GENERATOR STEP-UP TRANSFORMER SPECIFICATION DATASHEETS

PORTLAND GENERAL ELECTRIC 2012 REQUEST FOR PROPOSAL

NO. 0

DATE 23Apr12

REVISION Issued for RFP

BY

CHK'D

APPROVALS

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

SUBSTATION ENGINEERING STANDARD SPECIFICATION POWER TRANSFORMER DETAILED SPECIFICATION SDS-M011-03-(Generator Step-Up Transformer) OPEN

Engineer: Checked:

Ryan Jonak Jesse Duffy____________

Substation Engineering Manager: Brett Phillips EM&C Engineering Manager: Wayne Law

Portland General Electric

Page 1

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

PART I DESIGN REQUIREMENTS ................................................................................ 3 1.1 DESCRIPTION ................................................................................................................ 3 1.2 TRANSFORMER CAPACITY ....................................................................................... 3 1.3 PHASE DESIGNATION ................................................................................................. 3 1.4 WINDING TYPE ............................................................................................................. 3 1.5 TERTIARY WINDING ................................................................................................... 4 1.6 CORE AND COIL CONFIGURATION ......................................................................... 4 1.7 VOLTAGE AND SURGE ARRESTER RATINGS........................................................ 5 1.8 BUSHING REQUIREMENTS ........................................................................................ 6 1.9 BUSHING CURRENT TRANSFORMERS .................................................................... 8 1.10 IMPEDANCE ................................................................................................................. 10 1.11 PARALLELING ............................................................................................................ 10 1.12 DETC.............................................................................................................................. 11 1.13 LTC ................................................................................................................................ 11 1.14 OIL ................................................................................................................................. 12 1.15 OIL PRESERVATION SYSTEM ................................................................................. 12 1.16 COOLING ...................................................................................................................... 12 1.17 FIBER OPTIC TEMPERATURE PROBES................................................................. 13 1.18 TRANSFORMER MONITORING ............................................................................... 13 1.19 ALARMS ........................................................................................................................ 13 1.20 ON-LINE DISSOLVED GAS & MOISTURE MONITOR .......................................... 14 1.21 LIQUID LEVEL INDICATIORS ................................................................................. 14 1.22 PRESSURE RELIEF DEVICES ................................................................................... 14 1.23 TOP OIL TEMPERATURE INDICATOR................................................................... 15 1.24 WINDING TEMPERATURE INDICATOR ................................................................ 15 1.25 DEHYDRATING BREATHERS................................................................................... 15 1.26 AUXILLIARY POWER SOURCE ............................................................................... 16 1.27 AUDIBLE SOUND LEVEL........................................................................................... 16 1.28 ANGULAR DISPLACEMENT OR POLARITY ......................................................... 17 1.29 LOSS EVALUATION FACTORS ................................................................................ 17 1.30 DESIGN REVIEW REQUIREMENTS ........................................................................ 18 1.31 PGE EQUIPMENT NUMBER ...................................................................................... 18 1.32 SHIPMENT .................................................................................................................... 18 1.33 DELIVERY ADDRESS ................................................................................................. 18 1.34 SUBMITTALS AND TEST REPORTS ........................................................................ 19 1.35 SUBMITTAL AND DELIVERY DATES ..................................................................... 19 1.36 CORRESPONDENCE ................................................................................................... 19 1.37 DELIVERY NOTICE .................................................................................................... 19

Portland General Electric

Page 2

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 PART I 1.1 DESIGN REQUIREMENTS DESCRIPTION A. This specification covers the detailed design, construction, and operating requirements for mineral-oil-immersed outdoor station type power transformers. 1.2 TRANSFORMER CAPACITY The transformer capacity for the H, X and Y windings at 65 C shall be as specified by the rows checked ( ) in Table 1: Table 1 Transformer Capacity in MVA Winding ONAN ONAF 192 84 75 H&X 52 30 16.8 12 90 Y 256 112 100 66 40 22.4 16 120

ONAF 320 140 125 70 50 28 20 150

Shall be specified by manufacturer

1.3

PHASE DESIGNATION The phase of the transformer shall be as checked ( Single phase Three phase ) below.

1.4

WINDING TYPE The transformer winding type shall be as checked ( Two-winding Three-winding Autotransformer with tertiary winding ) below.

Portland General Electric

Page 3

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 1.5 TERTIARY WINDING The tertiary winding shall be as checked ( Buried Brought Out Not required 1.6 CORE AND COIL CONFIGURATION The core and coil configuration shall be as checked ( Circular Manufacturers Choice ) below. ) below.

Portland General Electric

Page 4

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 1.7 VOLTAGE AND SURGE ARRESTER RATINGS The transformer shall have the voltage ratings, BIL ratings, and surge arrester ratings for each terminal designation as specified by the rows checked ( ) in Table 2. Table 2 Transformer Voltage and Surge Arrester Rating Arrester Desired Nominal Duty Cycle Winding System Rating Rating BIL ( ) Voltage (Station Class) H Terminals 240 kV 120 kV 60 kV 60X120 kV 230kV 120 kV 60 kV 13.2 kV
(wye grounded)

750 kV 450 kV 350 kV 350X450 kV 825kV 450 kV 350 kV 110 kV

180 kV 90 kV 45 kV 45/90 kV 180kV 90 kV 45 kV 10 kV

X Terminals

13.2 kV
(wye, resistive grounded)

110 kV 110 kV 110 kV 110 kV 110 kV

15 kV 15 kV 15 kV 15 kV

13.8 kV 13.2 kV 13.8 kV Neutral

Y Terminals

Portland General Electric

Page 5

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 SURGE ARRESTER REQUIREMENTS The surge arresters shall be supplied for each required duty cycle by the rows checked ( ) in Table 3 (No substitutions are allowed). Table 3 Surge Arrester Manufacturers Desired Duty Arrester Cycle Manufacturer ( ) Rating 180 kV 90 kV 45 kV 15 kV 10 kV 6 kV Ohio Brass Siemens Ohio Brass Siemens Ohio Brass Siemens Ohio Brass Ohio Brass Ohio Brass

Type Polymer Polymer Polymer Polymer Polymer Polymer Polymer Polymer Polymer

Catalog Number PVN 314144-3001 3EL2 180-2PJ32-4NH5 PVN 314070-3001 3EL2 090-2PJ31-4NH5 PVN 314036-3001 3EL1045-1PH21-4YH5 PVN 314013-3001 PVN 314009-3001 PVN 314005-3001

1.8

BUSHING REQUIREMENTS Bushing requirements shall be as specified by the rows checked ( Table 4. ) in

Table 4 Bushing Bushing Require Continuous Voltage Current mentsD Rating esired Bushing ( )

BIL

XFMR Capacity

Acceptable Manufacturers & Catalog Number

H Bushings

Portland General Electric

Page 6

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 PCORE 230 kV 1200 A 900 kV 150 MVA 125 MVA 70 MVA 50 MVA 28 MVA MVA X Bushings PCORE 138 kV 3000 A 650 kV 320 MVA ABB PCORE 69 kV 2000 A 350 kV 125 MVA ABB PCORE 34.5 kV 4000 A 200 kV 70 MVA ABB PCORE 34.5 kV 3000 A 200 kV 50 MVA ABB PCORE 34.5 kV 113.8k V 2000 A 200 kV 28 MVA 150 MVA 8000A 150kV Y Bushings PCORE 34.5 kV 4000 A 200 kV 320 MVA ABB PCORE 34.5 kV 2000 A 200 kV 125 MVA ABB 88843-70 Interchangeable with PCORE 88823-70 Interchangeable with PCORE ABB Interchangeable with PCORE ABB POC650G3000S Interchangeable with PCORE 89523-70 Interchangeable with PCORE 88843-70 Interchangeable with PCORE 88833-70 Interchangeable with PCORE 88823-70 Interchangeable with PCORE ABB PCORE ABB POC900G1216S Interchangeable with PCORE POC650G0800S 138W0800AA

138 kV

800 A

650 kV

Neutral Bushing 320 MVA 230 kV 1200 A 900 kV PCORE ABB POC900G1216S Interchangeable with PCORE

Identical to Y Bushings

Portland General Electric

Page 7

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 Identical to X Bushings

1.9

BUSHING CURRENT TRANSFORMERS The manufacturer shall supply five-tap multi-ratio bushing current transformers (ANSI C800) as specified by the rows checked ( ) in Table 5. Table 5 - Bushing Current Transformer Requirements Quantity/ Required Bushing Full-Winding Terminals Bushings or Amperes ( ) ( ) Winding 3000:5 H 2 2000:5 1200:5 600:5 3000:5 H 2000:5 1200:5 4000:5 X 2 3000:5 2000:5 8000:5 4000:5 Y 2 3000:5 2000:5 3000:5 Tertiary Stabilizing Winding in Delta 2000:5 1200:5 3000:5 Neutral Bushing 1200:5 600:5 800:5

Portland General Electric

Page 8

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.10

BUSHING CURRENT TRANSFORMERS The manufacturer shall supply single-ratio bushing current transformers (Metering Class) as specified by the rows checked ( ) in Table 5.

Table 5 - Bushing Current Transformer Requirements Quantity/ Required Bushing Full-Winding Terminals Bushings or Amperes ( ) ( ) Winding 3000:5 H 1 2000:5 1200:5 600:5 3000:5 H 2000:5 1200:5 4000:5 X 1 3000:5 2000:5 8000:5 4000:5 Y 1 3000:5 2000:5 3000:5 Tertiary Stabilizing Winding in Delta 2000:5 1200:5 3000:5 Neutral Bushing 1200:5 600:5

Portland General Electric

Page 9

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.1

IMPEDANCE Impedances shall be designed to match that of an existing transformer or PGE standard as checked ( ) in Table 6. Table 6 Transformer Impedance Desired Impedance Percent Impedance ( ) H to X Winding 4.4 192 75 42 30 8.5 8.5 16.8 12

Base MVA

Shall Be Determined By Vendor H to Y Winding Shall Be Determined By Vendor X to Y Winding Shall Be Determined By Vendor 1.2 PARALLELING Transformer paralleling requirement is specified by the row checked ( ) below. Transformer will not be paralleled. Transformer will be paralleled with existing PGE Equipment #.

Portland General Electric

Page 10

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.3

DETC The de-energized tap changer requirement is specified by the row checked ( ) below. DETC Required on High Voltage DETC Not Required

1.4

LTC The LTC requirements shall be as specified by the rows checked ( ) below.

LTC Required on neutral-end of Low Voltage or Common Winding LTC Required on High Voltage Winding LTC Not Required Acceptable Manufacturers: Reinhausen RMV-II vacuum type with model B or later monitoring system Other The voltage regulation of the LTC shall be as specified as checked ( below. )

Plus and minus 10 percent automatic adjustment of the low-voltage winding voltage in 5/8 percent steps with 16 steps above and 16 steps below rated low voltage. Plus and minus 5 percent automatic adjustment of the low-voltage winding voltage in 5/8 percent steps with 8 steps above and 8 steps below rated low voltage. Other The LTC 8 hour current capability, according to section 2.9 (C) of the attached general specification, shall be specified as checked ( ) below. 4500 A

Portland General Electric

Page 11

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 3200 A 1800 A Manufacturer To Determine LTC Automatic controls shall be as specified as checked ( ) below:

Beckwith Model M-2001C mounted on M-2067 adapter plate with M-0329A LTC backup control. Reinhausen TAPCON 250 mounted on M-2067 adapter plate. Use Tapcon model #TC250-4-P-E1-03 with a potentiometer to 4-20 mA transmitter from Absolute Process Instruments, Inc. model #API 4003 GI for position indication. None Required 1.5 OIL The transformer oil shall be provided as checked ( Provided by Transformer Manufacturer Provided by Portland General Electric 1.6 OIL PRESERVATION SYSTEM The transformer oil preservation system shall be as checked ( Sealed Inert Gas Pressure System Regulated Inert Gas Pressure System Sealed Conservator Tank System Manufacturers Choice 1.7 COOLING Acceptable cooling system shall be checked ( Radiators with Fans Coolers with Pumps and Fans Manufacturers Choice ) below. ) below. ) below.

Portland General Electric

Page 12

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.8

FIBER OPTIC TEMPERATURE PROBES Acceptable fiber optic probe sensor manufacturers shall be checked ( below. )

OpSens OTG-T Fiber Optic Temperature Sensor with PowerSens II Signal Conditioner Other No Fiber Required 1.9 TRANSFORMER MONITORING Acceptable transformer monitoring systems are (checked ( ) below): PGE will install the transformer monitor. All available alarms shall be wired to terminal blocks for PGE's use. APT Eclipse Monitor Model Number ECLIPSE-0013 1.10 ALARMS The alarm/annunciation points checked ( ) in Table 7, shall be wired to a transformer monitor specified in Section 1.18. Refer to MSTR-3602 for alarm configuration into monitor. Table 7 Alarm/Annuciation Points
ALARM LOW N2 CYLINDER PRESSURE HIGH MAIN TANK PRESSURE LOW MAIN TANK PRESSURE LOW OIL LEVEL ALARM LOW OIL LEVEL TRIP TOP OIL TEMP GAUGE 100C PRESSURE RELIEF DEVICE (MAIN TANK) SUDDEN PRESSURE RELAY TRIP LOSS OF FAN AC

Portland General Electric

Page 13

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03


LOSS OF OIL FLOW LTC TROUBLE (Lockout, Off Tap, Vacuum Failure, Loss of Power) LTC HIGH/LOW OIL LEVEL LTC ACCESSORY TROUBLE PRESSURE RELIEF DEVICE (LTC) CALISTO TROUBLE WINDING TEMPERATURE 120C (Alarm) WINDING TEMPERATURE 140C (Trip) BLADDER MONITOR ATS ON ALTERNATE LTC NEUTRAL CAM SWITCH LTC FILTER ALARM SHALL BE DETERMINED LATER

1.11

ON-LINE DISSOLVED GAS & MOISTURE MONITOR Acceptable on-line dissolved gas & moisture monitor manufacturers and models shall be checked ( ) below. GE Hydran M2 Morgan Schaffer Calisto 2 Serveron TM5

1.12

LIQUID LEVEL INDICATIORS Acceptable liquid level gauge manufacturers shall be checked ( Qualitrol Messko Other ) below.

1.13

PRESSURE RELIEF DEVICES Acceptable pressure relief device manufacturers shall be checked ( Qualitrol ) below.

Portland General Electric

Page 14

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 Messko Other

1.14

TOP OIL TEMPERATURE INDICATOR Acceptable temperature gauge manufacturers shall be checked ( Qualitrol Messko Other ) below.

1.15

WINDING TEMPERATURE INDICATOR Acceptable temperature gauge manufacturers shall be checked ( Qualitrol Messko Not Required ) below.

1.16

DEHYDRATING BREATHERS Acceptable dehydrating breather manufacturers shall be as checked ( below. Messko MTraB Other )

Portland General Electric

Page 15

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.17

AUXILLIARY POWER SOURCE The AC control power supply, provided by PGE, shall be as checked ( below. 240/120V, single phase, 60 Hz, three-wire source 480 V, Three phase, 60 Hz, four wire source The AC control power automatic transfer switch shall be provided as checked ( ) below. Required Not Required The DC control power supply, provided by PGE, shall be as checked ( below. 125V, two wire ungrounded source (initial control voltage) 48V, two wire ungrounded source (initial control voltage) Easily convertible between a 48V and 125V, two wire source, initially set up for: 125V, two wire ungrounded source (initial control voltage) 48V, two wire ungrounded source (initial control voltage) ) )

1.18

AUDIBLE SOUND LEVEL The transformer shall designed to comply with the decibel rating as checked ( ) below. Standard NEMA TR1 -10 dB relative to NEMA TR1 Other

Portland General Electric

Page 16

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03

1.19

ANGULAR DISPLACEMENT OR POLARITY The transformer angular displacement or polarity shall be as checked ( Figure 1. Figure 1 Transformer Winding Angular Displacement ) in

1.20

LOSS EVALUATION FACTORS For evaluation purposes, the losses will be evaluated and the bid price adjusted as follows: Adjusted bid price = (Bid Price) +

Portland General Electric

Page 17

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 (No Load Loss) (K1) + (Full Load Loss) (K2) No Load Loss Cost Multiplier: Full Load Loss Cost Multiplier: K1 = $8,706.74/kW K2 = $4,197.22/kW

Total load losses shall include the losses in the LTC regulating winding and the first-stage cooling equipment load. Losses shall be expressed to the nearest 0.1 kW. 1.21 DESIGN REVIEW REQUIREMENTS If a design review is required, unless approved otherwise, major material items (core steel, copper, insulation material, LTC, bushings, etc.) may not be purchased prior to the approval of the transformer design or without prior approval from PGE. Manufacturer shall include in their schedule adequate time to complete a design review and order material. Design Review Required Design Review Not Required 1.22 PGE EQUIPMENT NUMBER The PGE equipment number specified below shall be included on the transformer nameplate, all transformer drawings and instruction books. PGE Equipment Number: 1.23 SHIPMENT The transformer shall be shipped with the following requirements as checked ( ) below. Oil Filled Without Oil, Pressurized with Dry Air Rider Required For Rail Shipment GPS Enabled Impact Recorders Required For Rail Shipment 1.24 DELIVERY ADDRESS The transformer shall be shipped to following address: Reference Purchase Order

Portland General Electric

Page 18

POWER TRANSFORMERS DETAILED SPECIFICATION SDS-M011-03 Substation: Address: Reference Purchase Order , OR

1.25

SUBMITTALS AND TEST REPORTS Submittals and Test Reports shall be made to the person named below: Name: Email: Phone: Address: Rick Tetzloff Rick.Tetzloff@pgn.com 503-464-8508 121 SW Salmon St. Portland, OR 97204

1.26

SUBMITTAL AND DELIVERY DATES Submittals and transformer delivery shall be made on the following dates: RFQ Issued: Bid Submittal: Purchased Order Issued: Transformer Delivery:

1.27

CORRESPONDENCE Correspondence regarding this specification or the bid shall be sent to the PGE purchasing department, with copies to: Name: Email: Phone: Address: Rick Tetzloff Rick.Tetzloff@pgn.com 503-464-8508 121 SW Salmon St. Portland, OR 97204

1.28

DELIVERY NOTICE The supplier shall notify the person(s) named below, when the transformer leaves the factory and before arrival at the PGE destination for confirmation of destination and unloading arrangements. Name: Phone: