Lexic:

who better than you to talk about it!

A COMPLETE RANGE FOR ALL APPLICATIONS

In choosing Lexic, I feel we have opted for a universal solution which answers all the problems we may encounter on site. This complete range guarantees consistency and uniformity in our consumer units.

Lexic: a universal range


Equally well suited to residential applications and large commercial installations, Lexic offers a complete range of protection devices and control/signalling auxiliaries. From 3000 A in accordance with domestic standard IEC 60898-1 to 50 kA for industrial standard IEC 60947-2, it is now one of the most comprehensive offers on the market and also ensures superb aesthetics and overall uniformity of appearance.

Being compliant with both the IEC 60898-1 and IEC 60947-2 standards, Lexic DX and DX-H MCBs are suitable for a very wide range of applications: domestic, commercial and industrial.

The wide choice of residual current devices means people can be protected in any scenario.

Breaking capacity IEC 60898-1 3000


LEXIC ALSO INCLUDES a complete range of additional functions: signalling, time delay, etc.

IEC 60947-2 10 kA 12.5 to 25 kA(1) 50 kA

Curve C B and C B and C C C

Rating 1 to 40 A 2 to 40 A 1 to 63 A 2 to 125 A 10 to 63 A

4500 6000 10000 -

The extensive technical characteristics of Lexic circuit breakers mean all types of project can be handled, from small residential to largescale service sector projects, from the main LV distribution board to the final distribution board.
(1) depending on ratings

RCD

RCBO

Add-on module

Isolating switch

1P/1 module MCB

3P/3 module MCB

High breaking capacity MCB

01

I know that Legrand attaches particular importance to the performance of its Lexic circuit breakers. Individually tested in the factory and conforming to international standards such as NF, the user can be sure of high-quality operation. We find it very reassuring!

02

Lexic: impeccable quality


Legrand pays particular attention to how these device perform, so each of them is set and checked individually on the production lines. Legrand's factories are certified ISO 9001 for quality and ISO 14001 for environmental protection.

The tripping characteristics are calculated and adjusted to ensure correct discrimination between the different protection levels in order to improve the user experience.

The different Hpi, the impeccable quality of the electronic circuits and components are designed to improve continuity of service by avoiding false tripping and provide better protection for people.

Lexic products are certified in accordance with international product standards. All approvals such as NF, universally recognised for its very high level requirements, are renewed annually.

THE BEST-PERFORMING CIRCUIT BREAKERS Lexic circuit breakers are in limitation class 3: they limit the short-circuit power in the cables and can prolong the installation's life by avoiding damage to the cables caused by the stress of power flowing through them. Products never work at the limit of their capacity.

03

I really appreciate the chance to mix and match protection and control devices on the same row. The Lexic range offers us real freedom of installation while letting us stick to our usual wiring practices!

04

Mix and match any function with the Lexic concept: protection, control, and signalling devices can thus be grouped by physical zone in the installation in the same order as the circuit diagram. The control and signalling devices and auxiliaries have a slot to allow the supply busbar to pass through.

Lexic: freedom of installation

Each circuit breaker can take up to 3 auxiliaries and 1 add-on module. The auxiliaries are common to the whole Lexic range.

Monobloc RCBOs up to 63 A save precious space in switchboards.

Lexic devices can be supplied with power via the bottom or the top to suit all types of wiring practice.

05

The Lexic range is reassuringly well designed. All the devices have 35 mm terminals so I can make connections which are perfectly safe. I have complete peace of mind when wiring up my switchboards.

06

Lexic: safety and ease of connection


The Lexic range ensures safety of installation and simplifies wiring operations. With wide terminals providing reliable, lasting connections, a wire guide and enhanced cable tensile resistance, Lexic ensures ease of installation and peace of mind.

The Lexic range guarantees IP2x protection. It prevents any risk of contact with live parts, even when the faceplate is open.

Lexic devices have a wire guide flap on their terminals, which avoids connection errors.

Prong or fork-type supply busbars eliminate any risk of short-circuits and provide a totally reliable connection via the top or bottom of the device. Easy to use, they can be adapted to suit any type of connection practice.

EXCLUSIVE TO LEGRAND
ALL LEXIC SWITCHES AND CIRCUIT BREAKERS HAVE LARGECAPACITY 35 MM TERMINALS FOR EASE OF CONNECTION. - The shape of the screws and terminals guarantees excellent mechanical withstand of the wires and limits the contact impedance, temperature rise and heat loss.

07

Marking of product characteristics, protected label holder really useful features which save me precious time when undertaking maintenance!

08

Lexic: simplicity and safety of maintenance


The many advantages of the Lexic range can optimise intervention times during maintenance operations without compromising on safety: product marking, circuit identification and coloured handles mean functions can be quickly identified Genuinely useful features which simplify operation and maintenance.

The label holder on the product front face protects the labels effectively and durably so that the circuits are easily identifiable.

To make it safe to work on the consumer unit and prevent accidental restarts, the handles can be padlocked.

Double clips on the back of the products can be used to remove individual devices without unscrewing the whole row.

Control handle - grey: isolating switch - black: circuit breaker Breaking capacity in accordance with IEC 60947-2 Rated voltage Breaking capacity in accordance with IEC 60898-1 Limitation class I - ON/red O - OFF/green Curve and rated current Circuit diagram

The clear and comprehensive marking on products makes the technical characteristics easier to read and allows the user to intervene quickly without the risk of making a mistake. The state of the contacts can be seen quickly thanks to the colour-coded marking on the handle (red: closed, green: open).

09

Catalogue Pages
On the following pages, you will find all the technical information and product characteristics for the Lexic offer.

10

MCBs and RCDs LRTM 6000

thermal magnetic MCBs from 6 A to 63 A - B and C curves residual current devices from 25 A to 63 A - AC and A types

6048 96

6048 50

6021 93

6021 53

MCBs: Conform to IEC 60898-1 Breaking capacity: 6000 - IEC 60898-1 - 230/400 V / 6 kA - IEC 60947-2 - 230/400 V 10000 - IEC 60898-1 - 127/220 V / 10 kA - IEC 60947-2 - 127/220 V Do not accept auxiliaries, and add-on modules RCDs: Conform to IEC 61008-1
Pack Cat.Nos

MCBs
Single pole - 230/400 V
In Number of modules

Pack

Cat.Nos

MCBs (continued)
4-pole - 400 V 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
In Number of modules

10 10 10 10 10 10 10 10 10 10

6049 02 6049 03 6049 04 6049 05 6049 06 6049 07 6049 08 6049 09 6049 10 6049 11

B curve

6048 02 6048 03 6048 04 6048 05 6048 06 6048 07 6048 08 6048 09 6048 10 6048 11

C curve

6A 1 10 A 1 13 A 1 16 A 1 20 A 1 25 A 1 32 A 1 40 A 1 50 A 1 63 A 1 Single pole + neutral - 230 V 6A 10 A 13 A 16 A 20 A 25 A 32 A 2-pole - 400 V


In In Number of modules

1 1 1 1 1 1 1 1 1

6048 47 6048 48 6048 50 6048 51 6048 52 6048 53 6048 54 6048 55 6048 56

C curve

4 4 4 4 4 4 4 4 4

5 5 5 5 5 5 5

6048 90(1) 6048 91(1) 6048 92(1) 6048 93(1) 6047 90(1) 6047 91(1) 6047 92(1) 6049 17 6049 18 6049 19 6049 20 6049 21 6049 22 6049 23 6049 24 6049 25 6049 26
B curve B curve

C curve

RCDs
AC type

2 2 2 2 2 2 2

A type

2-pole - 230 V - 30 mA 25 2 40 2 63 2 2-pole - 230 V - 100 mA 25 2 40 2 2-pole - 230 V - 300 mA


Nominal rating (A) Number of modules

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

6021 36 6021 37 6021 93 6021 38 6021 39 6021 40 6021 42 6021 43 6021 44

5 5 5 5 5 5 5 5 5 5

6048 17 6048 18 6048 19 6048 20 6048 21 6048 22 6048 23 6048 24 6048 25 6048 26
C curve

C curve

6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 3-pole - 400 V
In

Number of modules

2 2 2 2 2 2 2 2 2 2

1 1 1 1 1 1 1 1 1 1

6049 32 6048 32 6049 33 6048 33 6048 34 6049 35 6048 35 6049 36 6048 36 6049 37 6048 37 6049 38 6048 38 6049 39 6048 39 6049 40 6048 40 6049 41 6048 41 6047 96(1) 6048 94(1) 6048 95(1) 6048 96(1) 6048 97(1) 6048 98(1) 6048 99(1) 6047 97(1) 6047 98(1) 6047 99(1)
C curve

6A 3 10 A 3 13 A 3 16 A 3 20 A 3 25 A 3 32 A 3 40 A 3 50 A 3 63 A 3 3-pole + neutral - 400 V 6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A


In

Number of modules

25 2 40 2 63 2 4-pole - 400 V - 30 mA 6021 46(1) 25 4 6021 47(1) 6021 94(1) 40 4 6021 95(1) 63 4 4-pole - 400 V - 100 mA 6021 49(1) 6021 50(1) 6021 52(1) 6021 53(1) 25 4 40 4 4-pole - 400 V - 300 mA 25 40 4 4

Number of modules

1 1 1 1 1 1 1 1 1 1

4 4 4 4 4 4 4 4 4 4

(1) Neutral on right-hand side

11

MCBs DX-E 6000 - 6 kA

thermal magnetic MCBs from 6 A to 63 A B and C curves

MCBs DX 10kA

thermal magnetic MCBs from 6 A to 63 A B and C curves

032 70

034 33

033 28

6062 02

6062 72

Technical characteristics (p. 23-25) Breaking capacity 6000 - IEC 60898-1 - 400 VA 6 kA - IEC 60947-2 - 400 VA Do not accept add-on modules
Pack B curve Cat.Nos C curve

Technical characteristics (p. 23-25) Breaking capacity 10 kA - IEC 60947-2 - 400 VA


Pack B curve Cat.Nos C curve

Single pole - 230/400 V


Nominal rating (A)

Single pole - 230/400 V


Nominal rating (A)

10 10 10 10 10 10 10 10 10 10

032 66 032 68 032 69 032 70 032 71 032 72 032 73 032 74 032 75 032 76

033 82 033 84 033 85 033 86 033 87 033 88 033 89 033 90 033 91 033 92

6 10 13 16 20 25 32 40 50 63

Number of modules

10 10 10 10 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1

6062 02 6062 03 6062 04 6062 05 6062 06 6062 07 6062 08 6062 09 6062 10

6062 46 6062 47 6062 48 6062 49 6062 50 6062 51 6062 52 6062 53 6062 54

6 10 16 20 25 32 40 50 63

Number of modules

1 1 1 1 1 1 1 1 1

Green Red Grey Blue Yellow Violet Black White Copper

Handle colour

2-pole - 400 V
5 5 5 5 5 5 5 5 5 5

3-pole - 400 V
1 1 1 1 1 1 1 1 1

033 08 033 10 033 11 033 12 033 13 033 14 033 15 033 16 033 17 033 18

B curve

034 29 034 31 034 32 034 33 034 34 034 35 034 36 034 37 034 38 034 39

C curve

Nominal rating (A)

6 10 13 16 20 25 32 40 50 63

Number of modules

2 2 2 2 2 2 2 2 2 2

3-pole - 400 V
1 1 1 1 1 1 1 1 1 1

6062 24 6062 25 6062 26 6062 27 6062 28 6062 29 6062 30 6062 31 6062 32

B curve

6062 68 6062 69 6062 70 6062 71 6062 72 6062 73 6062 74 6062 75 6062 76

C curve

Nominal rating (A)

6 10 16 20 25 32 40 50 63

Number of modules

3 3 3 3 3 3 3 3 3

Green Red Grey Blue Yellow Violet Black White Copper

Handle colour

033 22 033 24 033 25 033 26 033 27 033 28 033 29 033 30 033 31 033 32

B curve

034 47 034 49 034 50 034 51 034 52 034 53 034 54 034 55 034 56 034 57

C curve

Nominal rating (A)

6 10 13 16 20 25 32 40 50 63

Number of modules

3 3 3 3 3 3 3 3 3 3

Auxiliaries and accessories for MCBs (p. 22)

4-pole - 400 V
1 1 1 1 1 1 1 1 1 1

033 68 033 70 033 71 033 72 033 73 033 74 033 75 033 76 033 77 033 78

B curve

034 89 034 91 034 92 034 93 034 94 034 95 034 96 034 97 034 98 034 99

C curve

Nominal rating (A)

6 10 13 16 20 25 32 40 50 63

Number of modules

4 4 4 4 4 4 4 4 4 4

12

remote trip isolating switches DXTM - IS


from 16 A to 125 A

isolating switches DXTM - IS


from 16 A to 125 A

073 61

023 58

023 66

043 22

043 26

043 74

Technical characteristics (p. 23-25) AC 22 A according to IEC 60947 - 3 Double break contacts
Pack Cat.Nos

Technical characteristics (p. 23-25) AC 22 A according to IEC 60947 - 3 Double break contacts
Pack Cat.Nos

Remote trip head isolating switches


Red handle (main device) Visible contact indication Remote tripping with associated control auxiliary Compatible with the following auxiliaries: - Control auxil. Cat.No 073 60/61/65/66/68/69 (p. 154) - Signalling auxil. Cat.No 073 50/54 (p. 154) Visual indication of the actual status of the contacts: - Closed position or fault (red indicator - I) - Open position (green indicator) on handle In case of fault when opening, the red position indicator indicates the faulty pole and the handle is in the central position 2P - 400 V

Isolating switches
Can be equipped with 1 signalling auxiliary Cat.Nos 073 50 or 073 54 (p. 154) 1P - 250 V

10 10 10 10 10 10

043 01 043 02 043 05 043 07 043 10 043 14

16 20 32 40 63 100 1P with indicator - 250 V Supplied with lamp 20

Nominal rating (A)

Number of modules

1 1 1 1 1 1

2 2 2 2 1 1 1 1 1 1 1 1

023 56 023 57 023 58 023 59 023 66 023 67 023 68 023 69 023 76 023 77 023 78 023 79

Nominal rating (A)

40 63 100 125

Number of modules

2 2 2 2 3 3 3 3 4 4 4 4

10

043 03

3P - 400 V 40 63 100 125 4P - 400 V 40 63 100 125

10 10 10 5 5 5 5

043 21 043 22 043 25 043 27 043 30 043 34 043 38

10 10

2P - 400 V 16 20 32 40 63 100 125 2P with indicator - 250 V Supplied with lamp 043 23 20 043 26 32

1 1 1 2 2 2 2

1 1

5 5 3 3 3 3 5 5 2 2 2 2

043 42 043 45 043 47 043 50 043 54 043 58 043 62 043 65 043 67 043 70 043 74 043 78

3P - 400 V 20 32 40 63 100 125 4P - 400 V 20 32 40 63 100 125

2 2 3 3 3 3 2 2 4 4 4 4

For three-phase version, please consult us

13

RCDs - DXTM

residual current devices from 16 A to 100 A - AC, A and Hpi types

6027 10

090 53

090 74

091 47

Technical characteristics (p. 25) AC type: detect AC component faults A type: detect AC and DC component faults Hpi type (High immunity): detect AC and DC component faults Enhanced immunity to unwanted tripping in disturbed environments Conform to IEC 61008 - 1
Pack Cat.Nos

2-pole - 230 V
AC type ? 10 mA
Nominal rating (A) Number of modules

Pack

Cat.Nos

4-pole - 400 V - Neutral on right-hand side


AC type ? 30 mA
Nominal rating (A) Number of modules

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

089 06 089 09 089 10 089 11 089 12 6027 10 089 15 089 16 089 17 089 18 089 27 089 28 089 29 089 30 6027 12 090 53 090 56 090 57 090 58 090 59 090 74 090 75 090 76 090 77 088 22 088 23 088 24

16 2 AC type ? 30 mA 25 2 40 2 63 2 80 2 100 2 AC type ? 100 mA 25 2 40 2 63 2 80 2 AC type ? 300 mA 25 2 40 2 63 2 80 2 100 2 A type M 10 mA 16 2 A type M 30 mA 25 2 40 2 63 2 80 2 A type M 300 mA 25 2 40 2 63 2 80 2 Hpi type MH 30 mA 25 2 40 2 63 2

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

089 93 089 94 089 95 089 96 089 99 090 00 090 01 090 02 090 11 090 12 090 13 090 14 090 18 090 19 090 23 090 24 090 25 090 26 091 40 091 41 091 42 091 43 091 44 091 46 091 47 091 48 091 49 091 50 091 58 091 59 091 60 091 61 091 62

25 4 40 4 63 4 80 AC type ? 100 mA 25 4 40 4 63 4 80 AC type ? 300 mA 25 4 40 4 63 4 80 AC type ? 300 mA selective 40 4 63 AC type ? 500 mA 25 4 40 4 63 4 80 A type M 30 mA 25 4 40 4 63 4 80 4 100 A type M 100 mA 25 4 40 4 63 4 80 4 100 A type M 300 mA 25 4 40 4 63 4 80 4 100 4

Auxiliaries and accessories (p. 22)

14

RCDs - DXTM

residual current devices from 25 A to 100 A - AC, A and Hpi types (continued)

technical characteristics

DXTM- IS isolating switches and DXTM-RCDs

n DX - IS isolating switches
Electrical characteristics
Thermal rating (Ith) Connection flexible rigid 16 - 32 A 1.5 to 16 mm2 40 - 63 A 1.5 to 25 mm2 1.5 to 35 mm2 250 - 400 V 4 kV AC 22 A AC 23 A 1700 A 3000 A > 30000 IP 2X wired 100 - 125 A 6 to 35 mm2 4 to 50 mm2 250 - 400 V 4 kV AC 22 A AC 23 A 2500 A 3700 A > 30000 IP 2X (> 25 mm2)

Insulation voltage (Hi) Impulse withstand voltage (Uimp) 086 95 Category of use(1)

250 - 400 V 4 kV AC 22 A AC 23 A 750 A 1500 A > 30000 IP 2X wired

Technical characteristics (p. 25) AC type: detect AC component faults A type: detect AC and DC component faults Hpi type (High immunity): detect AC and DC component faults Enhanced immunity to unwanted tripping in disturbed environments Conform to IEC 61008 - 1
Pack Cat.Nos

Short time withstand current (Icw) Short-circuit making capacity (Icm) No. of electrical operations Protection index

4-pole - 400 V - Neutral on right-hand side (continued)


A type M 300 mA selective
Nominal rating (A) Number of modules

(1) test conditions according to IEC 60947-3 AC 22 A: combined motor/resistor breaking AC 23 A: inductive motor breaking at In/2

n DX - RCDs (residual circuit devices)


Connection cross-section
RCDs Connection at top and bottom Cable (mm2) flexible 35

1 1 1 1 1 1 1 1

091 65 091 66 091 71 091 72 091 74 6021 08 6021 09 6021 10

40 4 63 4 A type M 500 mA 40 4 63 4 100 4 Hpi type MH 30 mA 25 4 40 4 63 4

rigid 50

n AC type ? - Standard applications


AC type RCDs detect AC residual currents In the majority of cases (standard applications), they are used for AC current detection at 50/60 Hz

4-pole - 400 V - Neutral on left-hand side


AC type ? 30 mA
Nominal rating (A) Number of modules

1 1 1 1 1 1

086 93 086 94 086 95

25 40 63 A type M 30 mA 090 98 25 090 99 40 091 00 63

4 4 4 4 4 4

n A type M - Specific applications: dedicated lines


In addition to the characteristics of AC type RCDs, A type RCDs also detect DC residual currents They are used whenever fault currents are not sinusoidal They are particularly suitable for the following specific applications (hobs, washing machines) or materials may produce DC fault currents, speed drives with frequency inverters, etc.

n Hpi type M H - Special applications


Type Hpi RCDs are devices which offer additional immunity to unwanted tripping which significantly exceeds the level required by the standard They are also able to detect AC and DC residual currents (A type) Operation between - 25 C and + 40 C They are used in special applications where: Loss of information is potentially damaging, e.g. power supply lines for computer equipment (banks, equipment on military bases, flight reservation centres, etc.) Loss of operation is potentially damaging (automated machinery, medical equipment, freezer cable, etc.) They are also used: On sites where there is an increased risk of lightning strikes (see p. 164) On sites where cables are subject to high levels of interference (use of fluorescents, etc.) On sites where very long cables are used

15

MCBs DXTM 6000 - 10 kA

thermal magnetic MCBs from 0.5 A to 63 A B and C curves

063 72

062 02

064 68

064 91

063 38

065 66

Technical characteristics (p. 23-25) Breaking capacity 6000 - IEC 60898-1 - 400 VA (230 VA for single pole + neutral) 10 kA - IEC 60947-2 - 400 VA (230 VA for single pole + neutral)
Pack B curve Cat.Nos C curve

Single pole - 230/400 V


Nominal rating (A) Number of modules

Pack B curve

Cat.Nos C curve

3-pole - 400 V
Nominal rating (A) Number of modules

1 1 1 1 10|1 10 10 10|1 10|1 10|1 1 1 1

061 52 061 53 061 54 061 55 061 56 061 58 061 60 061 61 061 62 061 63 061 64 061 65 061 66

063 68 063 69 063 70 063 71 063 72 063 74 063 76 063 77 063 78 063 79 063 80 063 81 063 82

1 2 3 4 6 10 16 20 25 32 40 50 63

1 1 1 1 1 1 1 1 1 1 1 1 1

Breaking capacity IEC 60947-2 (kA) 230 V

10 10 10 10 10 10 10 10 10 10 10 10 10

1 1 1 1 1 1 1 1 1 1 1 1 1

062 78 062 79 062 80 062 81 062 83 062 85 062 86 062 87 062 88 062 89 062 90 062 91

064 80 064 81 064 82 064 83 064 84 064 86 064 88 064 89 064 90 064 91 064 92 064 93 064 94

1 2 3 4 6 10 16 20 25 32 40 50 63

3 3 3 3 3 3 3 3 3 3 3 3 3

Breaking capacity IEC 60947-2 (kA) 400 V 230 V

10 10 10 10 10 10 10 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 25 25 25 25

Single pole + neutral - 230 V Neutral on right-hand side


B curve C curve Nominal rating (A) Number of modules Breaking capacity IEC 60947-2 (kA) 230 V B curve C curve

3-pole + neutral - 400 V Neutral on right-hand side


Nominal rating (A) Number of modules Breaking capacity IEC 60947-2 (kA) 400 V 230 V

1 1 1 1 1 1 10 10 1 1 1 1

061 95 061 96 061 97 061 98 062 00 062 02 062 03 062 04 062 05 062 06

064 01 064 03 064 04 064 05 064 06 064 07 064 09 064 12 064 13 064 14 064 15 064 16

0.5 1 2 3 4 6 10 16 20 25 32 40

1 1 1 1 1 1 1 1 1 1 1 1

10 10 10 10 10 10 10 10 10 10 10 10

1 1 1 1 1 1 1 1 1

063 31 063 34 063 36 063 37 063 38 063 39 063 40 063 41 063 42

065 39 065 41 065 43 065 44 065 45 065 46 065 47 065 48 065 49

6 10 16 20 25 32 40 50 63

4 4 4 4 4 4 4 4 4

10 10 10 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25

4-pole - 400 V
1 1 1 1 1 1 1 1 1 1 1 1 1

2-pole - 230/400 V
1 1 1 1 1|5 5 5 1|5 1 1 1 1 1

062 57 062 58 062 59 062 60 062 61 062 63 062 65 062 66 062 67 062 68 062 69 062 70 062 71

B curve

064 60 064 61 064 62 064 63 064 64 064 66 064 68 064 69 064 70 064 71 064 72 064 73 064 74

C curve

Nominal rating (A)

Number of modules

1 2 3 4 6 10 16 20 25 32 40 50 63

2 2 2 2 2 2 2 2 2 2 2 2 2

Breaking capacity IEC 60947-2 (kA) 400 V 230 V

10 10 10 10 10 10 10 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 25 25 25 25

065 55 065 56 065 57 065 58 065 59 065 61 065 63 065 64 065 65 065 66 065 67 065 68 065 69

C curve

Nominal rating (A)

Number of modules

1 2 3 4 6 10 16 20 25 32 40 50 63

4 4 4 4 4 4 4 4 4 4 4 4 4

Breaking capacity IEC 60947-2 (kA) 400 V 230 V

10 10 10 10 10 10 10 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 25 25 25 25

Add-on modules (p. 20) Auxiliaries and accessories (p. 22)

16

RCBO DXTM 6000 - 10 kA and DXTM 10000

residual current breaking overload from 3 A to 63 A - C curve, AC and A types

6064 00

6064 15

078 86

079 19

079 80

Technical characteristics (p. 23-25) Breaking capacity: 10000 - IEC 61009-1 - for single pole 6000 - IEC 61009-1 - 6 kA / IEC 60947-2 for single pole + neutral 6000 - IEC 61009-1 - 10 kA / IEC 60947-2 for 2 and 4 pole AC type: detect AC component faults A type: detect AC and DC component faults
Pack Cat.Nos Black neutral leads Blue neutral leads

Single pole - 230 V


AC type ? 30 mA
Nominal rating (A) Number of modules

Pack

Cat.Nos

2-pole - 230/400 V (continued)


AC type ? 30 mA
Nominal rating (A) Number of modules

1 1 1 1 1 1

6064 00 6064 01 6064 02 6064 03 6064 04 6064 05

6064 10 6064 11 6064 12 6064 13 6064 14 6064 15

10 16 20 25 32 45

1 1 1 1 1 1

Single pole + neutral - 230 V


Neutral on right-hand side AC type ? 10 mA
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

079 11 079 19 079 20 079 21 079 22 079 29 079 30 079 31 079 44 079 46 079 47 079 48 079 49 079 50 079 51 079 52

078 79 078 81 078 83 078 84 078 86 078 87 078 88 078 89 078 90 078 94 078 95 078 97 078 98 078 99 079 00 079 01 085 75 085 79 085 85 085 87 085 88 085 89 085 90 085 91

16 2 AC type ? 30 mA 3 2 6 2 10 2 16 2 20 2 25 2 32 2 40 2 AC type ? 300 mA 6 2 10 2 16 2 20 2 25 2 32 2 40 2 A type M 10 mA 16 2 A type M 30 mA 6 2 10 2 16 2 20 2 25 2 32 2 40 2

Nominal rating (A)

Number of modules

10 4 16 4 20 4 25 4 32 4 40 4 50 4 63 4 AC type ? 300 mA 10 4 16 4 20 4 25 4 32 4 40 4 50 4 63 4

4-pole - 400 V
AC type ? 30 mA
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Nominal rating (A) Number of modules

079 62 079 64 079 65 079 66 079 67 080 13 080 14 080 15 079 75 079 77 079 78 079 79 079 80 080 31 080 32 080 33 080 75 080 76 080 77 080 78 080 79 080 84 080 85 080 86 080 87 080 88

2-pole - 230/400 V
AC type ? 10 mA
1 1 1
Nominal rating (A) Number of modules

077 45 077 46 077 47

10 16 20

4 4 4

10 4 16 4 20 4 25 4 32 4 40 7 50 7 63 7 AC type ? 300 mA 10 4 16 4 20 4 25 4 32 4 40 7 50 7 63 7 A type M 30 mA 10 4 16 4 20 4 25 4 32 4 A type M 300 mA 10 4 16 4 20 4 25 4 32 4

17

MCBs DX-H 10000 - 25 kA

thermal magnetic, high breaking capacity MCBs from 2 A to 125 A C curve

068 60

069 20

064 76

069 43

070 00

Technical characteristics (p. 23-25) Breaking capacity 10000 IEC 60898-1 - 400 VA 25 kA to 12.5 kA - IEC 60947-2 - 400 VA
Pack Cat.Nos C curve

Single pole - 230/400 V


Nominal rating (A)

Pack

Cat.Nos C curve

3-pole - 400 V
Nominal rating (A)

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

068 53 068 54 068 56 068 58 068 59 068 60 068 61 068 62 068 63 068 64 068 65 068 66 063 83 063 84 063 85

2 3 6 10 13 16 20 25 32 40 50 63 80 100 125

Number of modules

1 1 1 1 1 1 1 1 1 1 1 1 1.5 1.5 1.5

Breaking capacity (kA) IEC 60947-2 230 V/400 V

25 25 25 25 25 25 25 20 15 12.5 12.5 12.5 12.5 12.5 12.5

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

069 33 069 34 069 36 069 38 069 39 069 40 069 41 069 42 069 43 069 44 069 45 069 46 064 95 064 96 064 97

2 3 6 10 13 16 20 25 32 40 50 63 80 100 125

Number of modules

3 3 3 3 3 3 3 3 3 3 3 3 4.5 4.5 4.5

Breaking capacity (kA) IEC 60947-2 400 V 230 V

25 25 25 25 25 25 25 20 15 15 12.5 12.5 12.5 12.5 12.5

50 50 50 50 50 50 50 50 50 50 25 25 16 16 16

Single pole + neutral - 230 V


Neutral on right-hand side
1 1 1 1 1 1 1 1 1 1
C curve Nominal rating (A) Number of modules Breaking capacity (kA) IEC 60947-2 230 V C curve

3-pole + neutral - 400 V


Neutral on right-hand side
1 1 1 1 1 1 1 1 1 1
Nominal rating (A) Number of modules Breaking capacity (kA) IEC 60947-2 400 V 230 V

068 96 068 98 068 99 069 00 069 01 069 02 069 03 069 04 069 05 069 06

6 10 13 16 20 25 32 40 50 63

2 2 2 2 2 2 2 2 2 2

25 25 25 25 25 20 15 15 12.5 12.5

069 76 069 78 069 79 069 80 069 81 069 82 069 83 069 84 069 85 069 86

6 10 13 16 20 25 32 40 50 63

4 4 4 4 4 4 4 4 4 4

25 25 25 25 25 20 15 15 12.5 12.5

50 50 50 50 50 50 50 50 25 25

2-pole - 230/400 V
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

4-pole - 400 V
Breaking capacity (kA) IEC 60947-2 400 V 230 V

069 13 069 14 069 16 069 18 069 19 069 20 069 21 069 22 069 23 069 24 069 25 069 26 064 75 064 76 064 77

C curve

Nominal rating (A)

2 3 6 10 13 16 20 25 32 40 50 63 80 100 125

Number of modules

2 2 2 2 2 2 2 2 2 2 2 2 3 3 3

30 30 30 30 30 30 30 25 20 20 15 15 16 16 16

50 50 50 50 50 50 50 50 50 50 25 25 25 25 25

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

069 93 069 94 069 96 069 98 069 99 070 00 070 01 070 02 070 03 070 04 070 05 070 06 065 70 065 71 065 72

C curve

Nominal rating (A)

2 3 6 10 13 16 20 25 32 40 50 63 80 100 125

Number of modules

4 4 4 4 4 4 4 4 4 4 4 4 6 6 6

Breaking capacity (kA) IEC 60947-2 400 V 230 V

25 25 25 25 25 25 25 20 15 15 12.5 12.5 12.5 12.5 12.5

50 50 50 50 50 50 50 50 50 50 25 25 16 16 16

Add-on modules (p. 20) Auxiliaries and accessories (p. 22) B and Z curve, please consult us

18

MCBs DXTM 6000 -15 kA

thermal magnetic MCBs from 1 A to 125 A D curve

065 89

066 36

066 62

066 71

Technical characteristics (p. 23-25) Breaking capacity 6000 - IEC 60898-1 up to 63 A - 400 VA 10000 - IEC 60898-1 80 A to 125 A 15 kA - IEC 60947-2 up to 32 A - 400 VA 10 kA - IEC 60947-2 40 A to 125 A - 400 VA Magnetic adjusted between 10 and 14 In
Pack Cat.Nos D curve

Single pole - 230/400 V


Nominal rating (A)

Pack

Cat.Nos D curve

4-pole - 400 V
Nominal rating (A)

1 1 1 1 1 1 1 1 1 1 1 1

065 75 065 76 065 77 065 79 065 81 065 83 065 84 065 85 065 86 065 87 065 88 065 89

1 2 3 6 10 16 20 25 32 40 50 63

Number of modules

1 1 1 1 1 1 1 1 1 1 1 1

Breaking capacity (kA) IEC 60947-2 230 - 400 V

15 15 15 15 15 15 15 15 15 10 10 10

2-pole - 400 V
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

066 25 066 26 066 27 066 29 066 31 066 33 066 34 066 35 066 36 066 37 066 38 066 39 066 40 066 41 066 42

D curve

Nominal rating (A)

1 2 3 6 10 16 20 25 32 40 50 63 80 100 125

Number of modules

2 2 2 2 2 2 2 2 2 2 2 2 3 3 3

Breaking capacity (kA) IEC 60947-2 400 V 230 V

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

066 65 066 66 066 67 066 68 066 69 066 71 066 73 066 74 066 75 066 76 066 77 066 78 066 79 066 80 066 81 066 82

1 2 3 4 6 10 16 20 25 32 40 50 63 80 100 125

Number of modules

4 4 4 4 4 4 4 4 4 4 4 4 4 6 6 6

Breaking capacity (kA) IEC 60947-2 400 V 230 V

15 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 25 20 20 20 16 16 16

15 15 15 15 15 15 15 15 15 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 20 20 20 16 16 16

Add-on modules (p. 20) Auxiliaries and accessories (p. 22)

3-pole - 400 V
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

066 45 066 46 066 47 066 49 066 51 066 53 066 54 066 55 066 56 066 57 066 58 066 59 066 60 066 61 066 62

D curve

Nominal rating (A)

1 2 3 6 10 16 20 25 32 40 50 63 80 100 125

Number of modules

3 3 3 3 3 3 3 3 3 3 3 3 4.5 4.5 4.5

Breaking capacity (kA) IEC 60947-2 400 V 230 V

15 15 15 15 15 15 15 15 15 10 10 10 10 10 10

25 25 25 25 25 25 25 25 25 20 20 20 16 16 16

For DX-MA magnetic tripping only version, please consult us

19

add-on modules DXTM


for DX, DX-H, MCBs up to 125 A

074 01

075 68

074 63

Technical characteristics (p. 23-25) Conform to EN 61009-1. Mounted on the right-hand side of the MCBs AC type: detects AC component faults A type: detects AC and DC component faults Hpi type: detects AC and DC component faults A type, enhanced immunity to unwanted tripping in disturbed environments
Pack Cat.Nos

2-pole 230/400 V
AC type ? 30 mA 32 2 63 2 80 to 125 4 AC type ? 300 mA 32 2 63 2 80 to 125 4 AC type ? 300 mA selective 63 2 AC type ? 1 A selective 63 2 A type M 30 mA 32 2 63 2 80 to 125 4 A type M 300 mA 32 2 63 2 80 to 125 4 A type M 300 mA selective 63 2 Hpi type M H 30 mA 63 2
Maximum rating (A) Number of modules

Pack

Cat.Nos

4-pole 400 V
AC type ? 30 mA
Maximum rating (A)

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

074 01 074 02 074 03 074 07 074 08 074 09 074 11 074 23 074 83 074 84 074 85 074 89 074 90 074 91 074 93 075 64

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

074 55 074 56 074 57 074 61 074 62 074 63 074 65 074 66 074 77 074 78 075 37 075 38 075 39 075 43 075 44 075 45 075 47 075 74

32 3 63 3 80 to 125 6 AC type ? 300 mA 32 3 63 3 80 to 125 6 AC type ? 300 mA selective 63 3 80 to 125 6 AC type ? 1 A selective 63 3 80 to 125 6 A type M 30 mA 32 3 63 3 80 125 6 A type M 300 mA 32 3 63 3 80 125 6 A type M 300 mA selective 63 3 Hpi type M H 300 mA selective 63 3

Number of modules

3-pole 400 V
AC type ? 30 mA
1 1 1 1 1 1 1 1 1 1 1 1

074 28 074 29 074 34 074 35 074 36 074 38 075 11 075 17 075 18 075 20 075 68 075 69

32 3 63 3 AC type ? 300 mA 32 3 63 3 80 to 125 6 AC type ? 300 mA selective 63 3 A type M 30 mA 63 3 A type M 300 mA 63 3 80 to 125 6 A type M 300 mA selective 63 3 Hpi type M H 30 mA 63 3 80 to 125 6

Maximum rating (A)

Number of modules

20

MCBs DX-L 50 kA

thermal magnetic high breaking capacity MCBs from 10 A to 63 A

add-on modules DX-L


for DX-L 50 kA MCBs

071 14

071 44

075 76

075 85

Technical characteristics (p. 23-25) Breaking capacity 50 kA - IEC 60947-2


Pack Cat.Nos Pack

Technical characteristics (p. 23-25)


Cat.Nos

Add on modules Hpi type (High immunity)


Conform to standard IEC 61009-1 Mounted on the right-hand side of the MCBs DX-L Enhanced immunity to unwanted tripping in disturbed environments Hpi type MH: detects AC and DC component faults A type, enhanced immunity to unwanted tripping in disturbed environments 2-pole - 230/400 V
Sensitivity

MCBs
2-pole - 400 V
Nominal rating (A) Number of modules Breaking capacity (kA) IEC 60947-2 400 V 230 V

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

071 12 071 14 071 15 071 16 071 17 071 18 071 19 071 20 071 27 071 29 071 30 071 31 071 32 071 33 071 34 071 35 071 42 071 44 071 45 071 46 071 47 071 48 071 49 071 50

C curve

10 3 16 3 20 3 25 3 32 3 40 3 50 3 63 3 3-pole - 400 V 10 4.5 16 4.5 20 4.5 25 4.5 32 4.5 40 4.5 50 4.5 63 4.5 4-pole - 400 V 10 6 16 6 20 6 25 6 32 6 40 6 50 6 63 6

50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70

1 1 1 1 1 1 1 1 1 1 1 1

075 76 075 77 075 78 075 79 075 80 075 81 075 82 075 83 075 84 075 85 075 86 075 87

30 mA 300 mA 300 mA selective 1 A selective 3-pole - 400 V 30 mA 300 mA 300 mA selective 1 A selective 4-pole - 400 V 30 mA 300 mA 300 mA selective 1 A selective

Number of modules

2 2 2 2 3 3 3 3 3 3 3 3

Auxiliaries and accessories (p. 22)

21

auxiliaries and accessories DXTM


for MCBs, RCDs, RCBOs and isolating switches

remote control DXTM


for MCBs, RCDs and RCBOs

073 50 Pack Cat.Nos

073 54

073 68

073 80

073 73

Auxiliaries

Pack

Cat.Nos

Motor-driven control modules


Clip on the left-hand side of the MCBs Can be used to remotely open and close the associated device For 1-pole and 2-pole devices To be used in combination with the shunt release Cat.No 073 61 For remote control of: - 2-pole RCD's, - single pole+neutral and 2-pole RCBOs, - 2-pole and 1 module single pole+neutral MCBs Equipped with one auxiliary signalling contact

1 1

Clip on the left-hand side of the MCB Possible configurations for 1 MCB: - 1 auxiliary control device + 1 signalling auxiliary 0.5 modules or - 2 signalling auxiliaries 1 module, Allow insertion of the supply busbar Auxiliaries common to: - DX, DX-H, DX-L and RCDs Number of Signalling auxiliaries modules 073 50 Auxiliary changeover switch 6 A - 250 V 0.5 Signals the state of the contacts for MCBs and modular isolating switches Can be used with DX-IS (p. 145) 073 51 Fault signalling changeover switch 0.5 6 A - 250 V 073 54 Auxiliary changeover switch 6 A - 250 V 1 + fault signalling switch Can be modified to 2 auxiliary changeover switches Shunt releases For remote tripping of MCBs, RCDs, RCBOs and remote trip head isolating switches (red handle) 073 60 12 to 48 V/= 073 61 110 to 415 V 110 to 125 V= Undervoltage release Time delay adjustable from 0 to 300 ms 073 68 230 V

073 80

230 V 2 For 2-pole, 3-pole and 4-pole devices For remote control of: - MCBs equipped with add-on modules and RCBO's 2P , 3P and 4P up to 63 A Equipped with: auxiliary changeover switch and fault signalling switch 2 A - 230 V
Control voltage

Control voltage

Number of modules

073 73(1)

230 V

Number of modules

Automatic resetting module


1 1 Gives automatically an order of resetting To be connected to motor-driven control modules Cat.No 073 73 For use in installations which are not monitored or staffed (transmission relays, pump stations etc.) in order to meet service/operational continuity requirements
1

1 1

1 073 83

Control voltage

Accessories
2 1/3 1 2 1

230 V

Number of modules

044 42 Support for 5 mm and 6 mm padlock 044 43 Padlock 5 mm 227 97 Padlock 6 mm 044 44 Sealable screw cover (4 separate poles) 044 47 Insulating shield
Insulating shield Screw cover

(1) Controlled by a volt-free contact or push button (not illuminated) Not compatible with 1.5 module per pole MCBs (DX-H 80 to 125, DX-L), MCBs single pole (DX), 2 modules phase / neutral RCBOs (DX), single pole RCBOs and RCDs (RCCBs)

22

Bold pack quantities : Minimum quantities to be ordered

performance of MCBs and auxiliaries

n Breaking capacity in the event of a short-circuit to earth and insulation voltage


DX Single pole + Neutral Icn 1 Ui 4500 A 250 V DX B and C curves D curve < 63 A 6 kA 500 V DX-H B and C curves DX D curve 80 to 125 A 10 kA 500 V DX-L C curve

n Technical characteristics of DX auxiliaries


- Max. connection cross-section: 2.5 mm2 - Operating temperature: - 5 to + 50 C Current shunt releases
Ph C1

25 kA 500 V N C2 12 U

Icn 1: Breaking capacity on 1 pole for multi-pole MCBs in the event of a short-circuit to earth Ui: rated insulation voltage

nominal voltage (Un) - 12 to 48 V and = - 110 to 415 V 110 to 125 V= Fitted with automatic breaking contact

n Connection cross-section for screw terminals (in


Copper cable rigid flexible DX single pole + neutral with or without add-on modules DX, add-on modules 63 A DX-L add-on modules DX-H, add-on modules 80, 100, 125 A, DX-L Auxiliaries 16 32 70 2.5 10 25

mm2)

Min. and max. voltage: from 0.7 to 1.1 Un Tripping time: < to 20 ms Power consumption: at 1.1 x 48 V = 121 VA at 1.1 x 415 V = 127 VA Impedance : 12 to 48 V = 23 110 to 415 V = 1640
Consumption U min. 522 mA 69 mA U max. 2610 mA 259 mA

50 2.5

12 to 48 V 110 to 415 V

Undervoltage releases

n Release curves of MCBs


t (time)

Ph/+ N/-

D1 D2 U

nominal voltage (Un) 24 V= 48 V= 230 V

Thermal (low overvoltage: slow release) 1h

Pull-in voltage: 0.55 Un Tripping time: from 100 to 400 ms 10% (adjustable) Power consumption: 24 V= 0.1 VA 48 V= 0.2 VA 230 VA 1 VA

MA

Z B

Magnetic (high overvoltage: fast release)

0.01 s

1 10 20 30 50 100 200 2 3 4 5 1.3 B C D x In (rating) 1.45 Thermal release for an ambient temperature 30 C Curves Z(1) B C D MA(1) (1) Please consult us Magnetic threshold setting 2.4 to 3,6 In 3 to 5 In 5 to 10 In 10 to 14 In (10 to 20 depending on standard) 12 to 14 In

23

performance of MCBs and auxiliaries (continued)

n Protection of DC circuits
Lexic DX and DX-H MCBs (1P/2P/3P/4P - In 63 A) designed for use in 230/400 V supplies, can also be used in DC circuits In this case, the following deratings and precautions must be taken into account 1 - Protection against short-circuits Max. magnetic tripping threshold: multiplied by 1.4 Example: For a C curve MCB for which the AC tripping threshold is between 5 and 10 In, the DC tripping threshold will be between 7 and 14 In 2 - Protection against overloads The time/current thermal tripping curve is the same as for AC 3 - Operating voltage Max. operating voltage: 80 V per pole (60 V for single-pole + N MCBs) For voltages higher than this value, several poles must be wired in series Example: for a 110 V voltage, use a 2-pole MCB and connect the 2 poles in series 4 - Breaking capacity 4000 A for a single pole MCB at max. voltage (80 V= per pole) At other voltages, the breaking capacities are as follows:
+ + + +

Example: circuit earthed via the negative polarity / U = 110 V= / Isc = 10 kA / In = 32 A Protect the positive polarity using an MCB capable of breaking 10 kA at 110 V (DX-H 2P 32 A with 2 poles on the positive polarity) For isolation, use a DX-H 3P 32 A with 2 poles on the positive polarity and one pole on the negative polarity
DX-H LEXIC Acc. to IEC 60947.2 Icu voltage 48 V 110 V 230 V + If isolation required + single-pole 10 kA 2P 10 kA 10 kA 10 kA 15 kA 3P 4P

DX-H 32 A 2P -

DX-H 32 A 3P

Network earthed via a middle point: Place on each polarity the number of poles necessary for max. Isc breaking at half voltage
+
(1)

U/2 U/2
(1)

U-Isc max. U/2-Isc max.

U/2-Isc max. (U/2-Isc max.)

(1) MCB

DX Acc. to IEC 60947.2 Icu voltage 48 V 110 V 230 V 48 V Ics(1) 110 V 230 V DX-H Acc. to IEC 60947.2 Icu voltage 48 V 110 V 230 V 48 V Ics(1) 110 V 230 V (1) As a % of Icu 100 % single-pole 10 kA 2P 100 % single-pole 6 kA 2P

3P 6 kA

4P

6 kA 6 kA 100 % 100 % 100 % 100 % 3P 10 kA 15 kA 100 % 100 % 100 % 100 % 4P 10 kA

Example: circuit earthed via a middle point / U = 230 V= / Isxc = 6 kA / In = 10 A Protect each polarity using an MCB capable of breaking 6 kA at half voltage, i.e. 115 V (DX 4P 10 A with 2 poles on each polarity)
DX LEXIC Acc. to IEC 60947.2 Icu + voltage 48 V 110 V 230 V single-pole 6 kA 2P 6 kA 6 kA 6 kA 10 kA 3P 4P

10 kA 10 kA DX 10 A 4P

5 - Distribution of breaking poles To choose the MCB and determine the pole distribution necessary for breaking on each of the polarities, it is necessary to know how the installation is earthed Supply with one polarity earthed: Place all the poles necessary for breaking on the other polarity If isolation is required, an additional pole must be added on the earthed polarity
+ U MCB (U-Isc max.) U-Isc max

Isolated earth supply: Distribute the poles necessary for breaking over the 2 polarities to provide protection in the event of a double earth fault (particularly if there are a number of circuits in parallel)
+
(1)

U (1)

U-Isc max.

U-Isc max.

1st earth fault : I = O 2sd earth fault : U and I Isc max.

(1) MCB

(U-Isc max.)

Example: isolated earth circuit / U = 48 V= / Isc = 4,5 kA / In = 40 A Protect the installation with an MCB capable of breaking 4.5 kA at 48 V and protect each polarity (DX MCB 2P 40 A with one pole on each polarity)
DX LEXIC voltage 48 V 110 V 230 V + single-pole 6 kA 2P 6 kA 6 kA 6 kA 10 kA 3P 4P Acc. to IEC 60947.2 Icu

(1)

U=0

(1) Only

if isolation required

DX 40 A 2P -

24

n Specific case of continuity of service


In certain locations, where there are no personnel, in which particular care is required to ensure continuity of service, false tripping of MCBs is not permissible (isolated telephone/TV/radio relay stations, pumping stations, etc.) The combination of an Hpi type RCBO with motor-driven control and a recloser provides optimum continuity of service (p. 155)

n 2P and 4P RCDs: withstand to short-circuits


Caution: it is advisable to provide overload protection for the RCD
Downstream RCD 16 A 25 A 40 A 2P/ 4P 63 A 80 A 100 A Upstream cartridge fuse gG 40 A 63 A 100 kA 50 kA 100 kA 50 kA 100 kA 50 kA 100 kA 50 kA 100 kA 50 kA 100 kA 50 kA 80 A 100 A Upstream MCB DX-L DPX 125

DX (B/C) DX-H (B/C) 1P+N 2,3,4P 63 A 80 < 125 A 15 kA 10 kA 6 kA 10 kA 20 kA(1) 12.5 kA 15 kA 10 kA 6 kA 10 kA 20 kA(1) 12.5 kA 15 kA 10 kA 6 kA 10 kA 15 kA(1) 12.5 kA 12.5 15 kA 10 kA 10 kA 12.5 kA kA(1) 12.5 15 kA 10 kA 12.5 kA (1) kA 12.5 15 kA 10 kA 12.5 kA kA(1)

50 kA 25 kA 50 kA 25 kA 50 kA 25 kA 50 kA 25 kA 25 kA 25 kA

(1) Same nominal rating for both, MCB and RCD

n DX RCBOs residual current breaking capacity


Im according to EN 61009-1
Add-on modules - DX 6000 , DX-H, D curve - DX-L Motor-driven control Cat.No 073 73 Automatic reclosing control device Cat.No 073 83 RCBOs -P+N - 2P (4 modules) - 4P 10 to 32 A (4 modules) 3000 A 6000 A 4500 A 6000 A 6000 A 30000 A

n RCD tripping curves


Average RCD operating curves
1 t(s)

- 4P 40 to 63 A (7 modules)

0.5 10mA 30mA 300mA 1A

0.1

0.05

A, AC or Hpi type selective (s)

Hpi type A or AC type instantaneous

0.01 10 0 10 1 10 2 10 3
4 I (mA) 10

For more information on the basic rules of protection, come and be trained at Innoval www.legrand.com