You are on page 1of 3

EARTHING MAT DESIGN FOR SUB STATION

As per ANSI/IEEE Std 80-1986 code


:Enter Your Details: Length of Area Occupied by Earthing Grid Width of Area Occupied by Earthing Grid Fault level at Incoming Bus Incoming Voltage Outgoing Voltage Soil Resistivity Resistance of Main Eartjing Mat Resistance of surface Material (Crushed Rock ) Thickness of Surface Material (Crushed Rock) Depth of Earthing Grid Conductor Diameter of Earthing Grid Conductor Reference Depth of Grid Area Occupied by Earthing Grid Spacing between Parallel Conductor of Grid Duration of Fault (To determine Size of earthing Mat) Duration of Fault (To determine safe Step & Touch Potential) Margine Factor in Earthing Mat against corrossion and Rusting Number of Adjacement Earthing Mat Conductor Relaction Factor Constant (KS) Constant (Ki) Number of Parallel Conductor in Longitudinal direction Number of Parallel Conductor in Transverse direction No of Lighting Arrestors No of Transformers la lb fault Vin Vout q qs hs h d 105 66 5000 132 66 40 0.5 3000 0.1 0.5 36 1 6930 5 3 0.5 100.00% 23 -0.973684 0.33145 4.612 21 13 10 2 mt mt MVA KV KV -m -m mt mt mm2 mt m2 mt sec sec nos

D t t nm K Ks Ki na nb

Earthing Conductor Standard Dia of Conductor (mm) 32 36 40

804 1018 1257 0 0 0 0 0 0 0 0 0

N FOR SUB STATION

Jignesh.Parmar www.jiguparmar.com, jiguparmar@yahoo.com

DESIGN OF EARTHING MAT Fault Current At Primary side Sizing of Earthing Conductor Size of Earthing Conductor after considering Margine Factor Standard Size of Earthing Rod (Round) Approximate Length of Earthing Mat Conductor Reduction Factor Tolerable Touch Potential Estimated Touch Potential
New Selection of Earthing Mat Conductor Length is OK L Cs Etouch Esti(Etouch) lg A Final A

21869 460.17 920.35 36 2203 0.66 570 885 3450 3450 565 3450 1788.1 387.600

Amp mm2 mm2 mm mt


OR Enter Your Value Selection is O.K

Volts Volts mt mt Volts mt Volts Volts

Now New Length of Earthing Conductor New Estimated Touch Potential


Result : Size of Earthing Mat Conductor is OK which is

New L L Esti(Etouch) Final L Estap Esti(Estap)

Tolerable Step Potential Estimated Step Potential Estimated Step Voltage is Less than Tolerable Step Potential Station Ground Resistance No of Earthing Rod used in Earthing Mat No of Earthing Rod used at perimeter Extra Earthing Rod used at 4 coners of Earthing Mat Earth Electrode for Lighting Arrestors Eatrh Electode for Transformer Control Room Earthing Total Earthing Rods Total Length of Earthing Mat Conductor Longitudinal direction Transverse direction Earthing Rod Total Length of Eartning Mat Conductor Estimated Touch Potential Estimated Step Potential Estimated Length of Earthing Mat Conductor No of Earthing Rod

Rg

0.224 68 16 20 6 2 112 2205 858 336 3399 565 388 3450 112

Nos Nos Nos Nos Nos Nos mt mt mt mt Volts Volts mt Nos

.Parmar guparmar@yahoo.com

1017.9

0.55

0.55

You might also like