Catalog HG 11.

42 2008

5EA A I 8=?KK
Medium-Voltage Equipment Selection and Ordering Data

4A? IAH !),

www.siemens.com/energy

Siemens Vacuum Recloser 3AD

Siemens HG 11.42 2008

R-HG11-172.tif

Siemens Vacuum Recloser 3AD

Contents

Contents

Page

Siemens Vacuum Recloser 3AD


Medium-Voltage Equipment Catalog HG 11.42 2008

Description
General Switch unit Controller, protection functions Ambient conditions, altitude correction factor and number of operating cycles Product range overview and scope of delivery

5
6 7 9 13 14

Product Selection
Ordering data and configuration example Selection of primary ratings Selection of controller Selection of additional equipment

15
16 17 20 24

Technical Data
Electrical data, dimensions and weights: Voltage level 12 kV Voltage level 15.5 kV Voltage level 27 kV Voltage level 38 kV

27
28 28 29 29

Annex
Inquiry form Configuration instructions Configuration aid

33
34 35 Foldout page

Siemens AG 2008

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Siemens HG 11.42 2008

R-HG11-300.tif

Siemens Vacuum Recloser 3AD

Description
Contents

Contents

Page

Description
General Switch unit: Recloser principle Design Pole assemblies Operating mechanism Magnetic actuator Mechanical lockout Recloser cycle Controller:
R-HG11-301.tif

5
6

7 7 7 7 7 8 8

User interface Protection functions Communications Protocols Metering functions Data records Software Standards Ambient conditions Altitude correction factor Number of operating cycles Product range overview Scope of delivery

9 10 11 11 11 11 12 12 13 13 13 14 14

Vacuum recloser with cubicle and controller

Siemens HG 11.42 2008

Description
General

Siemens Vacuum Recloser 3AD

Siemens vacuum recloser 3AD


3AD vacuum reclosers are outdoor circuit-breakers designed for frequent opening and reclosing in case of temporary faults. They fulfill this task automatically by monitoring the line and operating autonomously. The recloser consists of two main components: The switch unit being the circuit-breaker and the controller as protection and control unit. It is housed inside the control cubicle.

Switch unit

Controller inside the cubicle

R-HG11-302.tif

The switch unit is the primary part of the recloser. It is located on top of the pole to switch the overhead line. It is permanently exposed to weather and environment.

As the heart of the recloser, the controller is located in a cubicle at the bottom of the pole.

Siemens HG 11.42 2008

R-HG11-303.tif

Siemens Vacuum Recloser 3AD

Description
Switch unit

Recloser principle Reclosers are used in distribution systems of power supply companies (utilities). Like circuit-breakers they are capable of switching normal and fault currents. They are equipped with sensors and a controller being the protection and control device. In case of a line fault, they can break and make several times, thus avoiding longer network interruptions due to temporary faults. As outdoor devices they are normally pole-mounted and exposed to environment and weather. A recloser consists of two components: The switch unit (circuit-breaker) and the controller (inside the control cubicle), both connected through a control cable. Design Switching operation The vacuum switching technology, proven and fully developed for more than 30 years, is the basis for the vacuum interrupters. Pole assemblies Each vacuum interrupter is embedded in an epoxy-resin pole made out of weather-proof cycloalyphatic resin. This enables a small design as well as resistance against environmental effects. The vacuum interrupter is vertically mounted inside the pole, providing a long service life. Each recloser is equipped with an integrated current transformer. For special protection purposes, a resistive voltage sensor can also be incorporated in the pole. The accuracy achieved in this way is much higher than that of capacitive dividers.
R-HG11-305.tif

1
R-HG11-304.tif

Switch unit front view

Operating mechanism The pole assemblies of the recloser are directly mounted on the operating mechanism housing. Besides the complete kinematics, it also accommodates the position indicator and a mechanical operations counter. The operating mechanism housing is made of mild steel with a special coating for outdoor applications. Optionally, a stainless-steel housing is available. The recloser is installed on the pole by means of a pole mounting frame. Alternatively, the recloser can be mounted directly on a frame for pad-mounting in substations. Magnetic actuator The recloser is operated by a magnetic actuator enabling the recloser cycle, i.e. the high number of switching operations within a short period of time. The actuator is a bi-stable system, locked in the end positions by permanent magnets. If not in operation, the magnet coils do not consume any power. The operating force is transmitted to all three poles through a mechanical coupling.

Switch unit rear view

Structure of the switch unit

HG11-2728 eps

Siemens HG 11.42 2008

Description
Switch unit

Siemens Vacuum Recloser 3AD

Mechanical lockout A mechanical lockout enables tripping independently on the controller. If this handle is pulled, the recloser opens and is simultaneously locked out electrically and mechanically. The handle stays extended, thus indicating the interlocked state. To close the recloser again, the operating rod must first be pushed back to the operation position in order to release the lockout. Then the recloser can be closed electrically via the control. Recloser cycle In case of a network fault, the recloser opens and recloses several times. In case of temporary faults the automatic reclosing significantly reduces the loss of power supply. The recloser cycle is optimized accordingly:
The first interruption of a fault is done quickly and instantaneously, so that even the fuses in the system do not operate. After approx. 300 ms (user settable), it recloses back on.
R-HG11-306.tif

Lock-out handle pushed in (operational position)

The second and third interruption has a definite or inversetime delay. Thus, downstream fuses in the network have the chance to operate and isolate the affected network section, restoring normal operation in the remaining network. The following dead time is usually 210 s (user settable). The fourth (optional up to the fifth) interruption is fast again and serves as a check. This for example utilizes the physical effect that, when the short-circuit occurs, the lines move due to the magnetic forces of the current, and foreign objects are shaken off. If the fault still exists, the recloser turns to the lockout and can only be closed from the operator panel or via SCADA.

Lock-out handle pulled (open position)

Siemens HG 11.42 2008

R-HG11-307.tif

Siemens Vacuum Recloser 3AD

Description
Controller

The controller The Siemens Argus-M controller is based on the Argus-M directional overcurrent protection relay. These relays provide protection, control, monitoring, instrumentation and metering with integrated input and output logic, data logging & fault reports. Communication access to relay functionality is via a front USB port for local PC connection or a rear electrical RS485 port for remote connection. Additional rear port options are available. The controller is mounted in the control cubicle. Along with the controller, this cubicle also contains the auxiliary power supply with batteries for uninterruptible power supply, electronic boards, fuses, and a general-purpose outlet to power a laptop. The controller contains a large number of protection functions (elements) which can be selected or deselected through the menu driven display. These elements can be customized to the utilities needs by parameters (settings) as described below. User interface
20-character x 4-line backlit LCD Menu navigation keys 3 fixed LEDs 8 or 16 programmable tri-color LEDs are available eliminating the need for expensive panel-mounted pilot lights and associated wiring. Each LED is tri-colored (red, green, yellow) allowing for clear indication of the associated functions state. 12 programmable function keys each with tri-color LED are available for implementing scheme control functionality. Each function key has an associated tri-color LED (red, green, yellow) allowing for clear indication of the associated functions state.
R-HG11-309.tif

1
Argus-M controller
R-HG11-308.tif

Tri-color LEDs and pushbuttons of the controller

Siemens HG 11.42 2008

Description
Controller

Siemens Vacuum Recloser 3AD

Protection functions (in order of ANSI numbering) 37 Undercurrent Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if current falls below setting for duration of delay. 46BC Broken conductor/phase unbalance Element has settings for pickup level and DTL delay. With the circuit-breaker closed, if one or two of the line currents fall below setting, this could be due to a broken conductor. 46NPS Negative phase-sequence overcurrent Each element has user settings for pickup level and Inverse Definite Minimum Time Lag (IDMTL) or DTL delay. It operates if NPS current exceeds setting and delay. NPS current elements can be used to detect unbalances on the system or remote earth faults when a delta-star transformer is in circuit. 49 Thermal overload The thermal algorithm calculates the thermal states from the measured currents and can be applied to lines, cables and transformers. Outputs are available for thermal overload and thermal capacity. 50/51 Phase fault 50 INST (instantaneous)/DTL (Definite Time Lag) and 51 IDMTL (Inverse Definite Minimum Time Lag)/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time delays. The user can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic, either DTL or shaped current/time reset characteristic to improve grading with electromechanical protection. 50G/51G/50N/51N Earth fault/sensitive earth fault Earth-fault current is derived from the residual connection of the 3 integrated line CTs. 50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time delays. The user can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic, either DTL or shaped current/time reset characteristic to improve grading with electromechanical protection. 50BF Circuit-breaker fail The circuit-breaker fail function is triggered from an internal trip signal. Line currents are monitored following a trip signal and an output is issued if any current is still detected after a specified time interval. This can be used to re-trip the CB or to back-trip an upstream CB. A second back-trip time delay is available to enable another stage to be utilized if required.

64H Restricted earth-fault scheme The measured earth-fault input may be used in a 64H high impedance restricted earth-fault scheme. Required external series stabilizing resistor and non-linear shunt resistor can be supplied. 74TC Trip-circuit supervision The trip-circuit(s) can be monitored via binary inputs. Tripcircuit failure raises an HMI alarm and output(s). 81HBL2 Inrush restrain/second harmonic block Where second harmonic current is detected (i.e. during transformer energization) user selectable elements can be blocked. Cold load pickup If a circuit-breaker is closed onto a cold load, i.e. one that has not been powered for a prolonged period, this can impose a higher than normal load-current demand on the system which could exceed normal settings. These conditions can exist for an extended period and must not be interpreted as a fault. To allow optimum setting levels to be applied for normal operation, the cold load pickup feature will apply alternative settings for a limited period. The feature resets when either the circuit-breaker has been closed for a settable period, or if the current has been reduced beneath a set level for a user set period. 27/59 Under/overvoltage Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. It operates if voltage exceeds setting for duration of delay. It can be applied in load shedding schemes. 47 Negative phase-sequence overvoltage Each element has settings for pickup level and Definite Time Lag (DTL) delays. It operates if NPS voltage exceeds setting for duration of delay. 59N Neutral overvoltage Each element has settings for pickup level and Definite Time Lag (DTL) delays. It operates if neutral voltage exceeds setting for duration of delay. Neutral overvoltage can be used to detect earth faults in high impedance earthed or isolated systems. 60CTS CT supervision The CT supervision considers the presence of negative phase-sequence current, without an equivalent level of negative phase-sequence voltage, for a user set time as a CT failure. The element has user operate and delay settings.

10

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Description
Controller

67/67N Directional control Phase-fault, earth-fault and sensitive earth-fault elements can be directionalized. Each element can be user set to forward, reverse, or non-directional. Directional phase-fault elements are polarized from quadrature voltage. Earth-fault elements can be user set to be polarized from residual voltage or negative phase-sequence voltage. 81 Under/overfrequency Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. It operates if frequency exceeds setting for duration of delay. It is typically applied in load shedding schemes. 79 Auto-reclose Each element provides independent phase-fault and earthfault/sensitive earth-fault sequences of up to 5 trips, i.e. 4 reclose attempts before lockout. Auto-reclose sequence can be user set to be initiated from internal protection operation or via binary input from an external protection. Each trip in the sequence can be user set to be either instantaneous (fast) or delayed. The user can set each reclose (dead) time and the reclaim time. Battery and capacitor check (no number) Sag/swell detection Optional protection functionality
Sync check Fault locator Loop automation Single-triple operation

Metering functions
Primary current phases and earth Secondary current phases and earth Positive phase-sequence (PPS) current Negative phase-sequence (NPS) current Zero phase-sequence (ZPS) current Binary input/output status Trip circuit healthy/failure Time and date Starters Fault records Event records Frequency Waveform records Circuit-breaker trip counters It summation for contact wear Direction Primary line and phase voltages Secondary voltages Apparent power and power factor Real and reactive power W Hr forward and reverse VAr Hr forward and reverse Historical demand record Positive phase-sequence (PPS) voltage Negative phase-sequence (NPS) voltage Zero phase-sequence (ZPS) voltage

Communications
Front USB port Rear RS485 port

Data records Sequence of event records Up to 5000 events can be stored. Fault records The last 10 fault records are displayed on the HMI, with time and date of trip, measured quantities and type of fault. Disturbance recorder The waveform recorder stores analog data for all phases, the states of protection functions, binary inputs, LEDs and binary outputs with pre & post trigger data. A record can be triggered from protection function, binary input or via data communications. The waveform recorder stores up to 10 s data. Load profile recording A rolling record of demand over the last 24 h is stored. The demand is averaged over a user selectable period of time. A rolling record of such demand averages is stored and provides the demand history. A typical application is to record 15 min-averages for the last 7 days.
Siemens HG 11.42 2008

Optional functions
Rear fiber optic ports IRIG-B ports RS232 ports

Protocols
IEC 60870-5-103 Modbus RTU DNP 3.0

11

Description
Controller, standards

Siemens Vacuum Recloser 3AD

Software Reydisp Evolution For communication with the relay via a PC (personal computer) a user-friendly software package, Reydisp Evolution, is available to allow transfer of relay settings, waveform records, event records, fault data records, instruments/meters and control functions. Reydisp Evolution is compatible with IEC 60870-5-103. Programmable logic The user can map binary inputs and protection operated outputs to function inhibits, logic inputs, LEDs and/or binary outputs. The user can also enter up to 16 equations defining scheme logic using standard functions e.g. timers and/or gates, inverters and counters. Each protection element output can be used for alarm & indication and/or tripping. Waveform records analysis See figure left Quick logic The Quick logic feature allows the user to input up to 16 logic equations (E1 to E16) in text format. Equations can be entered using Reydisp or at the relay fascia. Each logic equation is built up from text representing control characters. Each can be up to 20 characters long. Standards The recloser conforms to the following standards
ANSI C37.60 (2003) IEC 60255 IEC 60694 (in future IEC 62271-1)

Typical Reydisp Evolution screenshot

12

Siemens HG 11.42 2008

R-HG11-310.tif

Description
Ambient conditions, altitude correction factor and number of operating cycles

Siemens Vacuum Recloser 3AD

Ambient conditions The recloser is designed for the normal operating conditions defined in ANSI C37.60. This comprises an ambient temperature from 40 C to +55 C plus solar radiation. Altitude correction factor The dielectric strength of air insulation decreases with increasing altitude due to low air density. The rated lightning impulse withstand voltage values specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite drawing. The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. To select the devices, the following applies: U W U0 x Ka
U U0 Ka Rated withstand voltage under standard reference atmosphere Rated withstand voltage requested for the place of installation Altitude correction factor according to the opposite diagram
Altitude correction factor 1.40

55C

-40C

max. 95% per day max. 90% per month

1
HG11-2515a_en eps

1.50

1.30

Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under standard reference atmosphere is required as a minimum: 90 kV W 75 kV x 1.2 Number of operating cycles The recloser is designed for 10,000 operating cycles at normal current. According to the standard IEEE C37.60, the recloser has been tested for 116 short-circuit breaking operations. The actual number of short-circuit breaking operations is higher than that, and can be even more than 200 depending on the parameters of the short-circuit current (amplitude, DC component).

1.20
HG11-2517c_en eps

1.10

1.00 1000

1500

2000

2500

3000 3500 m 4000 Site altitude

Siemens HG 11.42 2008

13

Siemens Vacuum Recloser 3AD

Description
Product range overview and scope of delivery

Product range overview


Rated voltage Rated short-circuit breaking current kA 12.5 12.5 16 12.5 12.5 16 12.5 16 Rated lightning impulse withstand voltage kV 95 110 110 125 150 150 170 170 400 A Rated normal current

kV

630 A

800 A

12 15.5 27

38

Scope of delivery
Standard equipment Optional available Remarks

Switch unit Operating mechanism Operating mechanism housing Switching medium Insulation Power supply Position indicator Operations counter Interlocking Configuration Sensors Controller and control cubicle Cubicle Socket outlet Controller size Number of inputs/ outputs for customer use Temperature range Control keys Controller interfaces

Electrical operating mechanism (magnetic actuator) Mild steel with outdoor protection coating IP 55 with lifting eyes and earthing connection Vacuum interrupters Cycloaliphatic epoxy resin/air Auxiliary power input OPEN: green CLOSED: red Mechanical in the switch unit; electronical in the controller Electrical; mechanical lockout Pole mounting and 6 m control cable Integrated current transformers

Stainless steel

Auxiliary transformer for supply from HV line Customer-specific color or inscription

Other cable lengths and/or substation frame Integrated voltage sensors

Mild steel with outdoor protection coating IP 65 with lifting eyes and earthing connection USA version E10 (= 10" width) 5 x BI, 8 x BO 12 function keys 8 user-definable LEDs Up to 30 C 5 navigation keys, 12 function keys, 2 pushbuttons USB (front), RS485 (rear)

Stainless steel Country-specific design E12 (= 12" width) Additional BI/BO and 12 LEDs 40 C Customer-specific pushbuttons or rotary CLOSE/OPEN switches RS232, fiber optic, IRIG-B

14

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Product Selection
Contents

Contents

Page

Product Selection
Ordering data and configuration example Selection of primary ratings: Voltage level 12 kV Voltage level 15.5 kV Voltage level 27 kV Voltage level 38 kV Selection of controller: Recloser configuration Current and voltage measuring Controller size Auxiliary voltage
R-HG11-311.tif

15
16

17 17 18 19

20 20 21 21 22 22 22 23 23 24 25

Control and sensor cables Communication protocols Communication interfaces Function packages Languages and power socket Selection of additional equipment Accessories and spare parts

Switch unit bottom view

Control cubicle

R-HG11-312.tif

Siemens HG 11.42 2008

15

Product Selection
Ordering data and configuration example

Siemens Vacuum Recloser 3AD

Order number structure The vacuum reclosers consist of a primary part as well as of a controller or secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The controller and secondary part covers all auxiliary devices and the controller, which are necessary for operating and controlling the recloser. Order codes Individual equipment versions, marked with 9 or Z in the 8th to 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.

Mounting parts and special versions ( ) In case of special versions, - Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix - Z is only listed once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made between your responsible sales partner and the order processing department in our Switchgear Factory in Berlin.

2
1st position 2nd position 3rd position 4th to 7th position Primary part Superior group Switching devices Main group Circuit-breaker Subgroup Outdoor vacuum recloser Basic equipment Design and ratings of the vacuum recloser Secondary part Controller, sensors, cables and other necessary data Order codes Group of 3 after the Order No. Format: a n a Special versions ( ) Initiated with -Z Group of 3 after the Order No. Format: a n n

a: alphabetical
Position: 1 2 3 4 5

n: numerical
6 7 8 9 10 11 12 13 14 15 16 Order codes

Order No.:

3 A D n

8th to 16th position

Configuration example In order to simplify the selection of the correct order number for the requested recloser type, you will find a configuration example on each page of the chapter Equipment Selection. For the selection of the auxiliary voltages, the fixing options, the controller, etc. always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (page 24) a completely configured recloser results as an example.

On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your recloser.

Example for Order No.: Order codes:

3 A D 6

16

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Product Selection
Selection of primary ratings

12 kV
50/60 Hz Rated lightning impulse withstand voltage Type Rated normal current Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

Three-phase for loop automation

3 x single-phase/ single-triple

Rated voltage

Single-phase

Three-phase

See page 20

See page 20

See page 21

See page 21

See page 22

See page 22

See page 22

See page 23

See page 23

Ur kV 12

Up kV 75

Ud kV 42

Isc kA 12.5

Ir A 630 3 3 3 3 3 3 3 3 A A A A A A A A D D D D D D D D 1 3 4 6 1 3 4 6 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3

800

See page 24

15.5 kV
50/60 Hz Ur kV 15.5 Up kV 110 Ud kV 50 Isc kA 12.5 Ir A 400 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D D D D D 1 3 4 6 1 3 4 6 1 3 4 6 1 3 4 6 1 3 4 6 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 1 1 1 1 2 2 2 2 3 3 3 3 2 2 2 2 3 3 3 3

630

800

16

630

800

Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 15.5 kV Rated lightning impulse withstand voltage Up = 110 kV Rated short-duration power-frequency withstand voltage Ud = 50 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 630 A Type: Three-phase recloser for loop automation Example for Order No.: Order codes:

3 A D

6 3 A D 6

2 2

3 3

2 2

Siemens HG 11.42 2008

17

Product Selection
Selection of primary ratings

Siemens Vacuum Recloser 3AD

27 kV
50/60 Hz Rated lightning impulse withstand voltage Type Rated normal current Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

Three-phase for loop automation

3 x single-phase/ single-triple

Rated voltage

Single-phase

Three-phase

See page 20

See page 20

See page 21

See page 21

See page 22

See page 22

See page 22

See page 23

See page 23

Ur kV 27

Up kV 125

Ud kV 60

Isc kA 12.5

Ir A 400 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D 1 3 2 1 3 3 2 1 4 3 2 1 6 3 2 1 1 3 2 2 3 3 2 2 4 3 2 2 6 3 2 2 1 3 2 3 3 3 2 3 4 3 2 3 6 3 2 3 On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request

2
150 60 12.5

630

800

400

630

800

16

630

800

Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 27 kV Rated lightning impulse withstand voltage Up = 125 kV Rated short-duration power-frequency withstand voltage Ud = 60 kV Rated short-circuit breaking current Isc = 12.5 kA Rated normal current Ir = 400 A Type: Three-phase Example for Order No.: Order codes:

3 A D

3 3 A D 3

3 3

2 2

1 1

18

Siemens HG 11.42 2008

See page 24

Siemens Vacuum Recloser 3AD

Produt Selection
Selection of primary ratings

38 kV
50/60 Hz Rated lightning impulse withstand voltage Type Rated normal current Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

Three-phase for loop automation

3 x single-phase/ single-triple

Rated voltage

Single-phase

Three-phase

See page 20

See page 20

See page 21

See page 21

See page 22

See page 22

See page 22

See page 23

See page 23

Ur kV 38

Up kV 170

Ud kV 70

Isc kA 12.5

Ir A 630 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A D D D D D D D D D D D D D D D D On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request On request

800

See page 24

16

630

800

Configuration example Siemens vacuum recloser 3AD Rated voltage Ur = 38 kV Rated lightning impulse withstand voltage Up = 170 kV Rated short-duration power-frequency withstand voltage Ud = 70 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 800 A Type: Single-phase Example for Order No.: Order codes:

3 A D

on request 3 A D

Siemens HG 11.42 2008

19

Product Selection
Selection of controller

Siemens Vacuum Recloser 3AD

8th position Recloser configuration

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

See page 21 See page 21 See page 22

See page 22 See page 22 See page 23 See page 23

See page 24

Options

Recloser for pole mounting 1) incl. cubicle, controller and control cable Recloser for substation application incl. cubicle and controller Switch unit only (w/o cubicle, controller and control cable) 2)

1 2 3

1) Pole mounting according to list of accessories 2) This option is only possible in the stated order number

9th position Current and voltage measuring


Current transformers 1 integrated CT per pole Voltage sensors 1 integrated sensor per pole (including sensor cables) 3 x external VTs (to be defined as accessories) A B C

1)

1)

1)

1) Necessary for recloser type: Three-phase for loop automation

Configuration example Siemens vacuum recloser 3AD 3 A D (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase 3 Recloser for pole mounting incl. control cubicle and control cable Current and voltage measuring: current transformers, 1 integrated CT per pole Example for Order No.: Order codes: 3 A D 3

1 A

1 A

20

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Product Selection
Selection of controller

10th position Controller size


Number of binary inputs (partly for customer use)

Position:

10 11 12

13 14 15 16

Order codes

Order No.: Number of binary outputs (partly for customer use)

3 A D

See page 22

See page 22

See page 22

See page 23

See page 23

Controller size

Function keys

E10 E12

12

Number of tri-color LEDs

16

13

23

33

43

14

22

30 A B C D E

For 3-phase and single-phase applications

See page 24

For loop automation F Without controller (refers to switch unit only) Y

11th position Auxiliary voltage

DC voltage

AC voltage

Without auxiliary voltage supply (need for switch unit only) 48 V 60 V 110 V 220 V 110/120 V 220/240 V With auxiliary transformer and rated voltage as below: Rated voltage 11 kV Rated voltage 12 kV Rated voltage 13.8 kV Rated voltage 15 kV

0 On request On request 3 4 5 6 9 9 9 9 With order code With order code With order code With order code T T T T 3 3 3 3 A B C D

Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Controller size: E12, 12 function keys, 16 tri-color LEDs, 33 binary inputs, 30 binary outputs Auxiliary voltage 110/120 V AC Example for Order No.: Order codes:

3 A D 3 3 2 1 1 A D 5 3 A D 3 3 2 1 1 A D 5

Siemens HG 11.42 2008

21

Product Selection
Selection of controller

Siemens Vacuum Recloser 3AD

12th position Control and sensor cables

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

See page 23 See page 23

See page 24 M 1

Options (also comprises sensor cables for external voltage sensors if selected)

Without (need for switch unit only) Cable length 6 m Cable with special length (to be specified in clear text)

0 1 9

13th position Communication protocols

Options

Without communication protocol (need for switch unit only) IEC 60870-5-103 and Modbus RTU DNP 3.0

0 1 2

14th position Communication interfaces


ST plug (multiple mode) ST plug (single mode)

1 x RS485 (rear)

2 x RS485 (rear)

1 x RS232 (rear)

1 x USB (front)

2 x optical

1 x IRIG-B

Without communication interface (need for switch unit only)

A B C D E Y

Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Length of control and sensor cable 6 m Communication protocol IEC 60870-5-103 and Modbus RTU Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B Example for Order No.: Order codes:

3 A D 3 3 2 1 1 A D 5 1 1 C 3 A D 3 3 2 1 1 A D 5 1 1 C

22

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Product Selection
Selection of controller

15th position Function packages

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

Options

Standard protection and monitoring functions Standard protection and monitoring functions plus synchro-check and fault locator Standard protection and monitoring functions for loop automation Standard protection and monitoring functions for loop automation with synchro-check and fault locator Standard protection and monitoring functions for single-triple application Standard protection and monitoring functions for single-triple application with synchro-check and fault locator Without protection functions (need for switch unit only)

A C D E F G Y

See page 24

16th position Languages and power socket


Language of operating instructions and nameplate Standard of power socket

English American English Spanish Portuguese Other languages on request

UK USA Mexico Brazil

1 2 3 4 9

Configuration example Siemens vacuum recloser 3AD (Ur = 27 kV, Up = 125 kV, Ud = 60 kV, Isc = 12.5 kA, Ir = 400 A) Type: Three-phase Controller with standard protection and monitoring functions Language of operating instructions and nameplate: English Standard of power socket: UK Example for Order No.: Order codes:

3 A D 3 3 2 1 1 A D 5 1 1 C A 1 3 A D 3 3 2 1 1 A D 5 1 1 C A 1

Siemens HG 11.42 2008

23

Product Selection
Selection of additional equipment

Siemens Vacuum Recloser 3AD

Selection of additional equipment

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A D

Options

Ambient temperature down to 40 C Seaworthy packing inside Germany Stainless steel for tank, control cubicle Radio modem power supply 12 V DC Serial to Ethernet converter Pole mounting frame with bracket for surge arrester (source and load side) Pole mounting frame Siemens design (with bracket for surge arresters, source and load side) Further non-listed special versions (only after consultation with your responsible sales partner). Information additionally in clear text

Z Z Z Z Z Z Z Z

A F T T T T T Y

3 0 0 0 0 2 2 9

8 2 1 2 3 1 2 9

Configuration example Siemens vacuum recloser 3AD 3 A D Rated voltage Ur = 27 kV Rated lightning impulse withstand voltage Up = 125 kV Rated short-duration power-frequency withstand voltage Ud = 60 kV Rated short-circuit breaking current Isc = 12.5 kA Rated normal current Ir = 400 A Type: Three-phase 3 Recloser for pole mounting incl. control cubicle and control cable Current and voltage measuring: current transformers, 1 CT integrated per pole Controller size: E12, 12 function keys, 16 tri-color LEDs, 33 binary inputs, 30 binary outputs Auxiliary voltage 110/120 V AC Length of control and sensor cable 6 m Communication protocol IEC 60870-5-103 and Modbus RTU Communication interfaces 1 x USB, 2 x RS485, 1 x IRIG-B Controller with standard protection and monitoring functions Language of operating instructions and nameplate: English Standard of power socket: UK Seaworthy packing inside Germany Stainless steel for tank, control cubicle Example for Order No.: Order codes: 3 A D 3 F 0 2 +

1 A D 5 1 1 C A 1 Z Z Z F T 0 0 2 1

3 T

2 0

1 1

1 A D 5

C A

24

Siemens HG 11.42 2008

Siemens Vacuum Recloser 3AD

Product Selection
Accessories and spare parts

Accessories and spare parts A wide range of spare parts and accessories is available. Please contact your responsible sales partner and the order processing department in our Switchgear Factory in Berlin.

Data on the nameplate Note: For any request regarding spare parts, subsequent deliveries, etc. the following details are necessary: Type designation Serial No. Design code Year of manufacture

HG11-2732_en eps

Siemens HG 11.42 2008

25

Siemens Vacuum Recloser 3AD

26

Siemens HG 11.42 2008

R-HG11-313.tif

Siemens Vacuum Recloser 3AD

Technical Data
Contents

Contents

Page

Technical Data
Electrical data, dimensions and weights: Voltage level 12 kV Voltage level 15.5 kV Voltage level 27 kV Voltage level 38 kV

27
28 28 29 29

Switch unit driver - discarge switch for the capacitor

R-HG11-314.tif

Controller with protective cap

R-HG11-315.tif

Siemens HG 11.42 2008

27

Technical Data
Electrical data, dimensions and weights

Siemens Vacuum Recloser 3AD

Rated lightning impulse withstand voltage

Rated operating sequence: O - 0.2s - CO 2s - CO - 2s - CO (-30s - CO) - Lock-out

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

Rated duration of short-circuit

50/60 Hz

Creepage distance, phase-to-earth

Rated short-circuit making current

12 kV
Rated normal current

Voltage drop U between connections

Ir Order No. 3AD 122 3AD 123 A 630 800

tk s 3 3

Isc kA 12.5 12.5

Ima kA 31.5 31.5

Up kV 75 75

Ud kV 42 42 mV 24 24 mm 810 810 mm 312 312 mm 287 287 kg 142 142 A 2 2 A 10 10

15.5 kV
50/60 Hz 3AD 221 3AD 222

Ir A 400 630 800 630 800

tk s 3 3 3 3 3

Isc kA 12.5 12.5 12.5 16 16

Ima kA 31.5 31.5 31.5 40 40

Up kV 110 110 110 110 110

Ud kV 50 50 50 50 50 mV 24 24 24 24 24 mm 810 810 810 810 810 mm 312 312 312 312 312 mm 287 287 287 287 287 kg 142 142 142 142 142 A 2 2 2 2 2 A 10 10 10 10 10

3AD 223 3AD 232 3AD 233

28

Siemens HG 11.42 2008

Cable charging current

Line charging current

Minimum clearance, phase-to-earth

Clearance, phase-to-phase

Weight

Siemens Vacuum Recloser 3AD

Technical Data
Electrical data, dimensions and weights

Rated lightning impulse withstand voltage

Rated operating sequence: O - 0.2s - CO 2s - CO - 2s - CO (-30s - CO) - Lock-out

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

Rated duration of short-circuit

50/60 Hz

Creepage distance, phase-to-earth

Rated short-circuit making current

27 kV
Rated normal current

Voltage drop U between connections

Ir Order No. 3AD 321 3AD 322 3AD 323 3AD 3AD 3AD 3AD 3AD ... A 400 630 800 400 630 800 630 800

tk s 3 3 3 3 3 3 3 3

Isc kA 12.5 12.5 12.5 12.5 12.5 12.5 16 16

Ima kA 31.5 31.5 31.5 31.5 31.5 31.5 40 40

Up kV 125 125 125 150 150 150 150 150

Ud kV 60 60 60 60 60 60 60 60 mV 24 24 24 mm 810 810 810 mm 312 312 312 On request On request On request On request On request mm 287 287 287 kg 142 142 142 A 5 5 5 5 5 5 5 5 A 25 25 25 25 25 25 25 25

Cable charging current

Line charging current

Minimum clearance, phase-to-earth

Clearance, phase-to-phase

Weight

38 kV
50/60 Hz 3AD 3AD 3AD 3AD

3
Ir A 630 800 630 800 tk s 3 3 3 3 Isc kA 12.5 12.5 16 16 Ima kA 31.5 31.5 40 40 Up kV 170 170 170 170 Ud kV 70 70 70 70 mV mm mm On request On request On request On request mm kg A 5 5 5 5 A 40 40 40 40

Siemens HG 11.42 2008

29

Technical Data
Dimension drawings

Siemens Vacuum Recloser 3AD

Dimension drawings

600

638 600

350

Dimensions of control cubicle

597

962

250

HG11-2729 eps

460 520.5

Dimensions of switch unit

Mabild 2 Mabild 1

30

Siemens HG 11.42 2008

HG11-2730_en eps

615

365

10

Siemens Vacuum Recloser 3AD

Technical Data
Dimension drawings

Dimension drawings

901 407 357

962 600 1334 1341

3
425 425 1173

Mabild 2
HG11-2731 eps

Dimensions of switch unit with pole mounting frame

Siemens HG 11.42 2008

31

Siemens Vacuum Recloser 3AD

32

Siemens HG 11.42 2008

R-HG11-181.tif

Siemens Vacuum Recloser 3AD

Annex
Contents

Contents

Page

Annex
Inquiry form Configuration instructions Configuration aid

33
34 35 Foldout page

Switchgear Factory in Berlin, Germany

R-HG11-180.eps

Siemens HG 11.42 2008

33

Annex
Inquiry form
Please copy, fill in and return to your Siemens partner

Siemens Vacuum Recloser 3AD

Inquiry concerning

Technical data
Rated voltage 12 kV 27 kV 75 kV 150 kV 42 kV 60 kV 15.5 kV 38 kV 110 kV 170 kV 50 kV 70 kV 125 kV

Other values _ _ _ kV

Siemens vacuum recloser 3AD

Rated lightning impulse withstand voltage

_ _ _ kV

Please

Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current Rated normal current

_ _ _ kV

Submit an offer Call us Visit us

12.5 kA

16 kA

_ _ _ kA

400 A

630 A

800 A

___A

Your address
Company Dept. Name Street Postal code/city Phone Fax E-mail

Secondary equipment
For possible combinations see pages 20 to 23
Recloser configuration Recloser for pole mounting Without control cubicle Integrated current transformers 4 binary inputs 34 binary inputs 9 binary outputs ___ Auxiliary voltage Control and sensor cable Communication interfaces _ _ _ V DC Without USB Optical Function packages additional to standard functions Synchronizing and synchro-check Loop automation 6m RS485 IRIG-B Fault locating Single-triple Made of stainless steel Others Application in substation

Current and voltage sensing

Integrated voltage sensors 14 binary inputs 17 binary outputs

External voltage transformers 24 binary inputs 25 binary outputs

Controller equipment

_ _ _ V AC, _ _ _ Hz ___m RS232

Siemens AG
Dept.

Application and other requirements


Name Street Postal code/city Fax

Please check off

_ _ _ Please fill in

34

Siemens HG 11.42 2008

You prefer to configure your Siemens vacuum recloser 3AD on your own?
Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use your prompted online configurator under www.siemens.com/energy

For configuration of your Siemens vacuum recloser 3AD

9 10 11 12

13 14 15 16

Instruction for configuration of the Siemens vacuum recloser 3AD 1st step: Definition of the primary part (see pages 17 to 19)
Please specify the following ratings: Possible options:

See page 17

See page 19

See page 20

See page 20

See page 21

See page 21

See page 22

See page 22

See page 22

See page 23

See page 23

Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (Isc) Rated normal current (Ir) These ratings define the positions 4 to 7 of the order number.

Ur: Up: Ud: Isc: Ir:

12 kV to 38 kV 75 kV to 170 kV 42 kV to 70 kV 12.5 kA and 16 kA 400 A to 800 A

3 A D + + 3 A D +

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + +

2nd step: Definition of the secondary equipment (see pages 20 to 23)


Please specify the following equipment features: Possible options: 3 A D

Recloser configuration (position 8) Sensors (position 9) Controller (position 10) Auxiliary voltage (position 11) Cable length of control and sensor cable (position 12) Communication protocol (position 13) Communication interfaces (position 14) Functions of the controller (position 15) Language of operating instructions and nameplate (position 16) These equipment features define the positions 8 to 16 of the order number.

Recloser incl. control cubicle and cables, recloser without control cubicle and cables, recloser for transformer substation, retrofit recloser Integrated current transformers, integrated voltage transformers, external voltage transformers Housing size, number of function keys and three-color LEDs, number of available binary inputs and outputs Voltages from 48 V DC to 240 V AC Standard length 6 m, special lengths possible IEC 60870-5-103 and Modbus RTU, DNP 3.0

3 A D

3 A D USB, RS485, RS232, IRIG-B, optical, ST plug Standard protection and monitoring functions, synchronizing and synchro-check, fault location English, American English, Spanish and Portuguese 3 A D

3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24) Should you still need more options than the possible special equipment like country-specific mains sockets, weather resistance down to 40 C, stainless-steel design, etc. please contact your responsible sales partner.
3 A D

3 A D

3 A D

Siemens HG 11.42 2008

35

See page 24

to

If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm.

Siemens AG Energy Sector Medium Voltage Division Nonnendammallee 104 13623 Berlin Germany www.siemens.com/energy

For questions concerning Power Transmission and Distribution: You can contact our Customer Support Center 24 hours a day, 365 days a year. Tel.: +49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) E-Mail: support.energy@siemens.com www.siemens.com/energy-support

Subject to change without notice Order No. E50001-K1511-A421-A1-7600 Printed in Germany Dispo 31601 KG 03.08 1.0 36 En 103063 6101/6519

Responsible for Technical contents: Siemens AG, Dept. PTD M C PPM Berlin

General editing: Siemens AG, Dept. PTD CC M Erlangen


R-HG11-182.tif

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract.