You are on page 1of 33

OPERATION AND MAINTENANCE MANUAL

HOTSV 69000/145
TRANSFORMER 132 / 33 / 11.5 kV VOLTAGE RATIO 63 / 50 / 25 MVA RATED POWER
1

OPERATION AND MAINTENANCE MANUAL

Table of contents
Table of contents ..................................................................................................................................2 1. General .........................................................................................................................................4 1.1 Safety instructions ......................................................................................................................4 1.2 Responsibility of the personnel ..................................................................................................5 1.3 Safety instructions regarding the oil ..........................................................................................5 1.4 Guarantee ...................................................................................................................................6 1.5 BKT code system .......................................................................................................................6 2. Identification ................................................................................................................................7 3. Technical data of the transformer.................................................................................................8 4. Transportation ..............................................................................................................................9 General .............................................................................................................................................9 5. Lifting.........................................................................................................................................11 5.1 Lifting of total weight ........................................................................................................11 5.2 Lifting of the active part.....................................................................................................11 5.3 Lifting of the bushings .......................................................................................................12 6. Storage........................................................................................................................................13 6.1 General .....................................................................................................................................13 6.2 Storage with oil ........................................................................................................................13 6.3 Storage without oil ...................................................................................................................13 6.4 Storing instructions of bushings...............................................................................................14 7. Commissioning...........................................................................................................................15 7.1 Assembly............................................................................................................................15 7.2 Control of painting .............................................................................................................16 7.2 Oil filling preparation.........................................................................................................16 7.4 Oil filling ............................................................................................................................16 7.4.1 Oil sampling, oil preparation......................................................................................17 7.4.2 Air release ..................................................................................................................18 7.5 Calibrations ........................................................................................................................19 7.5.1 Buchholz-relay ...........................................................................................................19 7.5.2 Oil- and winding temperature indicators........................................................................20 7.5.3 Air dryers....................................................................................................................20 7.5.4 Oil level indicators .....................................................................................................20 7.5.5 Overpressure protection of the transformer ...............................................................20 7.6 Control of the on-load tap-changer ....................................................................................21 7.7 Activities before energizing ...............................................................................................21 7.8 Energizing ..........................................................................................................................23 8. Operation....................................................................................................................................24 8.1 Operation above the rated voltage......................................................................................24 8.2 Operation above the rated current ......................................................................................24 8.3 Voltage regulation ..............................................................................................................24 8.4 Parallel operation ...............................................................................................................24 8.5 The circuits of the auxiliaries (cooling, protections, current transformers).......................24 8.6 Signals ................................................................................................................................25 8.7 Troubleshooting .................................................................................................................26 8.8 Emergency actions .............................................................................................................26 9. Maintenance ...............................................................................................................................27 9.1 Maintenance work without lifting of the active part..........................................................27

OPERATION AND MAINTENANCE MANUAL


9.1.1 Oil level indicators .....................................................................................................27 9.1.2 Air dryer .....................................................................................................................27 9.1.3 Thermometers.............................................................................................................27 9.1.4 Buchholz relay............................................................................................................28 9.1.5 Oil pipes and fittings ..................................................................................................28 9.1.6 Cooling .......................................................................................................................28 9.1.7 Bushings .....................................................................................................................28 9.1.8 Tank, earthing screws.................................................................................................28 9.1.9 Gaskets .......................................................................................................................28 9.1.10 Outside painting .........................................................................................................29 9.1.11 Deaerating ..................................................................................................................29 9.1.12 Tests ...........................................................................................................................29 9.2 Maintenance work with lifting of the active part ...............................................................29 9.2.1 Checking of the winding ............................................................................................30 9.2.2 Contaminations...........................................................................................................30 9.2.3 Insulating spacers .......................................................................................................30 9.2.4 Connections................................................................................................................30 9.2.5 Tap-changer................................................................................................................30 9.2.6 Bushings .....................................................................................................................30 9.2.7 Tank, conservators .....................................................................................................30 9.2.8 Assembly....................................................................................................................31 9.2.9 Test .............................................................................................................................31 9.3 Periodicity of maintenance work and checking of the oil transformers.............................31 9.4 Spare parts ..........................................................................................................................32

OPERATION AND MAINTENANCE MANUAL

1. General
1.1 Safety instructions
All personnel involved in installation, commissioning, operation, maintenance or repair of the equipment must: be suitably qualified and strictly observe these Operating Instructions. Improper operation or misuse can lead to a reduction in the efficiency of the equipment damage to the equipment and property of the user serious or fatal injury. Safety instructions in this manual are presented in three different forms to emphasize important information.

This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury.

This information indicates particular danger to the equipment or other property of the user. Serious or fatal injury cannot be excluded.

These notes give important information on a certain.

OPERATION AND MAINTENANCE MANUAL

1.2 Responsibility of the personnel


All site personnel have to wear appropriate personal protective clothing and equipment to suit the working environment. All tools and equipment must be well maintained and suitable for the application. The delivery of all materials and the subsequent disposal of all wastes shall be carried out in compliance with the current regulations. Follow all relevant local and international regulations at all times. Never exceed the operating limits stated in the delivery documents and on the rating plates. Do not alter or modify a unit without first consulting with the competent supplier. Use only factory authorized replacement parts and procedures. Before applying any supply voltage (power, motor, control, auxiliary etc. circuits) check whether the voltage and the output of the supply are in accordance with the required values. Do not climb to the cover before the transformer would be out of operation. For climbing to the cover a ladder is welded on the tank wall if any. Be careful on it to avoid any accident. Be careful on the cover to avoid: any accident by stiffeners, cables or tubes falling to the ground To avoid any injury do not remove the cover of the OLTC drive shaft. Must not stay under the lifted parts of transformer!

1.3 Safety instructions regarding the oil


The oil cannot be considered as hazardous material, however it shall be handled in accordance with current valid industrial hygiene and safety regulations.

The local management shall inform the operation labour about any hazards which could affect the health and safety requirements.

First aid measures: Inhalation: Skin contact: Eye contact: Ingestion:

Fresh air Remove contaminated clothing. Wash skin with soap and water Rinse with plenty water On occurrence of pain or redness, consult a doctor. Rinse mouth and give water to drink. Obtain medical advice if larger amount has been swallowed.

Fire fighting measures: The oil is flammable and thus it shall be kept away from naked flames or other sources of ignition. Extinguishing media: Carbon dioxide, dry chemical or foam.

OPERATION AND MAINTENANCE MANUAL


Do not use water jet. Water can be only used for cooling containers and objects in the area of fire. Ecological instructions: Do not allow the oil to escape into canalisation system, waterways, ponds or soil. Collect the accidental deposits as far as possible mechanically and bind the remains with sand or appropriate absorbent material and collect. Environmental instructions The dangerous wastes must be separeted, stored and transported according to the environmental specifications of the country and company where the transformer is applied. The dangerous wastes must be collected separatelly. The content of the vessels shall be indicated (in case of European countries EWC number must be marked). The dangerous waste must be given to an authorized carrier with required documents. Reffering documents shall be filed. Practically the following dangerous wastes can occur:

Dirty transformer oil Oily cloth/ sawdust /perlite Painty cloth Painty package

(EWC 13 03 07) (EWC 15 02 02) (EWC 15 02 02) (EWC 15 01 10)

1.4 Guarantee

During the guarantee period, draying, trearment in oil and all operations that act tank opening must be carried out by skilled personnel of Ganz Transelectro, otherwise the guarantee will not longer apply.

1.5 BKT code system


The important parts of the transformer are identified by a BKT code system. All BKT code using in this manual can be found on the Outline drawing.

Give us the BKT code and the exact type of any kind of parts if you would like to know more information about the product or ask some spare parts for trouble-shooting.

OPERATION AND MAINTENANCE MANUAL

2. Identification
Transformer type designation: Product serial number: HOTSV 69000/145 136482 136483 136484 136485

Give us the exact type and serial number if you would like to know more information about the product or ask some spare parts for trouble-shooting. The type and the serial number can be seen on the rating and connection plate.

Year of Manufacture: Manufacturer:

2007 Ganz Transelektro Electric Co. Ltd. H-1095 Budapest Mrissy u. 7. Telephone: (36-1) 483-6754 Telefax: (36-1) 483-6751

Applicable standards: IEC 60076 IEC 60076-4 IEC 60076-7 IEC 60076-10 IEC 60137 IEC 60044-1 IEC 60214 IEC 60214-2 IEC 60289 EN 60296 IEC 60616 IEC 60815

OPERATION AND MAINTENANCE MANUAL

3. Technical data of the transformer


Main characteristics: Three phases, core type, ONAN/ONAF cooled, 130 / 33 / 11.5 kV voltage, 63 / 50 / 25 MVA rated power oil-immersed transformer for outdoor installation with concentric copper winding arrangement. The iron core is made of cold rolled grain-oriented electrical steel. The on-load tapchanger is connected to the high voltage windings. The transformer is supplied with every fitting, which is necessary for transportation, operation and protection. The high voltage terminals are fitted with oil-air bushings. The medium and low voltage terminals are fitted with oil-air bushings and these bushings are installed in air insulated cable box. The insulation of the magnetic sheets is carlit. The joint of the limb -and yoke sheets is made occurred by overlap with 90 shearing. Because of the low noise level and core losses, the overlap of the magnetic sheets is Step-lapped. The tank and cover are welded steel-structure, which are able to resist 100 % internal vacuum, as well as stresses occurring during transportation (e.g. railways, roads). There are four jacking pads for hydraulic lifting. There are pulling lugs for lengthwise and crosswise moving, too. There are 4 ground screws on the lower parts near to the corners of the tank. Main electrical data can be seen in the Data sheet. Main mechanical data can be seen on the Outline drawing.

The test reports for these transformers are attached to the Operation and maintenance manual.

We cannot accept liability and exclude any guarantees for damage to equipment, which is due to the improper operation of the transformer!

OPERATION AND MAINTENANCE MANUAL

4. Transportation
General
The transformer was designed for road or railway transportation. It can be transported by means of trailer of adequate load carrying capacity. Main components have to be dismounted in order to decrease the size and weight of the transformer body.

All information can be found on the Outline drawing for transportation.

Before transportation dismount any During main part the transformer oparate valves and gauges the of transporatation the you tank have have to be filled the with nitrogen. according to the commission of the Valve location and function plate. The parts to be transported separately are listed on the Outline drawing for transportation. After careful sealing all the joining openings shall be closed by means of blank plates. Similarly all detached parts shall be closed. Attach proper labels on the disassembled parts for clear identification. Use packing adequate for the application. Make sure that the quantity of oil specified for the complete oil filling of the transformer is either transported with the transformer or available at the site of assembly.

During the transporatation the tank have to be filled with nitrogen.

Because of the heavy mass and the position of centre of gravity resulting from the relatively high construction of the transformer as well as the dynamic shocks occurring in the course of transportation, the transformer shall be firmly anchored with wire ropes and - if necessary - braced with beams.

Centre of the gravity is marked on the outline drawing for transportation. In order to prevent the possible damages, the more delicate parts of the transformer shall be wrapped and/or protected with proper covers.

OPERATION AND MAINTENANCE MANUAL

Impact indicators or / and one impact recorder will be used to indicate if there was any problem during transport or handling of transformer. Impact indicator: 3 pieces impact indicator will be fixed by glue to the tank body to indicate whether the transformer got any big shock during the transportation. They are in positions according to 3 main directions. The indicated minimum shock acceleration is 5g (50 m/s2). Impact recorder: The impact recorder is installed on the cover. It is firmly secured to the transformer for transport and handling analysis. This instrument is a mechanical recording accelerometer designed to record shock and impact from all directions. The number of impacts, the magnitude, the direction and the time are recorded on a chart paper by means of three independent styluses as follows: Stylus x lateral shock Stylus y longitudinal shock Stylus z vertical shock Operation: Check the battery. (The maximum recording time of about 180 days can be expected if the battery is fully charged) Install the chart paper. Remove the stylus guard, set the time and turn the recorder "on". Finally close and lock the cover. Note: the chart paper time is marked in one-hour intervals. Acceptance criteria: 1. The instrument shall be opened and the graphics shall be evaluated in the presence of the representative of the purchaser and the supplier. 2. The maximum shock acceleration shall not be higher than 5g (50 m/s2) horizontally or transversally or vertically. If the acceleration has more than one component in various direction, then the 5g applies to the resultant acceleration unless otherwise agreed between the purchaser and the supplier. 3. The impact recorder is and shall remain the Manufacturer's property. PLEASE RETURN IT.

10

OPERATION AND MAINTENANCE MANUAL

5. Lifting

Must not stay under the lifted parts of the transformer! Lifting can be performed after the location and fixing of the suitable rope on the component considering the gravity centre of the lifted part. All heavier parts of the transformer are provided with lifting lugs for easy moving and handling.

5.1 Lifting of total weight


Higher lifting of the transformer completely assembled is not possible. For higher lifting of the transformer not completely assembled (without conservator, pipe lines and bushings but with oil) it is provided with four lifting pins welded onto the lifting ribs on the tank wall (BQ 030). Smaller lifting of the transformer completely assembled and full of with oil is possible. There are four hydraulic jacking pads (BQ 029) at the corners of the transformer tank. Lifting weight filled with oil is acc. to the Outline drawing.

5.2 Lifting of the active part


For lifting the active part of the transformer, the drained conservator and its pipes about the cover have to be dismounted. After these the bevel gear and the driving shaft of the tap-changer has to be disassembled. After these pull down all cable and thermometer connections. Before lifting of the active part, the oil below the level of the cover has to be drained from the transformer. The untanking of the active part can be performed by means of four lifting lugs (BQ 031) provided welded on the cover.

Lifting of the active part shall be acc. to the sketch marked onto the Outline drawing! If you do not use advisable long rope the cover and the active part will damage!

All information regarding the lifting of the active part can be seen on the outline drawing.

11

OPERATION AND MAINTENANCE MANUAL

5.3 Lifting of the bushings


Before you dismount one of the bushings read carefully the catalogues of the bushings.

Catalogues regarding the above mentioned main components are attached to the Operation and maintenance manual.

All information regarding the lifting of the bushings can be seen on the outline drawing.

12

OPERATION AND MAINTENANCE MANUAL

6. Storage
6.1 General
Arriving at the site of installation the transformer and its fittings shall be carefully examined to detect casual damages that could have occurred during transportation. For this the main body and the packing should, whenever possible, be arranged on a covered and dry place. If there is no possibility to use a covered place, the packages shall be protected with canvas, at least the bushings and insulating material shall be maintained in a closed, dry place. When a transformer is received from the manufacturer, it should be preferably placed in its permanent location to minimize handling. All the parts that are not fitted should be unharmed, too. These are to be stored on wooden pillows in covered store protected against humidity. The components can be stored in transport packing provided it is considered in good condition. If the bushings must be transported or stored for longer period it is highly recommended to protect both bushing ends with the plastic covers in which they were originally wrapped and to use the packing. Check all parts of the transformer also for mechanical damages. If the transformer is out of operation for more than two weeks, the heater of the motor drive, control box and marshalling kiosk / terminal box must be connected and put in service in order to prevent condensed moisture inside the cabinet. If this is not possible, bags with at least 0.6 kg silicagel must be put into the cabinet.

6.2 Storage with oil


For long period storage it is highly recommended to fill the transformer with oil and the conservator is fitted. In the course of longer storage check the transformer monthly whether the oil level is corresponding to the level relating to the ambient temperature and the air-dryer is effective.

6.3 Storage without oil


For short period the transformer can be storied without oil but filled with nitrogen. Not more than four weeks it can be storied without any special action. Only the pressure of the nitrogen will be checked.

Before a longer storage more than four week with nitrogen starts you ask the recommendation of the manufacturer.

Checking of the oil level or pressure of the nitrogen is very important! During the inproper storage moisture gets into the tank. The insulation level of the active part will decrease! In this case you have to treat the oil!

13

OPERATION AND MAINTENANCE MANUAL

6.4 Storing instructions of bushings


Ordering the bushings, it has to be considered, that the storing conditions recommended by the supplier cannot always be assured (max. 70 % relative humidity and 15-30 C temperature). Consequently, the packing has to be suitable for storage in a roofed (but not closed) space for half year. Suppliers (Haefely, Micafil, Felten, ABB etc.) have to transport the bushings with protection against humidity. Above 52 kV the bushings are generally packed horizontally or the head of the bushing is raised by 5. The bottom parts are protected by slab covering, which is filled with oil and screwed to the flange. Under 52 kV the bushings are packed in the transporting box cushioned by chips. The lower parts of the bushings are protected against humidity by sheathing. They are packed into plastic foil. Store the bushings in the original transporting boxes without disjunction of the packing. If the supplied protection or the protective covering is injured, the storeman has to arrange the reconstruction of the same as original protection. In case of repairing, proceed as follows: Replace the damaged porcelain insulator, if any. Clean the complete surface of the bushing by a clean, dry and soft raggy material. Plastic foil can be used for protective covering, which is rolled up to the neck of the flange by self-adhesive plastic strip, ensuring the perfect sealing. Damp-asbsorbing silicagel has to be placed into the protective covering. Completing the above actions, bushings have to be put on balks with suitable bedding for the neck of the flange and the outlet-head. The bedding surface has to be varnished by felt or soft rubber sheet. If the bushings must be transported or stored for longer period it is highly recommended to lift the head by 5 compared to the flange. In case of such a storage, before using, the bushings has to be dried in vertical position at approx. 60C for more days. For the right drying technology refer to the Transformer Division of Ganz Transelektro. The bushings have to be stored in their original transport boxes till the starting of assembly. The protection can only be removed directly before mounting. If the bushings must be stored for longer period it is expedient to fit up the H.V. bushings on the transformer.

14

OPERATION AND MAINTENANCE MANUAL

7. Commissioning
7.1 Assembly

Before starting the operation materials and tools needed for possible danger averting must be prepared. Tray must be placed under the location of possible oil leakage. To clean the little oil spots, cloth, perlite, broom and shovel shall be put out. The clothes and sand used for oil absorbing are dangerous wastes. They must be collected separately, transported and handled properly after finishing the operation. A solid foundation suitable to the total transformer mass shall be provided for assembly. On the site, where the transformer will be installed the air shall be able to circulate freely to allow the cooling system to actuate appropriately during operation and the temperature to remain within the limits foreseen in the project.

Minimum 800 mm space will be between the transformer and any wall. In default whereof the cooling of the tranmsfomer will not be satisfying. Put the transformer on its foundation and remove the protecting covers, the packing and banding materials. The radiators, the conservator and the pipes shall be perfectly clean and dry, the devices shall be unharmed before assembly. Before fitting each part of the transformer each device shall be thoroughly checked and cleaned. If compressed air is available, all groves, corners, holes and other cavities shall be blown off. The insulators and live metallic parts are wiped with specified rags and cleaners. All parts removed for transportation are identified by appropriate marks, which are reproduced in the shipping lists. These are to be installed as shown on the overall drawing. The insulating oil delivered for the transformer is acc. to IEC 60296. Before filling of the transformer the oil must be properly tested. Remove the blind flanges one by one and fit all the components. During these operations take good care to avoid moisture, any type of contamination, foreign object to get into the transformer through the opening just free for assembly.

Be careful! Do not drop down any object into the tank! Metal parts cause short circuit in the winding, connection or on the surface of the core.

15

OPERATION AND MAINTENANCE MANUAL


The gasketed flanges are to be overbridged for earthing. Make the earthing link of the transformer to either of the earthing screws provided on both sides of the tank at the bottom. Finally make the connections of high and low voltage cables and those of the auxiliary cables.

Complete the oil filling of the transformer, the tap changer. Release the trapped air. Set the oil levels in the conservator chambers to the actual ambient temperature.

Set all the valves according to the instruction of the Valve location and function plate!

7.2 Control of painting


Check the transformer carefully. If there are mechanical failures, painting defects, repair the failures and the painting defects, replace the fixing elements if there is any corrosion on them. Do not put the transformer into operation without repairing the failures.

7.2 Oil filling preparation

Before starting the operation materials and tools needed for possible danger averting must be prepared. Tray must be placed under the location of possible oil leakage. To clean the little oil spots, cloth, perlite, broom and shovel shall be put out. The clothes and sand used for oil absorbing are dangerous wastes. They must be collected separately, transported and handled properly after finishing the operation. Remove the blind flanges one by one and fit all the components. During these operations take good care to avoid moisture, any type of contamination, foreign object to get into the transformer through the opening just free for assembly. The value of the vacuum in the transformer tank under oil filling shall be 667 Pa (5.0 mm Hg).

7.4 Oil filling

Before starting the operation materials and tools needed for possible danger averting must be prepared. Tray must be placed under the location of possible oil leakage. To clean the little oil spots, cloth, perlite, broom and shovel shall be put out. The clothes and sand used for oil absorbing are dangerous wastes. They must be collected separately, transported and handled properly after finishing the operation.

16

OPERATION AND MAINTENANCE MANUAL


If the transformer is not filled with oil completely, proceed as follows: Open the upper and lower butterfly valves (AB 230) of radiator groups. These are opened when marking on the shaft ends are collinear with the axis of pipe. Drums of oil are provided for each transformer for the first filling in of the adequate oil level. The oil shall conform to IEC 60296. In case of extra oil is required the vast majority of other insulating transformer oil of mineral oil basis satisfying the requirement of IEC 60296 can be used. In case of doubt make use of a mixing test carried out by a special laboratory or refer to the Transformer Division of Ganz Transelektro. Before being used the drums shall stand for minimum 2 days without moving. Before the oil utilization it must be tested for electric strength, moisture content and gas content. The oil before filling in to the transformer shall comply with the values below: Electric strength: Moisture content: Gas content: > 200 kV / cm < 15 p.p.m. (measured acc. to IEC 60814) acc. to IEC 60422

In case the results do not reach the specified minimum values, the oil shall accordingly treated before its utilization. For this use a filter and processing equipment type Micafil or certified equivalent. Take care that the oil quality is not effected by dirty filling devices, and hoses. Fill the transformer with oil of adequate quality via the oil filling pipe of the conservator. The oil filling should be continued until the oil-level indicator shows the highest level. In this way the conservator will be nearly full. This can provide enough oil for deaeration. If the oil level decreases for any leakage, check the place of leakage and stop the untightness. The separated oil space of the tap-changer - if any - can be filled through the filling opening of the conservator compartment connected to the tap-changer. Proceed with the filling as far as the oil level indicator of the separate oil space will show the level relating to the ambient temperature. Then close the oil filling valve. 7.4.1 Oil sampling, oil preparation

The dirty oil arising during the operation is dangerous waste. It must be collected separatelly, transported and handled properly after finishing the operation. Oil sampling is made through oil sampling valves (M12 and DN25). Oil samples have to be taken from the transformer tank and from one radiator group, separately into sampling vessels. On the tank you find the oil sampling valve(s) shown by the Outline drawing On the radiator the sampling valve (AB630) is installed onto the bottom collecting pipe of the radiator. Oil sampling procedure: Clean the outside part of valves carefully to avoid oil contamination in the vessel. To ensure the cleanliness 4-5 litres oil has to be let out. Part of this oil is used to rinse the cleaned, dry vessel two or three times, then fill the vessel with bubble free, foamless oil until completely full, taking care for cleanliness to avoid dust contamination and moisture. Cover the vessel with a clean, dry glass plate and leave it until no more air bubbles are released. The oil has to satisfy the IEC 60296 standard. If the oil test shows that there is moisture in the oil 17

OPERATION AND MAINTENANCE MANUAL


for some reason, then the oil has to be treated. In this case the oil has to be suctioned through the bottom draining valve (AA355), then through the oil filter and treatment equipment, heated to 5055oC with the heater of the equipment, the oil has to be refilled into the transformer through the oil filling valve (AA356). The treatment may be finished if the breakdown withstand strength of oil is higher than 200 kV/cm and the oil satisfies the requirements of the relevant standard. In case of local assembly the transformer can be energized if the oil sampling and the oil examination was done according to the above description, and the oil property is suitable for the specified values, furthermore, less than a month passed from oil sampling to energizing. If more than a month passed, the oil sampling and examination has to be repeated. If the oil properties do not suit the description, the oil has to strain and vacuum dry to achieve the specified values. 7.4.2 Air release After filling the transformer with oil the transformer has to be deaerated. If oil filtering - to remove impurities and moisture - was necessary, the deaeration should be repeated after this procedure. Open all the vent openings (AB 600), on the cooler-groups (installed the bottom collecting pipe of the radiator), on the pipes if any, on the head of the tap-changer, on the relays, on the bushings if any and release the trapped air. The deaeration can be finished if foamy oil, air-bubbles stop flowing out of openings. Then the transformer should rest for a period of 24 hours to enable any trapped air to be released. Then it is necessary to deaerate again. During resting do not switch-on the transformer. The deaerating is good, if air does not accumulate at the venting places at 40 C oil after 6 hours, at min. 10 C oil after 72 hours. After deaerating any missing oil must be replaced through the conservator.

Do not forget to close the deaeration openings! The oil will flow through the opened vent hole! Check if the oil levels in the conservator chambers are corresponding to the actual ambient temperature. Add or drain oil as necessary.

18

OPERATION AND MAINTENANCE MANUAL

7.5 Calibrations
After connecting the protection relays and other auxiliary devices, they have to be actuated.

It is very important to make sure their right operation! Improper operation causes damage of the transformer! 7.5.1 Buchholz-relay The transformer tank is protected by a Buchholz-relay. The relay is mounted into a pipeline, which places between the tank and the conservator. The relay has 2 floats. The upper float signals gasforming and oil bleeding. Smaller faults cause weaker gas-forming, bigger faults cause more increased gas-forming. Therefore, the lower float operates in case of bigger oil bleeding and more increased gas-forming, furthermore gives tripping signal. The bigger internal faults cause very strong gas-forming and/or oil stroke towards the conservator, which also gives tripping signal by moving of a sheet (placed in the oil-flow). That oil flow velocity may be set, where the relay switches. On the site of the transformer can be found an inspection cover whereby may be checked the oil level in the relay. The gathered gas in the relay may be let out and examined.

Connect the trip signal of the Buchholz relay to the transformer main circuit breaker or to the protection system! Checking of the Buchholz-relay: The upper cap has to be taken off. Unscrew the cover of the Buchholz-relay, and press the protruded actuating rod 10 mm down. At this time, the contact of the upper float shall be closed and gives alarm. After this, further 10 mm press down, then the contact of the lower float shall be closed and gives alarm. The contact of the upper float has to be used for alarm, the contact of the lower float has to be used for tripping. Checking of the Buchholz-relay may be occurred by air pumping across (E) valve. In both case can be followed the moving of the floats across the inspection covers on the site of the relay. The gathered gas amount in the relay for alarm: 200 cm3 Tripping occurs only if the gas-forming is continued or/and the velocity of the oil-flowing from the tank to the conservator exceeds 1 m/s.

19

OPERATION AND MAINTENANCE MANUAL


7.5.2 Oil- and winding temperature indicators

Connect the trip signal of the oil and winding temperature indicator to the transformer main circuit breaker or to the protection system! Alarm and trip signals are acc. to the Cooling control drawing. The built-in adjuster unit of the winding temperature indicator forms the winding temperature by the sign of the current transformer. For connection see the Cooling control drawing. 7.5.3 Air dryers Check the silicagel filling of the air dryer. If the filling has turned green, then replace the filling with new one or empty the air dryer and dry the silicagel for several hours at 110-115C temperature, until it turns evenly orange. Then mount the air dryer with the renewed filling back to its pipe. Check the lower oil seal. If it is not enough, fill it to the red marking line. 7.5.4 Oil level indicators The oil level indicators of the conservators are provided with two microswitches, which can be used for signalling when the oil level reaches the maximum and the minimum levels respectively. It is calibrated to +20 C.

Connect the alarm signal of the oil level indicators to the protection system! 7.5.5 Overpressure protection of the transformer A pressure relief device is placed on the cover of the transformer for releasing the overpressure due to a possible internal failure. It is essentially a springloaded valve. The valve operation is effected when the opening pressure exceeds the value of 0.5 bar. The pressure relief device is provided with a sealed, weather-proof alarm switch. A bright colour indicator pin on the top shows that unit has functioned. The pin may be reset by manually pushing it downward.

Connect the trip signal of the pressure relief devices to the transformer main circuit breaker or to the protection system!

20

OPERATION AND MAINTENANCE MANUAL

7.6 Control of the on-load tap-changer


Check the positions and the assembling of the driving shafts (between the tap-changer and drive control box). The tap-position mark has to be seen same in the drive control box and the tapchanger head. The motor drive control complies to the principle of step by step switching, i.e. one single control impulse starts each switching step.

See also the Technical Instruction of the tap changer and the motor drive. If the motor drive is out of operation for more than two weeks, the heater must be connected and put in service in order to prevent condensed moisture inside the cabinet. If this is not possible, bags with at least 0.6 kg Silica gel must be put into the cabinet.

7.7 Activities before energizing


Before energizing the transformer the following tests and controls must be performed:

The checklist is attached after this Manual.

a. The bushings have to be carefully cleaned. b. Check the right phase sequence compared to the network. c. Measure the insulation resistance of transformer windings. During the measurement the
terminals shall not be connected to the network. The insulation resistance measurement shall be performed with a 5 kV insulating tester. The winding, which is not tested, must be earthed together with the tank. The results of measurements made at the manufacturer's test room (see Test Certificate) and on the site have to conform. The values of insulation resistance varies highly in function of time and temperature. Apply the durations indicated in the Test Certificate (15 s and 60 s). For temperature correction use the formula below: (Where C (T) is the correction factor.) R (20 C) = R (T C) x C (T C) The C (T) function can be given by the approximate equation as follows: C (T) = 0.3 x e 0.06.T

d. Voltage ratio measuring by 400 V to verify flowing of the sequence of the regulating taps.
Check, whether the tapping voltages are in accordance with the voltages indicated on the connection scheme. If there are any deviations, the operator must inform the manufacturer. e. Check the right operation of the motor drive, if applicable. f.Check the right operation of the tap-changer, if applicable.

21

OPERATION AND MAINTENANCE MANUAL


g. Check the right connection of cables mounted onto the transformer, into the protecting and indicating equipment and into the terminal box. h. Check if the dielectric strength of the oil is adequate. i. Check if the oil levels in the conservator are correct. Check if the air-dryer is filled-up completely with silicagel. The colour of silicagel is orange if it is dry. If the filling is oily, replace it with new filling. Check the lower oil seal, that the oil volume is enough or not. If the oil level does not reach the red line, then oil must be added. j. Make sure that all valves between the conservator and the tank and the cable boxes respectively, if any, are open. k. Make sure that all valves between the tank and the radiator banks are open. Make sure that all draining valves, filling valves, air release openings and sampling valves are closed. l. Make sure that the thermometer pockets are full of oil. m. Check if all bushings are fully vented and are duly clean. n. Check the right operation of the auxiliary control box. o. Check if there are connected loads to the current transformer secondaries, otherwise they shall be maintained in short circuit. p. Check if the contacts of Buchholz relays, protecting relay, oil level indicators, thermometers and other relays act correctly on the alarm and tripping circuits. q. Check the wholeness of protective links of mounting panels, devices, cable armouring and equipment placed on the transformer. r. Check the connection of earthing terminals and links of transformer. Check carefully the tightening of screwed connections. s. Make sure there are no foreign materials on the transformer, specially on the cover.

22

OPERATION AND MAINTENANCE MANUAL

7.8 Energizing
Safety regulations

During energizing follow the safety regulations of country and local authority. Improper procedure before or during the energizing causes the damage of the transformer or injury of the operating labour The setup procedure and the operation must be performed by personnel having qualification and authorization. The results of technical checking and tests must be recorded.

Before putting the transformer into operation set all of protection and control equipment to be ready for operation. In case of differences detected between the results recorded and the values specified inform the Transformer Engineering Department of GANZ TRANSELEKTRO.

The voltage has to be switched on to the transformer -if it is possible- from the High Voltage side.

23

OPERATION AND MAINTENANCE MANUAL

8. Operation
The transformer is designed for the continuous operation at rated voltage and current assigned to each tapping position as specified in the data sheets in normal service conditions. Wave shape of the supply voltage has to be practically sinusoid, its frequency 50 Hz. The three phases has to be practically symmetrical.

8.1 Operation above the rated voltage


The permitted maximum continuous operation voltage is 105% of the rated voltage referring to the actual tap-position.

8.2 Operation above the rated current


The general limitations and effects of loading beyond the nameplate rating shall be considered as specified in the Loading Guide for Oil-immersed Power Transformers issued by IEC 60076-7.

8.3 Voltage regulation


The voltage regulation of the transformer is realized by means of a motor-driven on-load tap changer installed in the tank. The on-load tap changer has the function to change the transformation ratio by adding the turns of the regulation winding to the turns of the high voltage winding while maintaining the load conditions of the transformer unchanged. The type of the on-load tap changer is acc. to the Outline drawing or Rating and data plate. The motor drive control complies to the step-by-step switching, i.e. one single control impulse starts each switching step. After giving a control impulse the step movement will be commenced and it will be accomplished automatically without any interruption. The next control impulse is only observed with the control system being in rest position again. The type of motor drive unit is acc. to the Outline drawing. The on-load tap changer driven by the motor drive can be operated in the following ways: - by hand with crank kept in the motor drive - with push-buttons located in the motor drive - with push-buttons located in the remote control panel (if provided) - automatically using an Electronic Voltage Regulator (if provided) The "raise" or the "lower" control signal is generated by the voltage regulator and issued to the motor drive whenever the measured voltage of the network deviates from the preset conditions. If the motor drive is out of operation for more than two weeks, the heater must be connected and put in service in order to prevent condensed moisture inside the housing. If this is not possible, bags with at least 0.6 kg silicagel must be put into the housing.

8.4 Parallel operation


Two or more transformer in case of parallel operation, each transformer has to be in equal voltage value and vector group.

8.5 The circuits of the auxiliaries (cooling, protections, current transformers)


The circuits of auxiliaries and the terminal strips are shown in the Documentation. Describing of the devices can be found in the catalogues, the adjusting values are in the chapter of Calibrations (7.5)

24

OPERATION AND MAINTENANCE MANUAL

8.6 Signals
Alarm signals are given acc. to the drawing Cooling control: Trip signals are given acc. to the drawing Cooling control.

Connect the trip signal of the devices to the transformer main circuit breaker or to the protection system!

25

OPERATION AND MAINTENANCE MANUAL

8.7 Troubleshooting
The following trouble checks will help to correct the most common problems encountered with the transformer operation. The transformer shall be put in operation again, only after the cause of problem has eliminated.
Problem Alarm signal of oil indicator Alarm signal of oil indicator Probable Cause level Low oil level due to leakage Action Stop oil leakage and add oil

level High oil level due to high oil Check the transformer load, temperature the fan operation and the radiator valves Alarm signal of high temp. in oil Transformer overloaded, Check the transformer load or winding radiator valves closed check the positions of valves Alarm signal of Buchholz relay Gas development or oil Check the gas of relay, find the leakage cause of trouble or stop oil leakage Alarm signal of cooling Fans are out of operation Check the operation of fans and the switches, contactors in the control box Trip signal of high temp. in oil or Transformer overloaded Check the transformer load winding Trip signal of Buchholz relay Gas development, oil Check the gas of relay find the leakage/flow cause of trouble Trip signal of protective relay Oil flow from the tap changer Check the tap changer to find the cause of trouble Trip signal of High internal pressure Check the transformer, make pressure relief device due to internal trouble ratio and insulation test, find the cause of trouble Trip signal of differential or earth Internal trouble Check the transformer, make fault protection ratio and insulation test find the cause of trouble

8.8 Emergency actions


When alarm signal are given The time and conditions of signalling shall be recorded. Find the cause of signalling in order to stop any incorrect operation and to avoid tripping. When trip signals are given The time and conditions of signalling shall be recorded. Find the cause of tripping and eliminate the cause of troubles. General Performance data, overvoltages, short circuits, alarm and trip signals, misoperation of other electric devices and all important events related to operation, tests, inspections shall be registered in a log book.

26

OPERATION AND MAINTENANCE MANUAL

9. Maintenance
The proper maintenance is important for getting reliable operation of the transformer. The transformer is a typical device for outdoor installation, consequently it is exposed to variable weather conditions and various contaminations from the ambience. It is a general rule, that the transformer shall be kept clean, avoiding any heavy accumulation of dust, oily substance, sand, salt and foreign material of any kind, especially on bushings and live parts. Control boxes must be maintained clean and dry. All relevant gaskets shall be replaced in due time if the tightness is suspected to be precarious. All parts devoted to heat transfer shall be kept clean and free from deposits of any kind. Special tools are not required for the regular maintenance. Checking and the maintenance of the oil transformers have to be executed according to the enclosed table (9.3).

9.1 Maintenance work without lifting of the active part


Without lifting of the active part can be performed the following maintenance works: Oil For correct maintenance of the oil see IEC Publications: 60296: Specification for unused mineral insulating oil for transformer and switchgear. 60422: Maintenance and supervision guide for insulating oil in service. Check periodically the characteristics of oil at intervals as suggested. If acceleration in the process of deterioration is observed: conform the last value by means of a further test on a fresh sample and check the condition of oil more frequently, according to the degree of deterioration observed. The characteristic of oil to be tested, the test method, the permissible limit and the action to be taken are shown in the table (9.3) below. When the characteristics are normal: no action is necessary. When several characteristics are unsatisfactory: according to economic factors and local circumstances, it should be decided to examine the oil more thoroughly, to reclaim the oil or to replace it altogether. 9.1.1 Oil level indicators Clean carefully the oil level indicators. Check the oil level, substitute the missing volume, if necessary, with adequate quality oil. Check the reason for loss and repair the failures and leakage. 9.1.2 Air dryer Check the silicagel filling of the air dryer. If the filling has turned green, then replace the filling with new one or empty the air dryer and dry the silicagel for several hours at 110-115C temperature, until it turns evenly orange. Then mount the air dryer with the renewed filling back to its pipe. Check the lower oil seal. If it is not enough, fill it to the red marking line. 9.1.3 Thermometers Check the wholeness of thermometers, detectors in the thermometer pockets and capillary tubes. Do not twist or break the capillary tubes, the minimum bending radius has to be 25 mm. If the capillary tube is longer then necessary, the excess has to be rolled up in spiral form near to the detector or thermometer box. The minimum diameter of the spiral has to be 100 mm. Compare the readings of the thermometer to those of calibrating thermometer. The permitted maximum difference above 50C is + 2C related to calibrating thermometer. Replace the incorrect thermometer with good one.

27

OPERATION AND MAINTENANCE MANUAL


9.1.4 Buchholz relay Check the Buchholz relay for leakage and proper seat. If one of its two contacts cannot operate well, the relay has to be replaced with a new one. Check after each signalling whether the gas collected in the relay is combustible. If the gas is combustible the transformer may be suspected of failure. It is expedient to analyse the gas before energizing the transformer. The relay does not require special maintenance, but before putting into operation check the reliability of the operation. During the troubleshooting the volume of the tank and the conservator can be connected via a bay pass pipe connection, if any. 9.1.5 Oil pipes and fittings Replace any missing items, tighten the gaskets to stop any oil leakage. 9.1.6 Cooling Check the radiator elements and butterfly valves for leakage and mechanical failure. Stop eventual leakages with tightening or replacement of sealings. Check the cleanliness of radiating surface. Remove any contaminations, clear out the blocking of air routes. Check the operation of the fans. Remove all dirt and dust from the fan wheels. The motor bearings do not require any lubricant. The checks of the control box acc. to the operation instruction. 9.1.7 Bushings Check the tightening of all screwed connection. Replace the damaged porcelain insulator, if any. Clean the complete surface of the bushing. Make sure that the connected cables do not load the bushing. The storage, the transportation and the maintenance of the bushings are detailed in the Appendix 6.4 9.1.8 Tank, earthing screws If the tank is dangerously uneven or battered, or there is oil leakage on it, the transformer has to be transported into a workshop for repairing. Replace damaged earthing screws.

Generally small welding works on oil filled tanks can be performed safely by skilled workman.

9.1.9 Gaskets Check carefully all the gasketed joints of the transformer for oil tightness. The gasket does not require maintenance work. If you happen to find any oil leakage eliminate the leakage considering the followings:

The oil leakage is usually indicated by oil drops. To find the exact spot of the leakage wash the outside surface at and around the leakage with petrol and paint it with chalk or other indicating material. Try to eliminate the oil leakage with tightening the screws clamping the gasketed surface in question. Take care to even increasing of clamping pressure, which can be achieved by

28

OPERATION AND MAINTENANCE MANUAL


tightening the screws which are diagonally facing one another on the periphery, in succession. Continue this procedure as necessary. If the leakage can not be stopped with the procedure detailed above or the gasket is damaged replace the gasket with new one.

Always degrease the surfaces to be contacted with the gasket. The gaskets are made of heat- or oil permanent rubbers. For instance O-rings, flat gaskets, silicone rubber rings. D-profile rubber string can be used between the tank and the cover.

Before starting the operation materials and tools needed for possible danger averting must be prepared. Tray must be placed under the location of possible oil leakage. To clean the little oil spots, cloth, perlite, broom and shovel shall be put out. The clothes and sand used for oil absorbing are dangerous wastes. They must be collected separately, transported and handled properly after finishing the operation. 9.1.10 Outside painting Check carefully the surface of the transformer and the fittings to find the eventual painting defects. If there is any small defect in the painting, remove the base and final coast and the rust around the defect. Clean and degrease the damaged areas back to bright metal and apply primer coats immediately. Use the final top coat of the same colour specified for the contract. If there are many defected areas or those are big, paint again the whole tank with approved paint system.

After finishing the painting the empties, remaining paint and painty clothes are dangerous wastes. They must be collected separately, transported and handled properly after finishing the operation. 9.1.11 Deaerating After maintenance deaerated the transformer as described in the section "Commissioning" (7). The missing oil shall be replaced. 9.1.12 Tests After the maintenance works (without lifting of the active part) has to be measured the insulation resistance and the ratio of the transformer.

9.2 Maintenance work with lifting of the active part

Must not stay under the lifted parts of the transformer! Lifting can be performed after the location and fixing of the suitable rope on the component considering the gravity centre of the lifted part. 29

OPERATION AND MAINTENANCE MANUAL


Untanking: Before untanking make new gaskets, spare bolts and the damaged or missing parts available. Ensure with continued heating that the temperature of the transformer's active part is at least 5oC above the ambient temperature. The untanking of the active part can be performed by means of the lifting lugs (BQ031) fixed on the stiffeners of the cover. Before loosening the bolts of the cover drain approx. 2000 l of oil from the transformer tank. Take care of the vertical lifting of the active part to avoid accidental damage. After lifting out leave enough time to drop the oil from the lifted part into the tank. Then put it - if possible - onto a bordered iron sheet for investigation. 9.2.1 Checking of the winding Check the insulating material of winding for eventual brittleness and fragility. If it is so, no need any other tests as the winding has to be rewound, the transformer has to be delivered into a repairing workshop. 9.2.2 Contaminations Clean the active part of transformer with a soft brush or cloth, then wash it with oil jet at 50-60oC, to remove the contaminations. Use transformer oil of standard quality. 9.2.3 Insulating spacers Check, whether the winding clamping, the spacers between the winding and the end insulations are eventually loosened. If these are loosened, ensure the fixing tightening. 9.2.4 Connections Check the connections for eventual displacement, or if these are dangerously near to other construction part. If it is so, ensure reparation of the failure, and fix the connection, if necessary, to avoid repeated failure. Check the bolts, nuts, rivets, brazed points and welded points and repair any eventual failures. 9.2.5 Tap-changer The maintenance of the tap-changer has to be performed according to the related Operation and Maintenance Manual. Check the tightness of bolts fixing the connections between the tap winding and the tap-changer. 9.2.6 Bushings Clean the surfaces of bushings, replace any damaged on the bushings. 9.2.7 Tank, conservators Drain the oil from the tank, and clean carefully the empty tank. The necessary repairs must be performed only after cleaning. If any welding is necessary, ensure the good ventilation of the tank. For welding operations apply electric welding. Use heavy-coated rutine-cellulose type electrodes of 2.5-4 mm diameter according to the Standard ISO 2560/DIN 1913. If there is any rust in the tank, on the inner part of cover or inside the conservator, then clean the rusted surfaces with wire-brush, degrease, and paint the surfaces exposed to rust with oil resisting varnish.

30

OPERATION AND MAINTENANCE MANUAL


9.2.8 Assembly The active part of transformer, if there is any possibility at the site, has to be heated in short circuited state, it has to be dried and put into the empty tank. After putting all the gaskets discharge filtered oil heated to 50-55oC into the tank under vacuum. After placing the transformer on the base heat the transformer in short circuited state and filter the oil as long as moisture can removed by the filter apparatus. After resting and deaerating carry out oil test. When putting the transformer into operation follow the instructions of commissioning given in the Section 7. 9.2.9 Test The following tests have to be carried out after maintenance of the transformer: - visual inspection - functional test and calibration of all measuring, control and protection equipment - Megger test on all windings against each other and against earth - measurement of voltage ratio at each tap position and check of voltage vector relationship - dielectric test of oil and analysis of moisture content - if it is practicable perform the following: dielectric test with power frequency test voltage, but the voltage has to be 75% of the rated value.

9.3 Periodicity of maintenance work and checking of the oil transformers


The maintenance and inspection of the transformer have to be performed in the intervals indicated in the following table: Subject of checking Oil level Oil level indicator Conservator Breathing openings Air dryer Gaskets Thermometer Buchholz relay Protective relay Pressure relief device Oil fittings Coolers, control boxes, motor or manual drives Terminal connections, bushings Outside painting Tank Oil sampling and oil test Periodicity of maintenance work monthly monthly monthly monthly yearly yearly and after each operation yearly yearly yearly yearly yearly prior to energizing, then after half year, subsequently every two years. Occasionally in case of operating after oil supplement and replacement

Deaerating

31

OPERATION AND MAINTENANCE MANUAL

9.4 Spare parts


Request for spare part The request for spare parts or materials or service should be addressed to the nearest Representative of GANZ TRANSELEKTRO complete with the information as follows: Transformer type designation Serial number of the transformer Year of construction Exact type of the requested device or part BKT code Quantity Plant address Others: fault nature and causes etc..

32

You might also like