OPERATION FLOW AND SETTING MENU

Power ON Shows for 4 seconds (Warming up) Operate mode display


A.
Primary displays Set the temperature required : Press key Process value Setting value

Setting display shows the existence of option.


Selection memo for priority displays. Display NO. for record, 1st display
NO.

TTM-000 SERIES USER'S MANUAL 1 16 DIN. DIGITAL TEMPERATURE CONTROLLER


Thank you for purchasing model TTM-000 SERIES Digital Temperature Controller. Please go through this Instruction Manual carefully and use the unit in proper manner.

Setting mode
SET1 Initial Setting 1. Initial setting display
Initial setting mode Calling display

KEY

SET2 Control Setting 9. Details of control setting


Control setting mode Calling display

KEY

SET3 Event Output 1 37. Event output 1 setting


EV1 setting mode Calling display

SET4 Event Output 2 47. Event output 2 setting

EV2 setting mode Calling display

SET5 Digital Input 57. DI setting

DI setting mode Calling display

SET6 Communication 61. Communication setting

Communication setting mode Calling display

SET7 Timer 67. Timer setting

Timer setting mode Calling display

SET0 Priority Displays 74. Priority displays setting

Select priority displays Calling display (Refer to Ex.1.)

KEY
After select, press MODE key CurrentVoltage 22

KEY

MODE key 2. Input type setting


Select input type Refer to Table 1.

MODE key 10. High limit setting in SV limiter


Display of high limit setting CurrentVoltage of setting value. 9000 (Within setting range of Table 1)

MODE key 38. Function setting for EV 1


Select below functions.

MODE key 48. Function setting for EV 2


Select below functions.

MODE key 58. Function setting for DI


Select below functions. DI action SV2 READY Manual Normal AT start Normal SV2 Timer start

MODE key 62. Parameter setting for communication

MODE key 68. Timer output setting

MODE key 75. Setting for 1st priority display


Select 1st display on operation mode B.

MODE key 2nd display


NO.

NOTICE/WARNING BEFORE OPERATION USE


When having the purchased controller at hand, please be sure that its unit is

MODE key
B. Priority displays. Refer to Ex.1. SET0 : Priority displays by setting and shows max.9 displays by setting.

MODE key more than 2 seconds

MODE key 3. PV correction gain


When measurement value comes an error, set the correction value (Multiplication)

MODE key 11. Low limit setting in SV limiter


Display of low limit setting CurrentVoltage of setting value. 1000 (Within setting range of Table 1)

PV Event functions
0None 1Deviation high and low limit 2Deviation high limit 3Deviation low limit 4Deviation high and low limit range 5Absolute value high and low limit 6Absolute value high limit 7Absolute value low limit 8Absolute value high and low limit range

PV Event functions
0None 1Deviation high and low limit 2Deviation high limit 3Deviation low limit 4Deviation high and low limit range 5Absolute value high and low limit 6Absolute value high limit 7Absolute value low limit 8Absolute value high and low limit range

a correct model (See the following "Model Configuration" ). The following symbol marks provide to prevent incident or damage. Kindly refer to the details of the WARNING/CAUTION when using for the first time. Another copy of the user's manual "Advanced Version" is provided at customer's request.

MODE key, return to A

MODE key 4. Zero point setting for PV correction


When measurement value comes an error, set the correction value (Addition)

MODE key 12. Control mode setting


Usable for control mode setting Control performance Non-control performance
(Manipulated value low limiter output)

SV RUN AUTO Reverse AT release Reverse SV Reset

Stop bit length 1 bit 2 bit Parity check Nil Odd number Even number Data length 7 bit 8 bit BCC check None Available

Non-use Control output Event 1 output

MODE key 76. Setting for 2nd priority display


Select 2nd display on operation mode B.

MODE key 3rd display


NO.

MODE key 69. Timer function setting

MODE key 77. Setting for 3rd priority display


Select 3rd display on operation mode B.

MODE key 4th display


NO.

FUNC key
FUNK key operates on the selected setting mode 7. Refer to Ex.2.

WARNING CAUTION CAUTION


For

Due to mishandling, serious dangers may occur to the operator such as death, electrocution and a skin burn. Owing to mishandling, it may cause some damage to the unit or the operator getting slight injury.

MODE key 5. Filtre input


CR filter effect is operational on software when making first-order lag operation to process value (PV).

Manual control

Additional Event functions 0None 1EV output hold 2Stand-by sequence 3EV output hold & stand-by sequence

Additional Event functions 0None 1EV output hold 2Stand-by sequence 3EV output hold & stand-by sequence

MODE key 59. Polarity setting for DI


Select below polarity. Close action Open action

Ex.1.

Priority displays & its setting This function is to shift the most essential screens on setting mode into operation mode as a priority. Please select priority displays through priority display setting.
Output 1 manipulated value Setting high limit for event Output 1

MODE key 6. Position of decimal point


ThermocoupleR.T.D.(Pt100, JPt100) Not required Required CurrentVoltage Not required 1 digit 2 digits 3 digits

MODE key 13. Selection of control type setting


Selectable and switchable below control modes.

MODE key 39. High limit setting for EV 1


Set high limit value.

MODE key 49. High limit setting for EV 2


Set high limit value.

MODE key 60. Setting for SV2


Displays only when SV2 is selected at DI.()

MODE key 63. Speed setting

Auto start Manual start Event start Auto start Manual start Event start SV start

(ON delay) (ON delay) (ON delay) (OFF delay) (OFF delay) (OFF delay) (OFF delay)

MODE key 78. Setting for 4th priority display


Select 4th display on operation mode B.

MODE key 5th display


NO.

MODE key 70. Timer unit selection

MODE key 79. Setting for 5th priority display


Select 5th display on operation mode B.

MODE key 6th display


NO.

eg. : Basic display

PID, Refer to Ex.3.

Control output 1

Control output 2

MODE key 40. Low limit setting for EV 1


Set low limit value.

MODE key 50. Low limit setting for EV 2


Set low limit value.

MODE key, return to 57

Screen is shifted when pressing mode key each time. Ex.2. FUNC key work This function is to enable FUNC key to use as a specific key, for the following actions selected in FUNC key setting belonged to setting mode. 1.Digit shift Setting digit shift is enabled when setting value is changed. 2.RUNREADY Control stop (READY) and control performance (RUN) are alternately switched every time FUNC key is pressed. (READY lamp is ON during control stop) 3.Auto-Tuning (AT) AT starts instantly after pressing FUNC key. (StartReset operation is available, each time FUNC key is pressed) 4.Timer Available for startreset.

0Type A 1Type B

1PID 2ONOFF

0None 1PID 2ONOFF 3Event output

prevention of its malfunction, do not push the front key with sharp points. Spare terminal must not be used for other purposes.

MODE key 7. FUNK key setting (Refer to Ex.2.)


Selectable below functions None Change of digit RUNREADY Auto-Tuning Timer

MODE key 14. Change of normal or reverse


Switchable below control output actions. 0Reverse (Heating) 1Normal (Cooling)

MODE key 41. Control sensitivity setting for EV 1


Set sensitivity when required(C ).

MODE key 51. Control sensitivity setting for EV 2


Set sensitivity when required(C ).

1200bps 2400bps 4800bps 9600bps 19200bps

Hourminute Minutesecond

MODE key 80. Setting for 6th priority display


Select 6th display on operation mode B.

MODE key 7th display


NO.

MODE key 71. Timer SV start permissible range


ThermocoupleR.T.D.(Pt100, JPt100) Input Setting range : 0999 0.0999.9 Setting unit : CurrentVoltage Input Setting range : 09999 (Decimal point at designated position) Setting unit : digit

MODE key 64. Address setting


Setting range : 199

MODE key 81. Setting for 7th priority display


Select 7th display on operation mode B.

MODE key 8th display


NO.

MODE key 42. Delay timer setting for EV 1


Set delay timer when required(sec).

MODE key 52. Delay timer setting for EV 2


Set delay timer when required(sec).

MODE key 65. Response delay time setting


Setting range : 0250mS

MODE key 82. Setting for 8th priority display


Select 8th display on operation mode B.

MODE key 9th display


NO.

WARNING
Make sure the correct wiring connection before turning on electricity.

MODE key 15. Manipulated value for output 1


Shows process manipulated value for output 1, and setting the value on manual control. Display range : 0.0100.0% (10.0110.0%) Setting range : Manipulated value lowhigh limiter

MODE key 43. Abnormal for EV 1


For outbreak of sensor and heater abnormal

MODE key 53. Abnormal for EV 2


For outbreak of sensor and heater abnormal

MODE key 72. Timer time setting


Setting range : 0:0099:59 0:0059:59

Mis-wiring may cause malfunction of the unit and fire. Never modify the unit to prevent damage or incident such as malfunction and fire etc. Please put this user's manual aside for your reference, when operating the unit. Copy or reprint of this manual, wholly or partially, is not allowed. The contents of this manual may change without notice in future.

MODE key 8. Key lock setting


Key lock setting for protection of error operation. Selectable below functions None All lock Operation mode lock only Except operation mode

MODE key 66. Mode selection setting

MODE key 83. Setting for 9th priority display


Select 9th display on operation mode B.

MODE key Return to primary display

Type 0None 1PV abnormal (sensor break) 2Heater abnormal 3PV + Heater abnormal Action 0None 1Hold (Power reset)

Type 0None 1PV abnormal (sensor break) 2Heater abnormal 3PV + Heater abnormal Action 0None 1Hold (Power reset)
R communication RW communication

MODE key 73. Timer residual time monitor setting


Residual time monitor. Timer starts when pressing FUNC key.

MODE key, return to 74

MODE key

Ex.3. To select PID Feature of type A and B Type A Ordinary PID Type B Over shoot protection PID If control is unstable under self-tuning, please change to type A or B and also to ONOFF control. Ex.4. ARW Anti-reset wind-up take effect for overshooting by over-integral of PID control action.

MODE key, return to 61

MODE key, return to 67

MODE key, return to 1 When select PID control 16. Setting for PID tuning type 26. Manipulated value for output 2 (%)
Tunes suitably for setting value. Auto-tuning output 1 Self-tuning output 1 Auto-tuning output 2 Self-tuning output 2 Auto-tuning output 1.2
Auto-tuning : Select above or and press FUNC key once. Call off autotuning : press FUNC key once on operating.

ACCESSORY & CONFIGURATION


1) Please be sure that the unit enclosed in packing carton is a right model before using. 2) Kindly check the following accessory being contained in that carton box. Installation Attachment (For installation, please see "INSTALLATION AND WIRING" on the back.) This user's manual : 1 copy 3) Model Configuration
Model Input Output 1 Option

MODE key 44. Polarity setting for EV 1


Normal openclose is selectable while event output is ON. Normal open Normal close

MODE key 54. Polarity setting for EV 2


Normal openclose is selectable while event output is ON. Normal open Normal close

ARW controls integral action(PV accords with SV). If integral value goes down, it takes effects. If integral value is set "0", it stops integral action.

Shows process manipulated value for output 2, and setting the value on manual control. Display range : 0.0100.0% (10.0110.0%) Setting range : Manipulated value lowhigh limiter

How to release BLIND Function


1. Power ON Automatically

eg. Release of Timer Setting Mode from BLIND Function before newly its set-up.

MODE key 27. Proportional band setting for output 2


Adjusts proportional band.

MODE key 45. CT Input Monitor for EV 1


Monitors current value of heater current detector. 160A

MODE key 55. CT Input Monitor or EV 2


Monitors current value of heater current detector. 160A

taking 4 sec

CAUTION
ERROR MESSAGES AND TROUBLE SHOOTING

2. Initial Display Automatically 3. Operation Mode Press MODE Key (10 sec)

T T M - A
MODEL Front Dimensions 002 2448 mm 004 4848 mm X04 4848 mm 005 9648 mm 006 4896 mm 007 7272 mm 009 9696 mm CODE Input Type NIL Thermocouple (K, J, R,
T, N, S, B) R.T.D. (Pt100, JPt100) 2 05V, 15V, 420mA

Option CODE B Output 2 Relay contact B or P selectable P Output 2 SSR drive voltage R EV 2 Relay contact Not optional for TTM-002004.

CODE Output 1 R Relay contact P SSR drive voltage I Current 420 mA DC

When DI is selected for TTM-005, 006, 007 or 009, this option is not available. D CT input When DI is selected for TTM-002004, this option is not usable. When I output (420mA) is selected, this option is not provided. E DI (Digital input) When CT is selected for TTM-002004, this option cannot be obtained. When EV 2 is selected for TTM-005, 006, 007 or 009, this option cannot be chosen. M Communication RS-485

Table1. To select input sensors and setting range. unit: 0.0 Setting Symbol Low limitHigh limit 00 K Thermocouple 2001372 199.9990.0 01 J 200 850 199.9850.0 02 R 01700 03 T 200 400 199.9390.0 04 N 2001300 199.9990.0 05 S 01700 06 B 01800 10 Pt100 199 500 199.9500.0 11 JPt100 199 500 199.9500.0 20 DC0 5V 19999999 199.9999.9 19.9999.99 1.9999.999 21 DC1 5V 19999999 199.9999.9 19.9999.99 1.9999.999 22 DC4 20mA 19999999 199.9999.9 19.9999.99 1.9999.999

MODE key 17. AT coefficient setting


Coefficient is multiplied by proportional band value computed at auto-tuning.

(19. To Set multiple of output proportional band) MODE key 28. Proportional cycle setting for output 2
Adjusts proportional cycle time 1120 (second)

MODE key 46. Abnormal current value of heater for EV 1


Setting for current value when heater is abnormal. 130A

MODE key 56. Abnormal current value of heater for EV 2


Setting for current value when heater is abnormal. 130A

MODE key 18. AT sensitivity setting


Sensitivity is set up during ONOFF control at auto-tuning, particulary when PV is fairly unstable.

MODE key, return to 37

MODE key, return to 47

MODE key 29. High limit setting of manipulated value for output 2
For setting of manipulated high limit value. (output 2) (%)

4. Immediately after the "Blink", press FUNC Key, and quickly press MODE Key.

(Blink once)

MODE key 19. Proportional band setting for output 1


Adjusts proportional band for output 1 (% per SLL SLH)

5. Press MODE Key (3 sec)

MODE key 30. Low limit setting of manipulated value for output 2
For setting of manipulated low limit value. (output 2) (%)

(Display)

(Description)
Shown whenever input value exceeds the high limit of display range. Also displays when the wire thermocouple, ABb terminal of R.T.D is snapped off. Shown whenever input value exceeds the low limit of display range. Display of memory error. Display of A/D converter error or incorrect sensor connection with selectable input.

(Trouble Shooting)
Check the snapping of thermocouple and R.T.D. input. Check short circuit of input lines between A-B and A-b R.T.D. In case this indication shows after the reinput of power, replace unit if it persists. Ditto Check sensor connection or change to other tuning. Discontinue to change parameter. Normality Discontinue to change setting value (during control of SV2) Discontinue to change setting value of the self on digital input Discontinue to change setting value

6. Press UP Key () for 1 7

MODE key 20. Integral time setting


Adjusts integral time 03600 (second)

MODE key 31. Manual reset setting


For shifting proportional band.

7. Press FUNC Key for OFF ON 8. Power OFF 9. Power ON Automatically

MODE key 21. Deviative time setting

A (EV1) provided in the standard specifications. Without output 2, EV2 is not available. Output 2 is equally used as EV2, but both not activated simultaneously.

Either thermocouple or R.T.D. (Pt 100JPt 100) is selectable for input type, by pressing the front key. Either "B" or "P" is optional. A (Event 1) : Single alarm is provided in the standard specifications.

Adjusts deviative time 03600 (second)

MODE key 32. Dead band Setting


For heating and cooling control().

MODE key 22. Proportional cycle setting for output 1


Adjusts proportional cycle time 1120 (second)

When select ONOFF Control 33. Contorol sensitivity setting for output 1
Adjusts control sensitivity of ON/OFF control for output1.

Display of auto-tuning error. Displayed when parameter is changed in key-lock condition. Alternately this and SV/PV display are shown. Displayed when setting value is changed on SV2 control. Displayed when changing setting value of shift on DI. Displayed when making setting value change in control display while function key is on RUN/READY. Displayed when altering setting value in control display while being on timer.

taking 4 sec 10. Initial Display Automatically 11. TIMER Setting Mode (OPERATION Mode) Press MODE Key (2 sec) 12. Press UP Key () for 1 7

MODE key 23. ARW setting (see Ex. 4)


Adjusts ARW by % 0.0100.0% (10.0110.0%)

MODE key 34. OFF position setting for output 1


For setting OFF position of control output1.
From 25.

SPECIFICATIONS
Power Supply Voltage Power Consumption Memory Element Input of Sensor Control Output Control Method Operation Environment Storage Environment Weight Location of the Unit Setting

Conformed Standards
Safety : EN61010-1(IEC1010-1) EMI : EN50081-2 EMS : EN50082-2 UL3121-1(UL CUL)

MODE key 24. High limit setting of manipulated value for output 1
For setting of manipulated high limit value. (output 1) (%)

MODE key 35. Contorol sensitivity setting for output 2


Adjusts control sensitivity of ON/OFF control for output2.

13. Go on TIMER Setting Press MODE Key consecutively


1 Please select an appropriate charactor (eg. Timer Setting etc) being of

CAUTION
Installation condition

100 to 240V AC, 5060Hz Below 10 VA EEPROM Thermocouple , R.T.D. 05V, 15V, 420mA (Changeable by front key) Relay contact, SSR drive voltage, Current Two kinds of PID, ONOFF 0 to 50, 20 to 90%RH (Avoid making dew) 25 to 70, 5 to 95%RH (Avoid making dew) TTM-002004 Less than 180g, TTM-005006 Less than 240g, TTM-007 Less than 250g, TTM-009 Less than 310g. Keep away from the followings. Gas of corrosion, dust and oily smoke. The electric noise of generator. The influence of electromagnetic field. Mechanical vibration and shock. The direct sunlight. Installation category2

MODE key 25. Low limit setting of manipulated value for output 1
For setting of manipulated low limit value. (output 1) (%)
When output 2 is ONOFF, go to 35.

MODE key 36. OFF position setting for output 2


For setting OFF position of control output2.

BLIND Function effect for the demanding release.


2 Charactor selected for TIMER Setting. 3 BLIND Function for "SELECTION DISPLAY (Timer Setting Mode)" is released.

MODE key

MODE key, return to 9

CAUTION BEFORE CONTROL


Setting

See also "PARTS INDICATION" & "INSTALLATION AND WIRING" on the reverse.
PID Control Merit Better control result is achieved ONOFF Control
Head office: 1-13-21, Tanashioda, Sagamihara Kanagawa 229-1125 Japan. Phone: 81-42-777-3311 Fax: 81-42-777-3751 E-Mail: info@toho-inc.co.jp Web site: http://www.toho-inc.co.jp
Life span of relay is generally longer, as opposed to that of ONOFF control. as it is ON when temperature is below SV and it is OFF when temperature is over SV (For heating control). Demerit Life span of relay is shorter, as output Control value is worse in comparison exists frequently with relay contact . with that of PID control.

program is stored after power OFF, as non-volatile memory is equipped with TTM-000 SERIES controllers for setting storage. Either thermocouple or R.T.D.(Pt 100JPt 100) is selectable input type, but CurrentVoltage input needs to be selected individually. For suitable application, please select most appropriate input type and adjust input setup. PID or ONOFF control is selective for the optimal performance and each detail of features is specified in the table on the right side.

PID constants are automatically reckoned up to write in, when control begins or SV is altered on self-tuning.