You are on page 1of 3

Thermal Energy calculation for Natural gas 80/60C

DETERMINATION OF PRIMARY ENERGY DEMANDS AND EFFICIENCY FOR THE


WINTER AIR CONDITIONING

NEEDED THERMAL ENERGY

Ideal demand for heating demand:
Qh= 270 MWh

Fabbisogno ideale neto per riscaldamento
Q'h = Qh QW,Irh
Q W,lrh losses are recovered from the production system hot water, the term is
determined by the equation

Actual demand for heating

Qhr = Q'h+QI,e+QI,rg Qaux,e,Irh
Q'h ideal demand neto;
Q l,e total losses of emission;
Q l,rg total losses of regulation;
Q aux,e,lrh heat energy recovered from the electricity subsystem of emission.

EFFICIENCY COEFFICIENT AND SUBSYSTEM LOSSES FOR HEATING

- Subsystem losses of emission
Efficiency coefficient of emission (e) in locals of height less than 4 m

'e=0.94 (UNI/TS 11300-2:2008)

Ql,e =Q'h x(1 e)/e [MWh]
Ql,e= 17,23 [MWh]

- Subsystem losses of regolation
Efficiency coefficient of regulation ( rg)
rg = 0.97 (P band structures only with regulator prop.1C and radiators, convectors,
fan coils) (UNI/TS 11300-2:2008)
Ql,rg = (Q'h + Ql,e)x(1 rg)/rg [MWh]
Ql,rg= 8,88 [MWh]

- Subsystem losses of distribution

Efficiency coefficient of distribution
d= 0.913 (Centralized systems with vertical uprights current distribution in the
interspace, without isolation, construction period: before 1976, insufficient period for
completion before 1961, 5 floors) (UNI/TS 11300-2:2008)
Ql,d = Qhr x (1 d)/d [MWh]
Qhr= 329.02[MWh]
Ql,d = 28,22 [MWh]

- Subsystem losses of energy generation
Efficiency coefficient energy generation of heated air
'gn= 0.99 Generators of heat (natural gas or gasoil, or premixed draft burner,
modulating (UNI/TS 11300-2:2008)
Correction factors:
F1 = 0 relation between the power generator installed and the power of project
request.
modulating generator, F1 is determined by reference to the minimum power
regulated;
F2 = 0 installaed outside;
F3 = 0 chimney height greather than 10 m;
F4 = -1 average temperature of boiler over 65 C under the project;
F5 = 0 single stage generator;
F6 = -1 chimney height greater than 10 m in absence of closing the combustion air
arrest (not applicable to pre-mixed);
F7 = -1 boiler return temperature in the coldest month.
K=SFi -=-3

gn= 0,96

Ql,gn = (Qhr + Ql,d) x (1 gn)/gn [MWh]
QI,gn= 13,51 [MWh]

LEAVING ENERGY DEMAND OF GENERATOR
Qgn, in = Q d,in + QI,g



Qgn, in=337,85 [MWh]