Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-40
Step 1 Inspect Shipment . . . . . . . . . . . . . . . . . . . 1
Step 2 Rig and Place Unit . . . . . . . . . . . . . . . . . . 1
Step 3 Piping Connections . . . . . . . . . . . . . . . . 15
COOLER FLUID, VENT, AND DRAIN
BRINE UNITS
PREPARATION FOR YEAR-ROUND
OPERATION
FILL FLUID LOOP
INSULATE COOLER HEADS
30HXA PIPING, VALVE, AND SWITCH
INSTALLATION
30HXC PIPING AND VALVE INSTALLATION
INSTALL PRESSURE RELIEF REFRIGERANT
VENT PIPING
Step 4 Make Electrical Connections . . . . . . 21
FIELD POWER CONNECTIONS
FIELD CONTROL POWER CONNECTIONS
CONDENSER FAN CONTROL FOR
CONDENSER UNITS USED WITH
30HXA UNITS
Step 5 Install Accessories . . . . . . . . . . . . . . . 25
ELECTRICAL
30HXA LOW-AMBIENT OPERATION
MINIMUM LOAD ACCESSORY
MISCELLANEOUS ACCESSORIES
Step 6 Leak Test Unit . . . . . . . . . . . . . . . . . . . . 25
30HXC UNITS
30HXA UNITS
Step 7 Refrigerant Charge . . . . . . . . . . . . . . . 40
30HXC UNITS
30HXA UNITS
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and service mechanics should install, start up, and
service this equipment.
When working on the equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.
INTRODUCTION
These instructions cover installation of 30HX liquid chillers with electronic controls and units with factory-installed
options (FIOPs).
INSTALLATION
Step 1 Inspect Shipment Inspect unit for damage upon arrival. If damage is found, file a claim with the
shipping company right away. Do not store units in an area
exposed to weather because of sensitive control mechanisms and electronic devices.
Locate unit indoors. When considering unit location, consult National Electrical Code (NEC, U.S.A.) and local code
requirements. Allow sufficient space for wiring, piping, and
service. Install unit in an area which will not be exposed to
subfreezing weather. See Fig. 1-8 for clearance details.
Allow the following clearances for service access:
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ft (610 mm)
Ends . . . . . . . . . . . . . . . . tube removal at one (either) end;
3 ft (914 mm) at opposite end.
Be sure surface beneath unit is level and is capable of
supporting the operating weight of the unit. See Fig. 9 and
Tables 1A and 1B for unit mounting and operating weights.
If necessary, add supporting structure (steel beams or reenforced concrete slabs) to floor to transfer weight to nearest
beams.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-004
Printed in U.S.A.
Form 30HX-7SI
Pg 1
8-99
Replaces: 30HX-4SI
Tab 5c
106
096
086
076
UNIT
30HXC
OPERATING
WEIGHT
lb (kg)
5700
(2586)
5723
(2597)
5855
(2657)
6177
(2803)
B
45.87
(1165)
45.87
(1165)
37.63
(956)
37.63
(956)
45.87
(1165)
45.87
(1165)
54.12
(1375)
54.12
(1375)
32.50
(826)
32.50
(826)
32.50
(826)
33.50
(851)
LEGEND
Std
Minus
Plus
Std
Minus
Plus
076,086,096
076,086,096
076,086,096
106
106
106
UNIT 30HXC
3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).
2.
K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.
4.68 (119)
5.14 (131)
5.14 (131)
5.14 (131)
4.68 (119)
4.68 (119)
5.14 (131)
5.14 (131)
5.14 (131)
4.68 (119)
4
3
2
4
NUMBER
OF PASSES
49
59
59
59
49
49
CONNECTION
SIZES
146
136
126
116
UNIT
30HXC
OPERATING WEIGHT
lb (kg)
6415
(2911)
6465
(2933)
6688
(3034)
6718
(3048)
LEGEND
Std
Minus
Plus
116,126,136,146
116,126,136,146
116,126,136,146
UNIT 30HXC
3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).
2.
K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.
0.00
4.68 (119)
0.00
4.68 (119)
1
3
NUMBER
OF PASSES
49
49
49
CONNECTION
SIZES
186
171
161
UNIT
30HXC
7452
(3381)
7660
(3475)
7854
(3564)
OPERATING
WEIGHT
lb (kg)
DIMENSIONS
in. (mm)
A
B
72.12
50.63
(1832)
(1286)
61.37
61.37
(1559)
(1559)
61.37
61.37
(1559)
(1559)
LEGEND
3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).
2.
K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.
Std
Minus
Plus
161,171,186
161,171,186
161,171,186
UNIT 30HXC
0.00
4.68 (119)
A
4.68 (119)
0.00
4.68 (119)
B
4.68 (119)
1
3
NUMBER OF PASSES
59
59
59
CONNECTION SIZES
271
261
246
206
UNIT
30HXC
10,581
(4799)
10,969
(4976)
10,992
(4986)
11,029
(5003)
OPERATING
WEIGHT
lb (kg)
DIMENSIONS
in. (mm)
A
33.88
(860)
34.38
(873)
34.38
(873)
34.38
(873)
LEGEND
3.
2.
K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and
refrigerant.
Std
Minus
Plus
206,246,261,271
206,246,261,271
UNIT 30HXC
206,246,261,271
0.00
5.53 (140)
0.00
5.53 (140)
1
3
NUMBER OF
PASSES
69
69
69
CONNECTION
SIZES
Std
Minus
Plus
Std
Minus
Plus
076,086,096
076,086,096
076,086,096
106
106
106
A
8.48
(215)
8.48
(215)
8.48
(215)
10.48
(266)
5.14 (131)
5.14 (131)
5.14 (131)
5.14 (131)
5.14 (131)
5.14 (131)
B
4.68 (119)
4.68 (119)
4.68 (119)
DIMENSIONS
in. (mm)
A
4.68 (119)
4.68 (119)
4.68 (119)
4717
(2140)
4744
(2152)
4835
(2194)
5151
(2337)
OPERATING
WEIGHT lb (kg)
UNIT 30HXA
106
096
086
076
UNIT
30HXA
3
2
3
2
4
NUMBER OF
PASSES
B
45.87
(1165)
45.87
(1165)
54.12
(1375)
54.12
(1375)
59
59
59
49
49
49
CONNECTION
SIZES
C
45.87
(1165)
45.87
(1165)
37.63
(956)
37.63
(956)
D
32.50
(826)
32.50
(826)
32.50
(826)
33.50
(851)
H
59.48
(1511)
59.48
(1511)
42.77
(1086)
42.77
(1086)
J
5.72
(145)
5.72
(145)
5.72
(145)
5.87
(149)
L
46.25
(1175)
46.25
(1175)
38.00
(965)
38.00
(965)
K.O.
SAE
THK
TYP
K
45.81
(1164)
45.81
(1164)
54.06
(1373)
54.06
(1373)
Knockout
Society of Automotive Engineers, U.S.A.
Thickness
Typical
LEGEND
3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).
2.
NOTES:
1. Operating weight includes weight of water and refrigerant.
146
136
126
116
UNIT
30HXA
OPERATING
WEIGHT
lb (kg)
5163
(2342)
5205
(2362)
5309
(2408)
5333
(2420)
Minus
Plus
116,126,136,146
116,126,136,146
0.00
4.68 (119)
0.00
4.68 (119)
Std
116,126,136,146
UNIT 30HXA
NUMBER OF
PASSES
49
49
49
CONNECTION
SIZES
3.
Denotes accessory or factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance around machine 369 (914.4).
2.
NOTES:
1. Operating weight includes weight of water and refrigerant.
LEGEND
K.O. Knockout
THK Thickness
TYP Typical
161
171
186
Std
Minus
Plus
161,171,186
161,171,186
161,171,186
UNIT 30HXA
5752 (2610)
5777 (2621)
5946 (2698)
UNIT
OPERATING
30HXA WEIGHT lb (kg)
0.00
5.14 (131)
A
5.14 (131)
0.00
5.14 (131)
B
5.14 (131)
1
3
NUMBER OF
PASSES
59
59
59
CONNECTION
SIZES
DIMENSIONS in.
A
B
C
72.12 (1832) 50.63 (1286) 48.56 (1233)
61.37 (1559) 61.37 (1559) 43.25 (1099)
61.37 (1559) 61.37 (1559) 43.25 (1099)
LEGEND
Denotes accessory or
factory-installed option.
4. Dimensions are in inches (millimeters) and weights are in lb (kg).
5. Recommended service clearance
around machine 369 (914.4).
3.
2.
K.O. Knockout
THK Thickness
TYP Typical
NOTES:
1. Operating weight includes weight of water and refrigerant.
D
E
72.06 (1830) 51.00 (1295)
61.31 (1572) 61.75 (1568)
61.31 (1572) 61.75 (1568)
(mm)
UNIT
30HXA
206
246
261
271
OPERATING
WEIGHT lb (kg)
7485 (3395)
7621 (3457)
7621 (3457)
7621 (3457)
2.
3.
NOTES:
1. Operating weight includes weight of water and
refrigerant.
LEGEND
K.O. Knockout
THK Thickness
TYP Typical
738
738
686
730
728
738
758
763
817
936
962
948
985
985
985
1
(335)
(335)
(311)
(331)
(330)
(335)
(344)
(346)
(371)
(425)
(436)
(430)
(447)
(447)
(447)
943
947
968
1028
1114
1127
1176
1182
1272
1318
1361
2406
2515
2520
2529
2
(428)
(430)
(439)
(466)
(505)
(511)
(533)
(536)
(577)
(598)
(617)
(1091)
(1141)
(1143)
(1147)
1418
1427
1447
1510
1615
1628
1689
1697
1890
1946
1996
3133
3276
3283
3294
5
(643)
(647)
(656)
(685)
(733)
(738)
(766)
(770)
(857)
(883)
(905)
(1421)
(1486)
(1489)
(1494)
6
896 (406)
902 (409)
1034 (469)
1092 (495)
1127 (511)
1131 (513)
1171 (531)
1172 (532)
1346 (610)
1241 (563)
1265 (574)
1650 (748)
1733 (786)
1739 (789)
1749 (793)
1
555 (252)
555 (252)
509 (231)
555 (252)
530 (240)
540 (245)
548 (249)
551 (250)
560 (254)
627 (284)
648 (294)
671 (304)
681 (309)
681 (309)
681 (309)
2
793 (360)
798 (362)
808 (367)
869 (394)
895 (406)
905 (410)
926 (420)
930 (422)
965 (438)
968 (439)
1004 (455)
1702 (772)
1748 (793)
1748 (793)
1748 (793)
10
5
1326 (601)
1340 (608)
1350 (612)
1410 (640)
1456 (660)
1468 (666)
1498 (679)
1506 (683)
1650 (748)
1658 (752)
1703 (772)
2216 (1005)
2276 (1032)
2276 (1032)
2276 (1032)
6
699 (317)
705 (320)
827 (375)
880 (399)
887 (402)
887 (402)
908 (412)
908 (412)
1025 (465)
918 (416)
939 (426)
1167 (529)
1209 (548)
1209 (548)
1209 (548)
076
086
096
5700
4717
5723
4744
5855
4835
106
116
126
136
146
6177
6415
6465
5151
5163
5205
Semi-Hermetic, Twin Screw
2
2
2
6688
5309
6718
5333
39/39
No
46/39
No
56/39
No
66/39
No
66/46
No
66/56
No
80/56
No
80/66
No
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
20
10
20
10
20
10
20
10
20
10
20
10
60/60
76/65
124/89
119/100
001
17.0
001
17.0
006
24.0
006
24.0
220
220
220
220
220
220
220
220
300
300
300
300
300
300
300
300
12
12
12
12
12
12
12
12
34
31.7
34
31.7
3 4
31.7
3 4
31.7
3 4
31.7
3 4
31.7
3 4
31.7
34
31.7
165
320
165
320
166
320
166
320
167
320
167
320
167
320
167
320
218
118
218
118
218
118
218
118
218
118
218
118
218
118
218
118
58
21.6
58
21.6
5 8
21.6
58
21.6
173
16.8
220
173
16.8
220
5 8
5 8
5 8
5 8
21.6
21.6
21.6
21.6
Shell and Tube with Enhanced Copper Tubes
174
174
175
175
18.3
18.3
23.9
23.9
220
220
220
220
176
27.5
220
176
27.5
220
300
300
300
300
300
300
300
300
12
12
12
12
12
12
12
12
34
31.7
34
31.7
3 4
31.7
3 4
31.7
3 4
31.7
3 4
31.7
3 4
31.7
34
31.7
20
20
10
10
R-134a
94/70
110/70
105/76
112/89
Shell and Tube with Enhanced Copper Tubes
002
010
007
007
19.0
22.6
21.4
21.4
LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
11
161
171
186
206
246
7452
5752
7660
5777
7854
10,581
10,969
5946
7,485
7,621
Semi-Hermetic, Twin Screw
2
3
3
261
271
10,992
7,621
11,029
7,621
80/56
Yes
66/80
Yes
80/80
Yes
66/39/80
Yes
80/56/80
Yes
80/66/80
Yes
80/80/80
Yes
6
8
6
8
6
8
8
11
8
11
8
11
8
11
20
10
20
10
20
10
150/110
119/140
104
28.5
012
28.5
220
220
220
220
220
220
220
300
300
300
300
300
300
300
12
12
12
34
34
34
34
34
31.7
3 4
31.7
34
31.7
3 4
31.7
3 4
31.7
34
31.7
34
31.7
167
320
168
320
168
320
106
320
106
320
106
320
106
320
218
138
218
138
218
138
218 (2)
158/138
218 (2)
158/138
218 (2)
158/138
218 (2)
158/138
58
21.6
5 8
21.6
58
21.6
58
21.6
177
30.6
220
178
37.6
220
180
55.1
220
180
55.1
220
300
300
300
300
300
300
300
12
12
12
34
34
34
34
34
31.7
3 4
31.7
34
31.7
3 4
31.7
3 4
31.7
34
31.7
34
31.7
13
13
13
7
7
7
R-134a
135/135
220/135
220/135
220/135
Shell and Tube with Enhanced Copper Tubes
013
125
126
126
33.4
43.1
47.2
47.2
58
5 8
5 8
21.6
21.6
21.6
Shell and Tube with Enhanced Copper Tubes
178
179
180
37.6
47.6
55.1
220
220
220
LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
Circuit A/Circuit B.
12
13
7
220/135
126
47.2
076
086
096
2586
2140
2597
2152
2657
2194
106
116
2803
2911
2337
2342
Semi-Hermetic, Twin Screw
2
2
126
136
146
2933
2362
3034
2408
3048
2420
137/137
No
162/137
No
197/137
No
232/137
No
232/137
No
232/197
No
281/197
No
281/232
No
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
20
10
20
10
20
10
20
10
20
10
20
10
20
10
20
10
27.3/27.3
34.5/29.5
56.4/40.5
54.1/45.5
001
64.3
001
64.3
006
90.8
006
90.8
1517
1517
1517
1517
1517
1517
1517
1517
2068
2068
2068
2068
2068
2068
2068
2068
12
12
12
12
12
12
12
12
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
165
2205
165
2205
166
2205
166
2205
166
2205
167
2205
167
2205
167
2205
218
118
218
118
218
118
218
118
218
118
218
118
218
118
218
118
58
9.80
58
9.80
58
9.80
58
9.80
173
63.6
1517
173
63.6
1517
58
9.80
Tubes
175
90.5
1517
176
104.1
1517
176
104.1
1517
2068
2068
2068
2068
2068
2068
2068
2068
12
12
12
12
12
12
12
12
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
34
14.38
R-134a
42.7/31.8
50.0/31.8
47.7/34.5
50.9/40.5
Shell and Tube with Enhanced Copper Tubes
002
010
007
007
71.9
85.5
81.0
81.0
58
58
58
9.80
9.80
9.80
Shell and Tube with Enhanced Copper
174
174
175
69.3
69.3
90.5
1517
1517
1517
LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
13
161
171
186
3381
2610
3475
2621
3564
2698
206
246
261
271
4799
4976
3395
3457
Semi-Hermetic, Twin Screw
3
3
4986
3457
5003
3457
281/197
Yes
232/281
Yes
281/281
Yes
232/137/281
Yes
281/197/281
Yes
281/232/281
Yes
281/281/281
Yes
6
8
6
8
6
8
8
11
8
11
8
11
8
11
20
10
20
10
20
10
68.2/50.0
54.1/63.6
104
107.9
012
107.9
1517
1517
1517
1517
1517
1517
1517
2068
2068
2068
2068
2068
2068
2068
12
12
12
34
34
34
34
34
14.28
3 4
14.38
3 4
14.38
34
14.38
3 4
14.38
3 4
14.38
3 4
14.38
167
2205
168
2205
168
2205
106
2205
106
2205
106
2205
106
2205
218
138
218
138
218
138
218 (2)
158/138
218 (2)
158/138
218 (2)
158/138
218 (2)
158/138
58
9.80
5 8
9.80
177
115.8
1517
178
142.3
1517
2068
2068
2068
2068
2068
2068
2068
12
12
12
34
34
34
34
34
14.38
3 4
14.38
3 4
14.38
34
14.38
3 4
14.38
3 4
14.38
3 4
14.38
13
13
13
7
7
7
R-134a
61.2/61.2
99.8/61.2
99.8/61.2
99.8/61.2
Shell and Tube with Enhanced Copper Tubes
013
125
126
126
126.4
163.2
178.7
178.8
5 8
58
9.80
9.80
Shell and Tube with Enhanced
178
179
142.3
177.9
1517
1517
LEGEND
NPTF National Pipe Thread Female
SAE Society of Automotive Engineers
*Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only.
Cricuit A/Circuit B.
14
5 8
5 8
9.80
9.80
Copper Tubes
180
180
208.6
208.6
1517
1517
13
7
99.8/61.2
126
178.7
5 8
9.80
180
208.6
1517
5. Bolt the weld flanges back onto their respective fluid heads.
FILL FLUID LOOP Fill the fluid loop with water (or brine)
and a corrosion-resistant inhibitor suitable for the water of
the area. Consult the local water authority for characteristics
of area water and a recommended inhibitor for the cooler
fluid loop.
15
16
Fig. 10 Typical Cooler (30HXA, HXC) and Condenser (30HXC Only) Piping and Wiring
NOTES:
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for specific installation. Certified field wiring and dimensional diagrams are available upon request. The 30HXA and HXC units should be
installed using certified drawings.
2. All wiring must comply with applicable codes.
3. Refer to Carrier System Design Manual for details regarding piping techniques.
4. Piping, wiring, switches, valves, vent, gages, strainers, drain, and vibration isolation are all field supplied.
5. Water connections are shown on left side of control box in this figure. Actual connections are on right side of control box.
LEGEND
Field Wiring
Field Piping
NOTES:
1. Piping shown is for general point-of-connection only and is not intended to show
details for a specific installation. Certified field wiring and dimensional drawings
are available upon request. The 30HXA units should be installed using certified
drawings.
2. Refer to Carrier System Design Manual for details regarding piping techniques.
3. Piping and pressure relief devices are field supplied.
4. Vent pipes properly per local codes.
ACCESSORY SOUND ENCLOSURE
RELIEF VALVES
(IF REQUIRED BY
CODE)
COMPRESSOR
DOUBLE RISER
(IF REQUIRED)
COOLER*
OIL
SEPARATOR
DISCHARGE
LINES
LIQUID LINES
LIQUID LINE
SOLENOID VALVES
LIQUID LINE
(IF REQUIRED)
ANGLE VALVE
MECHANICAL ROOM
CONDENSER
LEGEND
COM Common
N.O. Normally Open
17
PRESSURE
R-134a
Psig
187.5
182.0
5.5
Complete the steps below to install the flanged backpressure valves on the 30HXA chiller before running discharge
piping. Follow these steps for both refrigerant circuits.
1. Be sure to remove nitrogen charge or properly recover
refrigerant charge before removing the blank-off plate.
Remove the blank-off plate from the mating flange on
top of the coil separator by removing the screws from
the flange. See Fig. 15 for location.
2. Using the screws that were removed in Step 1, bolt the
flanged back-pressure valve to the mating flange on
top of the coil separator. An O-ring is included in the
box with the back-pressure valve for sealing the
flange.
The valve may be oriented in any desired position in to
make discharge piping easier. Install pipe hangers
where needed. Make sure no weight or stress is placed
on the back-pressure valve.
R-22
kPa
1293
1255
38
Psig
281.6
274.3
7.3
kPA
1942
1891
51
PRESSURE
R-134a
Psig
124.3
120.1
4.2
kPa
857
828
29
R-22
Psig
195.9
190.2
5.7
kPA
1351
1311
40
18
19
500
137.2
450
121.9
400
106.7
350
91.4
76.2
61.0
45.7
152.4
300
250
200
15
/8"
150
.3
13
/8"
100
30.4
15.2
50
(41
mm
(34
.9 m
m)
1 1/8
" (28
30
40
50
60
70
.6 m
80
m)
100
90
110
120
130
140
150
160
170
180
190
200
457
492
527
562
598
633
668
703
TONS COOLING
105
141
176
211
246
280
387
422
kW COOLING
352
316
NOTES:
1. Values are for a 2 F pressure drop at 125 F (51.7 C)
saturated discharge temperature, and 105 F (40.6 C)
liquid refrigerant temperature.
2. Size each circuit separately.
152.4
500
137.2
450
121.9
400
106.7
350
91.4
76.2
61.0
45.7
30.4
300
250
31
/8"
200
(79
.4)
mm
150
2 5/8
" (66
100
2 1/
8" (5
15.2
50
0
30
40
50
60
70
80
90
4.0
.7 m
m)
mm
100
130
140
457
422
387
kW COOLING
492
110
120
150
160
170
180
190
200
TONS COOLING
105
141
176
211
246
281
316
352
NOTES:
1. Values are for a 2 F pressure drop at 125 F (51.7 C)
saturated discharge temperature, and 105 F (40.6 C)
liquid refrigerant temperature.
2. Size each circuit separately.
527
562
598
633
668
703
IMPORTANT: A separate, field-supplied power supply must be used with the 4 to 20 mA valve. Failure
to use a separate power supply may result in damage
to the chiller processor module (PSIO).
OUTLET
30HXC CONDENSER
SENSOR
INLET
OUTLET
30HXC CONDENSER
SENSOR
INLET
OUTLET
30HXC CONDENSER
INLET
22
23
ALM
CA-1M
CB-1M
CCN
CDFC
CDFS
CDWP
CWFS
CWP
CWPI
LLSV
NEC
TB
LEGEND
Alarm
Compressor A1, 1M Contactor
Compressor B1, 1M Contactor
Carrier Comfort Network
Condenser Fan Contactor
Condenser Flow Switch
Condenser Water Pump
Chilled Water Flow Switch
Chilled Water Pump
Chilled Water Pump Interlock
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be
in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire
size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source (except 380/415 v units) through a fieldsupplied disconnect with 15 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Control circuit
conductors for all units must be copper only. Control circuit power is factory wired for 380/415 v units.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated
for dry circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of
TB2 if remote ON-OFF is installed.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI)
functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled
water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.
7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va
inrush at 115 or 230 volt.
8. Terminal 6 of TB2 is for condenser water pump (HXC only) or circuit B condenser fan contactor (HXA only).
Terminal 1 of TB2 is for circuit A condenser fan contactor (HXA only). The maximum load allowed is 125 va
sealed, 1250 va inrush at 115 or 230 volt. Install CDWP or CDFC-B between TB2-6 and TB4-2 (unit control
power neutral). Install CDFC-A between TB2-1 and TB4-2 (unit control power neutral). Separate field power
supply is not required.
9. Terminals J7-25 and J7-32 of PSIO2 are for condenser flow switch (CDFS). The contacts must be rated for dry
circuit application capable of handling a 24 vac to 50 mA load. Separate field power supply is required.
24
ALM
CA-1M
CB-1M
CCN
CDFC
CDFS
CDWP
CWFS
CWP
CWPI
LLSV
NEC
TB
LEGEND
Alarm
Compressor A1, 1M Contactor
Compressor B1, 1M Contactor
Carrier Comfort Network
Condenser Fan Contactor
Condenser Flow Switch
Condenser Water Pump
Chilled Water Flow Switch
Chilled Water Pump
Chilled Water Pump Interlock
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Power Wiring
Field Control Wiring
Factory Installed Wiring
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be
in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. Maximum incoming wire
size for each terminal block is 500 kcmil.
3. Power for control circuit should be supplied from a separate source (except 380/415 v units) through a fieldsupplied disconnect with 15 amp maximum protection for 115 volt control circuits and 15 amp maximum protection for 230 volt control circuit. Connect control circuit power to terminals 1 and 2 of TB4. Control circuit
conductors for all units must be copper only. Control circuit power is factory wired for 380/415 v units.
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The contacts must be rated
for dry circuit application capable of handling a 24 vac to 50 mA load. Remove jumper between 13 and 14 of
TB2 if remote ON-OFF is installed.
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water pump interlock (CWPI)
functions. The contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA load.
6. Terminals 4 and 5 of TB2 are for control of chilled water pump starter. The maximum load allowed for the chilled
water pump relay is 125 va sealed, 1250 va inrush at 115 or 230 volt.
7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va
inrush at 115 or 230 volt.
8. Terminal 6 of TB2 is for condenser water pump (HXC only) or circuit B condenser fan contactor (HXA only).
Terminal 1 of TB2 is for circuit A condenser fan contactor (HXA only). The maximum load allowed is 125 va
sealed, 1250 va inrush at 115 or 230 volt. Install CDWP or CDFC-B between TB2-6 and TB4-2 (unit control
power neutral). Install CDFC-A between TB2-1 and TB4-2 (unit control power neutral). Separate field power
supply is not required.
9. Terminals J7-25 and J7-32 of PSIO2 are for condenser flow switch (CDFS). The contacts must be rated for dry
circuit application capable of handling a 24 vac to 50 mA load. Separate field power supply is required.
NOTE: The fan contactor relays are pre-wired to unit control power. A separate power supply is NOT required. The
maximum load allowed for these relays is 125 va sealed,
1250 va inrush at 115 or 230 volts.
Do not use interlocks or other safety device contacts connected between TB2 terminals 13 and 14 as remote
on-off. Connection of safeties or other interlocks between these 2 terminals will result in an electrical
bypass if the REMOTE-OFF-LOCAL switch is in
the LOCAL position. If remote on-off unit control is
required, a field-supplied relay must be installed in the
unit control box and wired as shown in Fig. 17 and 18.
Failure to wire the remote on-off as recommended will
result in tube freeze damage.
Terminals 2 and 3 of TB2 have been provided for a fieldsupplied remote alarm (ALM). If an audible alarm is
installed, an alarm shutoff is also recommended. Contacts
are rated for 125 va at either 115 or 230 v control power. See
Fig. 17 and 18.
Terminals 4 and 5 of TB2 have been provided for a fieldsupplied chilled water (fluid) pump relay (CWP). Use relays
with a coil rating of at least 75 va. A field-supplied power
supply of appropriate voltage must be provided. Contacts are
rated for 125 va at either 115 or 230 v control power. See
Fig. 17 and 18.
Terminal 6 of TB2 has been provided for a field-supplied
Circuit B fan control relay for the remote condenser (30HXA)
or a condenser pump relay (30HXC). Use relays with a coil
rating of at least 75 va. Terminal 1 of TB2 has been provided
for a field-supplied Circuit A fan control relay for a remote
condenser (30HXA only). Use relays with a coil rating of at
least 75 va. A separate field power supply is NOT required.
Connect Circuit B fan relay/Condenser Pump Relay between TB2-6 and TB4-2 (control power neutral). Use relays
with a coil rating of at least 75 va. Connect Circuit A fan
relay between TB2-1 and TB4-2. Maximum Load Allowed
for the fan/condenser pump relays is 125 va sealed, 1250 va
inrush at 115 or 230 volts.
CONDENSER FAN CONTROL FOR CONDENSER UNITS
USED WITH 30HXA UNITS The PIC control options
module and optional relay board provide two control outputs for energizing and deenergizing remote fan contactors.
If desired, wire the Circuit A main fan contactor between
TB2-1 and the unit control power neutral (TB4-2). The
Circuit B main fan contactor may be wired between TB2-6
and the unit control power neutral (TB4-2). This will cause
the main fans to be on when the compressors are on. Refer
to Fig. 17 and 18 for wiring details.
DO NOT OVERTIGHTEN THESE FITTINGS. Overtightening will result in the tube being crushed and will
cause a refrigerant system leak.
30HXA UNITS These units are shipped with a holding
charge of R-134a. Leak test and dehydrate the complete system (including both field and factory installed piping).
NOTE: Proper dehydration of 30HXA units is important to
ensure that no moisture is left in the system. Refer to the
separate section on Evacuation and Dehydration on page 19.
Copy continued on page 40.
25
UNIT
30HXC
076
086
096
106
116
126
136
VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
POWER CIRCUIT*
CONTROL CIRCUIT
ICF
MCA
MOCP
Recommended
Fuse Size
Voltage
(Single
Ph)
Min
Max
MCA
MOCP
WD
XL
187
187
414
518
342
253
253
506
633
418
123
123
100
80
121
200
200
150
110
175
175
150
125
100
150
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
307
307
148
118
169
374
299
419
207
207
342
253
253
440
115
115
126
200
200
175
150
150
150
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
266
266
165
400
187
187
414
518
342
253
253
506
633
418
148
123
111
89
135
250
200
150
125
200
200
150
125
100
175
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
307
307
148
118
169
374
299
419
207
207
342
253
253
440
140
115
140
250
200
200
75
150
175
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
305
305
190
479
187
187
414
518
342
253
253
506
633
418
181
122
126
101
153
300
200
175
150
225
225
150
150
125
175
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
354
354
172
137
195
449
359
502
207
207
342
253
253
440
169
115
158
300
200
225
225
150
200
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
347
347
216
562
187
187
414
518
342
253
253
506
633
418
219
123
143
115
174
350
200
200
175
250
300
150
175
150
200
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
405
405
197
158
223
529
423
590
207
207
342
253
253
440
202
115
178
350
200
250
250
150
225
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
397
397
247
661
187
187
414
518
342
253
253
506
633
418
219
148
153
122
185
350
250
225
175
250
300
200
175
150
225
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
426
426
207
166
234
539
431
601
207
207
342
253
253
440
202
140
190
350
250
250
250
175
225
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
417
417
259
673
187
187
414
518
342
253
253
506
633
418
219
181
165
131
199
350
300
225
175
250
300
225
200
150
225
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
452
452
219
175
248
551
440
615
207
207
342
253
253
440
202
169
204
350
300
300
250
225
250
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
440
440
273
687
187
187
414
518
342
253
253
506
633
418
263
181
184
147
222
450
300
250
200
300
350
225
225
175
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
512
512
249
199
282
646
536
720
207
207
342
253
253
440
245
169
230
400
300
300
300
225
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
496
496
308
797
26
UNIT
30HXC
146
161
171
186
206
VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
POWER CIRCUIT*
CONTROL CIRCUIT
ICF
MCA
MOCP
Recommended
Fuse Size
Voltage
(Single
Ph)
Min
Max
MCA
MOCP
WD
XL
187
187
414
518
342
253
253
506
633
418
263
219
198
158
240
450
350
250
225
350
350
300
225
200
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
542
542
262
210
299
659
547
737
207
207
342
253
253
440
245
202
246
400
350
350
300
250
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
523
523
324
813
187
187
414
518
342
253
253
506
633
418
285
197
200
160
242
500
350
300
225
350
350
250
250
200
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
591
591
287
230
325
756
605
843
207
207
342
253
253
440
266
182
249
450
300
350
350
225
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
578
578
358
944
187
187
414
518
342
253
253
506
633
418
238
285
215
172
260
400
500
300
250
350
300
400
250
200
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
624
624
302
242
343
771
617
861
207
207
342
253
253
440
219
266
267
350
450
350
300
350
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
607
607
376
962
187
187
414
518
342
253
253
506
633
418
285
285
232
185
281
500
500
300
250
400
400
400
300
225
350
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
661
661
319
255
364
788
630
882
207
207
342
253
253
440
266
266
289
450
450
400
350
350
350
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
645
645
399
985
187
187
414
518
342
253
253
506
633
418
345
285
263
210
319
500
500
350
250
400
400
350
300
250
350
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
907
907
247
198
277
716
573
795
207
207
342
253
253
440
318
266
327
450
450
450
400
350
400
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
892
892
307
893
27
UNIT
30HXC
246
261
271
VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
POWER CIRCUIT*
CONTROL CIRCUIT
ICF
MCA
MOCP
Recommended
Fuse Size
Voltage
(Single
Ph)
Min
Max
MCA
MOCP
WD
XL
187
187
414
518
342
253
253
506
633
418
443
285
303
242
367
600
500
400
300
450
600
350
350
300
400
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
1024
1024
287
230
325
756
605
843
207
207
342
253
253
440
411
266
378
600
450
500
500
350
450
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
1010
1010
358
944
187
187
414
518
342
253
253
506
633
418
476
285
318
254
385
700
500
400
300
500
600
350
350
300
450
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
1057
1057
302
242
343
771
617
861
207
207
342
253
253
440
400
266
395
600
450
500
500
350
450
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
1039
1039
376
962
187
187
414
518
342
253
253
506
633
418
514
285
335
268
406
700
500
400
350
500
600
350
400
300
450
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
1094
1094
319
255
364
788
630
882
207
207
342
253
253
440
478
266
418
600
450
500
600
350
350
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
1077
1077
399
985
LEGEND
Full Load Amps
Maximum Instantaneous Current Flow during start-up
(the point in the starting sequence where the sum of the
LRA for the start-up compressor, plus the total RLA for
all running compressors, plus the total FLA for all running fan motors is at a maximum)
LRA
Locked Rotor Amps
MCA Minimum Circuit Ampacity (for wire sizing)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
WD
Wye-Delta Start
XL
Across-the-Line Start
*Units with one MCA, MOCP, and fuse size value have one terminal
block and require one power supply. Units with one MCA, MOCP,
and fuse value for Circuit A and another for Circuit B have 2 terminal
blocks and require 2 power supplies.
Wye-Delta Start is standard. Not available in across-the-line start.
FLA
ICF
NOTES:
1. Each main power source must be supplied from a field-supplied
fused electrical service with a (factory- or field-installed) disconnect located in sight from the unit.
28
UNIT
30HXA
076
086
096
106
116
126
136
VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
POWER CIRCUIT*
CONTROL CIRCUIT
ICF
MCA
MOCP
Recommended
Fuse Size
Voltage
(Single
Ph)
Min
Max
MCA
MOCP
WD
XL
187
187
414
518
342
253
253
506
633
418
180
180
146
117
177
300
300
200
150
250
225
225
175
150
200
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
451
451
218
175
248
550
440
615
207
207
342
253
253
440
169
169
183
300
300
250
225
225
225
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
440
440
273
687
187
187
414
518
342
253
253
506
633
418
215
180
162
130
196
350
300
225
175
250
300
225
200
150
225
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
511
511
248
199
282
645
536
720
207
207
342
253
253
440
205
169
206
350
300
300
250
225
250
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
496
496
308
797
187
187
414
518
342
253
253
506
633
418
262
180
183
147
222
450
300
250
200
300
350
225
225
175
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
577
577
281
225
318
750
600
836
207
207
342
253
253
440
248
169
231
400
300
350
300
225
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
567
567
352
938
187
187
414
518
342
253
253
506
633
418
319
180
209
167
253
500
300
300
250
350
400
225
250
200
300
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
662
662
324
259
365
885
708
985
207
207
342
253
253
440
300
169
263
500
300
400
400
225
300
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
620
620
385
1042
187
187
414
518
342
253
253
506
633
418
319
215
222
177
269
500
350
300
250
400
400
300
300
200
350
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
690
690
337
269
380
898
718
1000
207
207
342
253
253
440
300
205
281
500
350
400
400
250
350
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
649
649
402
1059
187
187
414
518
342
253
253
506
633
418
319
262
239
191
289
500
450
350
250
400
400
350
300
225
350
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
728
728
354
283
401
915
732
1021
207
207
342
253
253
440
300
248
302
500
400
400
400
300
350
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
683
683
423
1080
187
187
414
518
342
253
253
506
633
418
389
262
271
216
328
700
450
400
300
450
500
350
350
250
400
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
791
791
386
309
436
1015
812
1132
207
207
342
253
253
440
369
248
343
600
400
500
450
300
400
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
817
817
507
1346
29
UNIT
30HXA
146
161
171
186
206
VOLTAGE
Supplied
Nameplate
V-Hz
Min
Max
(3 Ph)
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
575-60
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
POWER CIRCUIT*
CONTROL CIRCUIT
ICF
MCA
MOCP
Recommended
Fuse Size
Voltage
(Single
Ph)
Min
Max
MCA
MOCP
WD
XL
187
187
414
518
342
253
253
506
633
418
389
319
291
233
353
700
500
400
300
500
500
400
350
300
400
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
837
837
406
325
461
1035
828
1157
207
207
342
253
253
440
369
300
369
600
500
500
450
400
450
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
859
859
532
1371
187
187
414
518
342
253
253
506
633
418
437
295
304
243
368
700
500
450
350
500
600
400
350
300
450
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
979
979
478
382
539
1282
1025
1428
207
207
342
253
253
440
415
275
385
700
450
500
500
350
450
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
858
858
533
1398
187
187
414
518
342
253
253
506
633
418
359
437
327
261
396
600
700
450
350
500
450
600
400
300
450
115-60
115-60
115-60
115-60
230-60
104
104
104
104
207
127
127
127
127
254
15
15
15
15
15
15
15
15
15
15
1030
1030
501
401
567
1305
1044
1456
207
207
342
253
253
440
334
415
413
600
700
600
450
500
500
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
905
905
562
1427
187
187
414
518
253
253
506
633
437
437
355
284
700
700
500
400
600
600
400
350
115-60
115-60
115-60
115-60
104
104
104
104
127
127
127
127
15
15
15
15
15
15
15
15
1093
1093
529
539
1333
1066
342
342
418
418
239
239
400
400
300
300
230-60
230-60
207
207
254
254
15
15
15
15
601
601
1490
1490
207
207
342
253
253
440
415
415
453
700
700
600
500
500
600
230-50
230-50
230-50
198
198
198
254
254
254
15
15
15
15
970
970
601
1466
187
187
253
253
521
437
800
700
600
600
115-60
115-60
104
104
127
127
15
15
15
15
743
743
414
414
506
506
235
197
350
350
300
250
115-60
115-60
104
104
127
127
15
15
15
15
364
371
993
1175
518
518
633
633
188
158
250
250
225
200
115-60
115-60
104
104
127
127
15
15
15
15
292
297
796
940
342
342
418
418
285
239
400
400
350
300
230-60
230-60
207
207
254
254
15
15
15
15
410
410
1106
1299
207
207
253
253
486
415
700
700
600
500
230-50
230-50
207
207
254
254
15
15
15
15
771
638
342
342
440
440
294
252
450
450
350
250
230-50
230-50
207
207
254
254
15
15
15
15
479
400
1318
1265
30
246
261
271
VOLTAGE
Supplied
Nameplate
V-Hz (3 Ph)
Min
Max
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
208/230-60
Ckt A
Ckt B
460-60
Ckt A
Ckt B
575-60
Ckt A
Ckt B
380-60
Ckt A
Ckt B
230-50
Ckt A
Ckt B
380/415-50
Ckt A
Ckt B
POWER CIRCUIT*
CONTROL CIRCUIT
MCA
MOCP
Recommended
Fuse Size
187
187
253
253
673
437
1000
700
800
600
414
414
506
506
304
197
450
350
350
250
518
518
633
633
243
158
350
250
300
200
Voltage
(Single Ph)
115-60
115-60
342
342
418
418
368
239
500
400
450
300
207
207
253
253
636
415
800
700
800
500
342
342
440
440
385
252
500
450
450
350
187
187
253
253
724
437
1000
700
1000
600
414
414
506
506
327
197
450
350
400
250
518
518
633
633
261
158
350
250
300
200
342
342
418
418
396
239
500
400
450
300
342
342
440
440
413
252
600
450
500
350
187
187
253
253
787
437
1000
700
1000
600
414
414
506
506
355
197
500
350
400
250
518
518
633
633
284
158
400
250
350
200
600
400
500
300
207
207
253
253
748
415
1000
700
1000
500
342
342
440
440
453
252
600
450
15
104
127
15
15
15
207
207
104
104
104
254
254
127
127
127
15
15
15
15
15
230-50
207
254
15
15
104
127
15
15
382
297
1025
940
539
410
1428
1299
748
638
533
400
1398
1265
1030
743
501
371
1305
1175
401
297
1044
940
567
410
1456
1299
905
538
562
400
1427
1265
1093
743
529
371
1333
1175
423
297
1066
940
601
410
1490
1299
970
638
601
400
1466
1265
15
15
15
115-60
104
127
15
15
230-60
207
254
15
15
230-50
207
254
15
15
230-50
207
254
15
15
600
350
1282
1175
15
15
127
478
371
15
15
104
15
254
15
979
743
15
207
254
XL
15
230-60
207
WD
15
254
115-60
430
239
15
207
115-60
418
418
127
230-60
230-50
342
342
104
15
115-60
800
500
MOCP
15
115-60
1000
700
MCA
127
115-60
683
415
Max
104
230-50
253
253
Min
115-60
230-50
207
207
ICF
LEGEND
Full Load Amps
Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for
the start-up compressor, plus the total RLA for all running
compressors, plus the total FLA for all running fan motors is
at a maximum)
LRA
Locked Rotor Amps
MCA
Minimum Circuit Ampacity (for wire sizing)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
WD
Wye-Delta Start
XL
Across-the-Line Start
*Units with one MCA, MOCP, and fuse size value have one terminal block
and require one power supply. Units with one MCA, MOCP, and fuse
value for Circuit A and another for Circuit B have 2 terminal blocks and
require 2 power supplies.
Wye-Delta Start is standard. Not available in across-the-line start.
**The 30HXA186, 380-3-60 and 30HXA206-271 units have 2 terminal blocks/
non-fused disconnects and 6 parallel conductors.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a (factory- or field-installed) disconnect located in sight from
the unit.
2. Control circuit power must be supplied from a separate source through
a field-supplied disconnect (except for 380/415-50 units). An accessory control transformer may be used to provide control circuit power
from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
FLA
ICF
VOLTAGE
208/230
460
575
380
230
380/415
31
TERMINAL
BLOCKS
OR NON-FUSED
DISCONNECTS**
2
1
1
1
2
1
CONDUCTORS
6
3
3
3
6
3
076-XL
076-WD
086-XL
086-WD
096-XL
096-WD
106-XL
106-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
53.6
42.8
64.9
*
67.7
118.6
53.6
42.8
64.9
111.8
67.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8
B1
LRA
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
423
209
104
83
115
213
134
*
405
324
448
*
506
256
128
102
141
255
160
*
485
388
536
*
605
307
153
123
169
305
191
RLA
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
*
44.3
35.4
53.7
*
55.8
98.1
44.3
35.4
53.7
92.1
55.8
LRA
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109
*
330
264
365
*
344
209
104
83
115
174
109
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
32
116-XL
116-WD
126-XL
126-WD
136-XL
136-WD
146-XL
146-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
79.2
63.3
95.9
*
87.8
175.4
79.2
63.3
95.5
161.7
97.8
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8
*
94.9
75.8
114.9
*
118.8
210.0
94.6
75.8
114.9
196.3
118.8
*
94.9
75.8
114.9
*
118.8
210.0
94.9
75.8
114.9
196.3
118.8
B1
LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191
*
580
484
641
*
715
367
183
147
203
361
226
*
580
484
641
*
715
367
183
147
203
361
226
RLA
*
53.6
42.8
64.9
*
67.7
118.6
53.6
42.8
64.9
111.8
67.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
65.5
52.3
79.2
*
81.7
144.9
65.5
52.3
79.2
134.9
81.7
*
79.2
63.3
95.9
*
97.8
175.4
79.2
63.3
95.9
161.7
97.8
LRA
*
330
264
365
*
423
209
104
83
115
213
134
*
405
324
448
*
506
256
128
102
141
255
160
*
405
324
448
*
506
256
128
102
141
255
160
*
485
388
536
*
605
307
153
123
169
305
191
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
33
161-XL
161-WD
171-XL
171-WD
186-XL
186-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
86.1
68.8
104.2
*
105.8
190.6
86.1
68.8
104.2
174.8
105.8
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
B1
LRA
*
685
548
757
*
856
433
216
173
239
432
270
*
580
484
641
*
715
367
183
147
203
361
233
*
685
548
757
*
856
433
216
173
239
432
270
RLA
*
71.2
56.9
86.2
*
88.2
157.6
71.2
56.9
86.2
145.7
88.2
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
LRA
*
525
420
580
*
600
350
175
140
193
348
200
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
34
206-XL
206-WD
246-XL
246-WD
261-XL
261-WD
271-XL
271-WD
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
LEGEND
LRA
RLA
WD
XL
A1
RLA
*
86.1
68.8
104.2
*
105.8
190.6
86.1
68.8
104.2
174.8
105.8
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
LRA
*
580
484
641
*
715
367
183
147
203
361
233
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
COMPRESSOR NUMBERS
A2
RLA
LRA
*
*
44.3
330
35.4
264
53.7
365
*
*
55.8
344
98.1
209
44.3
104
35.4
83
53.7
115
92.1
174
55.8
109
*
*
71.2
525
56.9
420
86.2
580
*
*
88.2
600
157.6
350
71.2
175
56.9
140
86.2
193
145.7
348
88.2
200
*
*
86.1
580
68.8
484
104.2
641
*
*
105.8
715
190.6
367
86.1
183
68.8
147
104.2
203
174.8
361
105.8
233
*
*
103.1
685
82.4
548
124.8
757
*
*
128.6
856
228.8
433
103.1
216
82.4
173
124.8
239
212.5
432
128.6
270
B1
RLA
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
*
103.1
82.4
124.8
*
128.6
228.8
103.1
82.4
124.8
212.5
128.6
LRA
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
270
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
35
076-XL
076-WD
086-XL
086-WD
096-XL
096-WD
106-XL
106-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
77.6
62.1
94.0
*
99.2
171.9
77.6
62.1
94.0
163.9
99.2
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.5
114.7
198.2
119.9
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
B1
LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
580
484
641
*
715
367
183
147
203
361
226
*
685
548
757
*
856
433
216
173
239
432
270
*
820
656
906
*
960
518
259
207
286
485
303
RLA
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
*
64.9
51.9
78.7
*
81.5
143.8
64.9
51.9
78.7
134.8
81.5
LRA
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191
*
485
388
536
*
685
307
153
123
169
305
191
*
485
388
536
*
605
307
153
123
169
305
191
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
36
116-XL
116-WD
126-XL
126-WD
136-XL
136-WD
146-XL
146-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
*
140.7
112.4
170.2
*
178.8
311.4
140.7
112.4
170.2
295.3
178.8
*
140.7
112.4
170.2
*
178.8
311.4
140.7
112.4
170.2
295.3
178.8
B1
LRA
*
820
656
906
*
960
578
259
207
286
485
303
*
820
656
906
*
960
518
259
207
286
485
303
*
920
736
1017
*
1226
581
291
233
321
619
387
*
920
736
1017
*
1226
581
291
233
321
619
387
RLA
*
77.6
62.1
94.0
*
99.2
171.9
77.6
62.1
94.0
163.9
99.2
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.7
114.7
198.2
119.9
*
94.8
75.7
114.7
*
119.9
209.8
94.8
75.7
114.7
198.2
119.9
*
115.4
92.2
139.7
*
145.4
255.5
115.4
92.2
139.7
240.2
145.4
LRA
*
580
484
641
*
715
367
183
147
203
361
226
*
685
548
757
*
856
447
216
173
239
432
270
*
685
548
757
*
856
433
216
173
239
432
276
*
820
656
906
*
960
518
259
207
286
485
303
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
37
161-XL
161-WD
171-XL
171-WD
186-XL
186-WD
LRA
RLA
WD
XL
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
NAMEPLATE
V-Hz
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
COMPRESSOR NUMBERS
A1
RLA
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
129.6
103.6
156.9
*
161.7
286.9
129.6
103.6
156.9
267.2
161.7
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
B1
LRA
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
920
736
1017
*
1226
581
291
233
321
619
387
*
1175
940
1299
*
1265
743
371
297
410
638
400
RLA
*
106.6
85.1
129.0
*
133.4
235.9
106.6
85.1
129.0
220.3
133.4
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
LRA
*
790
630
870
*
1045
527
263
211
290
607
348
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
38
206-XL
206-WD
246-XL
246-WD
261-XL
261-WD
271-XL
271-WD
LRA
RLA
WD
XL
NAMEPLATE
V-Ph
(3 Phase)
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
208/230-60
460-60
575-60
380-60
230-50
380/415-50
A1
RLA
*
129.6
103.6
156.9
*
161.7
286.9
129.6
103.6
156.9
267.2
161.7
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
LRA
*
920
736
1017
*
1226
581
291
233
321
619
387
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
COMPRESSOR NUMBERS
A2
RLA
LRA
*
*
73.1
580
58.5
484
88.5
641
*
*
92.0
715
162.0
367
73.1
183
58.5
147
88.5
203
152.0
361
92.0
226
*
*
106.6
820
85.1
656
129.0
906
*
*
133.4
960
235.9
518
106.6
259
85.1
207
129.0
286
220.3
485
133.4
303
*
*
129.6
920
103.6
736
156.9
1017
*
*
161.7
1226
286.9
581
129.6
291
103.6
233
156.9
321
267.2
619
161.7
387
*
*
157.9
1175
126.2
940
191.2
1299
*
*
201.2
1265
349.6
743
157.9
371
126.2
297
191.2
410
332.3
638
201.2
400
LEGEND
Locked Rotor Amps
Rated Load Amps
Wye-Delta Start
Across-the-Line Start
*Units are shipped with wye-delta as standard. Across-the-line start is not available.
39
B1
RLA
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
*
157.9
126.2
191.2
*
201.2
349.6
157.9
126.2
191.2
332.3
201.2
LRA
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
*
1175
940
1299
*
1265
743
371
297
410
638
400
4. Check for a clear sight glass. If the unit is not fully loaded,
the sight glass may be flashing. This condition is normal
for a partially loaded unit. If the unit is fully loaded and
the sight glass is flashing, check EXV valve position. If
it is greater than 60% add additional charge.
NOTE: The liquid charging method is recommended for complete charging or when additional charge is required.
When charging, circulate water through the condenser and cooler at all times to prevent freezing. Freezing
damage is considered abuse and may void the Carrier
warranty.
DO NOT OVERCHARGE system. Overcharging results in higher discharge pressure with higher cooling
fluid consumption, possible compressor damage, and higher
power consumption.
30HXC UNITS The 30HXC units are shipped from
the factory with a full charge of R-134a. Unit should not
need to be charged at installation unless a leak was detected
in Step 6 Leak Test Unit section. If dehydration and
recharging is necessary, use industry standard practices or
refer to Carrier Standard Services Techniques Manual or the
Controls, Start-Up, Operation, Service, and Troubleshooting
Guide as required.
30HXA UNITS The 30HXA units are shipped with a holding charge of R-134a. The complete charge for the 30HXA,
the remote condenser(s), and interconnecting piping must be
field supplied.
To charge the 30HXA systems:
1. An initial refrigerant charge must be added after evacuation to allow the unit to start. Add approximately
2 lb/nominal ton (0.9 kg/nominal kW) liquid refrigerant
charge to the condenser. This amount of charge should be
sufficient to allow the unit to start. The approximate system charges are shown in Table 6 and cooler refrigerant
capacity is shown in Table 7.
2. Raise the compressor discharge to approximately 125 F
(51.7 C) saturated discharge temperature (185 psig
[1276 kPa]) by throttling the condenser air (or water)
intake.
3. Add liquid charge into the cooler until there is approximately 18 to 20 F (10.0 to 11.1 C) of system subcooling
(saturated discharge temperature actual temperature
entering the electronic expansion device [EXD]). When
adding charge, use the 14-in. Schrader-type fitting
located on the tube going into the bottom of the cooler.
This fitting is located between the EXD and the cooler.
When adding charge during unit operation, always use
this port so that the cooler liquid level sensor can detect
the additional charge and adjust the EXD valve position.
NOTE: Electronic Expansion Device (EXD) refers to EXV
(Electronic Expansion Valve) (076-146 units) or Economizer (161-271 units).
CIRCUIT A
CHARGE
lb
kg
75
34.0
94
42.6
114
51.7
134
60.8
137
62.1
137
62.1
147
66.7
161
73.0
190
86.2
154
69.9
186
84.4
224
101.6
288
130.6
311
141.1
335
152.0
CIRCUIT B
CHARGE
lb
kg
75
34.0
80
36.3
80
36.3
80
36.3
95
43.1
116
52.6
125
56.7
132
59.9
132
59.9
86
84.4
86
84.4
169
76.7
169
76.7
168
76.2
165
74.8
CKT
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
TOTAL
VOLUME
3
Ft
m3
2.538
0.072
2.538
0.072
2.813
0.080
1.929
0.055
3.945
0.112
2.705
0.077
4.044
0.115
2.810
0.080
3.777
0.107
2.625
0.074
5.297
0.150
3.682
0.104
4.490
0.127
4.490
0.127
4.068
0.115
4.068
0.115
7.523
0.213
4.946
0.140
7.090
0.201
4.661
0.132
REFRIGERANT
CAPACITY
lb
kg
161
73.0
161
73.0
178
80.7
122
55.3
250
113.4
172
78.0
256
116.1
178
80.7
240
108.9
167
75.8
336
152.4
234
106.1
285
129.3
285
129.3
258
117.0
258
117.3
477
216.4
314
142.4
450
204.1
296
134.3