2012

Transformer Failure Modes FRA Diagnostic Example Hoop Buckling


Hoop buckling is produced within a transformer winding due to excessive compressive forces during a fault.

ABB Inc. 2012

Transformer Failure Modes FRA Diagnostic Example Hoop Buckling

ABB Inc. 2012

Transformer Failure Modes FRA Diagnostic Example Clamping Failure


A clamping failure may be produced within a transformer winding due to bulk winding movement.

ABB Inc. 2012

Transformer Failure Modes Dielectric Frequency Response Testing


Hi

The DFR test is a series of power factor measurements at multiple frequencies. It provides more information about the dielectric behavior of the insulation system. The method be used to diagnose the following conditions in transformers:

Ground

Lo

Moisture in the cellulose insulation High oil conductivity due to aging or overheating of the oil Chemical contamination of cellulose insulation Carbon tracking in cellulose High resistance in the magnetic core steel circuit

Hi Lo

ABB Inc. 2012

Transformer Failure Modes DFR Testing Distinguishing Between Aged Oil and Moisture
1.000

Aged Oil, 0.5% Moisture


0.100

Good Oil 1.3% Moisture PF =. 00324

Tan D
0.010 0.001

.001

.01

.1

10

60 100

1000

Frequency, Hz
ABB Inc. 2012

Transformer Failure Modes DFR Analysis Fitting the Right Dielectric Parameters
1.000

0.100

Aged Oil, 0.5% Moisture Good Oil 1.3% Moisture PF =. 00324 Measured DR 0.7% Moisture

Tan D
0.010 0.001

.001

.01

.1

10

60 100 1000

Frequency, Hz
ABB Inc. 2012

Transformer Failure Modes DFR Example High Core Ground Resistance


XV to Ground

XV to Ground after Repair

.01

.10

1 Frequency, Hz

10

100

1000

ABB Inc. 2012

Dielectric Response Fingerprint Function caused by a High Core to Ground Resistance in Auxiliary Transformer

Transformer Failure Modes DFR Signature Example Chemical Contamination

.01

.10

1 Frequency, Hz

10

100

1000

Dielectric Response Fingerprint Function caused by Chemical Contamination of the Windings


ABB Inc. 2012

Transformer Failure Modes DFR Example Effect of High Insulation Moisture

Normal Moisture(.7%)

High Moisture(1.7%)

.01

.10

10

100

1000

Frequency, Hz

Dielectric Response Fingerprint Function Showing the Effect of High Moisture


ABB Inc. 2012

Transformer Failure Modes DFR Moisture Analysis versus Moisture Equilibrium Method
Volume Moisture in Paper
Xfrmr # 1 2 3 4 5 6 7 Temp (o C) 23 28 23 23 13 27 27 Type GSU GSU GSU GSU 3-wdg Auto Auto Constr. Core Core Core Core Shell Core Shell Oil Cond (pS/m) 0.381 0.492 0.412 1.34 1.5 3 0.3 Moist by Oil Moist. by DR Sat (%wt) (%wt) 2.5 1.8 1.4 2.8 * 3.5 3.3 0.9 0.9 0.9 0.7 1.2 2 1

Surface Moisture in Paper Estimated Only From Moisture in Oil Against Volume Moisture From DFR
ABB Inc. 2012

Transformer Failure Modes DFR Analysis Moistures and Loading Capability


Loading Limits Based On Moisture Content
Hottest Spot Temperature( C) 120 130 140 180
o

Cellulose Moisture (% ) 3.5 2.4 1.7 0.8

Overload Type

Overload Level with 40C Ambient 0% 6% 12% 40%

Normal Loading Planned O/L Beyond N/P Long Time Emergency (1-3 mo.) Short-Time Emergency ( -2hr)

ABB Inc. 2012

ABB Inc. 2012

You might also like