L1
L2
FBX
Gas-Insulated Medium-Voltage
Switchgear
up to 24 kV
for secondary distribution
- compact or extensible
L3
L1
L2
L3
L1
L2
L3
Cable
Cable
Trafo
System configuration
AREVA T&D
Delivery Conditions
The General Delivery Conditions as amended shall apply.
Illustrations
The illustrations are not binding.
>
>
Table of Contents
INTRODUCTION
Features
STANDARDS
Regulations, provisions and standards
Type designation
Maximum number of operations
8
9
10
TECHNICAL DATA
FBX with switch disconnector (C)
FBX with switch fuse combination (T1)
FBX with vacuum circuit-breaker (T2)
11
12
13
14
15
PRODUCT DESCRIPTION
Basic equipment
Example for FBX-E equipped with switch
disconnector (C) and switch fuse
combination (T1)
Example for FBX-E equipped with vacuum
circuit-breaker (T2)
WIC1 protection relay
Operation
Interlocking system
Motor-operated drive mechanism, shunt opening
release and auxiliary switch
FBX-E in-line arrangement
Voltage Detection System and gas compartment
technology
Integrated package solution for automation
Cable connections
Selection tables for cable connections
High voltage fuse links
Selection of HV HRC fuse links
16
18
19
20
21
22
23
24
25
26
27
28
30
31
ECOLOGICAL CONSIDERATIONS
34
METERING PANEL
35
DESIGN DATA
Pressure relief
Fastening and flooring ducts
Accessories
37
39
47
SHIPPING
Packing and transport
48
>
>
Overview
FBX - compact and extensible
FEATURES
Automated stations
Fields of application
The FBX ring main units are used in
non-accessible or in walk-in stations
belonging to the public power supply companies, of industry, infrastructure and windpower stations.
For automated power system operation, FBX can be managed from the
remote control station by motor control and electrically via the micro
remote control module.
Advantages
> Economic, space-saving design
> Extensible or non-extensible, to
suit your requirements
> Straightforward installation without
gas handling
> Independent of environmental
influences
> Very long service life and low life
cycle costs
> Eco-friendly
FBX Straightforward
planning
The FBX is a gas-insulated threepole enclosed switchgear system
for secondary distribution. SF6 gas is
used as the insulating medium. The
gas-filled, clad compartments of FBX
are insensitive to environmental
influences such as humidity, dust,
dirt and vermin, and afford maximum
operator safety.
FBX-C switchgear is available as
classical non-extensible ring main
units, with 2 to 4 switching units.
FBX-E is the extensible version,
with 1 to 4 switching units, which
are arranged in a common gas-filled,
clad compartment. The functional
units of FBX-E can be arranged in
any order, without gas handling, to
form the required multi-panel switchgear arrangement.
L1
L2
L3
L1
L2
L3
L1
L2
L3
Cable
Cable
Trafo
L1
L2
L3
L1
L2
L3
L1
L2
L3
Cable
Cable
Trafo
FBX-E, extensible
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
Cable
L1
Cable
L2
L3
L1
L2
L3
Cable
Trafo
Cable
Cable
Trafo
Cable
Trafo
FBX-C/C-C-C-T1
FBX-C/C-C-T1
Functional units:
C = Outgoing feeder cable with
switch disconnector
T1 = Transformer outgoing feeder
with switch fuse combination
T2 = Transformer outgoing feeder with
vacuum circuit-breaker
R = Busbar riser without earth switch
RE = Busbar riser with earth switch
FBX-C/C-T1
Complete range of FBX-C versions with two, three and four switching functions, see page 14.
L3
L1
L2
L3
L1
L2
L3
FBX-E/C
FBX-E/T1
Functional units:
C = Outgoing feeder cable with switch disconnector
T1 = Transformer outgoing feeder with
switch fuse combination
T2 = Transformer outgoing feeder with
vacuum circuit-breaker
R = Busbar riser without earth switch
RE = Busbar riser with earth switch
FBX-E/T2
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
FBX-E/C-C-C-T1
Functional units:
C = Outgoing feeder cable with switch
disconnector
T1 = Transformer outgoing feeder with
switch fuse combination
T2 = Transformer outgoing feeder with
vacuum circuit-breaker
R = Busbar riser without earth switch
RE = Busbar riser with earth switch.
FBX-E/C-C-T1
FBX-E/C-T1
For the complete FBX-E range, with one to four panel functions, see page 15.
7
>
>
Standards
Regulations, provisions and standards
DEGREE OF PROTECTION
AGAINST ACCIDENTAL
CONTACT AND INGRESS
OF FOREIGN OBJECTS
Main electric circuits
Drive mechanisms
and secondary
systems recess
IP65
IP2X
IP5X 1)
Cable connection
IP3X 1)
compartment (Operators
IP5X 1)
side with cable compartment
cover and sides)
1) Optional
ENVIRONMENTAL AND
OPERATING CONDITIONS
Ambient conditions
"minus 5 indoors 1)
Temperature class
Min./max. ambient temperature
FBX switchgear units must be installed and operated in normal conditions as specified in EN 60694 or
IEC 60694.
-51) / 40
35 2)
1000 3)
Insulating gas
Type
Rated pressure pre at 20 C
0,03
APPLICABLE STANDARDS
FBX switchgear units meet the
requirements of the following standards and regulations:
Designation
IEC standard
IEC classes
Switchgear
IEC 62271-200
IEC 60694
Partition class PM
EN 62271-200
Loss of service continuity category
EN 60694
(LSC) of cable connection compartments and locating tubes for HV HRC
fuse links: LSC 2A 1)
EN standard
IEC 62271-200
IEC 62271-102
E2
EN 62271-102
IEC 62271-102
M1
EN 62271-102
IEC 60265-1
M1, E3
IEC 62271-105
M1, E1
Circuit-breaker (T2)
EN 62271-200
E1, C1
EN 62271-100
Current transformer
IEC 60044-1
EN 60044-1
Voltage transformer
IEC 60044-2
EN 60044-2
IEC 61243-5
EN 61243-5
IEC 60529
N 60529
Installation
HD 637 S1
EN 50110
1)
If FBX-M air-insulated metering panels are used, operating availability may be restricted, depending on the entire switchgear configuration, below
LSC 2A. However, if the FBX-M1 metering panel can be isolated to the left or right (live operation of switchgear section on the left and right can be
maintained), the operating availability with LSC 2A is guaranteed for the entire switchgear.
TYPE DESIGNATION
The designation of the type-tested
switch disconnector unit defines its
design, rated short-time current,
rated voltage and components fitted.
Example
FBX-C /12-16/C-C-T1
5 000
5 000
50
1 000
500
500
5000
800
1000
500
5000
1000
1100
500
100
50
10
10
10
50
100
50
100
50
100
10
1 000
20
10
10
10
50
1000
100
50
10
500
630
50
100
100
500
0,4
0,5
0,6
500
1 000
0,1
1 000
10
2 000
>
>
Technical data
kV
12
17.5
24
Rated frequency
Rated lightning impulse withstand voltage
to earth
over the isolating distance
Rated power frequency withstand voltage
to earth
over the isolating distance
Insulating level for SF6 pressure Pre = 0.00 MPa
Rated lightning impulse withstand voltage
Rated power frequency withstand voltage
Insulating level of isolating distance for cable test
at busbar
Ur
at outgoing feeder Power-frequency test voltage
at outgoing feeder DC test voltage
Rated normal current
Busbar
Outgoing feeder
Rated peak withstand current, rated short-circuit making current
Hz
50/60
50/60
50/60
kV
kV
75
85
95
105
125
145
kV
kV
28
32
38
45
50
60
kV
kV
75
28
95
38
95
50
kV
kV 0.1 Hz
kV
12
18
48
17.5
26
60
24
35
96
A
A
kA
kA
kA
kA
kA
kA
kA
kA
A
A
A
A
630
630
630
630
630
630
1s
3s
1s
3s
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
40
40
16
16
16
16
16
16
52.5
52
21
20
20
20
21
0.85x20
630
160
600
277
40
40
16
16
16
16
16
16
52.5
52
21
20
20
20
21
0.85x20
630
160
600
277
40
40
16
16
16
16
16
16
50
20
20
20
0.85x20
630
160
600
277
1000
1000
1000
100
100
100
5
5
5
5
5
5
11
kV
12
17.5
24
Rated frequency
Rated lightning impulse withstand voltage
to earth
over the isolating distance
Rated power frequency withstand voltage
to earth
over the isolating distance
Insulating level for SF6 pressure Pre = 0.00 MPa
Rated lightning impulse withstand voltage
Rated power frequency withstand voltage
Rated normal current
Busbar
Outgoing feeder
Rated short-time current
Hz
50/60
50/60
50/60
kV
kV
75
85
95
105
125
145
kV
kV
28
32
38
45
50
60
kV
kV
75
28
95
38
95
50
A
A
kA
kA
kA
kA
kA
kA
A
630
1)
5
3
13
13
630
1)
5
3
13
13
630
1)
5
3
13
13
1s
3s
1s
3s
16
16
21
0.85x20
60
2)
12
21
0.85x20
60
16
16
20
0.85x20
60
200
200
A
A
ms
200
87
1100
34
87
800 3)
34
87
800 3)
34
1000
1000
1000
10
10
10
5
5
5
5
5
5
16
16
kV
12
17.5
24
Rated frequency
Rated lightning impulse withstand voltage
to earth
over the isolating distance
Rated power frequency withstand voltage
to earth
over the isolating distance
Insulating level for SF6 pressure Pre = 0.00 MPa
Rated lightning impulse withstand voltage
Rated power frequency withstand voltage
Insulating level of isolating distance for cable test
at busbar
Ur
at outgoing feeder Power-frequency test voltage
at outgoing feeder DC test voltage
Rated normal current
Busbar
Outgoing feeder
Rated peak withstand current, rated short-circuit making current
Hz
50/60
50/60
50/60
kV
kV
75
85
95
105
125
145
kV
kV
28
32
38
45
50
60
kV
kV
75
28
95
38
95
50
kV
kV 0.1 Hz
kV
12
18
48
17.5
26
60
24
35
96
1s
3s
1s
3s
A
A
kA
kA
kA
kA
kA
kA
kA
kA
kA
%
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
630
400/630 1)
40
52,5
40
52
16
21
16
20
16
20
16
20
16
21
16
0.85x20
16
20
28
25
630
400/630 1)
40
52,5
40
52
16
21
16
20
16
20
16
20
16
21
16
0.85x20
16
20
28
0-3 min-CO
31.5
630
400/630 1)
40
50
40
16
20
16
16
20
16
16
20
16
0.85x20
16
20
28
31.5
1000
1000
1000
1000
1000
1000
1000
50
1000
50
1000
50
630 A on request
Making snap-action mechanism and breaking stored-energy mechanism with motor
13
>
>
Number of panels
Height
[mm]
Depth
[mm]
Width
[mm]
Weights approx.
[kg]
RE-T1
2-panel unit
RE-T2
2-panel unit
1380
C-C
2-panel unit
C-T1
2-panel unit
C-T2
2-panel unit
1380
200
C-C-T1
3-panel unit
330
360
210
240
720
680
200
200
C-C-T2
3-panel unit
1380
C-RE-T1
3-panel unit
C-RE-T2
3-panel unit
1380
R-RE-T1
3-panel unit
320
R-RE-T2
3-panel unit
1380
350
C-C-C
3-panel unit
320
C-C-C-T1
4-panel unit
450
C-C-C-T2
4-panel unit
1380
C-T1-C-T1
4-panel unit
C-T2-C-T2
4-panel unit
1380
500
C-C-C-C
4-panel unit
440
720
1320
470
1000
C
C
1)
720
T1
1320
T2
C
Variants
RE-T1
RE-T2
C-C
C-T1
C-T2
14
360
13801)
720
1000
480
1380 1)
13801)
680
320
720
Variants
C-C-T1
C-C-T2
C-RE-T1
C-RE-T2
R-RE-T1
R-RE-T2
C-C-C
Variants
C-C-C-T1
C-C-C-T2
C-T1-C-T1
C-T2-C-T2
C-C-C-C
720
T2
FBX-E (EXTENSIBLE)
Dimensions and weights: Type FBX-E (extensible)
Function
Number of panels
Height
[mm]
Depth
[mm]
Width
[mm]
1380
720
Weights approx.
[kg]
Single panel
Single panel
360 2)
RE
Single panel
T1
Single panel
T2
Single panel
RE-T1
2-panel unit
RE-T2
2-panel unit
C-C
2-panel unit
C-T1
2-panel unit
210
C-T2
2-panel unit
210
C-C-T1
3-panel unit
340
C-C-T2
3-panel unit
370
C-RE-T1
3-panel unit
C-RE-T2
3-panel unit
R-RE-T1
3-panel unit
330
R-RE-T2
3-panel unit
330
C-C-C
3-panel unit
330
C-C-C-T1
C-C-C-T2
C-T1-C-T1
C-T2-C-T2
C-C-C-C
4-panel unit
4-panel unit
4-panel unit
4-panel unit
4-panel unit
460
490
480
510
450
135
125
135
160
490 2)
720
1380
190
220
250
1380
680 2)
720
210
330
1000 2)
720
1380
1380
330
1320 2)
720
720
720
C
720
680
RE T2
490
T1
360
1380
1380
1380
1380
1380
1) plus 19 mm for the busbar covers (left- and right-hand) at the end of the switchgear
2) Dimensions plus 10 mm width for in-line arrangement, refer to list
1000
C
C
720
T1
1320
T1
C
720
T1
1-panel functional
units
1-panel functional
units
2-panel functional
units
3-panel functional
units
4-panel functional
units
Variants
C
R
RE
Variants
T1
T2
Variants
RE-T1, RE-T2, C-C,
C-T1, C-T2
Variants
C-C-T, C-C-T2, C-RE-T1
C-RE-T2, R-RE-T1, R-RE-T2
C-C-C
Variants
C-C-C-T1, C-C-C-T2, C-T1-C-T1,
C-T2-C-T2, C-C-C-C
Installation
19 ,
,
,
10
490
A L P H A E L1
L1L2L3
P
N
I
L2
10
1000
,,
, ,
L3
ALPHA E
L1L2L3
0
52
0 6
2 -+
04 S
06 p
C
C F
C
C
C
0
2
52
0 6
6 +
04 -S
0 p
C
C F
C
C
C
P
N
I
1000
,,
L1
L2
L3
ALPHA E
L1L2L3
L1
L2
L3
19
,
L1
L2
L3
0
2
52
0 6
6 +
04 -S
0 p
C
C F
C
C
C
P
N
I
15
>
>
Product description
Basic equipment, operation
Gas-filled clad
compartment
BASIC EQUIPMENT
> manually actuated switching
devices
> gas-filled, clad compartments
with stainless-steel tanks
> cable compartment covers,
arc-proof
> mechanical interlocks for each
outgoing feeder
options available include
> fuse attachment featuring all-pole
tripping or
> vacuum switches with protection
equipment
> pressure gauge with green/red
indicator:
Gas monitoring is effected for
each gas-filled, clad compartment
via a pressure gauge with clear
indicator areas:
- green - gas pressure OK
- red - gas pressure low.
The check for zero voltage is performed via the (non-integrated) voltage
detection system to IEC 61243-5
part 5 system HR.
16
Illustrated: FBX-E
Pressure gauge
- secured on self-closing
disposal valve
Recess for secondary systems, and display mask
Control panel
Fuse cover
Supporting structure with cable
connection compartments
Additional recess
for automation
17
Function T1
Function C
T1
Transformer outgoing
feeder
switch disconnector
fuse combination
L1
L2
L3
L2
L3
C
Outgoing feeder cable
with switch
disconnector
T1
Illustrated: FBX-E
18
Function T2
T2
Transformer outgoing
feeder with vacuum
circuit-breaker
(400/630 A)
L1
L2
standard equipment
L3
I<
I<
<
Illustrated: FBX-E
19
sungs-
Adjustment range
Steps
Function
I>
0.9 x - 2,5 x Is
0.05 x Is
tI>
0.04 - 300 s
0.01 s
UMZ / DEFT
0.05 - 10
0.05
I>>
1 x - 20 x Is
0.1 x Is
tI>>
0.04 - 3 s
0.01 s
IE>
0.2 - 2.5 x Is
0.05 x Is
tIE>
0.1 - 300 s
0.01 s
UMZ / DEFT
WIC1-W3AR
WIC1-W4AR
WIC1-W5AR
32-112 A
64-224 A
128-448 A
OPERATION
Operator interfaces
With to its well-structured
layout and clear integrated
functional diagram, the operator
interface is designed to ensure
safe operation.
Each switching device is equipped with an access point for
the operating lever and a
mechanical position indicator.
The two earth switches, located
upstream and downstream of
the HV HRC fuse carriers on
the switch fuse combination T1,
are actuated simultaneously via
a common drive.
All actuator access points can
be provided with a locking facility as an option.
As an option, both switch disconnectors and vacuum circuitbreakers can be fitted with a
motor-drive. In this case, emergency manual mechanical
actuation can be provided for
the switching device drives.
10 11/12
5
9
7
13
17
6
6
1
2 14 15
16
7
17
6
2
7
6
Busbar riser R
21
INTERLOCKING SYSTEM
Switching
device
Operating
state
ON
locked
locked
unlocked
locked if earth
switch OFF
ON
locked
unlocked
OFF
Earth switch
OFF
Switch
disconnector
Earth switch
unlocked
locked
removed
locked
locked
inserted
unlocked if
earth switch OFF
unlocked if switch
disconnector
OFF
Mechanical interlocks
Interrogator lock
optional:
Switch disconnector cable compartment cover interlock,
e.g. for cable testing (refer to operating instructions!).
Operating state
ON
OFF
Earth switch
Cable compartment
or fuse cover
locked
unlocked
unlocked
locked if
disconnector ON
Circuit-breaker
Disconnector
locked
unlocked if
disconnector OFF
locked
Cable compartment
cover
22
unlocked
locked
locked
unlocked
unlocked
ON
unlocked
locked
unlocked
OFF
Earth switch
ON
OFF
unlocked
unlocked
locked
removed
unlocked
locked
locked
inserted
unlocked
locked
unlocked
48
VAC
230
Starting current
4.7
4.1
2.5
6.9
6.8
3.7
Normal current
[A]
1.2
1.1
0.6
2.3
2.2
1.2
5.5
2.8
2.2
Motor operating time in case of SFU drive for ON (making) and OFF (breaking) < 3 sec
VAC
24
Coil current
[A]
48
6.3
3.2
2.6
1.3
1.2
0.7
230
0.9
0.5
Note:
The values specified for the current consumption are mean values which can be used for calculating the supply rating. The actual values may be higher or lower.
Auxiliary switch
All switching devices of the FBX
switchgear can be equipped additonally with multi-pole auxiliary switches. 2- or 4-pole auxiliary switches
are available on the switch discon-
Auxiliary switch
VDC
VAC
24
Switching capacity
[A]
48
60
110
120
120
230
10
10
[ms]
[A]
20
10
23
IN-LINE ARRANGEMENT
FBX-E
FBX-E offers highly flexible in-line
configurations of switchgear for
secondary distribution applications.
Functional units comprising up to four
switching units can be lined up in any
order. In-line connection is possible
on both sides.
Local assembly and in-line connection of FBX-E does not require gas
handling.
In-line connection is a very straightforward process due to
- the F-link busbar couplers on the
medium-voltage end.
Variations between adjacent
panels are compensated by spherical fixed contacts and movable
couplers allowing adjustment in all
axial directions;
- very safe dielectric seals with
potential-controlled silicone
deflectors externally earthed and
adjustable to fit.
These are a press-fit on to the inline assembly, using a specified
force. Potential-controlled blanking
plugs, with a design based on the
the F-link silicon deflectors, are
located at the switchgear ends.
These blanking plugs are held in
position, at the press-fitting force,
by a common metal cover:
- integrated guide pins for alignment
of adjacent panels in a defined
position;
- panel screw couplings with clearly
fixed stoppers for the distances
between adjacent panels;
- a wall clearance of at least 180 mm
is required for replacement or
alignment of one or more
functional units.
24
VOLTAGE DETECTION
SYSTEM
Optionally, the IVIS integrated Voltage Detecting System with integrated indicator can be used to check
zero voltage. Logic flash arrow symbols on the indicators display if a
mains voltage within the defined
response thresholds is present. The
IVIS system does not require the
electrical repeat tests for voltage
detection systems.
GAS COMPARTMENT
TECHNOLOGY
The switching units are installed in
gas-filled tanks made of corrosion
proof chromium-nickel steel. SF6 is
used as the insulating and quenching medium. FBX is a sealed pressure system to IEC 60694.
During the service life of the switchgear, it is not necessary to replenish
the SF6 gas. The gas pressure is
indicated via a pressure gauge.
Pressure gauge
Horstmann indicator
L1 L2
L3
L1
L2
L3
L1
ALPHA E
L1 L2
L2
L3
L1
L2
L3
ALPHA E
L3
L1 L2
-25
C
0C
20
40 C
60 C
p
C
L1
L2
L3
L3
-25
C
0C
20
40 C
60 C
p
C
+
SF
6
+
SF
6
Short-circuit indicator
As an option, the outgoing cable
feeders, C, can be equipped with
short-circuit indicators, types Alpha
M or E, optional F or Gamma manufactured by Dipl.-Ing. H. Horstmann
GmbH. Other brands are available
on request.
T2
25
INTEGRATED PACKAGE
SOLUTIONS FOR AUTOMATION
In the secondary distribution sector,
automation of medium-voltage
switchgear is becoming more common.
L1
L2
L3
L1
L2
L3
L1
L2
L3
Cable
Cable
Trafo
26
conventional
remote signalling
AB 1
AB 2
AB = project stage
AB 3
CABLE CONNECTIONS
The amply designed cable connection area enables installation of different cable connection systems.
The cable connection compartment
has been designed to accept
> fully insulated
> metal-enclosed
or
> partially insulated connection
systems.
Installation of 2 x 3 cable screw-type
plugs or 3 x cable screw-type plugs
plus 3 surge arresters is possible for
outgoing feeder cables, type C, and
busbar risers types R and RE within
the normal cable connection compartment.
The switchgear has been equipped
as standard with outer cone-type
appliance coupler systems:
Outgoing feeder cable with switch
disconnector C, transformer outgoing feeder with vacuum circuitbreaker T2, busbar riser R and busbar risers with earth switch RE:
Appliance couplers 630A, connection type C, to EN 50181.
Transformer outgoing feeders with
switch fuse combination T1:
Appliance couplers 250A, connection type A, to EN 50181. The Tables
on pages 28/29 include a selection
of common connection systems.
Surge arresters
(1380 mm high switchgear only)
27
updated 04.02.2005
12 kV
24 kV
Rated
current
Connector
type
EUROMOLD
630
AGT 10/630
95 - 240
AGT 20/630
25 - 240
EUROMOLD
630
400LB/G
35 - 300
K400LB/G
25 - 300
EUROMOLD
630
430TB
35 - 300
430TB
35 - 300
EUROMOLD
630
400TB/G
35 - 300
K400TB/G
35 - 300
EUROMOLD
630
440TB/G
185 - 630
K440TB/G
185 - 630
Plasticinsulated
cable
Fully insulated technology
for crosssection
mm2
Connector
type
1)
for crosssection
mm2
Raychem
630
RSTI-L56xx
25 - 300
RSTI-L56xx
25 - 300 1)
nkt
630
CB 12/630
25 - 300 1) CB 24/630
25 - 300 1)
Sdkabel
630
SET 12
50 - 300
25 - 240
SET 24
SEHDT 13
Partially insu- nkt
lated technoRaychem
logy
630
400 - 500
SEHDT 23
300 - 500
AB 12/630
25 - 300
AB24/630
25 - 300
25 - 300
25 - 300
25 - 300
Earth cable
Partially insu- Raychem
lated technology
28
16 - 300
35 - 240
updated 04.02.2005
Manufacturer
12 kV
24 kV
Plasticinsulated
cable
Connector
Type
for crosssection
mm2
Connector
Type
for crosssection
mm2
158LR
16 - 120 1)
K158LR
16 - 120 1)
K158LR+MC3-158LR-R02
16 - 120 1)
1)
158LR+MC3-158LR-R02
16 - 120
EUROMOLD
AGW 10/250
25 - 95
AGW 20/250
25 - 95
EUROMOLD
AGWL 10/250
25 - 95
AGWL 20/250
25 - 95
nkt
EASW 20/250
25 - 95
EASW 20/250
25 - 95
Raychem
RSES-52xx-R
25 - 120
RSES-52xx-R
16 - 120
Sdkabel
SEW 12
25 - 150
SEW 24
25 - 95
Comply with the manufacturers technical details and instructions for assembly.
1) 150 mm2 on request
Plastic-insulated cables double connection for outgoing feeder cable with switch disconnector C, Busbar riser R and RE
Appliance couplers 630 A, outer cone-type to EN 50181, connection type C, screw-type contact with internal thread M16x2.
Examples
Cable type
updated 04.02.2005
Manufacturer
Plasticinsulated
cable
12 kV
Rated
current
Connector
Type
24 kV
for crosssection
mm2
Connector
Type
for crosssection
mm2
630
95 - 240
25 - 240
EUROMOLD
630
95 - 240
95 - 240
EUROMOLD
630
430 TB + 300 PB
35 - 300
430 TB + 300 PB
35 - 300
Raychem
630
RSTI-L 56xx +
RSTI-CC-L 56xx
25 - 300
RSTI-L 56xx +
RSTI-CC-L 56xx
25 - 300
nkt
630
CB 12/630 + CC 12/630
25 - 300
CB 12/630 + CC 12/630
25 - 300
Sdkabel
630
2x SET 12 + KV 23.2
50 - 300
2x SET 24 + KV 23.2
25 - 240
nkt
630
AB 12/630 + AC 12/630
25 - 300
AB 12/630 + AC 12/630
25 - 300
updated 04.02.2005
Manufacturer
Plasticinsulated
cable
12 kV
Rated
current
Connector
Type
24 kV
for crosssection
mm2
Connector
Type
for crosssection
mm2
EUROMOLD
630
430 TB + 300 PB
35 - 300
430 TB + 300 PB
35 - 300
Raychem
630
RSTI-L 56xx +
RSTI-CC-L 56xx
25 - 300
RSTI-L 56xx +
RSTI-CC-L 56xx
25 - 300
nkt
630
CB 12/630 + CC 12/630
25 - 300
CB 12/630 + CC 12/630
25 - 300
29
HIGH-VOLTAGE FUSE
LINKS
The fuse links are located in insulating tubes in normal atmosphere. The
fuse locating tubes are integrated in
the hermetically sealed, gas-filled,
clad compartment as required by the
system, which offers the following
benefits:
> The electrical field is contained
within the SF6 atmosphere.
> The grip end of the fuse is located
in the field intensity shadow.
> The area within the gas-filled, clad
compartment is completely protected.
> The grip end area is insensitive
in particular, the closed grip end is
not used to ensure electric tightness (insulating arrangement).
Option available: water-proof
design of the fuse locating tubes
and grip ends.
L1
L2
L3
L1
L2
L3
L1
L2
L3
Type
No.
Ur
Up
Ud
n
Pre
SF6
IAC
U1
kV Ir
kV Ik/sec
Er
MPa Pam
kg sealed
A fr
Hz
kA tk
s
Mr
MPa
pressurePme MPa
system
Medium
Alstom
Voltage
Sachsenwerk
Bussines
GmbH/Germany
Cable
Cable
Trafo
Fuse tripping
The stored-energy mechanism and
the tripping linkage ensure that all
three conductors of the switch fuse
combination are switched off when
tripped by the fuse striker. If the
striker of only one HV HRC fuse
link operates, all-pole breaking is
effected mechanically.
Replacement of fuses
The interrogation interlock ensures
maximum operator safety on fuse
replacement. The fuse cover can
only be opened if correct earthing
has been carried out. Conversely,
the earthing can only be reset after
the fuse cover has been closed and
locked.
Two make-proof earth switches
(upstream and downstream of the
fuse links) enable the fuses to be
replaced without the use of auxiliary
equipment. Both earth switches are
make-proof and are switched via a
common snap-action making mechanism.
30
SELECTION OF HV HRC
FUSE LINKS
1. HV HRC fuse links
This project document gives the
recommendations of the switchgear
manufacturer, as required by the
applicable Standards. The specified
data enables the user to choose
suitable HV HRC fuse links.
Technical data
Temperature-rise limits
The selection tables take into
account the temperature-rise limits
within the switchgear enclosure.
Ordering data
D (e)
38 max.
88 max.
33+2
88 max.
50 min.
20 max.
450,5
Striker
33+2
Dimensions in mm
31
32
AREVA
Supplier
SIBA
JEAN MLLER
Type designation
Fuse length
D or e
in mm
FBX./12./...
with adapter for mechanical extension to 442 mm
292
FBX./17./...
FBX./24./...
442
442
General-purpose fuses
General-purpose fuses are recommended for the exceptional case in
which the switch disconnector is to
be equipped with an SFU ON/OFF
snap-action drive (instead of an SF
stored energy mechanism), when allpole fuse tripping is not possible.
Rated voltage of
HV HRC
fuse link
Length D
(e) of
HV HRC
fuse link
Type of
switchgear
250
315
400
500
630
uk = 4 %
800
1000
uk = 6 %
kV
mm
7.2
292
50
FBX, 12 kV
31.5
40
50
with adapter 24 kV
10
12
292
with adapter 24 kV
15
17.5
442
FBX, 24 kV
25
31.5
31.5
40
50
20
24
442
FBX, 24 kV
16
25
25
31.5
40
0.4/0.5
NH-gTr
kVA
(A)
250
(361)
315
(455)
400
(577)
500
(722)
630
(909)
Rated short-circuit voltage uk and maximum admissible duration of short-circuit according to IEC 60076-5 and EN 60076-5.
This selection table must be used at ambient temperatures < +50 C, without overload.
(...) = Rated current in A
Rated voltage of
HV HRC
fuse link
Length D
(e) of
HV HRC
fuse link
Type of
switchgear
250
315
400
500
630
uk = 4 %
800
1000 1)
uk = 6 %
kV
mm
6/12
292
50
63
80
100
SSK
FBX, 12 kV
31.5
40
50
63
80
100
SSK
with adapter 24 kV
10
6/12
292
with adapter 24 kV
15
10/24
442
FBX, 24 kV
25
31.5
31.5
40
50
63
20
10/24
442
FBX, 24 kV
16
25
25
31.5
40
63
63
800
(1155)
1000
(1443)
1)
0.4/0.5
NH-gTr
kVA
(A)
250
(361)
315
(455)
400
(577)
500
(722)
630
(909)
1250 kVA for 20 kV at 80 A and higher ratings for 10-20 kV available on request (time delay required for mechanical tripping).
Rated short-circuit voltage and maximum permissible duration of short-circuit according to IEC 60076-5 and DIN EN 60076-5.
This selection table must be used at ambient temperatures < +50 C, without overload.
(...) = Rated current in A
33
>
>
Ecological considerations
Disposal valve
Plastics
Steel
Copper
Aluminium, Brass
Thermosetting
plastics
Thermoplastics
Elastomers
Electronics Plastics
Metals
Insulating Sulphur hexafluoride
Percent
by weight
80
6.5
2
7
2
0.5
0.5
1
0.5
>
>
Metering Panel
METERING PANEL
Instrument transformer
to DIN 42600
slim design
L3
h1
L3
FBX-M1
e2
e1
b1
40
120
Um in kV:
Dimension 12 kV
24 kV
b1
e1
e2
h1
178
150
280
280
148
125
270
220
h1
e1
b1
e2
Um in kV:
L3
L3
FBX-M2
Dimension 12 kV
24 kV
b1
e1
e2
h1
178
150
280
280
148
125
270
220
35
Instrument transformer
to DIN 42600
slim design
L1
h1
L1
e2
e1
b1
40
120
L1
L1
Um in kV:
Dimension 12 kV
24 kV
b1
e1
e2
h1
178
150
280
280
148
125
270
220
FBX-M3
Panel width 1000 mm
Height
1380 mm
Depth
720 mm
h1
e1
b1
e2
L3
Um in kV:
Dimension 12 kV
24 kV
b1
e1
e2
h1
L3
178
150
280
280
148
125
270
220
L3
Note:
- Installation of current and
voltage measuring devices with or without
change-over switch possible, if applicable with
voltage indicator for the
metering panels.
- Pre-assembled cable
connections can be
purchased as an option
from the switchgear
manufacturer.
L3
FBX-M4
Panel width 1000 mm
Height
1380 mm
Depth
720 mm
36
>
>
Design data
Pressure relief device, fastening and
flooring ducts
IAC Class AF
Side
Side attachment
ALPHA E
L1 L2 L3
Room height
2000 mm
Room height
2000 mm
100
52
40 +
62 -S
6 p6
0
C
F
00
C
C
C
C
P
N
I
140
Double base / duct
ALPHA E
L1 L2 L3
100
140
Double base / duct
ALPHA E
L1 L2 L3
100
Double base / duct
Pressure
relief
Pressure
relief
Rear panel
Gas cooler *
100
Gas cooler *
140
V 0.8 m3 at 20 kA
V 0.8 m3 at 16 kA
* (with 5 layers of expanded
metal, e.g. 6 x 3.4 x 1 x 0.5)
V 0.8 m3 at 20 kA
V 0.8 m3 at 16 kA
* Cross-section of duct
0.3 m2 at 16 kA
(with 5 layers of expanded
metal, e.g. 6 x 3.4 x 0.5)
Installation example (cable feeder)
FBX-C-C-T1
Distance to ceiling 100 mm
Distance to wall 30 mm
(Pressure relief into cable duct with gas cooler)
37
IAC Class AF
Room height
2400 mm
Room height
2000 mm
A L P H A E L1
L1L2L3
L3
ALPHA E
L1L2L3
0
52
0 6
2 -+
04 S
06 p
C
C F
C
C
C
0
2
52
0 6
6 +
04 -S
0 p
C
C F
C
C
C
P
N
P
N
L1
L2
L3
ALPHA E
L1L2L3
L1
L2
L3
L1
100
140
140
Dimensions
[mm]
1000
38
1320
1-module unit C, R, RE
360
720
680
490
Clearance to lateral
building wall for extensions at the end of the
switchgear
Clearance
between
rear of
switchgear and
building
wall
Only
downward
pressure
relief
Pressure
relief upwards to
the rear
Minimum width of
passage in front of
switchgear FBX -E
19
180
C
30
140
National standards/
regulations must be
complied with!
For subsequent extension of existing FBX-E:
assembly aisle E 950
30
1000
4-module unit
B
2-module unit
3-module unit
30
D
Functions and
clearances
10
B
19
10
A
L2
L3
0
2
52
0 6
6 +
04 -S
0 p
C
C F
C
C
C
P
N
100
L2
FASTENING AND
FLOORING DUCTS
Version shown:
C-C-T1
ALPHA M
L1
L2
L3
HORSTMANN
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
L3
Reset
Bj.
95
Test
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
AP
Pr
ALPHA M
L1
400A
600A
800A
1000A
I V I S
L2
HORSTMANN
L3
Version shown:
C-T1-C-T1
Reset
Bj.
95
ALPHA M
Test
L1
400A
600A
800A
1000A
I V I S
kA
kA
s
n max.
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
ma
th
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
L3
Reset
Bj.
95
Test
th
kA
AP
Pr
kA
s
n max.
ALPHA M
L1
400A
600A
800A
1000A
I V I S
I V I S
L2
HORSTMANN
I V I S
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
I V I S
bar
Made in Germany
1380
Made in Germany
95 95
320
95 95
643
95 95
180 320
1320
720
20
1000
Three-panel unit
980
(1300)
615
400
37.5
15
75
380.5
426
720
Fastening points
19.5
1000
(1320)
1000
(1320)
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
U
l
[kV] [kA]
FBX-C
12-16
C-C-T1
FBX-E
12-20
R-RE-T1
17-16
C-C-C
17-20
24-16
24-20
FBX-C
12-16
C-C-C-T1
FBX-E
12-20
C-T1-C-T1
17-16
C-C-C-C
17-20
24-16
24-20
39
Reset
ALPHA M
L2
L1
Bj.
95
L3
HORSTMANN
Test
Reset
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
Bj.
95
HORSTMANN
Test
400A
600A
800A
1000A
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
ma
th
kA
AP
kA
s
Pr
n max.
I V I S
bar
1380
Made in Germany
95 95
180 320
643
95 95
720
20
680
Two-panel unit
(660)
680
615
400
37.5
15
75
20
380.5
426
720
Fastening points
19.5
680
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
U
l
[kV] [kA]
FBX-C
12-16
FBX-E
12-20
C-T1
17-16
17-20
RE-T1
24-16
24-20
40
C-C
Version shown:
RE-T2
Reset
ALPHA M
L2
L1
Bj.
95
L3
HORSTMANN
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ma
th
kA
AP
kA
s
Pr
n max.
ALPHA M
L1
400A
600A
800A
1000A
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
Version shown:
C-C-T2
L2
L3
Reset
Bj.
95
HORSTMANN
Test
ALPHA M
L1
400A
600A
800A
1000A
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
kA
AP
kA
s
Pr
n max.
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
I V I S
I V I S
bar
Made in Germany
1380
Made in Germany
L2
HORSTMANN
I V I S
I V I S
95 95
180 320
100100
95 95
320
100100
593
95 95
180 320
720
680
20
1000
Two-panel unit
Three-panel unit
615
400
15
19.5
20
680
37.5
75
229.5
380.5
720
(660)
1000
(680)
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
U
l
[kV] [kA]
FBX-C
12-16
FBX-E
12-20
RE-T2
17-16
17-20
24-16
24-20
FBX-C
12-16
C-C-T2
FBX-E
12-20
C-RE-T2
17-16
R-RE-T2
17-20
24-16
24-20
41
Version shown:
C-T2-C-T2
Version shown:
C-C-C-T2
Reset
ALPHA M
L1
L2
L3
Bj.
95
HORSTMANN
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
HORSTMANN
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
ma
th
kA
AP
kA
s
Pr
n max.
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
bar U
kV
Uw
A
ma
th
kA
AP
kA
s
Pr
n max.
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
Reset
ALPHA M
L1
L2
L3
Bj.
95
HORSTMANN
I V I S
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
Reset
Bj.
95
HORSTMANN
I V I S
Test
400A
600A
800A
1000A
ALPHA M
L1
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
I V I S
L2
HORSTMANN
I V I S
L3
Reset
Bj.
95
Test
ALPHA M
400A
600A
800A
1000A
I V I S
L1
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
Reset
Bj.
95
HORSTMANN
I V I S
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
HORSTMANN
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
Made in Germany
kA
AP
kA
s
Pr
n max.
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
bar U
kV
Uw
A
AP
kA
s
ma
th
Made in Germany
kA
Pr
n max.
L2
HORSTMANN
I V I S
I V I S
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
Reset
ALPHA M
L1
L2
L3
Bj.
95
HORSTMANN
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
L3
Reset
Bj.
95
HORSTMANN
I V I S
I V I S
Test
400A
600A
800A
1000A
ALPHA M
L1
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
I V I S
L2
HORSTMANN
I V I S
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
ALPHA M
L1
I V I S
L2
HORSTMANN
L3
Reset
Bj.
95
Test
400A
600A
800A
1000A
I V I S
I V I S
bar
Made in Germany
1380
Made in Germany
L2
HORSTMANN
I V I S
95 95
320
95 95
320
95 95
100100
180
320
1320
95 95
95 95
320
320
1320
100100
229,5
320
593
95 95
180
720
20
19
1320
20
37.5
15
75
229.5
380.5
720
615
400
Fastening points
19.5
1320
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
U
l
[kV] [kA]
FBX-C
12-16
C-C-C-T2
FBX-E
12-20
C-T2-C-T2
17-16
17-20
24-16
24-20
42
L2
L3
HORSTMANN
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
L2
HORSTMANN
L3
Reset
Bj.
95
Test
ALPHA M
L1
400A
600A
800A
1000A
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
ma
th
kA
AP
kA
s
Pr
n max.
L2
L3
Reset
Test
Reset
ALPHA M
Bj.
95
HORSTMANN
I V I S
L2
L1
400A
600A
800A
1000A
L3
Bj.
95
HORSTMANN
I V I S
Test
400A
600A
800A
1000A
I V I S
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
kA
AP
kA
s
Pr
n max.
bar
Made in Germany
1380
Made in Germany
95 95
95 95
643
95 95
180 320
360 1er-Modul
490 T1-Modul
490 T2-Modul
680 2er-Modul
1000 3er-Modul
1320 4er-Modul
980
(30)
(360)
(660)
(1300)
720
20
19
Fastening points
340
10
615
37.5
37.5
15
15
75
400
720
(470)
19
10
1000
360
19
19.5
1000
19.5
360
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
FBX-E
FBX-E
FBX-E
FBX-E
U
l
[kV] [kA]
12-16
12-20
17-16
17-20
24-16
24-20
12-16
12-20
17-16
17-20
24-16
24-20
12-16
12-20
17-16
17-20
24-16
24-20
12-16
12-20
17-16
17-20
24-16
24-20
C
T1
T2
C-T1
RE-T1
C-C
C-C-T1
C-RE-T1
R-RE-T1
C-C-C
C-C-C-T1
C-T1-C-T1
C-C-C-C
43
Reset
ALPHA M
L1
L2
Bj.
95
L3
Test
Reset
ALPHA M
L1
400A
600A
800A
1000A
HORSTMANN
L2
Bj.
95
L3
Test
L1
ma
th
kA
AP
kA
s
Pr
n max.
L2
Bj.
95
L3
Test
400A
600A
800A
1000A
HORSTMANN
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
Reset
ALPHA M
400A
600A
800A
1000A
HORSTMANN
Version shown: T1
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
kA
AP
kA
s
Pr
n max.
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
Made in Germany
kA
AP
kA
s
Pr
n max.
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
bar
ma
th
kA
AP
kA
s
Pr
n max.
bar
Made in Germany
Made in Germany
1380
Made in Germany
I V I S
85 95 95
85 95 95
215
95 95
643
85 95 95
19
360
C-module
19
19
RE-module
360
19
R-module
340
490
19
720
T1-module
470
360
615
720
37.5
15
75
426
380.5
720
Fastening points
400
360
19
490
19
19.5
360
490
Type
Designation
FBX-E
U
l
[kV] [kA]
12-16
12-20
C, R, RE
17-16
17-20
24-16
24-20
44
T1
20
310
Version shown: T2
40
I V I S
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
ma
th
kA
AP
kA
s
Pr
n max.
bar
Made in Germany
210 100100
Sachsenwerk
Type
No.
VDE 0670 T.6 / IEC 298
kV
U
kV
Uw
ma
th
kA
AP
kA
s
Pr
n max.
1900
1380
I V I S
bar
Made in Germany
593
1380
229.5
100100
19
490
20
593
720
T2-module
470
Fastening points
490
720
20
615
400
37.5
15
75
380.5
720
T2-module
optional with low-voltage cabinet
490
19.5
19
490
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
Type
Designation
FBX-E
U
l
[kV] [kA]
12-16
12-20
T2
17-16
17-20
24-16
24-20
45
I V I S
Type
No.
Ur
Pr
n max.
Up
U
n
Pre
SF6
IAC
Ua
bar
kV lr
kV lk/sc
kV
A f
kA t
r
k
MPa Pam
MPa Pme
kg sealed pressure system
Hz
s
MPa
10
1000
115
720
60
580
648
254
1380
1287,5
20
254
400
615
Fastening points
75
15
19.5
25
1000
10
Extensible design FBX-E: Additional space required on either side > 180 mm (clearance to the
adjacent building wall) for extension/s on the switchgear side/s.
46
ACCESSORIES
Auxiliary products and accessories
are available from AREVA Sachsenwerk GmbH. The use of other auxiliary products and accessories is not
permitted.
Standard accessories supplied with
the switchgear are control levers
and, in the case of motor-operated
drives, emergency handles and
double-bit keys.
Double-bit key
47
>
>
Shipping
Packing and transport
Packing
> If packed for truck transport,
switchgear units are delivered on
pallets with PE protective film.
Plastic straps are used to secure
the switchgear units to the pallets.
> For sea transport, the units are
packed in sealed aluminium film
with desiccant, in a closed case
with a close-boarded wooden
base.
> For air transport, the switchgear
units are wrapped in blister film
for dust protection and packed in
either wooden crates or wooden
cases, all with close-boarded
wooden bases.
Leave the equipment in its original
packaging during storage. If units or
parts are unpacked for checking,
they must be repacked for continued
storage, using the original packaging. Avoid condensation.
48
Transport
When transporting the switchgear,
it must be ensured that the units do
not slip or tilt (if necessary, nail down
transport pallets to the loading surface).
center of
gravity
>45
Notes:
49
Notes:
50
AREVA Sachsenwerk GmbH Rathenaustrae 2 D-93055 Regensburg Postfach 10 01 55 D-93001 Regensburg, Germany
Telephone +49 (0)9 41/46 20-0 Telefax +49 (0)9 41/46 20-4 18
SW.06.39/0505 EN
AREVA T&D
T&D Worldwide Contact Centre
contact.centre@areva-td.com
www.areva-td.com