DETERMINATION OF PRIMARY ENERGY DEMANDS AND EFFICIENCY FOR THE
WINTER AIR CONDITIONING
NEEDED THERMAL ENERGY
Ideal demand for heating demand: Qh= 270 MWh
Fabbisogno ideale neto per riscaldamento Q'h = Qh QW,Irh Q W,lrh losses are recovered from the production system hot water, the term is determined by the equation
Actual demand for heating
Qhr = Q'h+QI,e+QI,rg Qaux,e,Irh Q'h ideal demand neto; Q l,e total losses of emission; Q l,rg total losses of regulation; Q aux,e,lrh heat energy recovered from the electricity subsystem of emission.
EFFICIENCY COEFFICIENT AND SUBSYSTEM LOSSES FOR HEATING
- Subsystem losses of emission Efficiency coefficient of emission (e) in locals of height less than 4 m
'e=0.94 (UNI/TS 11300-2:2008)
Ql,e =Q'h x(1 e)/e [MWh] Ql,e= 17,23 [MWh]
- Subsystem losses of regolation Efficiency coefficient of regulation ( rg) rg = 0.97 (P band structures only with regulator prop.1C and radiators, convectors, fan coils) (UNI/TS 11300-2:2008) Ql,rg = (Q'h + Ql,e)x(1 rg)/rg [MWh] Ql,rg= 8,88 [MWh]
- Subsystem losses of distribution
Efficiency coefficient of distribution d= 0.913 (Centralized systems with vertical uprights current distribution in the interspace, without isolation, construction period: before 1976, insufficient period for completion before 1961, 5 floors) (UNI/TS 11300-2:2008) Ql,d = Qhr x (1 d)/d [MWh] Qhr= 329.02[MWh] Ql,d = 28,22 [MWh]
- Subsystem losses of energy generation Efficiency coefficient energy generation of heated air 'gn= 0.99 Generators of heat (natural gas or gasoil, or premixed draft burner, modulating (UNI/TS 11300-2:2008) Correction factors: F1 = 0 relation between the power generator installed and the power of project request. modulating generator, F1 is determined by reference to the minimum power regulated; F2 = 0 installaed outside; F3 = 0 chimney height greather than 10 m; F4 = -1 average temperature of boiler over 65 C under the project; F5 = 0 single stage generator; F6 = -1 chimney height greater than 10 m in absence of closing the combustion air arrest (not applicable to pre-mixed); F7 = -1 boiler return temperature in the coldest month. K=SFi -=-3