Professional Documents
Culture Documents
What This Presentation Covers: Functions of a Control system Basic Controller Terms:
SV PV2 MV
Alarm the operator to critical conditions. eg: High pH, low flow, high level, pump tripped etc
Control plant variables to Given Set Points, eg: Redox Tank pH, Saturator level, Lime Flow etc
Provide Long Term trending of key variables Control the sequence operation of the plant, eg: DAF plant start-up/shutdown, Lime slaker start-up/shutdown
Process Variable (PV) More About Process Variable Set Point (SV) or Set Variable Output (MV) or Manipulated Variable
4
The reasons for choosing a set point may be: Environmental (eg pH set points) Safety related To give the best Process Operating Conditions (ie slaker temperature control, pH control, or level control etc)
The Controller will try to keep the Process Variable as close as possible to the Set Point
60
The Speed limit is the Set Point
60
The Speed limit is the Set Point
PV
60
The Speed limit is the Set Point
PV
You look at the speedo You decide:Am I going too fast or Am I Going too slow ? You adjust your speed by adjusting the position of the accelerator pedal
10
60
The Speed limit is the Set Point
PV
You look at the speedo You decide:Am I going too fast or Am I Going too slow ? You adjust your speed by adjusting the position of the accelerator pedal
11
12
PV You are the Controller Your senses measure the temperature of the water
13
PV You are the Controller You decide:Your senses measure Is the water too hot ? the temperature of the Is the water too cold ? water You adjust the temperature of the water by adjusting the position of the hot and cold water taps
14
PV You are the Controller You decide:Your senses measure Is the water too hot ? the temperature of the Is the water too cold ? water You adjust the temperature of the water by adjusting the position of the hot and cold water taps
15
17
Controller Modes
A controller has 3 basic modes of operation
AUTO CASCADE MANUAL
The Controller mode determines: Where the Set Point (SV) comes from Auto or Cascade How the Controller Output (MV) is set Auto and cascade, or Manual
18
Controller Modes
Symbols used in examples
Instrument (LIT= Lev Indicator Transmitter)
LIT 3030
The instrument (Level, flow, pH, conductivity transmitter) lives in the field.
19
Controller Modes
Symbols used in examples
Instrument (LIT= Lev Indicator Transmitter)
LIT 3030
The instrument (Level, flow, pH, conductivity transmitter) lives in the field. Controller (FIC= Flow-Indicator-Controller)
FIC 3061
The square around the controller tells us that the controller lives in the XL Control System.
20
Controller Modes
Symbols used in examples
Instrument (LIT= Lev Indicator Transmitter)
LIT 3030
The instrument (Level, flow, pH, conductivity transmitter) lives in the field. Controller (FIC= Flow-Indicator-Controller)
FIC 3061
The square around the controller tells us that the controller lives in the XL Control System. Final Control Element - Control Valve Although most Final Control Elements are control valves, some may be vibro feeders or variable speed and/or variable stroke pumps.
21
22
23
FIC 3061
0 to 100%
24
Note:- The link between the controller and the valve is broken. The valve is positioned by the operator
Controller
0 to 100%
25
Controller Modes-Auto-Example
DAF Saturator - Level Control
LIT 3050 Level (in mm) Measured by level transmitter This will be the Process Variable (PV)
27
Controller Modes-Auto-Example
DAF Saturator - Level Control
LIT 3050 Level (in mm) Measured by level transmitter This will be the Process Variable (PV)
28
Controller Modes-Auto-Example
DAF Saturator - Level Control
Set Point (SV) in mm entered by the operator SV PV LIC 3050 MV
LIT 3050 Level Measured by level transmitter This will be the Process Variable (PV)
29
Controller Modes-Auto-Example
DAF Saturator - Level Control
Set Point (SV) in mm entered by the operator SV PV LIC 3050 MV The controller automatically controls the level in the saturator by adjusting the amount of water flowing to it
LIT 3050 Level Measured by level transmitter This will be the Process Variable (PV)
30
LIT 3050 Level Measured by level transmitter This will be the Process Variable (PV)
2. Remember Output (MV) 0-100% In AUTO mode thesent controller More the control its valve automatically adjusts output to try to maintain the PV at the Set Point
31
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter34
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
The lime controller operates in CASCADE & controls the lime flow by adjusting the the lime flow control valve Mix Tank
SV FIC 3061 MV Lime Flow (l/m) measured by Mag Flow Meter FT 3061
PV
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter35
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
Where does the Lime Flow Set Point Come From ???
The lime controller operates in CASCADE & controls the lime flow by adjusting the the lime flow control valve Mix Tank
SV FIC 3061 MV Lime Flow (l/m) measured by Mag Flow Meter FT 3061
PV
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter36
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
The Lime Flow Set Point comes from the pH Controller. The pH Controller determines how much lime is required
pHC 3047L MV
The lime controller operates in CASCADE & controls the lime flow by adjusting the the lime flow control valve Mix Tank
Set Point (SV) FIC 3061 MV Lime Flow (l/m) measured by Mag Flow Meter FT 3061
PV
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter37
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
pH is measured and this is the Process pHT Variable(PV) for the 3047B pH Controller SV PV pHC 3047L MV SV The lime controller operates in CASCADE FIC 3061 MV Mix Tank Output (MV) 0-100% sent the control valve PV Lime Flow (l/m) measured by Mag Flow Meter FT 3061 The pH Controller operates in AUTO mode. Its Set Point (SV) is entered by the Operator
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter38
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
pH is measured and Cascade Loops have two controllers:this is the Process pHT Variable(PV) for the 3047B 1. Master Controller (eg pH controller) pH Controller This operates in AUTO mode and adjusts the set point of the Slave Controller SV PV pHC 3047L MV SV FIC 3061 MV Mix Tank Output (MV) 0-100% sent the control valve PV Lime Flow (l/m) measured by Mag Flow Meter FT 3061 The pH Controller operates in AUTO mode. Its Set Point (SV) is entered by the Operator
2. Slave Controller (eg Lime controller) This operated in CASCADEThe mode and lime controller receives its set point from the master operates in CASCADE controller
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter39
Controller Modes-Cascade-Example
Mix Tank Lime Flow / pH Control
pH is measured and Cascade Loops have two controllers:this is the Process pHT Variable(PV) for the 3047B 1. Master Controller (eg pH controller) pH Controller This operates in AUTO mode and adjusts the set point of the Slave Controller SV PV pHC 3047L MV The pH Controller operates in AUTO mode. Its Set Point (SV) is entered by the Operator
2. Slave Controller (eg lime controller) This operated in CASCADEThe mode and lime controller receives its set point from the master operates in CASCADE controller
HOW IS THE SET POINT SV FIC CALCULATED Flow (l/m) 3061 PV ???? Lime measured by
MV Mag Flow Meter FT 3061
Mix Tank
Lime To Tank Lime to Mix tank adjusted by Control Valve Magnetic Flowmeter40
SV
FIC 3061
41
The pH Controller output is ranged 0 to 100 % The Lime Controller set point is ranged 0 to 30 L/min
SV
FIC 3061
42
The pH Controller output is ranged 0 to 100 % The Lime Controller set point is ranged 0 to 30 L/min
The Lime Flow set point is calculated as follows:-
More
SV Lime Set Point = pH output % X Lime Maximum Range 100 Example:- If pH Output = 10% Lime Set Point = 10% X 100 = 3 L/min 30 L/min
FIC 3061
43
44
45
47
48
TIC 3026 MV
Lime Slaker
Magnetic Flowmeter49
TIC 3026 MV
Lime Slaker
Magnetic Flowmeter50
Lime Slaker
Magnetic Flowmeter51
SV TIC 3026 MV SV
Temp Measured by a Thermocouple Output (MV) 0-100% sent the control valve
FIC 3027 MV
Lime Slaker
Magnetic Flowmeter52
SV TIC 3026 MV SV low limit guarantees that the This PVtrip point of low flow FIC 7 l/min is always exceeded. 3027 Lime trips Flow (l/m) The system no longer measured by MV on low flow Output (MV) Mag Flow 0-100% sent Meter the control valve
Lime Slaker
Magnetic Flowmeter53
Summary
In this lesson on Process Control Concepts, we have learnt about the following:
The main functions of the XL Control System.
To monitor, alarm, control and trend key plant variables.
Summary
A controller has 3 basic modes of operation
MANUAL AUTO CASCADE MV set by the operator SV fixed and set by the operator, MV adjusted automatically Similar to Auto mode but the SV is varied by another controller (Master Controller)
The Controller mode determines: Where the Set Point (SV) comes from How the Controller Output (MV) is set
You have also seen some examples of why some control modes are used instead of others.
55
Assessment
To check your understanding of the course content we would now ask you to complete the short written quiz supplied. This should only take about 15 - 20 minutes, and you may use the presentation to answer the questions. (Open Book) When you have finished, we will go through the answers and correct any mistakes or misunderstandings you may have about the course material Thank you for completing this course.
56