Sl.

PARTICULARS NO I PLANT ROOM

QTY I/O DETAILS AI DI AO

DO

Soft

Type Runs

CABLE DETAILS Tag From

To

HAIL'S Scope of Work

CLIENT'S Scope of Work

Response by ETA

Response by HAIL

Response by ANC

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

A CHILLED WATER PUMPS SECONDARY 1 On/Off Command 2 Run Status

4 4 4 2 Core 2 Core 4 4 PUMPx-ONOF-CMD PUMPx-RUN-STS DDC Pump Panel Pump PanelBMS DDC shall provide Pump panel shall accept Confirmed Ok Ok, Closed potential free potential free DDC BMS DDC shall accept Pump panel shall provide Confirmed Ok Ok, Closed potential free potential free (N.O.) contact from pump (N.O.) contact to BMS DDC. BMS DDC shall accept potential Pump freepanel (N.O.) shall contact provide from potential pump Not panel. free Available. (N.O.)Can contact be fetched to BMS Ok, through provide DDC. MODBUS Modbus register portProvided of VFD no. and by multiplicatin ETA & Closedfactor

3 High current Alarm

Pump VFD

4 Bypass Line Valve Feedback

2 Core

AHU-VLV-STS

Valve Actuator DDC

DDC

5 Bypass Line Valve Control

4 Core

VLV-CTRL

Valve Actuator

6 VFD Integration 7 Secondary Pump's VFD Speed Feedback 8 Secondary Pump's VFD Frequency 9 Secondary Pump's VFD Current 10 Secondary Pump's VFD Voltage 11 Secondary Pump's VFD Power 12 Secondary Pump's VFD Run Time 13 BTU Meter (400mm) 14 15 16 17 18 19 20 21 Supply Temperature Return Temperature Delta Temperature Flow Rate Total Flow Power Energy Chilled water common supply temp

4 4 4 4 4 4 4 1 1 1 1 1 1 1 1 2 Core1 BTU-COMM (Daisy Chain) DDC 2 Core1 VFD-COMM (Daisy Chain) DDC

BMS DDC shall accept 0-10 output for 0-100% valve open to Not scope of ETA Client to clarify Bypass line is not in design and hence this point do BMSin DDC. Vdc signal for 0100% valve open from Valve BMS DDC shall provide 0-10 Vdc Valve signal Actuator output shall for 0-100% accept valve 0- Not open in scope to Valve of ETA Actuator. 24Vac Client supply to clarify to valve actuator. Bypass line is not in design and hence this point do 10Vdc signal for 0100% valve open from BMS Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed Ok, provide VFD parameter list 16-00 to 16-95 for register address 416000 416950. Provided & closed

Pump VFD 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software. BTU

2 Core

CHWS-TEMP

Imm.Temp Sensor Imm.Temp Sensor

DDC

Supply, Installation, Testing Flow meter installation The & BTU Meter Confirmed has already Through been MODBUS procured Need port by further inETA , clarifications ETA Has submitted from cleint. approved HAIL Tech already Modbus Submittal considered interface to HAILs M- Bus for the BTU Confirmed Through MODBUS port in and Commissioning of provision of 2 nos.1/2" NPT confirmed by ETA Confirmed Through MODBUS port in Ultrasonic BTU meter. socket for Immersion Temp & Closed Confirmed Through MODBUS port in Confirmed Through MODBUS port in Sensors installation. Confirmed Through MODBUS port in Confirmed Through MODBUS port in Supply, Installation, Testing & Provision Commissioning of 1/2" of NPT Imm socket Temp toSensor. be HAIL made to confirm for Immersion thread Temp size, Ok, location, Sensor Sample Thermowell other & location details installation. will and Ok, be to Closed coordinated provide one at sample site. for the requirement to

22 Chilled watercommon return Temp

2 Core

CHWR-TEMP

DDC

Supply, Installation, Testing & Provision Commissioning of 1/2" of NPT Imm socket Temp toSensor. be HAIL made to confirm for Immersion thread Temp size, Ok, location, Sensor Sample Thermowell other & location details installation. will and Ok, be to Closed coordinated provide one at sample site. for the requirement to

23 Outside Air Temperature Monitoring 24 Outside Air RH Monitoring 25 Integration of the Sec pump Controller

1 1

1 1 0

2 Core

OD-TEMP OD-RH PUMP-CTRL-COMM

OD T+RH Sensor DDC DDC

Supply, Installation, Testing & - Commissionig of Outdoor Temp & RH Sensor. HAILS will revert with the list of shortcoming of data through the proposed controlling through VFD Since hard points only availble, hardwire integration considered. Closed

4 Core 1 2 Core25

26 Sec Pump Controller Common fault monitoring 27 Sec Pump Controller Common On/Off Command B PRESSURIZATION UNIT 1 Unit run status 2

2 Core

Pump 1) Supply, Installation, Shall provide - 1) Pump Common Fault & Client to clarify further. Controller Testing & Commissioning of Controller Modbus RTU RS-485 Common Operation Modbus RS485 Integrator. wire terminals. command only are 2) Communication Cable 2) Pump Controller Modbus available. laying from register No Soft Integration is integrator to mapping list. possible. Controlling Pump Controller in daisy 3) Pump Controller can be done through SCHW-CTLR-FAULT SCHW Controller DDC BMS DDC shall accept potential SCHW freePump (N.O.) controller contact from shallSCHW provide Pump potential controller. free (N.O.) contact to BMS DDC.

2 Core

SCHW-CTLR-CMD

DDC

SCHW Controller BMS DDC shall provide potential SCHW free Pump (N.O.) controller contact to shall SCHW accept Pump potential controller. free (N.O.) contact from BMS DDC.

Hardware point considered in place of software. Closed Hardware point considered in place of software. Closed

4 Core

PU-RUN-STS

Panel

DDC

BMS DDC shall accept potential free (N.O.) contact from AHU panel.

AHU panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

Ok, closed

As discussed with ETA, the pump run intermidently for short period hence status not require. Ok, Closed

Sl. PARTICULARS NO 2 Unit trip alarm

QTY I/O DETAILS AI DI AO 0

4 Core DO Soft

Type Runs

CABLE DETAILS Tag From PU-TRIP-STS Panel

To DDC

HAIL'S Scope of Work BMS DDC shall accept potential free (N.O.) contact from AHU panel. Supply, Installation, Testing & Commissioning of Water Pressure Transmitter (DPT).

CLIENT'S Scope of Work

Response by ETA

Response by HAIL

Response by ANC

3 System pressure

4 Core

PU-PRES

Water Pressure Sensor DDC

AHU panel shall provide Confirmed. Ok Ok, closed potential free (N.O.) contact to BMS DDC. Provision of 8mm dia hole at suitable HAIL to location confirm for thread pressure size, Ok, pickup Sample location, tubes & location other installation. details will Ok, be closed and coordinated to provide at one site. sample for the requireme

As discussed with ETA, the As per MOM dated 06pump run intermidently Feb-2013 between ANC, for short period hence ETA, HAIL & ILFS status not require. Ok, Closed

C AHU 1 On/Off Command

99 10 107 2 Core 107 AHU-ONOF-CMD

2 Run Status

107

2 Core 107

AHU-RUN-STS

3 Auto Manual status

107

4 Core 107

AHU-A/M-STS

4 Trip Status

107

AHU-TRIP-STS

5 Filter status

107

2 Core 107

AHU-FLTR-STS

6 Supply Air Temperature Monitoring

107

2 Core 107

AHU-SA-TEMP

TOTAL 98 + 09 = 107 Please provide AHU list. ETA Submitted AHU = 107 Nos. Ok, Closed AHUs to be considered the revised list DDC AHU Panel BMS DDC shall provide AHU panel shall accept HAIL to generate outputs Provision for single NO/NC ETA to to beprovide made in closed panel by ETA. In undesirable cond potential free potential free for Start & Stop. (N.O.) (N.O.) - Start Signal shall be of contact to AHU panel. contact from BMS DDC. Latching Type (N.O.) - Stop Signal shall be Momentary Air DPS DDC Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tube & installation. location other details will Ok, be Closed and coordinated to provide at one site. sample for the requireme & Commissioning of Air Diff. Pressure Switch (DPS). AHU Panel DDC BMS DDC shall accept AHU panel shall provide Confirmed. Auto mode status Ok shall be provided Ok, Closed potential free potential free (N.O.) (N.O.) AHU Panel DDC BMS DDC shall accept AHU panel shall provide Confirmed. Available in various It should Feeders. be AHU Please starter refer panel Ok, attached Closed and TBs SLD to be for shown location at and site. other details. potential free potential free (N.O.) (N.O.) Air DPS DDC Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tube & installation. location other details will Ok, be Closed and coordinated to provide at one site. sample for the requireme & Commissioning of Air Diff. Pressure Switch (DPS). Duct Temp DDC Supply, Installation, Testing Provision of 1/4" hole to be made HAIL on the to side confirm of duct thread for Duct size, Ok,Temp Sample location, Sensor & location other probe details will insertion. Ok, be Closed and coordinated to provide at one site. sample for the requireme Sensor & Commissioning of Duct Temp Sensor. Duct Temp Sensor DDC DDC

7 Return Air Temperature Monitoring

107

2 Core 107

AHU-RA-TEMP

Supply, Installation, Testing Provision of 1/4" hole to be made HAIL on the to side confirm of duct thread for Duct size, Ok,Temp Sample location, Sensor & location other probe details will insertion. Ok, be Closed and coordinated to provide at one site. sample for the requireme & Commissioning of Duct Temp Sensor.

8 Valve Modulation

107

4 Core 107

AHU-VLV-MOD

Valve Actuator AHU VFD

9 VFD control Signal

107

2 Core 107

AHU-VFD-CTR

DDC

10 VFD modulation using diff press transmitter 11 VFD soft integration 13 14 15 16 17 18 AHU's VFD AHU's VFD AHU's VFD AHU's VFD AHU's VFD AHU's VFD Speed Feedback Frequency Current Voltage Power Run Time 6 107

107

4 Core 107

AHU-DP

Air DPT

DDC

BMS DDC shall provide 0-10 Vdc Valve signal Actuator outputshall for 0-100% acceptvalve 0- Confirmed. open to Valve Actuator. 24Vac Ok supply to valve actuator. Ok, Closed 10Vdc signal for 0100% valve open from BMS DDC. BMS DDC shall provide 0-10 Vdc AHU signal VFD output shall accept for 0-100% 0-10Vdc speed Confirmed. to AHU VFD. Ok Ok, Closed signal for 0100% VFD speed from BMS DDC Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tubes &installation. location other details will Ok, be Closed and coordinated to provide at Location one site. sample of Diff. forpressure the requireme & Commissioning of sensor to be in SA Duct Air Diff. Pressure within AHU room itself. Transmitter (DPT). Closed Available through 1) Supply, Installation, Shall provide - 1) VFD Modbus Testing & Commissioning of RTU RS-485 wire terminals. Modbus RS485 2) VFD Modbus register Integrator. mapping list. 2) Communication Cable 3) VFD Configuration as per MODBUS Port of MODBUS Confirmed Through Ok, port provide in VFD Confirmed Through MODBUS port in list parameter Confirmed Through MODBUS port in 16-00 Confirmed Through MODBUS port to in 16-95 for register Confirmed Through MODBUS port in Confirmed Through MODBUS port in416000 address provided by ETA , closed

107 107 107 107 107 107

2 Core1 VFD-COMM (Daisy Chain)

DDC

AHU VFD

D FAHU 1 Supply Air Temperature Monitoring 2 Temperature After Heat Recovery 3 Exhaust Temperature before heat recovery 4 Ambient temperature Monitoring 5 Temperature After Heat wheel

6 6 6 6 6

2 Core 2 Core 2 Core 2 Core 2 Core

6 6 6 6 6

FAHU-SA-TEMP FAHU-AHR-TEMP FAHU-BHR-TEMP FAHU-AMB-TEMP FAHU-AHW-TEMP

Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor

DDC DDC DDC DDC DDC

Supply, Installation, Testing & Provision Commissioning of 1/4" of hole to be for HAIL to confirm thread size, Ok, Sample location, & location other details will be Ok, and coordinated Closed to provide at one site. sample for the requireme Duct Temp Supply, Installation, Testing & Provision Commissioning of 1/4" of hole to be for Duct Temp Supply, Installation, Testing & Provision Commissioning of 1/4" of hole to be for Duct Temp Supply, Installation, Testing & Provision Commissioning of 1/4" of hole to be for Duct Temp Supply, Installation, Testing & Provision Commissioning of 1/4" of hole to be for Duct Temp

Sl. PARTICULARS NO 6 Supply Fan Run Status

QTY I/O DETAILS AI DI AO 6

DO

Soft

Type Runs 2 Core 6

CABLE DETAILS Tag From FAHU-SF-RUN Air DPS

To DDC

7 Supply Fan Trip Status 8 Exhaust Fan Run Status

6 6

2 Core 2 Core

6 6

FAHU-SF-TRIP FAHU-EF-RUN

FAHU Panel Air DPS

DDC DDC

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tube & installation. location other details will Ok, be Closed and coordinated to provide at one site. sample for the requireme & Commissioning of Air Diff. Pressure Switch (DPS). BMS DDC shall accept AHU panel shall provide Confirmed Ok Ok, Closed

HAIL'S Scope of Work

CLIENT'S Scope of Work

Response by ETA

Response by HAIL

Response by ANC

9 Exhaust Fan Trip Status

2 Core

FAHU-EF-TRIP

FAHU Panel

DDC

10 HW Motor Run Status

2 Core

FAHU-HW-RUN

FAHU Panel

DDC

11 HW Motor Trip Status

2 Core

FAHU-HW-TRIP

FAHU Panel

DDC

12 Filter before HW on Exhaust 13 Pre Filter Fresh Air 14 Bag Filter Fresh Air 15 VFAU Start/Stop

6 6 6 6

2 Core 2 Core 2 Core 2 Core

6 6 6 6

FAHU-HW-FLTR FAHU-PR-FLTR FAHU-BG-FLTR FAHU-ONOF-CMD

Air DPS Air DPS Air DPS DDC

DDC DDC DDC

potential free potential free Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tube & installation. location other details will Ok, be Closed and coordinated to provide at one site. sample for the requireme & Commissioning of Air Diff. Pressure Switch (DPS). BMS DDC shall accept AHU panel shall provide Confirmed Ok Ok, Closed potential free potential free (N.O.) (N.O.) BMS DDC shall accept AHU panel shall provide Confirmed Ok Ok, Closed potential free potential free (N.O.) (N.O.) BMS DDC shall accept AHU panel shall provide Confirmed Ok Ok, Closed potential free potential free (N.O.) (N.O.) Supply, Installation, Testing & Provision Commissioning of 8mmof dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tube & location other details will Ok, be Closed and coordinated to provide at one site. sample for the requireme Supply, Installation, Testing & Provision Commissioning of 8mmof dia hole at suitable location for pressure pickup tube Supply, Installation, Testing & Provision Commissioning of 8mmof dia hole at suitable location for pressure pickup tube AHU panel shall accept potential free (N.O.) contact from BMS DDC. Ok, Closed Ok, Closed

FAHU PanelBMS DDC shall provide potential free (N.O.) contact to AHU panel.

16 HOA Switch

2 Core

FAHU-A/M-STS

FAHU Panel

DDC

17 AHU Trip on Fire Mode

FAHU-TRIP-STS

FAHU Panel

DDC

BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) contact from AHU panel.

AHU panel shall provide potential free (N.O.) AHU panel shall provide potential free (N.O.) contact to BMS DDC.

HAIL to generate outputs Provision for single NO/NC ETA to to beprovide made in , panel closedby ETA. In undesirable cond for Start & Stop. - Start Signal shall be of Latching Type (N.O.) - Stop Signal shall be Momentary Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

Not Available. DDC to for stop safety the purpose system in fire case interface HAILs of fire. toshall develop be direct the ETA logic confirmed with and HVAC confirm FAHU system that as works it sha panel interlock to be used for tripping. Closed

18 Valve Modulation

4 Core

FAHU-VLV-MOD

DDC

Valve Actuator

19 VFD control Signal

2 Core

FAHU-VFD-CTR

DDC

20 VFD modulation using diff press transmitter 21 VFD soft integration 6 7

4 Core

FAHU-DP

Air DPT

BMS DDC shall provide 0-10 Vdc Valve signal Actuator outputshall for 0-100% acceptvalve 0- open to Valve Actuator. 24Vac Client supply to clarify to valve scope actuator. of ETA valve to reposnd Modulating valve provided 10Vdc signal for 0by ETA & BMS interface 100% valve open from BMS confirmed. Closed DDC. FAHU VFD BMS DDC shall provide 0-10 Vdc AHU signal VFD output shall accept for 0-100% 0-10Vdc speed Confirmed. to AHU VFD. Ok Ok, Closed signal for 0100% VFD speed from BMS DDC DDC Supply, Installation, Testing Provision of 8mm dia hole at suitable HAIL location to confirm for pressure thread size, pickup Ok, Sample location, tubes &installation. location other details will Ok, be Closed and coordinated to provide at ETA one site. tosample check on forthe the requireme & Commissioning of control logic and give to Air Diff. Pressure ANC. OPEN Transmitter (DPT). Available through MODBUS Client Port to of confirm VFDs. Only Supply HAILS will FAN revert have Bsmt VFDs. floorExhaust FAHU has& two HW fans with the list of shortcoming of data through the proposed Ok, Closed SA fan so one VFD increased. Only control of supply fan without control of exhaust will create

22 23 24 25 26 27

AHU's VFD AHU's VFD AHU's VFD AHU's VFD AHU's VFD AHU's VFD

Speed Feedback Frequency Current Voltage Power Run Time

7 7 7 7 7 7

2 Core1 VFD-COMM (Daisy Chain)

DDC

FAHU VFD 1) Supply, Installation, Shall provide - 1) VFD Modbus Testing & Commissioning of RTU RS-485 wire terminals. Modbus RS485 2) VFD Modbus register Integrator. mapping list. 2) Communication Cable 3) VFD Configuration as per laying from integrator to site requirement.

Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed

Through MODBUS Ok, port provide in VFD Through MODBUS port in list parameter Through MODBUS port to in 16-95 for 16-00 Through MODBUS port in register Through MODBUS port in address 416000 Through MODBUS port in 416950.

II FANS A SMOKE EXTRACT FAN 1 Common Damper open/close command 1 0 4 Core 1 SEF-DMPR-CMD DDC Damper Actuator BMS DDC shall provide Damper actuator shall accept potential free (N.O.) potential free contact to Damper actuator. (N.O.) contact from BMS DDC. No Motorized Fire Damper Client to is confirm provided

HAILS to revert with Common specific damper application not inof commo design scope hence removed. Closed

Sl. PARTICULARS NO 2 Damper open status

QTY I/O DETAILS AI DI AO 0

4 Core DO Soft

Type Runs

CABLE DETAILS Tag From SEF-DMPR-STS Fan Panel

To DDC

HAIL'S Scope of Work

CLIENT'S Scope of Work Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) Fan Panel shall provide potential free (N.O.) Fan Panel shall accept potential free (N.O.) contact from BMS DDC.

Response by ETA No Motorized Fire

Response by HAIL Damper Client to is confirm provided

3 `Auto' position of H/O/A switch

4 Core

SEF-A/M-STS

Fan Panel

4 Fan trip alarm

SEF-TRIP-STS

Fan Panel

5 Fan Start/Stop Command

4 Core

SEF-ONOF-CMD

DDC

BMS DDC shall accept potential free (N.O.) contact from Fan Panel. DDC BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) Fan Panel BMS DDC shall provide potential free (N.O.) contact to Fan Panel.

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS not inof commo HAILS to revert with Common specific damper application design scope hence removed. Closed

Response by ANC

Confirmed. Auto Mode Status Ok shall be provided

Ok, Closed

Confirmed.

Ok

Ok, Closed

6 Fan run status

SEF-RUN-STS

Fan Panel

DDC

7 FA signal

2 Core

SEF-FIRE-STS

Fan Panel FAS CR

DDC

BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.)

Fan Panel shall provide potential free (N.O.) Fan Panel shall provide potential free (N.O.) contact to BMS DDC.

HAIL to generate outputs Provision for single NO/NC HAILs to be tomade develop in panel the ETA logic confirmed by ETA. and confirm In single undesirable that works cond for Start & Stop. point contact for - Start Signal shall be of start/stop. Closed Latching Type (N.O.) - Stop Signal shall be Momentary Confirmed. Ok Ok, Closed

Can be done through Auto (Start) Ok, will as be described taken from in Point FAS Ok, CR 5. Closed Module

B STAIRCASE PRESSURIZATION FAN + PASSAGE 2+1 PRESSURIZATION FAN 1 Common Damper open/close command 0 4 Core 4 SPFx-DMPR-CMD BMS DDC shall provide potential free (N.O.) contact to Damper actuator. Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. Fan Panel shall Confirmed. provide potential Ok free DDC Damper Actuator Damper actuator shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Ok, Closed

Actual Qty. is 02 + 01 No Motorized Fire

Ok, client to confirm Damper Client to is confirm provided

Follow ETA's quantity . HAILS to revert with Common specific damper application not inof commo

2 Damper open status

SPFx-DMPR-STS

No

Motorized

Fire

Damper Client to is confirm provided

4 Fan trip alarm

5 Fan Start/Stop Command

SPFx-TRIP-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel.

design scope hence removed. Closed HAILS to revert with Common specific damper application not inof commo design scope hence removed. Closed

(N.O.) contact to BMS DDC.

6 Fan run status

7 VFD Control Signal

2 Core

3 `Auto' position of H/O/A switch for Fire + Normal Starters 6

4 Fan trip alarm Fire Mode + Normal Mode 5 Fan Start/Stop Command Fire Mode + Normal Mode 6 Fan run status Fire Mode + Normal Mode 7 FA signal 12

SPFx-RUN-STS Fan Panel DDC BMS DDC shall Fan Panel Confirmed. To be provided in Vendor Ok, to Closed make provision in Manual accept potential shall provide free (N.O.) potential SPFx-VFD-CTR DDC Fan VFDBMS DDC shall Fan VFD shall Confirmed. OkOk, Closed provide 0-10 Vdc accept 0signal output for 0- 10Vdc signal 100% speed to Fan for 04 Core 6 EXFx-A/M-STS Fan Panel DDC BMS DDC shall accept Fan Panel shall provide potential free potential free (N.O.) (N.O.) EXFx-TRIP-STS Fan Panel DDC BMS DDC shall accept Fan Panel shall provide potential free potential free (N.O.) (N.O.) 2 Core 6 EXFx-ONOF-CMD DDC Fan Panel BMS DDC shall provide Fan Panel shall accept potential free potential free (N.O.) (N.O.) contact from BMS DDC. 2 Core 12 EXFx-RUN-STS Fan Panel DDC BMS DDC shall accept Fan Panel shall provide potential free potential free (N.O.) (N.O.) 2 Core 6 EXFx-FIRE-STS Fan Panel DDC BMS DDC shall accept Fan Panel shall provide potential free potential free (N.O.) (N.O.) contact from Fan Panel. contact to BMS DDC.

Mode only. In Auto mode panel for on/off status in both status can be taken from VFD mode

Cofirmed.

Ok

Ok, Closed

Cofirmed.

Ok

Ok, Closed

Cofirmed.

Ok

Ok, Closed

Cofirmed.

Ok

Ok, Closed

Directly controlled by CO sensors provided by ETA. Closed

BMS Shall provide fire signal Ok, to will Fan take Starters fromafter FAS CR confirmation Ok, module Closed of fire. Fire Fan signal can be given started fromaccordingl FAS CR to Extract Fan panel. Closed Actual Quantity is 06 Nos. instead of 04 Pls clarify on qty whether 6 or 3, HAILS to consider 06

C EXTRACT FAN (SINGLE SPEED)

Sl. PARTICULARS NO 1 Common Damper open/close sommand

QTY I/O DETAILS AI DI AO

DO 0

Soft

Type Runs 4 Core 6

CABLE DETAILS Tag From EXFx-DMPR-CMD DDC

To Damper Actuator

HAIL'S Scope of Work

CLIENT'S Scope of Work Damper actuator shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) Fan Panel shall provide potential free (N.O.) Fan Panel shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) Fan Panel shall provide potential free (N.O.) contact to BMS DDC.

Response by ETA No Dampers are there.

Response by HAIL Client to confirm

2 Damper open status

EXFx-DMPR-STS

Fan Panel

3 `Auto' position of H/O/A switch

4 Core

EXFx-A/M-STS

Fan Panel

4 Fan trip alarm

EXFx-TRIP-STS

Fan Panel

5 Fan Start/Stop Command

2 Core

EXFx-ONOF-CMD

DDC

6 Fan run status

2 Core

EXFx-RUN-STS

Fan Panel

7 FA signal

2 Core

EXFx-FIRE-STS

Fan Panel

BMS DDC shall provide potential free (N.O.) contact to Damper actuator. DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. DDC BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) Fan Panel BMS DDC shall provide potential free (N.O.) contact to Fan Panel. DDC BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel.

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS not inof commo HAILS to revert with Common specific damper application

Response by ANC

No Dampers are there.

Client to confirm

Cofirmed.

Ok

design scope hence removed. Closed HAILS to revert with Common specific damper application not inof commo design scope hence removed. Closed Ok, Closed

Cofirmed.

Ok

Ok, Closed

Cofirmed.

Ok

Ok, Closed

Cofirmed.

Ok

Ok, Closed

Directly controlled by CO sensors provided by ETA. Closed

BMS Shall provide fire signal Ok, to will Fan take Starters fromafter FAS CR confirmation Ok, module Closed of fire. Fire Fan signal can be given started fromaccordingl FAS CR to Extract Fan panel. Closed NOT IN SCOPE OF ANC to confirm. ETA. ANC TO CONFIRM

III LIFT 1 Floor Position 2 Door fully Closed Signal 3 Status of Landing Floor (Open/Close) 4 Inspection Status (Normal/Maintenance) 5 Emergency Stop Status 6 Fault Indication 7 Fireman Switch Status 8 Lift Auto/Manual Status 9 Lift Run Status IV FCU FOR COMMON AREAS (Max. 10 Points per FCU)

14 14 14 14 14 14 14 14 14 14 100 1000 FCUs Points data mapping into BMS software. 2 Core1 LIFT-COMM (Daisy Chain) DDC LIFT 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to Lifts in daisy chain. 3) Lift point data mapping into BMS Software. Shall provide - 1) Lift Modbus RTU RS-485 wire terminals. 2) Lift Modbus register mapping list. 3) Lift Configuration as per site requirement. 4) Demonstrate Lift communication in open Modbus software like MODSCAN at site.

ANC Provided the ANC LIFT to DATA. provide HAILS Modbus to revert with details. OPEN

1) Shall provide BACnet/IP HAIL to provide/generate controller's Make, Model, PIC Statement & Point mapping list. 2) Demonstrate Device communication in open BACnet software at site after commissioning of BACnet/IP

24VAC ETA to to provide Actuator FCU & Temperature ANC will revert. Sensing TheEquipment end to endas FCU per the requir data on BACnet/IP and control solution to given scope of work shall be by HAIL additionally. till BACnet/IP gateway Closed and then HAIL scope of work start after gateway. ETA to show BACnet/IP data in open

V BTU METER VIA M-BUS 1 Supply Temperature 2 Return Temperature 3 Delta Temperature 4 Flow Rate 5 Total Flow 6 Power 7 Energy VI PUBLIC HEALTH ENGG. A TRANSFER PUMP 1 H/O/A Switch in auto position

98 98 98 98 98 98 98 98 Total 98 BTU Meters are already supplied by ETA as per original scope. 2 Core1 BTU-COMM (Daisy Chain) DDC BTU Supply, Installation, Testing Flow meter installation & and Commissioning of provision of 2 nos.1/2" NPT Ultrasonic BTU meter. socket for Immersion Temp Sensors installation.

MODBUS port available HAILs in Need to develop further the clarifications logic and confirm from cleint. that works HAIL already with Modbus ETA considered proposed interface system M- Bus BTU . BTU Meter through which confirmed by ETA HAIL can access the & Closed required signals.

4 4 4 Core 4 TX-Px-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) Pump Panel shall provide potential free (N.O.) Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

2 - flushing & 2 - domestic pumps. Closed

Sl. PARTICULARS NO 2 Run Status

QTY I/O DETAILS AI DI AO 4

4 Core DO Soft

Type Runs

CABLE DETAILS Tag From TX-Px-RUN-STS Pump Panel

To DDC

HAIL'S Scope of Work

CLIENT'S Scope of Work Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall accept potential free (N.O.) contact from BMS DDC.

Response by ETA Confirmed

Response by HAIL Ok

Response by ANC Ok, Closed

3 Trip Status

4 Core

TX-Px-TRIP-STS

Pump Panel

4 On/Off Command

TX-Px-ONOF-CMD

DDC

BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) Pump PanelBMS DDC shall provide potential free (N.O.) contact to Pump Panel.

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

Confirmed

Ok

Ok, Closed

HAIL to generate outputs Provision for single NO/NC HAILs to be tomade develop in panel the ETA logic confirmed by ETA. and confirm In single undesirable that works cond for Start & Stop. point contact for - Start Signal shall be of start/stop. Closed Latching Type (N.O.) - Stop Signal shall be Momentary

B SUMP PUMP 1 Unit Fault status

6 6 4 Core 6 SUMP-Px-FAULT Pump Panel DDC BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Trip Status is Available Ok, client to confirm Sump pump controlled by ETA, only monitoring by HAIL. Closed

2 Run Status

SUMP-Px-RUN-STS Pump Panel

DDC

Confirmed.

Ok

3 Auto Manual Status

2 Core

SUMP-Px-A/M-STS Pump Panel

DDC

Confirmed. Auto Mode Status Ok shall be provided

C BOOSTER PUMP 1 H/O/A Switch in auto position

6 6 4 Core 6 BSTR-Px-A/M-STS Pump Panel BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump PanelBMS DDC shall provide potential free (N.O.) contact to Pump Panel. DDC Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall accept potential free (N.O.) contact from BMS DDC. Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

3 Trip

BSTR-Px-TRIP-STS Pump Panel

Confirmed.

Ok

Ok, Closed

2 Run Status

4 Core

BSTR-Px-RUN-STS Pump Panel

Confirmed.

4 On/Off Command

BSTR-Px-ONOF-CMD

DDC

5 6 7 8 9 10 11

VFD soft integration Pump VFD Speed Feedback Pump VFD Frequency Pump VFD Current Pump VFD Voltage Pump VFD Power Pump VFD Run Time

6 6 6 6 6 6 6 1 6 6 12 13 13 2 Core1 daisy chain MTRx-FLOW Flow Meter DDC 2 Core 1 FIRE-TANK-LVL Level Sensor DDC Supply and Installation of Level Pressure Sensor BMS DDC shall accept 0-10 Vdc signal from water flow meter. 2 Core 1 VFD-COMM (Daisy Chain) DDC Pump VFD 1) Supply, Installation, Shall provide - 1) VFD Modbus Testing & Commissioning of RTU RS-485 wire terminals. Modbus RS485 2) VFD Modbus register Integrator. mapping list. 2) Communication Cable 3) VFD Configuration as per laying from integrator to site requirement.

Pump controlled interpritably by pressure sensor, hence status not HAIL to generate outputs Provision for single NO/NC HAILs to be tomade develop in panel the Pump logic by controlled ETA. and confirm In undesirable that works cond for Start & Stop. interpritably by pressure - Start Signal shall be of sensor by ETA. Closed Latching Type (N.O.) - Stop Signal shall be Momentary Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed Through MODBUS port Ok, inprovide VFD Through MODBUS port in parameter list Through MODBUS port in to 16-95 for 16-00 Through MODBUS port inregister Through MODBUS port in address 416000 Through MODBUS port in 416950. Ok, Closed

Ok

Ok, Closed

D WATER TANK 1 Tank Level 2 High/Low Level Alarm 3 Water meter

Suitable provision for level pressure sensor installation

6 = 3 - fire+ domestic+ flushing at basement & 3 fire+ domestic+ flushing at

Water flow meter shall providde 0-10Vdc signal for BMS interface with

Selected Water Meter shall ETA beto BMS specify competiable extact interface through ETA toMODBUS/Equivalent with revert BMS. Qty & Modbus communication interface protoco with detailed confirmed by ETA. Closed technical data

VII FIRE FIGHTING SYSTEM A FIRE FIGHTING PUMP 1 Pump auto-manual status 1 1 4 Core 1 FFP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) Pump Panel shall provide potential free (N.O.) Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

Sl. PARTICULARS NO 2 Pump run status

QTY I/O DETAILS AI DI AO 1

4 Core DO Soft

Type Runs

CABLE DETAILS Tag From FFP-RUN-STS Pump Panel

To DDC

HAIL'S Scope of Work BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.)

CLIENT'S Scope of Work Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.)

Response by ETA Confirmed.

Response by HAIL Ok

Response by ANC Ok, Closed

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

3 Pump fault status

2 Core

FFP-FLT-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

4 Trip Status

2 Core

FFP-TRIP-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

Trip status already considered hence not require. Ok, Closed

B JOCKEY PUMP 1 Pump auto-manual status

1 1 4 Core 1 JKP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

2 Pump run status

JKP-RUN-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

3 Pump fault status

2 Core

JKP-FLT-STS

Pump Panel

DDC

4 Trip Status

2 Core

JKP-TRIP-STS

Pump Panel

DDC

Not Required. As it is meant Ok, client for system to confirm pressurization HAILS to only. revert with Trip specific status shortcoming already as per E considered hence not require. Ok, Closed Confirmed. Ok Ok, Closed

C DIESEL ENGINE PUMP 1 Pump auto-manual status

1 1 4 Core 1 DEP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) Confirmed. Auto Mode Status Ok shall be provided Ok, Closed

2 Pump run status

DEP-RUN-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

3 Pump fault status

2 Core

DEP-FLT-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

4 Trip Status

2 Core

DEP-TRIP-STS

Pump Panel

DDC

Confirmed.

Ok

Ok, Closed

Trip status already considered hence not require. Ok, Closed

D MOTORISED FIRE DAMPER 1 Damper On/Off Status

## 140 2 Core 140 FDx-ONOF-STS Fire Damper BMS DDC shall accept potential free (N.O.) Fire Damper BMS DDC shall provide potential free (N.O.) contact to Fire Damper. DDC BMS DDC shall accept potential free (N.O.) DDC Fire Damper shall provide potential free (N.O.) Fire Damper shall accept potential free (N.O.) contact from BMS DDC. Sprinkler flow switch shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

2 Damper On/Off Command

2 Core140

FDx-ONOF-CMD

DDC

To

be

routed

throughOk, control client to module confirm of FDAHAIls system. to revert his FAS acceptance. CR module will be provided for fire damper. Closed Ok Ok, Closed

E Flow Switch for Fire Sprinkler System

32

32

2 Core

32

SPRINK-FSx-STS

Flow Switch

Confirmed.

VIIIELECTRICAL SYSTEM A LV PANEL 1 Incoming breaker 1 1 4 Core 1 LV-P1-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall provide potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

2 Trip alarm indication of main incoming breaker

LV-P1-IC-TRIP-STS

Panel

DDC

Confirmed.

Ok

Ok, Closed

3 Breaker Trip Command

2 Core

LV-P1-IC-TRIP-CMD

DDC

Panel

Confirmed.

Ok

Ok, Closed

Outgoing breaker

Confirmed.

Ok

Ok, Closed

Sl. PARTICULARS NO

QTY I/O DETAILS AI DI AO 4

DO

Soft

Type Runs 4 Core 4

CABLE DETAILS Tag From LV-P1-OGx-ONOF-STS Panel

To DDC

HAIL'S Scope of Work BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall provide potential free (N.O.) BMS DDC shall accept potential free (N.O.)

CLIENT'S Scope of Work Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC.

Response by ETA Confirmed.

Response by HAIL Ok

Response by ANC Ok, Closed

1 ON/OFF Status of each main outgoing breaker

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

2 Trip alarm indication of main outgoing breaker

LV-P1-OGx-TRIP-STS

Panel

DDC

Confirmed.

Ok

Ok, Closed

3 Breaker Trip Command

2 Core

LV-P1-OGx-TRIP-CMD

DDC

Panel

Confirmed.

Ok

Ok, Closed

4 Fire Suppression System

2 Core

FIRE-SUP-SYS1-STS Fire Panel

DDC

Not Required.

Ok, client to confirm

HAILS to revert shorcoming ETA to provide on proposed potential applicatio free contact. Closed

B LV PANEL 2 Incoming breaker

1 ON/OFF Status of each main incoming breaker

4 Core

LV-P2-IC-ONOF-STS

Panel

DDC

2 Trip alarm indication of main incoming breaker

LV-P2-IC-TRIP-STS

Panel

DDC

3 Breaker Trip Command

2 Core

LV-P2-IC-TRIP-CMD

DDC

Panel

Outgoing breaker

4 4 4 Core 4 LV-P1-OGx-ONOF-STS Panel DDC

BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall provide potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.) BMS DDC shall provide potential free (N.O.) BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

Ok, Closed

Confirmed.

Ok

Ok, Closed

Confirmed.

Ok

Ok, Closed

Confirmed. Confirmed.

Ok Ok

Ok, Closed Ok, Closed

1 ON/OFF Status of each main outgoing breaker

2 Trip alarm indication of main outgoing breaker

LV-P1-OGx-TRIP-STS

Panel

DDC

Confirmed.

Ok

Ok, Closed

3 Breaker Trip Command

2 Core

LV-P1-OGx-TRIP-CMD

DDC

Panel

Confirmed.

Ok

Ok, Closed

4 Fire Suppression System

2 Core

FIRE-SUP-SYS1-STS Fire Panel

DDC

Not Required.

Ok, Client to confirm

HAILS to revert shorcoming ETA to provide on proposed potential applicatio free contact. Closed

B LV PANEL 3 Incoming breaker

1 ON/OFF Status of each main incoming breaker 2 Trip alarm indication of main incoming breaker 3 Breaker Trip Command Outgoing breaker 5

1 1 1

4 Core

LV-P2-IC-ONOF-STS LV-P2-IC-TRIP-STS

Panel Panel DDC

DDC DDC Panel

2 Core

LV-P2-IC-TRIP-CMD

BMS DDC shall accept potential free BMS DDC shall accept potential free BMS DDC shall provide potential free BMS DDC shall accept potential free accept BMS DDC shall potential free provide BMS DDC shall potential free accept BMS DDC shall potential free

Panel shall provide potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall accept potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall accept potential free (N.O.) Panel shall provide potential free (N.O.)

Confirmed. Confirmed. Confirmed. Confirmed. Confirmed. Confirmed. Confirmed. Not Required.

Ok Ok Ok Ok Ok Ok Ok Ok, Client to confirm

Ok, Closed Ok, Closed Ok, Closed Ok, Closed Ok, Closed Ok, Closed Ok, Closed

1 ON/OFF Status of each main outgoing breaker 2 Trip alarm indication of main outgoing breaker 3 Breaker Trip Command 4 Fire Suppression System I ESMDB Incoming breaker 1 1

5 0 0 1

4 Core

LV-P1-OGx-ONOF-STS LV-P1-OGx-TRIP-STS

Panel Panel DDC

DDC DDC Panel DDC

2 Core 2 Core

4 1

LV-P1-OGx-TRIP-CMD

FIRE-SUP-SYS1-STS Fire Panel

HAILS to revert shorcoming ETA to provide on proposed potential applicatio free contact. Closed

1 ON/OFF Status of each main incoming breaker

2 Core

ESMDB-IC-ONOF-STS

Panel

DDC

Outgoing breaker

6 6 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC

BMS DDC shall accept potential free (N.O.) BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

Ok, Closed

1 ON/OFF Status of each main incoming breaker

Confirmed.

Ok

Ok, Closed

MCC - B

Sl. PARTICULARS NO Incoming breaker

QTY I/O DETAILS AI DI AO 1 1

DO

Soft

Type Runs

CABLE DETAILS Tag From

To

HAIL'S Scope of Work

CLIENT'S Scope of Work

Response by ETA

Response by HAIL

Response by ANC Ok, Closed

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

1 ON/OFF Status of each main incoming breaker

2 Core

ESMDB-IC-ONOF-STS

Panel

DDC

BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

EMCC - B Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB - B Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC

1 ON/OFF Status of each main incoming breaker

BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

ok

Ok, Closed

MCC - PUMP Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

MCC SUMP PUMP Incoming breaker

2 2 2 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

MCC ETS Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC

1 ON/OFF Status of each main incoming breaker

BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

Ok, Closed

SMDB - G Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

MCC - R1 Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

MCC - R2 Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC

1 ON/OFF Status of each main incoming breaker

BMS DDC shall accept potential free (N.O.)

Panel shall provide potential free (N.O.) contact to BMS DDC.

Confirmed.

Ok

Ok, Closed

SMDB UR Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB RT Incoming breaker

1 1

Sl. PARTICULARS NO

QTY I/O DETAILS AI DI AO 1

DO

Soft

Type Runs 2 Core 1

CABLE DETAILS Tag From ESMDB-IC-ONOF-STS Panel

To DDC

HAIL'S Scope of Work BMS DDC shall accept potential free (N.O.)

CLIENT'S Scope of Work Panel shall provide potential free (N.O.) contact to BMS DDC.

Response by ETA Confirmed.

Response by HAIL Ok

Response by ANC Ok, Closed

1 ON/OFF Status of each main incoming breaker

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS

EMCC - R Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB UPS Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB UPS II Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB GYM Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB F & B Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

SMDB CF1 & CF2 Incoming breaker

2 2 2 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

MCC FF Incoming breaker

1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

FLOOR SMDBs Incoming breaker

28 28 28 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

TENANT SMDBs Incoming breaker

73 73 73 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact to BMS DDC. Confirmed. Ok Ok, Closed

1 ON/OFF Status of each main incoming breaker

N TRANSFORMERS

Sl. PARTICULARS NO 1 Signals for monitoring

QTY I/O DETAILS AI DI AO 3

DO

Soft

Type Runs 2 Core 3

CABLE DETAILS Tag From TX-SINGx-MTR Panel

To DDC

HAIL'S Scope of Work

CLIENT'S Scope of Work

Response by ETA

Response by HAIL

Response by ANC

2 Signals for monitoring

16

4 Core

TX-SINGx-STS

Panel

DDC

BMS DDC shall accept 0-10 Vdc Panel signal shall from providde panel 0-10Vdc signal for BMS interface with DDC. BMS DDC shall accept Panel shall provide potential potential free free (N.O.) (N.O.) contact to BMS DDC.

Confirmed. Please refer Ok. attached ETA to details show exact for signals. TBs Ok, atClosed site

As per MOM dated 06Feb-2013 between ANC, ETA, HAIL & ILFS to be Point description share by ETA. OPEN

Confirmed. Please refer Ok. attached ETA to details show exact for signals. TBs Ok, atClosed site

Point description to be share by ETA. OPEN

O HT PANELS/BREAKERS 1 Signals for monitoring

4 3 2 Core 3 HT-SINGx-MTR Panel DDC BMS DDC shall accept 0-10 Vdc Panel signal shall from providde panel 0-10Vdc signal for BMS interface with DDC. BMS DDC shall accept Panel shall provide potential potential free free (N.O.) (N.O.) contact to BMS DDC. Client to clarify ETA To respond Point description to be share by ETA. OPEN Point description to be share by ETA. OPEN

2 Signals for monitoring

32

4 Core

16

HT-SINGx-STS

Panel

DDC

Client to clarify

ETA To respond

P LOAD MANAGERS INTEGRATION ENERGY METERS 91 INTEGRATION

Can be taken through RS - 485Port. Ok Cat. Attached as ready Ok, Closed reference. Please refer SLD for exact locations of Lo

1 2 3 4 5 6 7 8 9 10

Average Current Voltage Kilowatt Run hour Power Factor Forward Active Energy Power Factor Average Line to Line Voltage Average Line to Line Neutral Average Frequency 64 64 64 1 1 1 1 1 1 2

91 91 91 91 91 91 91 91 91 91

2 Core1 EM-COMM (Daisy Chain)

DDC

Load 1) Supply, Installation, Manager Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to EMs in daisy chain. 3) EM point data mapping into BMS Software.

Shall provide - 1) EM Modbus Through RS - 485 Port RTU RS-485 wire terminals. of Multi 2) EM Modbus register mapping Function Mtrs. list. 3) EM Configuration as per site requirement. 4) Demonstrate EM communication in open Modbus software like MODSCAN

Q LIGHTING CONTROL 1 Circuit open/close status 2 Circuit open/close command R AIRCRAFT WARNING LIGHT 1 Circuit on/off status 2 Circuit trip alarm S PA/BGM SYSTEM 1 Panel power ON status 2 Panel fault status U UPS 1 2 3 4 5 6 7 8 9 10 O/P Voltage - R O/P Voltage - Y O/P Voltage - B O/P Current - R O/P Current - Y O/P Current - Y Battery Voltage Battery Charge Remaining Frequency Alarm Status

4 Core

64

LP-CKT-ONOF-STS LP-CKT-ONOF-CMD

Panel DDC

DDC Panel

BMS DDC shall accept potential free provide BMS DDC shall potential free

Panel shall provide potential free (N.O.) Panel shall accept potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall provide potential free (N.O.) Panel shall provide potential free (N.O.)

Confirmed. Confirmed.

Ok Ok

Ok, Closed Ok, Closed

4 Core

AL-CKT-ONOF-STS AL-CKT-TRIP-STS

Panel Panel

DDC DDC

BMS DDC shall accept potential free BMS DDC shall accept potential free BMS DDC shall accept potential free BMS DDC shall accept potential free 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to UPSs in daisy chain. 3) UPS point data mapping into BMS Software. DVM Interface

As it is Ok, being client provided to confirm through ETA normal will Provide MCB only Ok, Closed potential free Not Available. Ok, client to confirm ETA will Provide Ok, Closed potential free NOT IN SCOPE OF ETA PAS BY HAIL Ok Ok AVAILABLE THROUGH Ok, MODBUS ETA toPORT provide Modbus details as through MODBUS Port in mentioned through MODBUS Port in in client's scope through MODBUS Port of inwork through MODBUS Port in through MODBUS Port in through MODBUS Port in through MODBUS Port in through MODBUS Port in through MODBUS Port in through MODBUS Port in OK, HAIL DVM OK, HAIL ESSER OK, HAIL TEMA Ok, Closed Ok, Closed Ok, Closed

Not

Available.

4 Core

BMG-CKT-ONOF-STS BMG-CKT-FLT-STS

Panel Panel

DDC DDC

2 2 2 2 2 2 2 2 2 2

2 Core1 UPS-COMM (Daisy Chain)

DDC

UPS

Shall provide - 1) UPS Modbus RTU RS-485 wire terminals. 2) UPS Modbus register mapping list. 3) UPS Configuration as per site requirement. 4) Demonstrate UPS communication in open Modbus software like MODSCAN

Available Available Available Available Available Available Available Available Available Available

IX CCTV SYSTEM INTEGRATION X FIRE ALARM SYSTEM INTEGRATION XI ACCESS CONTROL SYSTEM TOTAL 382 1092 229 205 6740 3200

NOT IN SCOPE OF ETA NOT IN SCOPE OF ETA NOT IN SCOPE OF ETA

Ok, Closed Ok, Closed Ok, Closed

Modbus Interface Tema Interface