Minimizing downtime and optimizing consumption in a hospital

One of my concerns for the electrical distribution part is to ensure high availability of current in the common areas of the hospital. Due to increasingly severe economic constraints, I am also looking to save power consumption. I need a simple, scalable and competitive solution which will fit simply into the centralized hospital management system

Solution

The solution consists of: Supervision of the lighting circuit power supply to intervene rapidly in the event of protection system tripping. Supervision of the power supply for emergency lighting circuits. For non-public areas: - remote control of lighting for switching off outside of useful hours - allowing local restarting for greater flexibility. Checking that the surge arrester protecting the switchboard is in good condition. Power consumption measurement. Equipment used An EGX100 gateway for the Modbus TCP/IP Ethernet port at the switchboard level. Modbus RS485 Smartlink interface modules especially designed to optimize the electrical distribution boards, connected to the equipment's indication and control auxiliaries. A PM3250 power monitoring unit for energy metering and supervision of electrical parameters.

For the end user


> Minimization of lighting system downtime due to immediate, precise information for more efficient intervention. > Cost savings due to optimization of lighting time. > Control of expenses through visibility of the installation's power consumption and electrical settings.

Version : 1.0

Benefits
A9 FA 19 E A

Energy monitoring
Application: Hospital

Measure

Reduce energy consumption

Reduce energy costs

Preferential busbar 230 V AC


Local network: Ethernet / TCP-IP 230/240 V - 50 Hz Compact NSX EGX100
9 1 2 3 4 5 6 7 8 12 1314 15 16 17 18 19 20

iC60

1 iQuick PRD40r O/C contact 2 Multiclip

Acti 9 Smartlink Multiclip

Acti 9 Smartlink PM3250 Modbus / RS485 24 V DC Alim 24 V DC

(x8)
iC60+Vigi iC60

(x12)
iC60+Vigi iC60

3...9 iOF+SD24

(x7)

19...20

(x2)

iC60+Vigi iC60 iOF+SD24

iC60+Vigi iC60

12...18 iACT24 Plugs Lighting, technical rooms Fan coils Various Y2 BP+V iCT

Transformer 230 V AC / 24 V AC

System integrator Time saving for integration into the Building Management System, thanks to the Acti 9 Smartlink which requires no configuration settings.

Modbus / RS485

For professionals

230/240 V - 50 Hz

Lighting, corridors Lighting, staff rooms

1 iQuick PRD40r

2 iSW-NA iOF+SD24

9 1 2 3 4 5 6 7 8

22 12 1314 15 16 17 18 19 20 21

Acti 9 Smartlink Multiclip Multiclip

Acti 9 Smartlink

3...9 iOF+SD24

(x7)

12...16 iOF+SD24

iC60+Vigi iC60

(x5)
iC60+Vigi iC60

22 iC60+Vigi iC60 iOF+SD24

+ Panelbuilder
Time saving for installation thanks to pre-wiring between the Acti 9 Smartlink and the switchgear.
17...21 Emergency lighting: - technical rooms - common areas iACT24 iCT

Y2 BP+V Lighting stairs Emergency lighting of staff rooms Auxiliaries 230 V

Acti 9 Smartlink can very simply connect all the switchboard equipment with a supervision and automatic control system

Rail mounting, with a row of devices. Easy, fast wiring, thanks to 4 types of prefabricated connections and their oneclick plug-in connectors.

11 channels, to supervise and monitor the Reflex iC60 devices managing lighting. Connected to iACT24, Acti9Smartlink controls the iCT contactor and obtains feedback from its open/closed position.

PM3250

This is a cost-attractive, competitive range of DIN rail-mounted power meters ideal for power metering and network monitoring applications in addition to sub-billing and cost allocation applications.

The Powerlogic PM3000 series power meters are fully compatible with the Acti9 communication system, which makes it easier than ever to integrate electrical distribution into your customer's facility management system. Electrical parameters I, In, U, V, PQS, E, PF, Hz, THD. Power/current demand and peak demand. Min/max and 14 alarms with time stamping. LED to indicate communications. Up to 4 tariffs. Memory for load profile (demand 10 to 60 min.). Wrong wiring detection. Display in multiple languages.

A9 FA 19 E A

24 V DC

Safety busbar 230 V AC

Auxiliaries for medic Auxiliaries for HVAC