JOB NO.
Fire Protection System Study process area Equipment to be Protected Name Type Height Length Width Protected Volume Concentration Room Volume Protected Volume Type of Clean Agent Minimum Design Quantity Net Volume Hazard Agent Design Concentration Min. Anticipated Temperature Agent Specific Vapor Volume Weight of Clean Agent Design Factor for Piping Tee Amount of Piping Tee Clean Agent Design Factor Minimum Design Quantity Final Design Quantity Flame Extinguishment Design Conc. Discharge Time Required Safety Factor Final Design Quantity Spec. of Bottle Agent Storage Type Manufacture Part Number Cylinder and Valve Assembly Capacity Valve Fill Agent Capacity a. Minimum b. Maksimum c. Agent Capacity Additional Clean Agent Quantity Required Clean Agent Bottle Quantity a. Main b. Reserve Summary Final Design Quantity Bottle Quantity a. Main b. Reserve Note : No Observed Adverse Effect Level Rev. Date Description : :
DWG NO.
: : : : :
: : :
: : : : :
(NOAEL)*
NFPA 2001
NFPA 2001
: : :
5 ea 0.01 lb 1530.08 lb
: : : :
Point 3-8.1.2.3 NFPA 2001 Point 3-8.1.2.3 NFPA 2001 Point 3-4.2.2.1 NFPA 2001
: : : : : : : : : : : :
Bottle Kidde Fire System 45-100601-001 600 lb 3 inch 300 600 550 1744.30 lb lb lb lb
4 bottles 1 bottle
1744.30 lb
4 bottles 1 bottle
Prepared by
Reviewed by
Approved by
WO NO.
JOB NO.
004 Fire Protection System Study Switch Gear / Control Room Equipment to be Protected Name Type Height Length Width Protected Volume Concentration Room Volume Protected Volume Type of Clean Agent Minimum Design Quantity Net Volume Hazard Agent Design Concentration Min. Anticipated Temperature Agent Specific Vapor Volume Weight of Clean Agent Design Factor for Piping Tee Amount of Piping Tee Clean Agent Design Factor Minimum Design Quantity Final Design Quantity Flame Extinguishment Design Conc. Discharge Time Required Safety Factor Final Design Quantity Spec. of Bottle Agent Storage Type Manufacture Part Number Cylinder and Valve Assembly Capacity Valve Fill Agent Capacity a. Minimum b. Maksimum c. Agent Capacity Additional Clean Agent Quantity Required Clean Agent Bottle Quantity a. Main b. Reserve Summary Final Design Quantity Bottle Quantity a. Main b. Reserve Note : No Observed Adverse Effect Level Rev. A B Date 9-Dec-13 21-Apr-14 Description Issued For Review Issued For Approval Prepared by HRS HRS : : 1 bottle 1 bottle
DWG NO.
058/SP3MP-06/2013 137597-63-PE-03-RP-005
: : : : :
: : :
: : : : :
(NOAEL)*
NFPA 2001
NFPA 2001
: : :
5 ea 0.01 lb 467.31 lb
: : : :
Point 3-8.1.2.3 NFPA 2001 Point 3-8.1.2.3 NFPA 2001 Point 3-4.2.2.1 NFPA 2001
: : : : : : : : : : : :
Bottle Kidde Fire System 45-100601-001 600 lb 3 inch 300 600 550 532.74 lb lb lb lb
1 bottle 1 bottle
532.74 lb
Reviewed by GI / AG AH / HS