You are on page 1of 36

8/27/2013

Equipment Short-Circuit Current Rating and Available Fault Current


Dan Neeser Field Application Engineer Eatons Bussmann Business Dan.Neeser@CooperIndustries.com

2013 Eaton. All rights reserved.

Agenda
Interrupting Rating & Series Rating Short-Circuit Current Ratings Maximum Fault Current Marking Fault Current Calculations UL 508A Industrial Control Panels Supplement SB - SCCR

2013 Eaton. All rights reserved.

8/27/2013

Interrupting Rating
NEC Article 100 Definition
Highest current an OVERCURRENT DEVICE (fuse or circuit breaker) is rated to safely interrupt. Self protection rating only

NEC 110.9 Interrupting Rating.


Requires the overcurrent device to have an interrupting rating not less than the maximum available fault current. The maximum fault current must be calculated and varies based on system size/location. Similar Requirements in OSHA 1910.303(b)(4)
2013 Eaton. All rights reserved.

Interrupting Rating
NEC 110.9: Device interrupting rating MUST be equal to or greater than the maximum available fault current. Chapter 1 Video Clips - Interrupting Rating

2013 Eaton. All rights reserved.

8/27/2013

Interrupting Rating - Proper Application


1st Determine available short-circuit current (Isca) at lineside terminals of each OCPD. MSB Isca 3 Isca 4 Isca 1 2nd Apply OCPDs with adequate Interrupting Rating. Isca 2 Isca 5 Isca 6

M
2013 Eaton. All rights reserved.

Interrupting Rating - Proper Application

Must select circuit breaker with interrupting rating adequate for point of application varies by voltage and circuit breaker type.

2013 Eaton. All rights reserved.

8/27/2013

I.R. - Proper Application

High Interrupting rating of current-limiting fuses at full voltage reduces concerns about proper interrupting rating at point of application

2013 Eaton. All rights reserved.

Series Rated Systems


A combination of: - Circuit breakers / circuit breakers OR - Fuses / circuit breakers that can be applied at available fault levels above the interrupting rating of the load side circuit breaker, but not above that of the main or line side device.
Downstream device will ALWAYS be a circuit breaker
2013 Eaton. All rights reserved.

8/27/2013

Series Rated Systems: CB-CB


Series Rated Combination 200A Circuit Breaker 65,000 A.I.R. 65,000 A.I.R.

20A Circuit Breaker


10,000 A.I.R.

ISC=65,000 A
2013 Eaton. All rights reserved.

ISC=65,000 A
9

Series Rated Systems: Fuse-CB


Series Rated Combination LPJ 400 SP 300,000 A.I.R. 200,000 A.I.R.

20A Circuit Breaker


10,000 A.I.R.

ISC=300,000 A
2013 Eaton. All rights reserved.

ISC=200,000 A
10

8/27/2013

Series Rated Systems


NEC 240.86(A) Selected Under Engineering Supervision in Existing Installations
The series rated combination devices must be selected by licensed, professional engineer. Requires Documentation and Stamp. Series combination rating and upstream device must be field marked on end use equipment. Downstream circuit breaker must remain passive.

NEC 240.86(B) Tested Combinations


The combination of line side and load side devices must be tested and marked on the end-use equipment (panelboards & switchboards).
2013 Eaton. All rights reserved.

11

Series Rated Systems


Additional Limitations and Requirements
Labeling Requirements
Manufacturer NEC 240.86(B) Field Marking NEC 110.22(B)&(C)

Motor Contribution Limitations


NEC 240.86(C) Motor FLA cannot exceed 1% of IR of protected CB.

Lack of Selective Coordination


2013 Eaton. All rights reserved.

12

8/27/2013

Current Limitation
A current limiting fuse will clear a fault within one half of a cycle.
Thermal energy is proportionate to the square of RMS current multiplied by the time (Irms2t) Mechanical stresses are proportionate to the square of peak current multiplied by the time (Ip2t)

2013 Eaton. All rights reserved.

13

Current Limitation
Conductor protection for fault of 45kA/480V (26kA with conductor) with non-current-limiting device (1 cycle) vs. current-limiting device (>1/2 cycle)

2013 Eaton. All rights reserved.

14

8/27/2013

Short-Circuit Current Ratings


NEC Article 100 Definition
The highest current EQUIPMENT can withstand without extensive damage (fire or shock hazard). Also known as component protection May be based on a specific type of overcurrent device

NEC 110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics. Requires the equipment to have a short circuit current rating not less than the maximum available fault current. The maximum fault current must be calculated and varies based on system size/location. Similar Requirements in OSHA 1910.303(b)(5)

2013 Eaton. All rights reserved.

15

Motor Starter - SCCR


High Fault Test: starter protected by an instantaneous trip circuit breaker (MCP) that only provides Type 1 protection High Fault Test: starter protected by Low-Peak fuses that provides Type 2 (No Damage) protection

480V - 22,000A

480V - 22,000A

Fault
2013 Eaton. All rights reserved.

Fault
16

8/27/2013

SCCR Marking Requirements


430.8 Marked on motor controllers 440.4(B) Marked on HVAC equipment 409.110(3) Marked on industrial control panels
409.22 Fault current cannot exceed marked SCCR

670.3(A)(4) Marked on industrial machinery control panel


670.5 Fault current cannot exceed marked SCCR

UL 508A, Supplement SB is an approved method to determine SCCR for industrial control panels and industrial machinery control panels

2013 Eaton. All rights reserved.

17

Fault Current Marking Requirement 110.24 Available Fault Current.


(A) Service equipment must be marked with the maximum available fault current and date of calculation (B) If fault current increases due to system modification, the marking must be updated.

2013 Eaton. All rights reserved.

18

8/27/2013

How to Comply?
All equipment must comply with: NEC 110.9 (IR) &110.10 (SCCR)
Service Equipment Engineer Calculate
Isc = 60,142 A

Contractor Label

Max Avail. Fault Current = 58,524 A Date Determined/Calculated: 9/2010

Required per NEC 110.24

Isc = 38,525 A

Isc = 42,153 A

Isc = 27,532 A

Isc = 18,752 A

HVAC
SCCR = 40kA

Industrial Machinery Panel


SCCR = 65kA

Industrial Control Panel


SCCR = 30kA

Motor Controller
SCCR = 25kA
19

2013 Eaton. All rights reserved.

IR/SCCR Inspection Check-List

2013 Eaton. All rights reserved.

20

10

8/27/2013

Fault Current Calculations


To determine the fault current:
Draw the one-line diagram Identify sources of short-circuit current (utility, generation, motors) Include system component information (tranformers, conductors, busway, overcurrent devices are not considered) Use calculation method (ohmic, per unit, point-topoint, software) Use typical fault current values as a reference only.
2013 Eaton. All rights reserved.

21

Typical Short-Circuit Current Values


Short-Circuit Current at service entrance equipment varies by type/size of system:
Small residential systems (100A to 200A) 10,000A to 15,000A or less Small commercial building systems (400A to 800A) 20,000A to 30,000A Larger commercial and manufacturing building systems (2,000A to 3,000A) - 50,000A to 65,000A Higher short-circuit currents are possible where low impedance (energy-efficient) transformers are used (or where larger transformers (kVA) feed multiple services. Commercial buildings directly connected to utility grid system 200,000A or greater
2013 Eaton. All rights reserved.

22

11

8/27/2013

Short-Circuit Current Factors


Typically highest at service point Decreases in downstream equipment (due to impedance of transformers and conductors)
2013 Eaton. All rights reserved.

23

Calculation Example
480V/3000A Service supplied from 2500 kVA Transformer Find Isc at Transformer Secondary & Service Equipment
480V, 3000A Service Equipment Service Transformer 2500 kVA 13.2kV 480V 5% Impedance
Isc = 60,142 A Isc = 58,524A

7 600 Cu kcmil/phase 25 Feet in PVC

2013 Eaton. All rights reserved.

24

12

8/27/2013

Calculation Example
Step One: Calculate Secondary FLA of Transformer (3 phase)

IFLA =

KVA X 1000 EL-L X 1.732

KVA = KVA of Transformer EL-L = Secondary Phase to Phase voltage


2013 Eaton. All rights reserved.

25

Calculation Example ISC


2500 KVA Transformer 13.2kV - 480V, 3 Phase Z = 5%

IFLA =

2500 X 1000 480 X 1.732

IFLA = 3007 A
2013 Eaton. All rights reserved.

26

13

8/27/2013

Calculation Example
Step Two: Calculate Multiplier
Z = Impedance of Transformer, refer to transformer nameplate or manufacturer data

Mult = Mult = Mult = 20

100 %Z 100 5

2013 Eaton. All rights reserved.

27

Calculation Example
Step Three: Calculate Secondary Short Circuit Current

ISC = IFLA X Mult ISC = 3007 X 20 ISC = 60,140 A


2013 Eaton. All rights reserved.

28

14

8/27/2013

Calculation Example
Calculate Short Circuit Current at 480V Switchgear

480V Switchgear
7 600 Cu kcmil/phase

ISC = 60,140A
2013 Eaton. All rights reserved.

25 Feet in PVC

29

Calculation Example

Isc known from previous calculation


Calculate multiplier for Cable Step One: Calculate f value

ISC 480V SWGR = ISC X Mult

2013 Eaton. All rights reserved.

30

15

8/27/2013

Calculation Example
Step One: Calculate f value

f =

1.732 X L X ISC C X EL-L

L = Length of conductor ISC = Short-circuit current at beginning of circuit C = C Value Constant for Cable From Table. Multiply by # of runs EL-L = Phase to Phase Voltage
2013 Eaton. All rights reserved.

31

Calculation Example
C Value 600 kcmil, CU, PVC = 28,033

2013 Eaton. All rights reserved.

32

16

8/27/2013

Calculation Example
Step One: Calculate f Value
L = 25 Feet ISC = 60,140 A C = 7 X 28,033 - See C Value Table EL-L = 480V

f =

1.732 X 25 X 60,140 7 X 28,033 X 480


2013 Eaton. All rights reserved.

= 0.0276

33

Calculation Example
Step Two: Use Calculated f Value
Calculate Multiplier

Mult = Mult =
1

1 1+f

1 + 0.0276
2013 Eaton. All rights reserved.

= 0.9731

34

17

8/27/2013

Calculation Example
Calculate Short Circuit Current at 480V Switchgear

ISC 480V SWGR = ISC X Mult ISC 480V SWGR = 60,140 X .9731 ISC 480V SWGR = 58,522 A*
* Add motor contribution if present

2013 Eaton. All rights reserved.

35

What if the System Changes?


Service Transformer 3000 kVA 13.2kV 480V 5% Impedance
Isc = 72,171 A Isc = 70,587A

480V, 4000A Service Equipment

9 600 Cu kcmil/phase 25 Feet in PVC Service Transformer 2500 kVA 13.2kV 480V 4% Impedance
Isc = 75,178 A Isc = 72,667A

480V, 3000A Service Equipment

7 600 Cu kcmil/phase 25 Feet in PVC

2013 Eaton. All rights reserved.

36

18

8/27/2013

Cooper Bussmann Short-Circuit Calculator


Old version
Download for Window XP

New version
Apple or Android Apps Web (run from homepage)

2013 Eaton. All rights reserved.

37

Create a System

1
Choosethreephaseor singlephasesystem

2
ClickonAddtomy System

3
Selectacomponent youwanttoadd

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

38

19

8/27/2013

Add a Transformer

1
SelectAdd Transformer

2
Ifyouhaveaknownprimaryfault currentyoucanaddithere.Ifnot, selectassumeinfinite

3
Entervaluesintothe appropriatefields

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

39

Add Motor Contribution

1
AfteraddingaTransformer, youwillbeaskedifyouwant toaddmotorcontribution

2
Youcancompleteaquickcalculation byselectinga%ofyour transformersFLAoradditmanually

3
Addthese calculationstoyour system

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

40

20

8/27/2013

Add Other Components

1
SelectAddTo MySystem

2
AddConductor RunorBussRun

3
Addthecorrectvalues andAddToSystem

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

41

System Summary

1
Viewsystemoneline diagram

2
Emailoneline diagram

3
Selectaspecificfaultto createalabel

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

42

21

8/27/2013

Create a Label

1
Selectafaultandclick onCreateLabel

2
Entertheemailaddress,projectname, faultname,andlabelsize,thenSendLabel

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

43

Fuse Sizing

1
TaponFuse SizingDiagram

2
Taponthecircuit toprotect

3
Revieweachsectionandthefuse suggestionsfortheselectedlocation

Sizing fuses for mains, feeders, and branch circuits has never been easier!
2013 Eaton. All rights reserved.

44

22

8/27/2013

User Guide & Contact Us

TheUserguide providesuseful informationaboutFC2 Thereisauserguide selectionatthebottom ifeachpage Basedonwhereyou areintheapp,youwill beprovidedaspecific overviewofFC2s functionality

WhiletheFC2isvery intuitive,theremaybe additionalquestions ThereisaContactUs selectionatthe bottomofeachpage Fromthislocation, youcanselecttosend anemailfortechnical assistanceor customerservice support

Calculating available fault current and creating 110.24 labels has never been easier!
2013 Eaton. All rights reserved.

45

Cooper Bussmann FC2 Web Version - Example

2013 Eaton. All rights reserved.

46

23

8/27/2013

How to Determine SCCR?


Short-Circuit Current Rating (SCCR)
Can be established by testing during the listing and labeling process OR Can be determined using an approved (calculation) method
UL 508A Supplement SB is an approved method (industrial control panels and industrial machinery control panel) AHJ Approved Method

NRTL field evaluation can also be used.


2013 Eaton. All rights reserved.

47

Industrial Control Panel SCCR


Industrial Control Panel.
An assembly of two or more components consisting of one of the following: 1)power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers; 2)control circuit components only, such as push buttons, pilot lights, selector switches, timers, switches, and control relays; 3)a combination of power and control circuit components. These components, with associated wiring and terminals, are mounted on, or contained within, an enclosure or mounted on a subpanel. The industrial control panel does not include the controlled equipment.

48

2013 Eaton. All rights reserved.

48

24

8/27/2013

UL 508A Supplement SB
What Needs to be Analyzed per UL 508A, Supplement SB?
All power circuit components (SB 4.1)
Feeder and branch circuit components that supply power to loads (motors, lighting, heating and appliances) Includes disconnect switches, fuses, circuit breakers, load controllers, overload relays, power distribution/terminal blocks, bus bars, etc.

Control circuit components are not required to be analyzed


Pushbuttons, pilot lights, selector switches, timers, control relays, etc.
2013 Eaton. All rights reserved.

49

Power vs. Control Circuits


Control circuit components dont have to be analyzed

Power Transformer

*Control Circuit, but affects SCCR


2013 Eaton. All rights reserved.

Control Transformer
50

25

8/27/2013

UL 508A Supplement SB
How to Determine Component SCCR (SB4.2.2)?
The SCCR marked on the component or on instructions. The SCCR determined by the voltage rating of the component and the assumed short circuit current from Table SB4.1. or The SCCR for a load controller, motor overload relay, or combination motor controller that has been investigated in accordance with the performance requirements, including short circuit test requirements for standard fault currents or high fault currents specified in the Standard for Industrial Control Equipment, UL 508, and described in the manufacturers procedure.

2013 Eaton. All rights reserved.

51

UL 508A Supplement SB

What are the Rules (Sweep 1)?


Lowest component SCCR limits assembly SCCR unless:
Combination ratings can be used to increase branch circuit component ratings (SB 4.2.2) Component with marked/specified OCPD Check with component manufacturer for combination ratings
2013 Eaton. All rights reserved.

52

26

8/27/2013

Combination Ratings - Branch


Component SCCR Nameplate Voltage: SCCR: 480 100kA OCPD I.R.

Use combination ratings with specified/marked OCPD to fix low rated branch components
Combination ratings of overcurrent protective devices and components can be used
2013 Eaton. All rights reserved.

53

Combination Ratings - Contactor

2013 Eaton. All rights reserved.

54

27

8/27/2013

Combination Ratings - MMP


OL Protection Only Fuse or Circuit Breaker Required for SC Protection Suitable for Group Installations Straight Ratings (480V)

2013 Eaton. All rights reserved.

55

Combination Ratings Type E/F


Combination Motor Controller SC & OL Protection Line Side Adapters Required Slash Ratings (480/277V)

2013 Eaton. All rights reserved.

56

28

8/27/2013

Combination Ratings - ASD

200kA with Class CC/J/T Fuse Suitable for Group Installations 65kA with Type E CMC (480/277V)

2013 Eaton. All rights reserved.

57

Combination Ratings - Feeder


Component SCCR Nameplate Voltage: SCCR: 480 100kA OCPD I.R.

Use UL Listed power distribution block with high SCCR when used with specified fuses or circuit breakers and required load side conductors Must have feeder circuit spacing (Listed PDB) if in feeder circuit Combination ratings of PDBs is cost effective fix
2013 Eaton. All rights reserved.

58

29

8/27/2013

Combination Ratings - PDBs

PDBFS220 (4 14 Load Side Conductors) 100kA with 175A Class J fuse or less

59

2013 Eaton. All rights reserved.

59

UL 508A Supplement SB What are the Rules (Sweep 1)?


Lowest component SCCR limits assembly SCCR unless:
Feeder components are used that limit the shortcircuit current reducing the need for higher branch circuit component SCCR (SB 4.3) Current limiting overcurrent protective devices Transformers rated 10kVA or less
2013 Eaton. All rights reserved.

60

30

8/27/2013

Feeder vs. Branch Circuits

Feeder Circuit
Branch Circuit Branch Circuit

2013 Eaton. All rights reserved.

61

Use of CL Devices - OCPD


CL Device must be in the feeder circuit For CL Fuses or Circuit Breakers
Use PEAK Let-through, Not RMS Let-Through (more conservative) Fuses - cannot use manufacturer specific fuse data only tables based on performance requirements from UL 248 (more conservative - apply to all manufacturers) Circuit Breakers - must be Listed and marked currentlimiting and use published let-thru curves (most circuit breakers are not CL) Can only raise downstream BRANCH circuit components (not overcurrent protective devices fuses/circuit breaker IR or Combination motor controllers SCCR)
2013 Eaton. All rights reserved.

62

31

8/27/2013

Fuse LT UL vs Manufacturer
LPJ-100SP UL Limits
50kA = 12kA 100kA = 14kA 200kA = 20kA

Manufacturer Let Through Curves


Ip LT:
50kA = 9kA 100kA = 12kA 200kA = 14kA

Irms LT:
50kA = 4kA 100kA = 5kA 200kA = 6kA

2013 Eaton. All rights reserved.

63

Use of CL Devices - OCPD


Component SCCR Nameplate Voltage: SCCR: 480 14kA
F

OCPD I.R.

Current limiting feeder OCPD can be used to increase branch component SCCR.

Use of CL OCPD can only fix components


2013 Eaton. All rights reserved.

64

32

8/27/2013

Use of CL Devices - Transformers


CL Device must be in the feeder circuit For Transformers
If 10kVA with secondary devices (components and overcurrent devices) of 5kA or higher, apply the IR of the primary overcurrent protective device If 5kVA (120V Secondary) with secondary devices (Components and overcurrent devices) of 2kA or higher, apply the IR of the primary overcurrent protective device

2013 Eaton. All rights reserved.

65

Use of CL Devices - Transformers


Component SCCR Nameplate
Voltage: SCCR: 480 200kA 10 kVA

OCPD I.R.

Transformers can be used to limit the short-circuit current available


If 10kVA & sec comp = 5kA+ If 5kVA/120V & sec comp = 2kA+ Then assign entire circuit I.R. of primary overcurrent device
Use of Small Transformers (10kVA or less) can increase secondary component/OCPD ratings
2013 Eaton. All rights reserved.

66

33

8/27/2013

UL 508A Supplement SB
What are the Rules (Sweep 2)?
Lowest overcurrent protective device interrupting rating (or SCCR for some devices) always limits assembly SCCR
All Feeder and branch circuit overcurrent devices Tested series combination ratings or series ratings (fuse-circuit breaker or circuit breaker-circuit breaker) are NOT allowed. Branch circuit overcurrent devices tapped from the feeder circuit supplying a control circuit. Supplemental protective devices protecting the control circuit transformer in a motor branch circuit.
2013 Eaton. All rights reserved.

67

Overcurrent Protection Devices


Branch Circuit Protective Devices
Fuses Circuit Breakers Application Limited Devices

Supplemental Protectors/Fuses
Not suitable for branch circuit protection (protecting a load) Can only be used in control circuits

2013 Eaton. All rights reserved.

68

34

8/27/2013

Why High SCCR?


NEC & Equipment standards only require the SCCR to be marked NEC requires the marked value to be adequate for the maximum available fault current Although not required, high SCCR is often preferred
Flexibility of application
Multiple installations Fault current unknown Insufficient SCCR can delay installation

2013 Eaton. All rights reserved.

69

Fix It - Solutions
High I.R. Protective Devices
Class R Class J Class J Drive Fuse Class T Class CC CubeFuse High Speed High IR/CL CBs
2013 Eaton. All rights reserved.

70

35

8/27/2013

Fix It - Solutions
High SCCR Components

2013 Eaton. All rights reserved.

71

Questions?

2013 Eaton. All rights reserved.

36

You might also like