Air Conditioning Disconnects

February 2007

7-1

Air Conditioning Disconnects

Contents
Description Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features, Benets and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross-Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-2 7-2 7-3 7-3 7-3 7-4 7-7 7-8

Complete Line of Fused, Unfused and Molded Case Switch Type Air Conditioning Disconnects

CA08101001E

For more information visit: www.eaton.com

7-2

Air Conditioning Disconnects


February 2007

Product Description
An Air Conditioning Disconnect (ACD) is a disconnect located between a loadcenter (distribution panel) and air conditioner. The Cutler-Hammer ACD by Eaton Corporation provides an installer or repair personnel with a visible disconnecting means when performing maintenance. ACDs are also known as disconnects, pullouts or air conditioning switches. Non-fused pullout and molded case switch devices provide personnel with a visible on-off disconnecting means. While fused pullout units also perform this function, they also provide an additional level of protection for the air conditioner. Fused and non-fused devices are of a pullout design, where the user physically removes or pulls out a tab to break the electrical connection. A molded case switch is similar to a light switch where the user switches the unit to the indicated ON-OFF position.

Application Description
Note: Most applications involving water require a ground fault breaker.

The most widely used application is for residential and light commercial air conditioning units. An ACD is installed outdoors, in a visible range from the air conditioner. ACDs are also found in use with heat pumps, swimming pools, spas, whirlpools and pump houses. Metallic enclosures are galvanized steel and are installed in various locations. Non-metallic enclosures are a plastic (polycarbonate) enclosure commonly used in coastal or saltwater areas.

Molded Case Switch

Non-Fused Pullouts

Fused Pullouts

DPB222R

DPU222R

DPF222R

Rugged molded case construction in a disconnect switch that looks like a circuit breaker but operates like an ordinary household light switch. Plug-in molded case switch eliminates the need for pullout handles. No need for replacement pullout handles due to loss or theft. Includes non-automatic molded case switch.

ON/OFF control provided by a pullout handle. Pullout handle can be conveniently stored in the compartment in the OFF position, helping to prevent the handle from being misplaced. Protective shield cannot be removed until the pullout handle is removed, disconnecting the power.

Fuses are installed behind the protective shield that cannot be removed until the pullout handle is removed, disconnecting the power. Horsepower ratings apply when time delay fuses are used. Class H fuse clips are provided. Fuses not included. ON/OFF control provided by a pullout handle. Pullout handle can be conveniently stored in the compartment in the OFF position, helping to prevent the handle from being misplaced.

For more information visit: www.eaton.com

CA08101001E

Air Conditioning Disconnects


February 2007

7-3

Features, Benets and Functions


Single-phase, 2-wire, 240 Vac and 3-phase, 3-wire, 240 Vac. NEMA 3R outdoor enclosures offered in metallic and non-metallic versions. Easy-to-remove high strength protective shield for easier wiring and mounting. Easy-to-remove front cover (no screws or fasteners to remove). 1-inch knockouts on the bottom, back and side of unit. Cu rated line and load lugs that are easily accessible. Ample wiring space for mounting with a stud gun (single keyhole, two- or three-point mounting). Fused devices are service entrance rated.

Type 3R Rainproof Metallic Enclosure Provides Plenty of Knockout Sizes

Air Conditioning Disconnect with Whip

Easily Accessible Neutral

Note: Fused non-metallic units require the addition of GB4NM ground bar.

Horsepower rated (10 hp maximum at 240 Vac). Padlockable door provision for safety and reduction of tampering. Metallic enclosures are bottom entry and exit only. Non-metallic enclosures have knockouts and a hub provision for top access. Non-metallic enclosures have a single unit door and protective shield for installer convenience. Non-metallic enclosures are durable and provide excellent resistance to climate changes.

Air Conditioning Disconnect with Ground Fault Type 3R Rainproof Non-Metallic Enclosure Provides Durable Strength and Excellent Resistance to Climate Changes

Standards and Certications


UL listed File No. E5239. Separate CSA approved unit.

Contact us for details and part numbers for CSA approved units.

Cutler-Hammer Quick-ProSM
All you need to know to save time and make more money. Specied on certain Cutler-Hammer products, the Quick-Pro symbol allows for immediate recognition of products that are designed for straightforward installation. When you see Quick-Pro, you know you can install quickly sometimes up to 50% less than the usual installation time and move onto your next job.
Pullout Handle Can be Stored in Enclosure in OFF Position

Product Specications

10,000 amperes rms symmetrical interrupting rating. Horsepower rated. Fusible and non-fusible pullout and molded case switch designs. 30 and 60 amperes available in fusible. 60 amperes available in non-fusible and molded case switch. Class H fuse clips provided on fusible pullout design.

CA08101001E

For more information visit: www.eaton.com

7-4

Air Conditioning Disconnects


February 2007

Technical Data and Specications


Table 7-1. Dimensions and Shipping Carton Information
Description Dimensions in Inches (mm) Height Width 5.40 (137.2) 5.40 (137.2) 5.40 (137.2) 5.30 (134.6) 12.50 (317.5) 12.50 (317.5) 7.50 (190.5) 7.50 (190.5) 7.50 (190.5) 5.30 (134.6) 7.50 (190.5) 7.50 (190.5) 7.50 (190.5) 5.00 (127.0) 5.00 (127.0) 5.00 (127.0) 5.00 (127.0) Depth 3.15 (80.0) 3.15 (80.0) 3.15 (80.0) 3.74 (95.0) 4.00 (101.6) 4.00 (101.7) 4.75 (120.7) 4.75 (120.7) 4.75 (120.7) 3.74 (94.9) 4.75 (120.7) 4.75 (120.7) 4.75 (120.7) 3.50 (88.9) 3.50 (88.9) 3.50 (88.9) 3.50 (88.9) Carton Quantity Weight Lbs. (kg) Catalog Number Price U.S. $

Metallic/Galvanized Steel Enclosure


30 A Fused 60 A Fused 60 A Non-Fused 60 A Molded Case Switch 60 A Non-Fused with 1/2-inch wire harness 60 A Non-Fused with 3/4-inch wire harness 60 A Non-Fused with 20 A ground fault receptacle 30 A Fused with 20 A ground fault receptacle 60 A Fused with 20 A ground fault receptacle 60 A Molded Case Switch 3-Phase 240 V 60 A Non-Fused with 15 A ground fault receptacle 30 A Fused with 15 A ground fault receptacle 60 A Fused with 15 A ground fault receptacle 8.70 (220.9) 8.70 (220.9) 8.70 (220.9) 8.60 (218.4) 14.75 (374.6) 14.75 (374.6) 13.00 (330.2) 13.00 (330.2) 13.00 (330.2) 8.60 (218.4) 13.00 (330.2) 13.00 (330.2) 13.00 (330.2) 8.63 (219.0) 8.63 (219.0) 8.63 (219.0) 8.63 (219.0) 10 10 10 10 1 1 1 1 1 1 1 1 1 10 10 10 10 27 (12) 27 (12) 27 (12) 34 (15) 6 (3) 6 (3) 8 (4) 8 (4) 8 (4) 4 (2) 8 (4) 8 (4) 8 (4) 15 (7) 15 (7) 15 (7) 18 (8) DPF221R DPF222R DPU222R DPB222R DPU222R12W DPU222R34W DPU222RGF20 DPF221RGF20 DPF222RGF20 DPU362R DPU222RGF15 DPF221RGF15 DPF222RGF15 ACD221RNM-A2 ACD222RNM-A2 ACD222URNM-A2 B60NARNM-A2

Non-Metallic/Polycarbonate Enclosure
30 A Fused 60 A Fused 60 A Non-Fused 60 A Molded Case Switch

Cutler-Hammer Quick-Pro designated item.

Note: Refer to Page 7-7 for prices.

5.40 (137.2) 1.47 (37.2)

3.15 (80.1) 2.54 (64.4) 1.11 (28.2)

2.00 (50.8)

4.00 (101.6)
.25 (6.4)

8.79 (223.4)

8.70 (221.0)

5.14 (130.6) 5.26 (133.6)

0.26 (6.5) Dia.


3 Holes Req'd.

1.65 (41.9) 5.25 (133.5)


1.13 (28.7) 2.39 (60.8)

1.09 (27.7)
1.00 (25.4) 1.55 (39.4) 1.55 (39.4)

5.10 (129.5)

2.97 (75.3)

7 Knockouts for 1/2 (12.7), 3/4 (19.1) or 1 (25.4) Conduit


1.13 0.55 (28.7) (14.0) 1.05 (26.7) 1.50 (38.1) 3.00 (76.2)

0.28 (7.1) Diameter Knockout 1 Req'd.

Figure 7-1. DPF221R, DPF222R, DPU222R, DPU222R12W and DPU222R34W


Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22CD For more information visit: www.eaton.com CA08101001E

Air Conditioning Disconnects


February 2007

7-5

Dimensions in Inches (mm)

8.60 (218.4)

7
3.74 (94.9)

5.30 (134.6)

Figure 7-2. DPB222R and DPU362R

6.26 (159.0) .20 (5.1) DIA. 4.33 (110.2) .90 (22.9)

7.03 (178.7) 8.69 (220.8) 8.36 (212.2)

.96 (24.4)

1.00 (25.4)

1.35 (34.3) FOR .50 (12.7), 1.83 (46.4) 1.25 (31.8) CONDUIT 4.08 (103.6) 4.20 (106.6)

.81 (20.6) 6.00 (152.4) 1.05 (26.5) .21 (5.3) DIA. 4 KNOCKOUTS FOR .75 (19.1) OR 1.00 (25.4) CONDUIT

1.35 (34.3) (34.5) ( (44.7) ) 3.52 (89.3) 2 KNOCKOUTS FOR .50 (12.7), .75 (19.1) OR 1.00 (25.4) CONDUIT

Figure 7-3. ACD221RNM-A2, ACD222RNM-A2, ACD222URNM-A2 and B60NARNM-A2

CA08101001E

For more information visit: www.eaton.com

7-6

Air Conditioning Disconnects


February 2007

Dimensions in Inches (mm)


6.63 (168.4) .25 (6.4) DIA. HOLE 3 PLACES

4.44 (112.8)

11.63 (295.4)

8.75 (10.31)

2.31 (58.7) 1.44 (36.6)

0.75, 1.00, 1.25, 1.50 (19.1, 25.4, 31.8, 38.1) K.O.


20A GFCI RECEPTACLE

0.69 (17.5)

1.69 (42.9) 5.13 (130.3) 6.25 (158.8)

0.50, 0.75, 1.00 (12.7, 19.1, 25.4) K.O.

4.06 (103.1)

4.31 (109.5) 1.25 (31.8)

0.50, 0.75 (12.7, 19.1) K.O. 0.94 (23.9) 4.44 (112.8)

Figure 7-4. DPU222RGF20, DPF221RGF20, DPF222RGF20, DPU222RGF15, DPF221RGF15 and DPF222RGF15

For more information visit: www.eaton.com

CA08101001E

Air Conditioning Disconnects


February 2007

7-7

Product Selection
Table 7-2. Molded Case Switch
Main Ampere Rating Maximum hp Rating 120 V 240 V Wire Size Range Cu/Al 60C or 75C Catalog Number Price U.S. $

Table 7-5. ACD with 20 Ampere Ground Fault Receptacle


Main Maximum hp Ampere Rating Rating 120 V 240 V Wire Size Range Cu/AI 60C or 75C Catalog Number Price U.S. $

Non-Fused Pullouts
60 10 10 #14 3 #14 2 DPB222R B60NARNM-A2 30 60 20 Catalog Number Price U.S. $

Galvanized Steel
60 60

3 3 3

10 10 10

#14 3 #14 3 #14 3 #12

DPU222RGF20 DPF221RGF20 DPF222RGF20

Fused Pullouts

Non-Metallic

Table 7-3. Non-Fused Pullouts


Main Ampere Rating Maximum hp Rating 120 V 3 3 Wire Size Range Cu/Al 240 V 60C or 75C #14 3 #14 2

GFCI Receptacle
Included in above.

Table 7-6. ACD with 15 Ampere Ground Fault Receptacle


DPU222R ACD222URNM-A2 Main Maximum hp Ampere Rating Rating 120 V 240 V Wire Size Range Cu/AI 60C or 75C Catalog Number Price U.S. $

Galvanized Steel
60 60

10 10

Non-Metallic
For replacement pullout head, order part number 96-3258-4.

Non-Fused Pullout
60 30 60 15

3 3 3

10 10 10

#14 3 #14 3 #14 3 #14

DPU222RGF15 DPF221RGF15 DPF222RGF15

Table 7-4. Fused Pullouts


Main Ampere Rating 30 60 30 60

Fused Pullouts
Wire Size Range Cu/Al 60C or 75C Catalog Number Price U.S. $

Maximum hp Rating 120 V 1-1/2 3 1-1/2 3 240 V 3 10 3 10

GFCI Receptacle
Included in above.

Galvanized Steel
#14 3 #14 3 #14 2 #14 2 DPF221R DPF222R ACD221RNM-A2 ACD222RNM-A2

Table 7-7. Three-Phase Non-Fused ACD


Main Maximum hp Ampere Rating Rating 120 V 240 V 60 10 15 Wire Size Catalog Range Cu/AI Number 60 C or 75 C #14 3 DPU362R Price U.S. $

Non-Metallic

To obtain a Service Entrance Rating, the addition of a DPFG is required. For replacement pullout head, order part number 96-3258-4. To obtain a Service Entrance Rating, the addition of GB4NM (Ground Bar Kit) is required.

Table 7-8. ACD with Factory-Installed Whip Non-Fused Pullout


Whip Diameter 1/2 Inch 3/4 Inch Hot Wire Size #10 #8 Ground Wire Size #10 #10 Flexible Conduit Length 6 ft. (1.8 m) 6 ft. (1.8 m) Non-Metallic Fittings 1 90, 1 Straight 1 90, 1 Straight Catalog Number DPU222R12W DPU222R34W Price U.S. $

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . 22CD CA08101001E For more information visit: www.eaton.com

7-8

Air Conditioning Disconnects


February 2007

Cross-Reference
Table 7-9. Cross-Reference
Description Catalog Number Cutler-Hammer Square D GE Siemens (Murray) WF2030 WF2060 WN2060 WNFC2060 WNAS2060 WN2060GFCI WF2030GFCI WF2060GFCI WF2030PL WF2060PL WN2060PL Milbank Thomas & Betts ACM221 ACM222 ACM222NF ACPO222NF ACM2620NA ACP221 ACP222 ACP222NF ACP260NA Midwest

Metallic/Galvanized Steel Enclosure


30 A Fused 60 A Fused 60 A Non-Fused 60 A Non-Fused Compact Design 60 A Molded Case Switch 60 A Non-Fused with GF Receptacle DPF221R DPF222R DPU222R DPU222R DPB222R DPU222RGF DPF221RGF DPF222RGF DPU222R12W DPU222R34W DPU362R ACD221RNM-A2 ACD222RNM-A2 ACD222URNM-A2 B60NARNM-A2 FP221R FP222R UFP222R QO200TR UFP222RGFI FP221RNM FP222RNM UFP222RNM QO200TRNM TF30R TF60R TFN60R TNA60R1 TFN60RGFR TPF30R TPF60R TPN60R1 TPNA60R1 U3803 U3806 U3800 U3822-20GR U035F2 U065F1 U065P010 U065NA1 U065P010 U035F010 U065F010 U0653F P035F P065F P065P1 P065NA1

30 A Fused with GF Receptacle 60 A Fused with GF Receptacle 60 A Non-Fused with1/2-inch Wire Harness 60 A Non-Fused with 3/4-inch Wire Harness 60 A 3-Phase 600 V Molded Case Switch

Non-Metallic/Polycarbonate Enclosure
30 A Fused 60 A Fused 60 A Non-Fused 60 A Molded Case Switch

CSA is a registered trademark of the Canadian Standards Association. General Electric is a federally registered trademark of General Electric Company. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. Siemens is a federally registered trademark of Siemens AG. Square D is a federally registered trademark of SNA Holdings Inc. Thomas & Betts is a federally registered trademark of Thomas & Betts Corporation. UL is a federally registered trademark of Underwriters Laboratories Inc. Cutler-Hammer is a federally registered trademark of Eaton Corporation. Murray is a federally registered trademark of Siemens Energy & Automation, Inc.