Thermostatic and Automatic


Expansion Valves
Catalog E-1, October 2007

Page 2 / Catalog E-1, Thermostatic & Automatic Expansion Valves

Table of Contents
Thermostatic Expansion Valves (TEVs) and
Constant Pressure (Automatic) Expansion Valves (AEVs)
Visual Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Thermostatic Expansion Valves
Model Number Selection Guide - N, C(E), SC(E), EC(E) Valves . . . . . . . . . . . . . . . . . . . . . . . . . 4
N Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
C(E) Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SC(E) Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
EC(E) Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
H Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
HC Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model Number Selection Guide - EBS, OE Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
EBS Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OE Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Constant Pressure (Automatic) Expansion Valves
A Series Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 3

Visual Table of Contents


C(E) Series TEV

page 6
Applications:
Rail and Transport
Refrigeration,
Supermarket Cases,
Walk-in Coolers

SC(E) Series TEV

page 5
Applications:
Low Profile Coolers,
Ice Machines,
Beverage Dispensers

EC(E) Series TEV

H Series TEV

HC Series TEV

N Series TEV

page 8
Applications:
Supermarket Cases,
Transport Refrigeration,
Walk-in Coolers

EBS Series TEV


page 12
Applications:
Air Conditioning,
Industrial Chillers

page 9
Applications:
Air Conditioning,
Heat Pumps, Bi-flow
(Package Systems)

page 7
Applications:
Supermarket Cases,
Walk-in Freezers,
Ice Machines

page 9
Applications:
Air Conditioning,
Heat Pumps

OE Series TEV

page 13
Applications:
Air Conditioning,
Industrial Chillers

AT Series AEV

A7 Series AEV

AS Series AEV

A1 Series AEV

A2 Series AEV

A3 Series AEV

page 18
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
PTAC/PTHP, High Cycle

page 18
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
Vending, Ice Machines

page 18
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
PTAC/PTHP, High Cycle

page 19
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
Vending, Ice Machines

A4 Series AEV

page 19
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
Vending, Ice Machines

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

page 18
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
Vending, Ice Machines

page 19
Applications:
Ice Cream/Slush
Machines,
Hot Gas Bypass,
Freeze Protection,
Refrigerant Reclaim,
Vending, Ice Machines

Page 4 / Catalog E-1, Thermostatic & Automatic Expansion Valves

TEV Model Number Selection Guide


Nomenclature (Example) N, C(E), SC(E), EC(E) Valves

SC

100

20

Valve
Model

External
Equalizer
(Optional)

Nominal
Capacity
in Tons

Refrigerant

Valve
Charge

Maximum
Operating
Pressure
(MOP)

Bleed
(Optional)

Bleed
Capacity

(E) for Externally Equalized


Evaporator pressure drop > 3 psi
BLANK for Internally Equalized
Evaporator pressure drop < 3 psi
or smaller tonnage evaporators
See Catalog E-1a, TEV and AEV
Theory & Application.

Bleed
Denoted by B.
Not available on all TEVs.
See bleed capacity.
Used for equalizing system
during off cycle (compressor
unloading). Consult Parker.
See Catalog E-1a, TEV and
AEV Theory & Application.

Capacity
Parkers expansion valves
offer a range of capacities
from 1/8 ton to 70 tons depending on refrigerant. See
pages 15-18 for capacity
tables.

Bleed Capacity
Percentage based on nominal
capacity of valve specified by
manufacturer or Parker.

Rainbow Charge
Refrigerant Designation
Z
J
V
S

R-410A
R-134a, R-401A (MP39),
R-401B (MP66)
R-407C (AC9000), R-22
R-125, R-404A (HP62),
R-402A (HP80), R-402B
(HP81), R-507 (AZ50)

Refrigerant
Color Code
R-12 - yellow
R-22 - green
R-134a - light blue
R-404A - orange
R-407C - light brown
R-410A - rose
R-502 - purple
HP80 - canary
HP81 - olive

Charge Operating Temperature Range


VX100, JX60, SX110, ZX200
Air Conditioning
VX35, SX35
Low Temp. Ref.
VZ, SZ
Low Temp. Ref.
VW, JW, SW
All purpose liquid
-40

-30 -20 -10 0 10 20 30 40


Evaporator Temperature F

50

60

Charge Type
"W (all-purpose) liquid charge maintains nearly flat superheat control over a -40F to +60F (-40C to +15C) evaporator temperature range.
Z (low temperature) charge provides fast pulldown benefits like a gas charge with the non-migrating benefits of a liquid charge; usable over a -40F to 0F
(-40C to -20C) evaporator temperature range.
X (damped response) gas charge provides a pressure limiting (MOP) charge with anti-hunt characteristics over a -40F to +60F (-40C to +15C) evaporator
temperature range.
Notes: M.O.P. not available on W or Z charge.
1. Maximum operational pressure 500 psig (35 bar) high side and 275 psig (19 bar) low side.
2. Maximum storage temperature 130F (55C).
3. Consult Parker for pressure and temperature exceptions.
4. Do not use W or Z liquid charges in applications where bulb temperatures can exceed 130F (55C).
For these applications use type X MOP gas charge only.

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 5

N Series
This small flare brass valve series is ideally suited where space is at a
premium. Its stainless steel power element and compact body has always made it
the first choice for installation in commercial refrigeration systems. External equalized models are provided with a 30" capillary and 1/4" SAE flare nut, eliminating
the need to run a separate equalizer line. Medium, low & MOP X charges are
available as noted below.

Applications

Features and Benefits

Low Profile Coolers

Compact body

Beverage Dispensers

Inlet strainer

Beverage Boxes

Factory set superheat

Small Chillers

Accurate and stable control

Ice Machines

Right angle configuration

Small Freezers

30" capillary tube


Weight: 5.0 oz. / .14 kg

Specifications
Refrigerant

Refrigerant
Designation

R-12
R-134a
R-401A
R-401B

R-402A
R-402B
R-404A
R-502
R-507

R-22
R-407C

Nominal
Capacity
(Tons)

Internally
Equalized

Externally
Equalized

1/4
1/2
2
1/2

N-1/4-J
N-1/2-J
N-2-J
N-1/2-S

1/4
2

N-1/4-S
N-2-S

1/4
1/2
1
3

N-1/4-V
N-1/2-V
N-1-V
N-3-V

Rainbow
Charges

W, X60

NE-2-J

Inlet
Connection
(Inches)
1/4 SAE

Outlet
Connection
(Inches)

1/2 SAE

3/8 SAE
1/4 or 3/8 SAE

Dimensions Inches

W, Z, X110
NE-2-S

1/4 SAE

1/2 SAE

3/8 SAE
1/4 SAE

W, Z, X100

NE-3-V

3/8 SAE

0.093 OD Capillary Tube


2.50
0.50

1.50

Inlet
2.40
1.38
Outlet
1.27

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

1/4 or 3/8 SAE

1/2 SAE

Page 6 / Catalog E-1, Thermostatic & Automatic Expansion Valves

C(E) Series
The C(E) series incorporates an angle style brass body with SAE flare fittings using balanced port construction, allowing operation over varying load conditions.
Designed for use on small refrigeration and or air conditioning systems, the external
equalized models are provided with a 1/4" SAE male connection.

Applications

Features and Benefits

Small Refrigeration Systems

Balanced port design

Slush Machines

Removable power element

Air Conditioning Units

Inlet strainer 100 mesh

Freezers

60" capillary tube

Walk-in Coolers

Field adjustable superheat

Refrigerated Cases

1/4" SAE external equalizer

Rail & Transport Refrigeration

Weight: 1.0 lbs / 0.45 kg

Specifications Element Size No. 46


Refrigerant

Refrigerant
Designation

R-12
R-134a
R-401A
R-401B

R-402A
R-402B
R-404A
R-502
R-507

R-22
R-407C

Orifice
Designation

Nominal
Capacity
(Tons)

Internally
Equalized

Externally
Equalized

AA
A
B
C
D
AA
A
B
C
D
AA
A
B
C
D

1/8 to 1/2
1/2 to 1
1 to 2
1-1/2 to 3
3-1/2 to 5
1/8 to1/2
1/2 to 1
1-1/2 to 2-1/2
3 to 4
5 to 6
1/8 to1/2
1/2 to 1-1/2
2 to 3
3-1/2 to 5
5 to 6

C-AA-J
C-A-J
C-B-J
C-C-J
N/A
C-AA-S
C-A-S
C-B-S
C-C-S
N/A
C-AA-V
C-A-V
C-B-V
C-C-V
N/A

CE-AA-J
CE-A-J
CE-B-J
CE-C-J
CE-D-J
CE-AA-S
CE-A-S
CE-B-S
CE-C-S
CE-D-S
CE-AA-V
CE-A-V
CE-B-V
CE-C-V
CE-D-V

Rainbow
Charges

Inlet
Connection
(Inches)

Outlet
Connection
(Inches)

Equalizer
Connection
(Inches)

W, X60

1/4 SAE (3/8 optional)

1/2 SAE

1/4 SAE

W, Z,
X35

1/4 SAE (3/8 optional)

1/2 SAE

1/4 SAE

W, Z, X100
X35

1/4 SAE (3/8 optional)

1/2 SAE

1/2 SAE

Dimensions Inches

Fitting Size
1/4 SAE
3/8 SAE
1/2 SAE

60.0

A
1.13
1.35

C
1.93

3.375

2.43

2.02
.97
A

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

2.43

1.80

C
1.54

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 7

SC(E) Series
The SC(E) series refrigeration right angle brass body expansion valve incorporates
a removable inlet strainer that may be replaced or cleaned without removing the
valve from the system, and is an ideal choice for commerical refrigeration and supermarket applications.

Applications

Features and Benefits

Supermarket Cases

Removable power element

Self-contained Cases

60" capillary tube

Walk-in Coolers/Freezers

Removable inlet strainer 100 mesh

Ice Machines

Field adjustable superheat

Salad Bars

1/4" ODF external equalizer

Transport Refrigeration

W, Z or MOP X charges available


Weight: 1.0 lbs / 0.45 kg

Specifications Element Size No. 46


Refrigerant

Refrigerant
Orifice
Designation Designation

R-12
R-134a
R-401A
R-401B

R-402B
R-404A
R-402A
R-502
R-507

R-22
R-407C

AA
A
B
C
D
AA
A
B
C
D
AA
A
B
C
D

Nominal
Capacity
(Tons)

Internally
Equalized

Externally
Equalized

1/8 to 1/2
1/2 to 1
1 to 2
1-1/2 to 3
3-1/2 to 5
1/8 to 1/2
1/2 to 1
1-1/2 to 2-1/2
3 to 4
5 to 6
1/8 to 1/2
1/2 to 1-1/2
2 to 3
3-1/2 to 5
5 to 6

SC-AA-J
SC-A-J
SC-B-J
SC-C-J
N/A
SC-AA-S
SC-A-S
SC-B-S
SC-C-S
N/A
SC-AA-V
SC-A-V
SC-B-V
SC-C-V
N/A

SCE-AA-J
SCE-A-J
SCE-B-J
SCE-C-J
SCE-D-J
SCE-AA-S
SCE-A-S
SCE-B-S
SCE-C-S
SCE-D-S
SCE-AA-V
SCE-A-V
SCE-B-V
SCE-C-V
SCE-D-V

Rainbow
Charges

Inlet
Connection
(Inches)

Outlet
Connection
(Inches)

Equalizer
Connection
(Inches)

W, X60

3/8 ODF

1/2 ODF

1/4 ODF

W, Z, X35

3/8 ODF

1/2 ODF

1/4 ODF

W, Z, X35,
X100

3/8 ODF

1/2 ODF

1/4 ODF

Dimensions Inches
1.71

1.93

3.375
.44

.31
.71

.505 1.83
.503

.31

.256
.254
1.48

.380
.378

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 8 / Catalog E-1, Thermostatic & Automatic Expansion Valves

EC(E) Series
The EC(E) series features extended ODF solder connections, brass body and
balanced port design. It is suited for both refrigeration and air conditioning
applications.

Applications

Features and Benefits

Small Chillers

Extended ODF connections

Heat Pump Units

Balanced port design

Air Conditioning Units

60" capillary tube

Freezers

Removable power element

Walk-in Boxes

Field adjustable superheat

Refrigerated Cases

1/4" ODF external equalizer

Mobile Refrigeration

Weight: 1.0 lbs / 0.45 kg

Specifications Element Size No. 46


Refrigerant
Designation

Refrigerant

R-12
R-134a
R-401A
R-401B

R-402A
R-402B
R-404A
R-502
R-507

R-22
R-407C

Orifice
Designation

Nominal
Capacity
(Tons)

Internally
Equalized

Externally
Equalized

AA
A
B
C
D
AA
A
B
C
D
AA
A
B
C
D

1/8 to 1/2
1/2 to 1
1 to 2
1-1/2 to 3
3-1/2 to 5
1/8 to 1/2
1/2 to 1
1-1/2 to 2-1/2
3 to 4
5 to 6
1/8 to 1/2
1/2 to 1-1/2
2 to 3
3-1/2 to 5
5 to 6

EC-AA-J
EC-A-J
EC-B-J
EC-C-J
N/A
EC-AA-S
EC-A-S
EC-B-S
EC-C-S
N/A
EC-AA-V
EC-A-V
EC-B-V
EC-C-V
N/A

ECE-AA-J
ECE-A-J
ECE-B-J
ECE-C-J
ECE-D-J
ECE-AA-S
ECE-A-S
ECE-B-S
ECE-C-S
ECE-D-S
ECE-AA-V
ECE-A-V
ECE-B-V
ECE-C-V
ECE-D-V

Rainbow
Charges

Inlet
Connection
(Inches)

Outlet
Connection
Inches
(Optional)

Equalizer
Connection
(Inches)

W, X60

3/8 ODF
(1/2)

1/2 ODF
(5/8 ODF)
(7/8 ODF)

1/4 ODF

W, Z, X35

3/8 ODF
(1/2)

1/2 ODF
(5/8 ODF)
(7/8)

1/4 ODF

W, Z, X100
X35

3/8 ODF
(1/2)

1/2 ODF
(5/8 ODF)
(7/8)

1/4 ODF

Note: Optional connections not available on all models.

Dimensions Inches

1.71

Fitting
3/8
1/2
5/8
7/8

1.93

1.93

3.375
2.21

2.43

1.83

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Dimensions (Inches)
Inlet
2.50
2.43
2.43

Outlet

2.50
2.50
2.49

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 9

H Series and HC Series


The H series balanced port valve is designed specifically for air conditioning and
heat pumps used in both air or water source systems. It offers features such as bleed
ports and a variety of connection styles for the inlet, outlet and external equalizer.
The HC series adds a built-in 5 ton check valve for R-22, R-407C and R-410A heat
pump applications with either factory set or field adjustable superheat.

Applications

Features and Benefits

Air Conditioning Systems

Stainless steel power element

Heat Pump Systems

Bleed ports available

Bi-flow (package) Heat Pump Systems

Bi-directional metering available


Weight: 10.7 oz. (.30 kg)
Factory set or field adjustable
Low pressure drop internal check valve

Specifications
Refrigerant

R-22
R-407C

R-410A

Refrigerant
Designation

Nominal
Capacity
(Tons)

Internally
Equalized

1-1/2
3
5

HA 1-1/2V
HA 3V
HA 5V

V
1-1/2
3
5
1-1/2
3
5
Z

1-1/2
2
3
5

Externally
Equalized

Rainbow
ChargesTM

Bleed Port
for Off Cycle
Operation
(Optional)

Inlet
Connections
(Inches)

HAE 1-1/2V
1/4, 3/8, 1/2
HAE 3V
X100
B
& 5/8 ODF
flo-rater
HAE 5V
models with internal check valves - C designation
HCA 1-1/2V
HCAE 1-1/2V
1/4, 3/8, 1/2
HCA 3V
HCAE 3V
X100
B
& 5/8 ODF
flo-rater
HCA 5V
HCAE 5V
HA 1-1/2Z
HAE 1-1/2Z
1/4, 3/8, 1/2
HA 3Z
HAE 3Z
X200
B
& 5/8 ODF
flo-rater
HA 5Z
HAE 5Z
specific models with internal check valves - C designation
HCA 1-1/2Z
HCAE 1-1/2Z
1/4, 3/8, 1/2
HCA 2Z
HCAE 2Z
X200
B
& 5/8 ODF
HCA 3Z
HCAE 3Z
flo-rater
HCA 5Z
HCAE 5Z

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Outlet
Connections
(Inches)
3/8, 1/2, 5/8
& 7/8 ODF
flo-rater
3/8, 1/2, 5/8
& 7/8 ODF
flo-rater
3/8, 1/2, 5/8
& 7/8 ODF
flo-rater
3/8, 1/2, 5/8
& 7/8 ODF
flo-rater

Page 10 / Catalog E-1, Thermostatic & Automatic Expansion Valves

H Series and HC Series


Dimensions Inches
Connections ODF

0.093 OD Capillary Tube


1.50

Outlet

2.47

Inlet
1.54

1.16

3.00

Optional Inlet Screen Available


Inlet/Outlet
0.250
0.375
0.500
0.625
0.875

0.75 OD

Dimensions Inches
Connections flo-rater
Inlet 3/4 20
Outlet 3/4 20

A
1.46
1.69
1.46
1.57

0.093 OD Capillary Tube


1.50

Check valve section


Allows reverse flow in
heating mode.

Inlet

1.60
Outlet

1.60

3.00

B
1.46
1.69
1.46
1.57
2.07

0.75 OD

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

1.25

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 11

TEV Model Number Selection Guide


Nomenclature (Example) EBS, OE Valves

EBS

Valve
Model

Refrigerant

External
Equalizer
(Optional)

15
Nominal
Capacity
in Tons

CP

100

Valve
Charge

Maximum
Operating
Pressure
(MOP)

(E) for Externally Equalized


Evaporator pressure drop > 3 psi
BLANK for Internally Equalized
Evaporator pressure drop < 3 psi
or smaller tonnage evaporators
See Catalog E-1a, TEV and AEV
Theory & Application.

Capacity
Parkers expansion valves
offer a range of capacities
from 1/8 ton to 70 tons, depending on refrigerant. See
pages 15-18 for capacity
tables.

Rainbow Charge
Refrigerant Designation
V
Z

R-407C (AC9000), R-22


R-410A (OE only)

Charge Operating Temperature Range


VCP 100, VGA, ZCP200
Air Conditioning

-10

0 10 20 30 40 50
Evaporator Temperature F

60

Charge Type
"W (all-purpose) liquid charge maintains nearly flat superheat control over a -40F to +60F (-40C to +15C) evaporator temperature range.
Z (low temperature) charge provides fast pulldown benefits like a gas charge with the non-migrating benefits of a liquid charge; usable over a -40F to 0F
(-40C to -20C) evaporator temperature range.
X (damped response) gas charge provides a pressure limiting (MOP) charge with anti-hunt characteristics over a -40F to +60F (-40C to +15C) evaporator
temperature range.
Notes: M.O.P. not available on W or Z charge.
*May not be used on systems in which bulb temperature will exceed 130F (i.e. defrost). Contact Parker for pressure and temperature.
1. Maximum operational pressure 500 psig (35 bar).
2. Maximum storage temperature 130F (55C) .
3. Consult Parker for pressure and temperature exceptions.
4. Do not use W or Z liquid charges in applications where bulb temperatures can exceed 130F (55C).
For these applications use type X MOP gas charge only.

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 12 / Catalog E-1, Thermostatic & Automatic Expansion Valves

EBS Series
The EBS series valve is a brass bar body valve for R-22 and R-407C. The Type EBS
features a balanced port construction and extended ODF connections. The thermostatic element is replaceable. The balanced port construction makes this valve
ideally suited for air conditioning applications which operate over widely varying
conditions.

Applications

Features and Benefits

Air Conditioning

Balanced port design


Removable power element
Field adjustable superheat
1/4 sweat external equalizer

Element Size Number 83


Refrigerant

Type

Refrigerant
Designation

R-22
R-407C

Externally
Equalized
EBSVE-8
EBSVE-11
EBSVE-15
EBSVE-20

Thermostatic
Charge

CP100

Nominal
Capacity
(Tons)

Inlet

Outlet

External Equalizer (pointing


down parallel to body)

8
11
15
20

5/8
5/8
7/8
7/8

7/8
7/8
1-1/8
1-3/8

1/4
1/4
1/4
1/4

Dimensions Inches

Fitting Size
5/8
7/8
1-1/8
1-3/8

2.31

1.81

Connections (Inches)
Extended ODF Solder

Standard
Tubing
Length
(Feet)

C
C
3.5

A
2.46
2.46

1/4 ODF
External
Equalizer
Connection
30

3.41

2.82
0.50

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

2.53
2.53
3.04

C
.50
.75
.81
.97

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 13

OE Series
The OE series valve utilizes balanced port construction to provide optimum operation on medium to large tonnage air conditioning systems. Two brass body styles
with copper ODF connections and a removable thermostatic power element provide
the stability and control required in a variety of applications, especially where there
are wide changes in load conditions. Body Style 1 has an R-22 nominal capacity up
to 30 tons, while Body Style 2 extends the capacity range to 70 tons.

Applications

Features and Benefits

Air Conditioning

Balanced port design

Process Chillers

Removable power element


Field adjustable superheat
1/4 sweat external equalizer
Wt: Body Style 1 to 1.7 lbs. / .77 kg Body
Style 2 to 2.5 lbs. / 1.13 kg

Specifications

60 capillary tube (120 optional)

Element Size Numbers 83, 85,


85-3 and 33, Knife Edge Joint
Type

Refrigerant
Designation

Refrigerant

R-22

External
Equalizer
OVE-15
OVE-20
OVE-30
OVE-40
OVE-55
OVE-70
OZE-20
OZE-25
OZE-35
OZE-50
OZE-60

R-410A

Nominal
Capacity
(Tons)

Thermostatic
Charges
Available

Element
Size No.

15
20
30
40
55
70
20
25
35
50
60

Connections (Inches)
ODF Solder

Standard
Tubing
Length
(Feet)

Inlet

Outlet

Shipping
Weight
(Lbs.)

1-1/8

7/8

83

Net Weight
(Lbs.)

1-3/8
CP100

5
1-1/8

33

1-3/8 or 1-5/8
1-1/8

7/8

85
GA

1-3/8

5
1-1/8

85-3

1-3/8 or 1-5/8

Dimensions Inches
Type OE with number 33 & 85-3 element

Type OE with number 83 & 85 element


2.31

2.75

1.70

1.93

2.43

2.90
C

3.5

C
4.14

1/4 ODF External


Equalizer Connection
0.50

5.52

1/4 ODF External


Equalizer Connection

1.40 1/4 ODF

1.59 1/4 ODF


A

Straight Thru
ODF Solder

7/8
1-1/8
1-3/8

2.09
2.21

2.23
2.39

0.75
0.91
0.97

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

B
Straight Thru
ODF Solder

7/8
1-1/8
1-3/8
1-5/8

2.09
2.69

2.84
3.12

0.78
0.91
0.97
1.09

Page 14 / Catalog E-1, Thermostatic & Automatic Expansion Valves

Capacity Tables
R-22 Capacities in Tons (R-407C Refrigerant & Liquid Temperature Correction Factor below)
Evaporator TemperatureF
20F
0F
Valve Type
Pressure Drop (PSI)
75 100 125 150 175 200 225 250 75 100 125 150 175 200 225 250 75 100 125 150 175
HC(E)

1-1/2
1.30 1.50 1.68 1.84 1.98 2.12 2.25 2.37 1.27 1.47 1.64 1.80 1.94 2.08 2.21 2.33 1.14 1.32 1.48 1.62 1.75
HC(E)

3
2.60 3.00 3.35 3.67 3.97 4.24 4.37 4.48 2.55 2.94 3.29 3.60 3.89 4.16 4.28 4.40 2.29 2.64 2.95 3.23 3.49
HC(E)

5
4.33 5.00 5.59 6.12 6.61 7.07 7.17 7.27 4.24 4.90 5.48 6.00 6.48 6.93 7.03 7.13 3.81 4.40 4.92 5.39 5.82
C(E), SC(E), EC(E) AA
1/2
0.54 0.62 0.69 0.76 0.82 0.88 0.93 0.98 0.52 0.60 0.68 0.74 0.80 0.86 0.91 0.96 0.47 0.54 0.60 0.66 0.72
C(E), SC(E), EC(E)
A
1-1/2
1.52 1.75 1.96 2.14 2.32 2.48 2.36 2.77 1.48 1.71 1.91 2.09 2.26 2.41 2.56 2.70 1.32 1.52 1.70 1.87 2.02
C(E), SC(E), EC(E)
B
3
2.77 3.20 3.58 3.92 4.23 4.53 4.80 5.06 2.70 3.12 3.49 3.82 4.13 4.41 4.68 4.93 2.41 2.79 3.12 3.42 3.69
C(E), SC(E), EC(E)
C
5
4.33 5.00 5.59 6.13 6.62 7.07 7.50 7.91 4.22 4.87 5.45 5.97 6.45 6.89 7.31 7.71 3.77 4.36 4.87 5.34 5.76
C(E), SC(E), EC(E)
D
6
5.20 6.00 6.71 7.35 7.94 8.49 9.00 9.49 5.07 5.85 6.54 7.16 7.74 8.27 8.77 9.25 4.08 4.72 5.27 5.78 6.24
EBS

8
7.4 8.5 9.5 10.4 11.2 12.0 12.8 13.4 6.8 7.9 8.8 9.6 10.4 11.1 11.8 12.4 5.7 6.5 7.3 8.0 8.6
EBS

11
10.0 11.5 12.9 14.1 15.2 16.3 17.3 18.2 9.2 10.7 11.9 13.0 14.1 15.1 16.0 16.8 7.6 8.8 9.9 10.8 11.7
EBS

15
13.4 15.5 17.3 18.9 20.5 21.9 23.2 24.4 12.6 14.6 16.3 17.8 19.3 20.6 21.9 23.0 9.4 10.9 12.2 13.3 14.4
EBS

20
19.3 22.3 25.0 27.4 29.5 31.6 33.5 35.3 17.7 20.4 22.8 25.0 27.0 28.9 30.6 32.3 13.1 15.1 16.9 18.5 20.0
OVE

15
13.0 15.0 16.8 18.4 19.8 21.2 22.5 23.7 12.0 13.9 15.5 17.0 18.4 19.6 20.8 22.0 10.1 11.7 13.0 14.3 15.4
OVE

20
19.2 22.2 24.8 27.2 29.4 31.4 33.3 35.1 17.8 20.6 23.0 25.2 27.2 29.1 30.8 32.5 14.9 17.2 19.3 21.1 22.8
OVE

30
26.4 30.5 34.1 37.4 40.4 43.1 45.8 48.2 24.5 28.2 31.6 34.6 37.4 39.9 42.4 44.7 20.5 23.7 26.5 29.0 31.3
OVE

40
34.9 40.3 45.1 49.4 53.3 57.0 60.5 63.7 33.7 38.9 43.5 47.6 51.5 55.0 58.3 61.5 24.8 28.6 32.0 35.1 37.9
OVE

55
47.6 55.0 61.5 67.4 72.8 77.8 82.5 87.0 46.0 53.1 59.3 65.0 70.2 75.1 79.6 83.9 33.8 39.1 43.7 47.9 51.7
OVE

70
63.2 73.0 81.6 89.4 96.6 103 110 115 61.0 70.5 78.8 86.3 93.2 99.6 106 111 44.9 51.9 58.0 63.5 68.6
These ratings are based on vapor free 100F liquid refrigerant entering the expansion valve, and a maximum of 7F change in superheat.
Nominal
Orifice Capacity
(Tons)

Refrigerant
R-22
R-407C

40F

Liquid Temperature Entering TEV


20F 40F 60F 80F 100F 120F 140F
Correction Factor
1.57 1.45 1.34 1.23 1.12 1.00 0.88 0.76
1.58 1.45 1.32 1.18 1.04 0.89 0.74 0.57
0F

200
1.87
3.73
6.22
0.76
2.16
3.94
6.16
6.67
9.2
12.5
15.4
21.4
16.5
24.4
33.5
40.5
55.3
73.3

225
1.98
3.84
6.31
0.81
2.29
4.18
6.54
7.08
9.8
13.2
16.3
22.7
17.5
25.9
35.5
42.9
58.6
77.8

250
2.09
3.94
6.40
0.85
2.41
4.41
6.89
7.46
10.3
14.0
17.2
23.9
18.4
27.3
37.5
45.6
61.8
82.0

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
0F to 40F since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-407C
at a 40F evaporator, 125 psi pressure drop across the TEV, and a 80F liquid temperature entering the
TEV = 3.58 (from rating chart) x 1.04 (CF liquid temperature) = 3.72 tons

R-22 Capacities in Kilowatts (R-407C Refrigerant & Liquid Temperature Correction Factor below)
Evaporator TemperatureC
-5C
-15C
Valve Type
Pressure Drop (BAR)
4
6
8 10 12 14 16 18 4
6
8 10 12 14 16 18 4
6
8 10 12
HC(E)

5
4.02 4.92 5.68 6.35 6.96 7.52 8.04 8.52 3.93 4.82 5.56 6.22 6.81 7.36 7.86 8.34 3.57 4.37 5.04 5.64 6.17
HC(E)

11
8.04 9.84 11.4 12.7 13.9 15.0 16.1 17.0 7.86 9.63 11.1 12.4 13.6 14.7 15.7 16.7 7.13 8.73 10.1 11.3 12.3
HC(E)

18
13.4 16.4 18.9 21.2 23.2 25.1 26.8 28.4 13.1 16.1 18.5 20.7 22.7 24.5 26.2 27.8 11.9 14.6 16.8 18.8 20.6
C(E), SC(E), EC(E) AA
1.8
1.63 1.99 2.30 2.57 2.82 3.04 3.25 3.45 1.59 1.95 2.25 2.51 2.75 2.97 3.18 3.37 1.45 1.78 2.06 2.30 2.52
C(E), SC(E), EC(E)
A
5.3
4.68 5.74 6.62 7.41 8.11 8.76 9.37 9.94 4.20 5.14 5.93 6.63 7.27 7.85 8.39 8.90 4.20 5.14 5.93 6.63 7.27
C(E), SC(E), EC(E)
B
10.5
8.57 10.5 12.1 13.5 14.8 16.0 17.1 18.2 7.67 9.40 10.8 12.1 13.3 14.4 15.3 16.3 7.67 9.40 10.8 12.1 13.3
C(E), SC(E), EC(E)
C
17.6
13.4 16.4 18.9 21.2 23.2 25.0 26.8 28.4 12.0 14.7 17.0 19.0 20.8 22.4 24.0 25.4 12.0 14.7 17.0 19.0 20.8
C(E), SC(E), EC(E)
D
21.1
16.1 19.7 22.7 25.4 27.8 30.0 32.1 34.1 13.4 16.4 18.9 21.1 23.1 25.0 26.7 28.3 13.4 16.4 18.9 21.1 23.1
EBS

28
22.8 27.9 32.3 36.1 39.5 42.7 45.6 48.4 21.3 26.1 30.1 33.7 36.9 39.8 42.6 45.2 18.3 22.4 25.9 29.0 31.7
EBS

39
30.9 37.8 43.6 48.8 53.4 57.7 61.7 65.5 28.8 35.3 40.7 45.5 49.9 53.9 57.6 61.1 24.8 30.4 35.0 39.2 42.9
EBS

53
41.4 50.8 58.6 65.5 71.8 77.5 82.9 87.9 39.3 48.1 55.6 62.1 68.1 73.5 78.6 83.4 31.5 38.6 44.6 49.9 54.6
EBS

70
59.9 73.4 84.8 94.8 104 112 120 127 55.4 67.8 78.3 87.5 95.9 104 111 117 43.9 53.8 62.1 69.4 76.1
OVE

53
40.2 49.3 56.9 63.6 69.7 75.3 80.5 85.4 37.6 46.0 53.1 59.4 65.1 70.3 75.1 79.7 32.6 39.9 46.1 51.6 56.5
OVE

70
59.6 73.0 84.2 94.2 103 111 119 126 55.6 68.1 78.6 87.9 96.3 104 111 118 48.3 59.1 68.3 76.3 83.6
OVE

105
81.8 100 116 129 142 153 164 174 76.4 93.6 108 121 132 143 153 162 66.3 81.2 93.8 105 115
OVE

141
108 132 153 171 187 202 216 229 105 128 148 165 181 196 209 222 83.3 102 118 132 144
OVE

193
147 180 208 233 255 276 295 312 143 175 202 226 247 267 285 303 114 139 161 180 197
OVE

246
195 239 276 309 339 366 391 415 189 232 268 299 328 354 379 402 151 185 213 238 261
These ratings are based on vapor free 40C liquid refrigerant entering the expansion valve, and a maximum of 4C change in superheat.
Nominal
Orifice Capacity
(kW)

5C

Liquid Temperature Entering TEV


Refrigerant -10C 0C 10C 20C 30C 40C 50C 60C
Correction Factor
R-22
1.52 1.42 1.32 1.21 1.11 1.00 0.89 0.78
R-407C
1.53 1.41 1.28 1.15 1.02 0.88 0.74 0.59

14
6.67
13.3
22.2
2.72
7.85
14.4
22.4
25.0
34.3
46.4
59.0
82.2
61.0
90.3
124
156
213
282

16
7.13
14.3
23.8
2.91
8.39
15.3
24.0
26.7
36.6
49.6
63.1
87.8
65.2
96.5
133
167
227
302

18
7.56
15.1
25.2
3.09
8.90
16.3
25.4
28.3
38.9
52.6
66.9
93.2
69.2
102
141
177
241
320

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-15C to 5C since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-407C
at a 5C evaporator, 8 bar pressure drop across the TEV, and a 30C liquid temperature entering the TEV
= 12.1 (from rating chart) x 1.02 (CF liquid temperature) = 12.3 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 15

Capacity Tables
R-134a Capacities in Tons (R-401A, R-409A Refrigerant & Liquid Temperature Correction Factor below)
Nominal
Orifice Capacity
(Tons)

Valve Type
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)

AA
A
B
C
D

1/2
1
2
2-1/2
4

40F
40
0.37
1.03
1.89
2.48
3.54

60
0.45
1.26
2.31
3.03
4.33

80
0.52
1.46
2.67
3.50
5.01

100
0.58
1.63
2.98
3.92
5.60

120
0.63
1.79
3.27
4.29
6.13

140
0.68
1.93
3.53
4.64
6.62

160
0.73
2.06
3.78
4.96
7.08

180
0.78
2.19
4.00
5.26
7.51

40
0.35
0.99
1.80
2.37
3.38

Evaporator Temperature F
20F
Pressure Drop (PSI)
60 80 100 120 140 160
0.43 0.49 0.55 0.61 0.65 0.70
1.21 1.39 1.56 1.71 1.84 1.97
2.21 2.55 2.85 3.12 3.37 3.61
2.90 3.35 3.74 4.10 4.43 4.73
4.14 4.78 5.34 5.85 6.32 6.76

0F
180
0.74
2.09
3.82
5.02
7.17

40
0.31
0.86
1.58
2.07
2.67

60
0.37
1.06
1.93
2.54
3.27

80
0.43
1.22
2.23
2.93
3.77

100
0.48
1.36
2.50
3.27
4.22

120
0.53
1.49
2.73
3.59
4.62

140
0.57
1.61
2.95
3.87
4.99

160
0.61
1.73
3.16
4.14
5.34

180
0.65
1.83
3.35
4.39
5.66

These ratings are based on vapor free 100F liquid refrigerant entering the expansion valve, and a maximum of 7F change in superheat.
Refrigerant
R-134a
R-401A
R-409A

Liquid Temperature Entering TEV


0F 20F 40F 60F 80F 100F 120F
Correction Factor
1.69 1.56 1.42 1.29 1.14 1.00 0.85
1.75 1.62 1.49 1.36 1.23 1.09 0.95
1.65 1.54 1.42 1.31 1.19 1.06 0.94

140F
0.71
0.81
0.81

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
0F to 40F since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-409A
at a 20F evaporator, 120 psi pressure drop across the TEV, and a 80F liquid temperature entering the
TEV = 3.12 (from rating chart) x 1.19 (CF liquid temperature) = 3.72 tons

R-134a Capacities in Kilowatts (R-401A, R-409A Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)

Nominal
Orifice Capacity
(kW)
AA
A
B
C
D

1.8
3.5
7.0
8.8
14.1

5C
2.5
1.22
3.46
6.32
8.29
11.8

4.0
1.55
4.37
7.99
10.5
15.0

5.5
1.82
5.12
9.37
12.3
17.6

7.0
2.05
5.78
10.6
13.9
19.8

8.5
2.26
6.37
11.6
15.3
21.8

10.0
2.45
6.91
12.6
16.6
23.7

11.5
2.63
7.41
13.6
17.8
25.4

13.0
2.79
7.88
14.4
18.9
27.0

2.5
1.17
3.32
6.06
7.96
11.4

Evaporator Temperature C
-5C
Pressure Drop (BAR)
4.0 5.5 7.0 8.5 10.0 11.5
1.49 1.74 1.97 2.17 2.35 2.52
4.19 4.92 5.55 6.11 6.63 7.11
7.67 8.99 10.1 11.2 12.1 13.0
10.1 11.8 13.3 14.7 15.9 17.1
14.4 16.9 19.0 21.0 22.7 24.4

-15C
13.0
2.68
7.56
13.8
18.1
25.9

2.5
1.06
2.98
5.45
7.16
9.49

4.0
1.34
3.77
6.90
9.05
12.0

5.5
1.57
4.42
8.09
10.6
14.1

7.0
1.77
4.99
9.12
12.0
15.9

8.5
1.95
5.50
10.1
13.2
17.5

10.0
2.11
5.96
10.9
14.3
19.0

11.5
2.27
6.40
11.7
15.3
20.4

13.0
2.41
6.80
12.4
16.3
21.6

These ratings are based on vapor free 40C liquid refrigerant entering the expansion valve, and a maximum of 4C change in superheat.
Liquid Temperature Entering TEV
Refrigerant -10C 0C 10C 20C 30C 40C 50C
Correction Factor
R-134a
1.64 1.52 1.39 1.26 1.13 1.00 0.87
R-401A
1.70 1.59 1.46 1.34 1.22 1.09 0.96
R-409A
1.61 1.50 1.40 1.29 1.18 1.07 0.95

60C
0.73
0.83
0.83

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-15C to 5C since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-409A
at a -5C evaporator, 8.5 bar pressure drop across the TEV, and a 30C liquid temperature entering the
TEV = 11.2 (from rating chart) x 1.18 (CF liquid temperature) = 13.2 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 16 / Catalog E-1, Thermostatic & Automatic Expansion Valves

Capacity Tables
R-404A Capacities in Tons (R-507 Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)

Nominal
Orifice Capacity
(Tons)
AA
A
B
C
D

1/2
1
1-1/2
3-1/2
6

Evaporator Temperature F
40F
75
0.31
1.00
1.32
2.86
4.58

100
0.36
1.16
1.52
3.31
5.29

125
0.40
1.29
1.70
3.70
5.92

150
0.44
1.42
1.86
4.05
6.48

Nominal
Orifice Capacity
(Tons)

175
0.47
1.53
2.01
4.38
7.00

20F
200
0.50
1.64
2.15
4.68
7.48

Pressure Drop (PSI)


225
250
75
100
0.54 0.56 0.29 0.34
1.74 1.83 0.95 1.10
2.28 2.41 1.25 1.44
4.96 5.23 2.71 3.13
7.94 8.37 4.34 5.02

125
0.38
1.23
1.61
3.51
5.61

150
0.41
1.34
1.77
3.84
6.14

175
0.45
1.45
1.91
4.15
6.64

Refrigerant
R-404A
R-507

0F

Liquid Temperature Entering TEV


0F 20F 40F 60F 80F 100F 120F 140F
Correction Factor
2.04 1.84 1.64 1.43 1.22 1.00 0.77 0.53
1.95 1.76 1.56 1.37 1.18 0.98 0.76 0.50

225
0.51
1.65
2.16
4.70
7.52

250
0.53
1.73
2.28
4.96
7.93

200
0.36
0.86
1.15
2.42
3.11

225
0.38
0.91
1.22
2.57
3.3

250
0.40
0.96
1.29
2.71
3.48

Evaporator Temperature F

-10F
Pressure Drop (PSI)
75
100
125
150
175
200
225
250
75
100
125
150
175
C(E), SC(E), EC(E)
AA
1/2
0.25 0.29 0.33 0.36 0.39 0.41 0.44 0.46 0.22 0.25 0.28 0.31 0.33
C(E), SC(E), EC(E)
A
1
0.82 0.95 1.06 1.16 1.26 1.34 1.42 1.50 0.53 0.61 0.68 0.75 0.81
C(E), SC(E), EC(E)
B
1-1/2
1.08 1.25 1.40 1.53 1.65 1.77 1.87 1.97 0.71 0.82 0.91 1.00 1.08
C(E), SC(E), EC(E)
C
3-1/2
2.35 2.71 3.03 3.32 3.59 3.84 4.07 4.29 1.48 1.71 1.92 2.10 2.27
C(E), SC(E), EC(E)
D
6
3.76 4.34 4.85 5.31 5.74 6.14 6.51 6.86
1.9
2.2
2.46 2.69 2.91
These ratings are based on vapor free 100F liquid refrigerant entering the expansion valve, and a maximum of 7F change in superheat.
Valve Type

200
0.48
1.55
2.04
4.43
7.09

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
-10F to 40F since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-507
at a 20F evaporator, 175 psi pressure drop across the TEV, and a 80F liquid temperature entering the
TEV = 1.91 (from rating chart) x 1.18 (CF liquid temperature) = 2.25 tons

R-404A Capacities in Kilowatts (R-507 Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)
C(E), SC(E), EC(E)

Nominal
Orifice Capacity
(kW)
AA
A
B
C
D

1.8
3.5
5.3
12.3
21.1

Evaporator Temperature C
5C
4
0.95
3.10
4.07
8.85
14.2

6
1.17
3.79
4.98
10.8
17.3

8
1.35
4.38
5.75
12.5
20.0

Nominal
Orifice Capacity
(kW)

10
1.51
4.90
6.43
14.0
22.4

12
1.65
5.36
7.05
15.3
24.5

14
1.78
5.79
7.61
16.5
26.5

8
1.29
4.17
5.49
11.9
19.1

10
1.44
4.67
6.13
13.3
21.3

12
1.57
5.11
6.72
14.6
23.4

Liquid Temperature Entering TEV


Refrigerant -10C 0C 10C 20C 30C 40C 50C 60C
Correction Factor
R-404A
1.98 1.79 1.60 1.41 1.21 1.00 0.79 0.56
R-507
1.89 1.71 1.53 1.35 1.17 0.98 0.78 0.53

14
1.70
5.52
7.26
15.8
25.2

16
1.82
5.90
7.76
16.9
27.0

18
1.93
6.26
8.23
17.9
28.6

14
1.21
2.93
3.81
8.23
10.4

16
1.30
3.13
4.07
8.80
11.1

18
1.38
3.32
4.32
9.33
11.7

Evaporator Temperature C

-25C
Pressure Drop (BAR)
4
6
8
10
12
14
16
18
4
6
8
10
12
C(E), SC(E), EC(E)
AA
1.8
0.81 0.99 1.15 1.28 1.40 1.52 1.62 1.72 0.65 0.79 0.92 1.03 1.12
C(E), SC(E), EC(E)
A
3.5
2.63 3.22 3.72 4.16 4.55 4.92 5.26 5.58 1.56 1.92 2.21 2.47 2.71
C(E), SC(E), EC(E)
B
5.3
3.46 4.23 4.89 5.46 5.99 6.46 6.91 7.33 2.04 2.49 2.88 3.22 3.53
C(E), SC(E), EC(E)
C
12.3
7.51 9.20 10.6 11.9 13.0 14.1 15.0 15.9 4.40 5.39 6.22 6.96 7.62
C(E), SC(E), EC(E)
D
21.1
12.0 14.7 17.0 19.0 20.8 22.5 24.0 25.5 5.54 6.78 7.83 8.76 9.59
These ratings are based on vapor free 40C liquid refrigerant entering the expansion valve, and a maximum of 4C change in superheat.
Valve Type

-15C

-5C
Pressure Drop (BAR)
16
18
4
6
1.91 2.02 0.91 1.11
6.19 6.57 2.95 3.62
8.14 8.63 3.88 4.75
17.7 18.8 8.43 10.3
28.3 30.0 13.5 16.5

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-25C to 5C since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an SCE-B using R-507
at a -5C evaporator, 12 bar pressure drop across the TEV, and a 30C liquid temperature entering the
TEV = 6.72 (from rating chart) x 1.17 (CF liquid temperature) = 7.86 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 17

Capacity Tables
R-410A Capacities in Tons
Valve Type
HC(E)
HC(E)
HC(E)
OZE
OZE
OZE
OZE
OZE

Nominal
Capacity
(Tons)
1-1/2
3
5
20
25
35
50
60

Refrigerant
R-410A

40F
120
1.30
2.60
4.33
17.1
20.5
28.2
42.7
51.3

160
1.50
3.00
5.00
19.7
23.7
32.6
49.3
59.2

200
1.68
3.35
5.59
22.1
26.5
36.4
55.2
66.2

240
1.84
3.67
6.12
24.2
29.0
39.9
60.4
72.5

280
1.98
3.97
6.61
26.1
31.3
43.1
65.3
78.3

Liquid Temperature Entering TEV


0F 20F 40F 60F 80F 100F 120F 140F
Correction Factor, CF Liquid Temperature
1.79 1.63 1.47 1.32 1.16 1.00 0.83 0.62

320
2.12
4.24
7.07
27.9
33.5
46.1
69.8
83.7

120
1.27
2.55
4.24
16.7
20.1
27.6
41.8
50.2

Evaporator Temperature F
20F
Pressure Drop (PSI)
160
200
240
280
1.47 1.64 1.80 1.94
2.94 3.29 3.60 3.89
4.90 5.48 6.00 6.48
19.3 21.6 23.7 25.6
23.2 25.9 28.4 30.7
31.9 35.6 39.0 42.2
48.3 54.0 59.1 63.9
57.9 64.8 71.0 76.7

0F
320
2.08
4.16
6.93
27.3
32.8
45.1
68.3
82.0

120
1.22
2.44
4.07
15.8
19.0
26.1
39.5
47.4

160
1.41
2.82
4.70
18.2
21.9
30.1
45.6
54.7

200
1.58
3.15
5.25
20.4
24.5
33.6
51.0
61.2

240
1.73
3.45
5.76
22.3
26.8
36.9
55.8
67.0

280
1.87
3.73
6.22
24.1
29.0
39.8
60.3
72.4

320
1.99
3.99
6.65
25.8
31.0
42.6
64.5
77.4

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
0F to 40F since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an HCE-3 using R-410A
at a 40F evaporator, 160 psi pressure drop across the TEV, and a 80F liquid temperature entering the
TEV = 3.00 (from rating chart) x 1.16 (CF liquid temperature) = 3.48 tons

R-410A Capacities in Kilowatts


Valve Type
HC(E)
HC(E)
HC(E)
OZE
OZE
OZE
OZE
OZE

Nominal
Capacity
(kW)
5
11
18
70
88
123
176
211

5C
8
4.49
8.98
15.0
59.8
71.7
98.6
149
179

11
5.27
10.5
17.6
70.1
84.1
116
175
210

14
5.94
11.9
19.8
79.1
94.9
130
198
237

17
6.55
13.1
21.8
87.1
105
144
218
261

20
6.55
13.1
21.8
94.5
113
156
236
284

Liquid Temperature Entering TEV


Refrigerant -10C 0C 10C 20C 30C 40C 50C 60C
Correction Factor, CF Liquid Temperature
R-410A
1.73 1.59 1.44 1.30 1.15 1.00 0.84 0.65

23
7.62
15.2
25.4
101
122
167
253
304

8
4.40
8.80
14.7
58.5
70.2
96.5
146
175

Evaporator Temperature C
-5C
Pressure Drop (BAR)
11
14
17
20
5.16 5.82 6.41 6.41
10.3 11.6 12.8 12.8
17.2 19.4 21.4 21.4
68.6 77.4 85.2 92.5
82.3 92.8 102
111
113
128
141
153
171
193
213
231
206
232
256
277

-15C
23
7.46
14.9
24.9
99.2
119
164
248
297

8
4.29
8.57
14.3
55.7
66.9
92
139
167

11
5.02
10.0
16.7
65.3
78.4
108
163
196

14
5.67
11.3
18.9
73.7
88.5
122
184
221

17
6.25
12.5
20.8
81.2
97.5
134
203
244

20
6.25
12.5
20.8
88.1
106
145
220
264

23
7.27
14.5
24.2
94.5
113
156
236
283

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-15C to 5C since the variation in the actual factors across this range is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature Example: Actual capacity of an HCE-3 using R-410A
at a 5C evaporator, 11 bar pressure drop across the TEV, and a 30C liquid temperature entering the
TEV = 10.5 (from rating chart) x 1.15 (CF liquid temperature) = 12.1 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 18 / Catalog E-1, Thermostatic & Automatic Expansion Valves

A Series Constant Pressure (Automatic) Valves


Specifications
0-90 psig adjustment range
Bypass bleeds available
Construction: Brass, copper and stainless
steel
Optional external equalizer
U.L. recognized for maximum operating
pressure of 500 psig high side, 225 psig
low side

Model
No.
A1
A2*
A3
A4
AS
A7

Equalizer

AT

Internal
Internal
Internal
Internal
Internal
Internal
Internal

Model A7

Connections ( Inches)
Inlet
Outlet
1/4 SAE
1/4 NPTF
1/4 SAE
1/2 SAE
3/8 SAE
1/2 SAE
1/4 SAE
1/2 SAE
1/4 ODF
3/8 ODF
3/8 ODF
3/8 ODF
1/4 SAE
1/4 ODF
8 mm ODF

* 1/2" x 3/8" SAE flare adaptor available.

1/4 NPTF
8 mm ODF

1.50

Model AS
2.00

4.36
Outlet
Inlet
Outlet

2.10
1.16
Inlet
1.40

Model AT

Model A1
1.50

2.00

3.80

3.67
Ref

Inlet

1.64

1.38
Outlet
1.31

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

1.27

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 19

A Series Constant Pressure (Automatic) Valves


Model A2
1.50

3.67
Ref

Inlet

1.38

Outlet
1.27

Model A3
1.50

3.67
Ref

Inlet

1.38

Outlet
1.27

Model A4
1.50

3.67
Ref

Inlet

1.38

Outlet
1.27

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 20 / Catalog E-1, Thermostatic & Automatic Expansion Valves

Capacity Tables
R-134a Capacities in Tons (R-401A, R-409A Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Valve Type

Nominal Capacity
Orifice Capacity Range
(Tons)
(Tons)
B

AA
A
B
C

2
1/2
1/2
1
2
3
1

1 to 2
1/4 to 3/4
1/8 to 1/2
1/4 to 1
1 to 2
1-1/2 to 3
1/4 to 1

Nominal Capacity
Orifice Capacity Range
(Tons)
(Tons)

A1, A2, AT
B
2
1 to 2
A4

1/2
1/4 to 3/4
A7-AA
AA
1/2
1/8 to 1/2
A7-A
A
1
1/4 to 1
A7-B
B
2
1 to 2
A7-C
C
3
1-1/2 to 3
AS, ASB20

1
1/4 to 1
nGold areas are standard conditions.
Refrigerant
R-134a
R-401A
R-409A

140
3.06
1.15
0.76
1.53
3.06
4.58
1.53

Evaporator Temperature F
20F
Pressure Drop (PSI)
60
80 100 120 140 160
1.90 2.19 2.45 2.69 2.90 3.10
0.71 0.82 0.92 1.01 1.09 1.16
0.48 0.55 0.61 0.67 0.73 0.78
0.95 1.10 1.23 1.34 1.45 1.55
1.90 2.19 2.45 2.69 2.90 3.10
2.85 3.29 3.68 4.03 4.35 4.65
0.95 1.10 1.23 1.34 1.45 1.55

180
2.46
0.92
0.61
1.23
2.46
3.69
1.23

Evaporator Temperature F
-20F
Pressure Drop (PSI)
80 100 120 140 160 180
1.34 1.50 1.64 1.77 1.89 2.01
0.50 0.56 0.62 0.66 0.71 0.75
0.33 0.37 0.41 0.44 0.47 0.50
0.67 0.75 0.82 0.89 0.95 1.00
1.34 1.50 1.64 1.77 1.89 2.01
2.01 2.25 2.46 2.66 2.84 3.01
0.67 0.75 0.82 0.89 0.95 1.00

40F
40
1.63
0.61
0.41
0.82
1.63
2.45
0.82

60
2.00
0.75
0.50
1.00
2.00
3.00
1.00

80
2.31
0.87
0.58
1.15
2.31
3.46
1.15

100
2.58
0.97
0.65
1.29
2.58
3.87
1.29

120
2.83
1.06
0.71
1.41
2.83
4.24
1.41

-10F
80
1.64
0.61
0.41
0.82
1.64
2.46
0.82

100
1.83
0.69
0.46
0.92
1.83
2.75
0.92

Liquid Temperature Entering AEV


0F 20F 40F 60F 80F 100F 120F
Correction Factor
1.69 1.56 1.42 1.29 1.14 1.00 0.85
1.75 1.62 1.49 1.36 1.23 1.09 0.95
1.65 1.54 1.42 1.31 1.19 1.06 0.94

120
2.01
0.75
0.50
1.00
2.01
3.01
1.00

140F
0.71
0.81
0.81

140
2.17
0.81
0.54
1.08
2.17
3.25
1.08

160
2.32
0.87
0.58
1.16
2.32
3.48
1.16

0F
60
1.70
0.64
0.43
0.85
1.70
2.55
0.85

80
1.96
0.74
0.49
0.98
1.96
2.94
0.98

100
2.19
0.82
0.55
1.10
2.19
3.29
1.10

120
2.40
0.90
0.60
1.20
2.40
3.61
1.20

140
2.60
0.97
0.65
1.30
2.60
3.90
1.30

160
2.78
1.04
0.69
1.39
2.78
4.16
1.39

160
1.24
0.47
0.31
0.62
1.24
1.86
0.62

180
1.32
0.49
0.33
0.66
1.32
1.97
0.66

-40F
80
0.88
0.33
0.22
0.44
0.88
1.32
0.44

100
0.98
0.37
0.25
0.49
0.98
1.47
0.49

120
1.07
0.40
0.27
0.54
1.07
1.61
0.54

140
1.16
0.44
0.29
0.58
1.16
1.74
0.58

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
-40F to 40F since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-409A
at a 20F evaporator, 120 psi pressure drop across the AEV, and a 80F liquid temperature entering the
AEV = 2.69 (from rating chart) x 1.19 (CF liquid temperature) = 3.20 tons

R-134a Capacities in Kilowatts (R-401A, R-409A Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Valve Type

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)
B

AA
A
B
C

7
3
2
4
7
11
4

4 to 7
1 to 3
1/2 to 2
1 to 4
4 to 7
5 to 11
1 to 4

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)

A1, A2, AT
B
7
A4

3
A7-AA
AA
2
A7-A
A
4
A7-B
B
7
A7-C
C
11
AS, ASB20

4
nGold areas are standard conditions.

4 to 7
1 to 3
1/2 to 2
1 to 4
4 to 7
5 to 11
1 to 4

10
11.3
4.25
2.84
5.67
11.3
17.0
5.67

Evaporator Temperature C
0C
Pressure Drop (BAR)
4
6
7
8
10
11
6.89 8.44 9.11 9.74 10.9 11.4
2.58 3.16 3.42 3.65 4.08 4.28
1.72 2.11 2.28 2.44 2.72 2.86
3.44 4.22 4.56 4.87 5.45 5.71
6.89 8.44 9.11 9.74 10.9 11.4
10.3 12.7 13.7 14.6 16.3 17.1
3.44 4.22 4.56 4.87 5.45 5.71

12
9.57
3.59
2.39
4.78
9.57
14.4
4.78

Evaporator TemperatureC
-30C
Pressure Drop (BAR)
6
7
8
10
11
12
5.01 5.41 5.78 6.47 6.78 7.08
1.88 2.03 2.17 2.42 2.54 2.66
1.25 1.35 1.45 1.62 1.70 1.77
2.50 2.70 2.89 3.23 3.39 3.54
5.01 5.41 5.78 6.47 6.78 7.08
7.51 8.11 8.68 9.70 10.2 10.6
2.50 2.70 2.89 3.23 3.39 3.54

10C
3
6.21
2.33
1.55
3.11
6.21
9.32
3.11

4
7.17
2.69
1.79
3.59
7.17
10.8
3.59

6
8.79
3.30
2.20
4.39
8.79
13.2
4.39

7
9.49
3.56
2.37
4.75
9.49
14.2
4.75

8
10.1
3.80
2.54
5.07
10.1
15.2
5.07

-20C
6
6.77
2.54
1.69
3.38
6.77
10.1
3.38

7
7.31
2.74
1.83
3.65
7.31
11.0
3.65

Liquid Temperature Entering AEV


Refrigerant -10C 0C 10C 20C 30C 40C 50C
Correction Factor
R-134a
1.64 1.52 1.39 1.26 1.13 1.00 0.87
R-401A
1.70 1.59 1.46 1.34 1.22 1.09 0.96
R-409A
1.61 1.50 1.40 1.29 1.18 1.07 0.95

8
7.81
2.93
1.95
3.91
7.81
11.7
3.91

60C
0.73
0.83
0.83

10
8.74
3.28
2.18
4.37
8.74
13.1
4.37

11
9.16
3.44
2.29
4.58
9.16
13.7
4.58

-10C
4
6.46
2.42
1.61
3.23
6.46
9.69
3.23

6
7.91
2.97
1.98
3.95
7.91
11.9
3.95

7
8.54
3.20
2.14
4.27
8.54
12.8
4.27

8
9.13
3.42
2.28
4.57
9.13
13.7
4.57

10
10.2
3.83
2.55
5.10
10.2
15.3
5.10

11
10.7
4.02
2.68
5.35
10.7
16.1
5.35

11
4.40
1.65
1.10
2.20
4.40
6.60
2.20

12
4.60
1.72
1.15
2.30
4.60
6.90
2.30

-40C
6
3.25
1.22
0.81
1.63
3.25
4.88
1.63

7
3.51
1.32
0.88
1.76
3.51
5.27
1.76

8
3.75
1.41
0.94
1.88
3.75
5.63
1.88

10
4.20
1.57
1.05
2.10
4.20
6.30
2.10

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-40C to 10C since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-409A
at a 0C evaporator, 8 bar pressure drop across the AEV, and a 30C liquid temperature entering the
AEV = 9.74 (from rating chart) x 1.18 (CF liquid temperature) = 11.5 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Catalog E-1, Thermostatic & Automatic Expansion Valves / Page 21

Capacity Tables
R-22 Capacities in Tons (R-407C Refrigerant & Liquid Temperature Correction Factor below)
Nominal
Orifice Capacity
(Tons)

Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

AA
A
B
C

3
1
3/4
1-1/2
3
5
1-1/2

Nominal
Orifice Capacity
(Tons)

Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

AA
A
B
C

3
1
3/4
1-1/2
3
5
1-1/2

Capacity
Range
(Tons)
1-1/2 to 3
1/2 to 1
1/5 to 3/4
1/2 to 1-1/2
1-1/2 to 3
3-1/2 to 5
1/2 to 1-1/2
Capacity
Range
(Tons)
1-1/2 to 3
1/2 to 1
1/5 to 3/4
1/2 to 1-1/2
1-1/2 to 3
3-1/2 to 5
1/2 to 1-1/2

200
4.24
1.41
1.06
2.12
4.24
7.07
2.12

Evaporator TemperatureF
20F
Pressure Drop (PSI)
75 100 125 150 175 200
2.55 2.94 3.29 3.60 3.89 4.16
0.85 0.98 1.10 1.20 1.30 1.39
0.64 0.74 0.82 0.90 0.97 1.04
1.27 1.47 1.64 1.80 1.94 2.08
2.55 2.94 3.29 3.60 3.89 4.16
4.24 4.90 5.48 6.00 6.48 6.93
1.27 1.47 1.64 1.80 1.94 2.08

225
3.33
1.11
0.83
1.67
3.33
5.55
1.67

Evaporator Temperature F
-20F
Pressure Drop (PSI)
125 150 175 200 225 250
2.05 2.24 2.42 2.59 2.75 2.89
0.68 0.75 0.81 0.86 0.92 0.96
0.51 0.56 0.61 0.65 0.69 0.72
1.02 1.12 1.21 1.29 1.37 1.45
2.05 2.24 2.42 2.59 2.75 2.89
3.41 3.74 4.03 4.31 4.58 4.82
1.02 1.12 1.21 1.29 1.37 1.45

40F
75
2.60
0.87
0.65
1.30
2.60
4.33
1.30

100
3.00
1.00
0.75
1.50
3.00
5.00
1.50

125
3.35
1.12
0.84
1.68
3.35
5.59
1.68

150
3.67
1.22
0.92
1.84
3.67
6.12
1.84

175
3.97
1.32
0.99
1.98
3.97
6.61
1.98

-10F
100
2.22
0.74
0.56
1.11
2.22
3.70
1.11

125
2.48
0.83
0.62
1.24
2.48
4.14
1.24

150
2.72
0.91
0.68
1.36
2.72
4.53
1.36

175
2.94
0.98
0.73
1.47
2.94
4.89
1.47

200
3.14
1.05
0.78
1.57
3.14
5.23
1.57

0F
75
2.29
0.76
0.57
1.14
2.29
3.81
1.14

100
2.64
0.88
0.66
1.32
2.64
4.40
1.32

125
2.95
0.98
0.74
1.48
2.95
4.92
1.48

150
3.23
1.08
0.81
1.62
3.23
5.39
1.62

175
3.49
1.16
0.87
1.75
3.49
5.82
1.75

200
3.73
1.24
0.93
1.87
3.73
6.22
1.87

225
1.85
0.62
0.46
0.92
1.85
3.08
0.92

250
1.94
0.65
0.49
0.97
1.94
3.24
0.97

-40F
125
1.38
0.46
0.34
0.69
1.38
2.29
0.69

150
1.51
0.50
0.38
0.75
1.51
2.51
0.75

175
1.63
0.54
0.41
0.81
1.63
2.71
0.81

200
1.74
0.58
0.43
0.87
1.74
2.90
0.87

Gold areas are standard conditions.

Refrigerant
R-22
R-407C

Liquid Temperature Entering AEV


20F 40F 60F 80F 100F 120F 140F
Correction Factor
1.57 1.45 1.34 1.23 1.12 1.00 0.88 0.76
1.58 1.45 1.32 1.18 1.04 0.89 0.74 0.57
0F

These factors include corrections for liquid refrigerantdensity and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
-40F to 40F since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-407C
at a 40F evaporator, 125 psi pressure drop across the AEV, and a 80F liquid temperature entering the
AEV = 3.35 (from rating chart) x 1.04 (CF liquid temperature) = 3.48 tons

R-22 Capacities in Kilowatts (R-407C Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)
B

AA
A
B
C

11
4
3
5
11
18
5

5 to 11
2 to 4
3/4 to 3
2 to 5
5 to 11
12 to 18
2 to 5

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)
B

AA
A
B
C

11
4
3
5
11
18
5

5 to 11
2 to 4
3/4 to 3
2 to 5
5 to 11
12 to 18
2 to 5

14
15.1
5.02
3.77
7.54
15.1
25.1
7.54

Evaporator Temperature C
0C
Pressure Drop (BAR)
5
7
9
10
12
14
8.83 10.4 11.8 12.5 13.7 14.8
2.94 3.48 3.95 4.16 4.56 4.92
2.21 2.61 2.96 3.12 3.42 3.69
4.41 5.22 5.92 6.24 6.84 7.38
8.83 10.4 11.8 12.5 13.7 14.8
14.7 17.4 19.7 20.8 22.8 24.6
4.41 5.22 5.92 6.24 6.84 7.38

17
13.5
4.48
3.36
6.73
13.5
22.4
6.73

Evaporator Temperature C
-30C
Pressure Drop (BAR)
9
10
12
14
16
17
7.25 7.64 8.37 9.04 9.67 9.96
2.42 2.55 2.79 3.01 3.22 3.32
1.81 1.91 2.09 2.26 2.42 2.49
3.63 3.82 4.19 4.52 4.83 4.98
7.25 7.64 8.37 9.04 9.67 9.96
12.1 12.7 14.0 15.1 16.1 16.6
3.63 3.82 4.19 4.52 4.83 4.98

10C
5
9.01
3.00
2.25
4.50
9.01
15.0
4.50

7
10.7
3.55
2.66
5.33
10.7
17.8
5.33

9
12.1
4.03
3.02
6.04
12.1
20.1
6.04

10
12.7
4.25
3.18
6.37
12.7
21.2
6.37

12
14.0
4.65
3.49
6.98
14.0
23.3
6.98

-20C
9
9.79
3.26
2.45
4.89
9.79
16.3
4.89

10
10.3
3.44
2.58
5.16
10.3
17.2
5.16

12
11.3
3.77
2.83
5.65
11.3
18.8
5.65

14
12.2
4.07
3.05
6.10
12.2
20.3
6.10

16
13.1
4.35
3.26
6.53
13.1
21.8
6.53

-10C
7
10.1
3.37
2.53
5.06
10.1
16.9
5.06

9
11.5
3.83
2.87
5.74
11.5
19.1
5.74

10
12.1
4.03
3.03
6.05
12.1
20.2
6.05

12
13.3
4.42
3.31
6.63
13.3
22.1
6.63

14
14.3
4.77
3.58
7.16
14.3
23.9
7.16

16
15.3
5.10
3.83
7.65
15.3
25.5
7.65

16
6.44
2.15
1.61
3.22
6.44
10.7
3.22

17
6.64
2.21
1.66
3.32
6.64
11.1
3.32

-40C
9
4.83
1.61
1.21
2.42
4.83
8.06
2.42

10
5.09
1.70
1.27
2.55
5.09
8.49
2.55

12
5.58
1.86
1.40
2.79
5.58
9.30
2.79

14
6.03
2.01
1.51
3.01
6.03
10.0
3.01

Gold areas are standard conditions.

Liquid Temperature Entering AEV


Refrigerant -10C 0C 10C 20C 30C 40C 50C 60C
Correction Factor
R-22
1.52 1.42 1.32 1.21 1.11 1.00 0.89 0.78
R-407C
1.53 1.41 1.28 1.15 1.02 0.88 0.74 0.59

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-40C to 10C since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-407C
at a 10C evaporator, 7 bar pressure drop across the AEV, and a 30C liquid temperature entering the
AEV = 10.7 (from rating chart) x 1.02 (CF liquid temperature) = 10.9 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Page 22 / Catalog E-1, Thermostatic & Automatic Expansion Valves

Capacity Tables
R-404A Capacities in Tons (R-507 Refrigerant & Liquid Temperature Correction Factor below)
Nominal Capacity
Orifice Capacity Range
(Tons)
(Tons)

Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

AA
A
B
C

2
1/2
1/2
1
2
4
1

1 to 2
1/4 to 3/4
1/8 to 1/2
1/4 to 1
1 to 2
1-1/2 to 4
1/4 to 1

Nominal Capacity
Orifice Capacity Range
(Tons)
(Tons)

Valve Type

A1, A2, AT
B
2
1 to 2
A4

1/2
1/4 to 3/4
A7-AA
AA
1/2
1/8 to 1/2
A7-A
A
1
1/4 to 1
A7-B
B
2
1 to 2
A7-C
C
4
1-1/2 to 4
AS, ASB20

1
1/4 to 1
nGold areas are standard conditions.
Refrigerant
R-404A
R-507

200
2.83
1.06
0.71
1.41
2.83
5.66
1.41

Evaporator Temperature F
20F
Pressure Drop (PSI)
75 100 125 150 175 200
1.66 1.92 2.15 2.35 2.54 2.72
0.62 0.72 0.80 0.88 0.95 1.02
0.42 0.48 0.54 0.59 0.63 0.68
0.83 0.96 1.07 1.18 1.27 1.36
1.66 1.92 2.15 2.35 2.54 2.72
3.33 3.84 4.29 4.70 5.08 5.43
0.83 0.96 1.07 1.18 1.27 1.36

225
2.22
0.83
0.56
1.11
2.22
4.44
1.11

Evaporator Temperature F
-20F
Pressure Drop (PSI)
125 150 175 200 225 250
1.36 1.49 1.61 1.73 1.83 1.93
0.51 0.56 0.61 0.65 0.69 0.72
0.34 0.37 0.40 0.43 0.46 0.48
0.68 0.75 0.81 0.86 0.92 0.96
1.36 1.49 1.61 1.73 1.83 1.93
2.73 2.99 3.23 3.45 3.66 3.86
0.68 0.75 0.81 0.86 0.92 0.96

40F
75
1.73
0.65
0.43
0.87
1.73
3.46
0.87

100
2.00
0.75
0.50
1.00
2.00
4.00
1.00

125
2.24
0.84
0.56
1.12
2.24
4.47
1.12

150
2.45
0.92
0.61
1.22
2.45
4.90
1.22

175
2.65
0.99
0.66
1.32
2.65
5.29
1.32

-10F
100
1.48
0.56
0.37
0.74
1.48
2.96
0.74

125
1.65
0.62
0.41
0.83
1.65
3.31
0.83

150
1.81
0.68
0.45
0.91
1.81
3.63
0.91

Liquid Temperature Entering AEV


20F 40F 60F 80F 100F 120F 140F
Correction Factor
2.04 1.84 1.64 1.43 1.22 1.00 0.77 0.53
1.95 1.76 1.56 1.37 1.18 0.98 0.76 0.50
0F

175
1.96
0.73
0.49
0.98
1.96
3.92
0.98

200
2.09
0.78
0.52
1.05
2.09
4.19
1.05

0F
75
1.51
0.57
0.38
0.75
1.51
3.01
0.75

100
1.74
0.65
0.44
0.87
1.74
3.48
0.87

125
1.95
0.73
0.49
0.97
1.95
3.89
0.97

150
2.13
0.80
0.53
1.07
2.13
4.26
1.07

175
2.30
0.86
0.58
1.15
2.30
4.60
1.15

200
2.46
0.92
0.62
1.23
2.46
4.92
1.23

225
1.17
0.44
0.29
0.59
1.17
2.34
0.59

250
1.23
0.46
0.31
0.62
1.23
2.47
0.62

-40F
125
0.87
0.33
0.22
0.44
0.87
1.74
0.44

150
0.96
0.36
0.24
0.48
0.96
1.91
0.48

175
1.03
0.39
0.26
0.52
1.03
2.06
0.52

200
1.10
0.41
0.28
0.55
1.10
2.21
0.55

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of 0F. However, they may be used for any evaporator temperature from
-40F to 40F since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-507
at a 20F evaporator, 175 psi pressure drop across the AEV, and a 80F liquid temperature entering the
AEV = 2.54 (from rating chart) x 1.18 (CF liquid temperature) = 3.00 tons

R-404A Capacities in Kilowatts (R-507 Refrigerant & Liquid Temperature Correction Factor below)
Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Valve Type
A1, A2, AT
A4
A7-AA
A7-A
A7-B
A7-C
AS, ASB20

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)
B

AA
A
B
C

7
3
2
4
7
14
4

4 to 7
1 to 3
1/2 to 2
1 to 4
4 to 7
5 to 14
1 to 4

Nominal Capacity
Orifice Capacity Range
(kW)
(kW)
B

AA
A
B
C

7
3
2
4
7
14
4

4 to 7
1 to 3
1/2 to 2
1 to 4
4 to 7
5 to 14
1 to 4

14
10.1
3.80
2.54
5.07
10.1
20.3
5.07

Evaporator Temperature C
0C
Pressure Drop (BAR)
5
7
9
10
12
14
5.88 6.96 7.89 8.32 9.11 9.84
2.21 2.61 2.96 3.12 3.42 3.69
1.47 1.74 1.97 2.08 2.28 2.46
2.94 3.48 3.95 4.16 4.56 4.92
5.88 6.96 7.89 8.32 9.11 9.84
11.8 13.9 15.8 16.6 18.2 19.7
2.94 3.48 3.95 4.16 4.56 4.92

16
8.57
3.21
2.14
4.28
8.57
17.1
4.28

Evaporator Temperature C
-30C
Pressure Drop (BAR)
9
10
12
14
16
17
4.80 5.06 5.54 5.99 6.40 6.60
1.80 1.90 2.08 2.24 2.40 2.47
1.20 1.26 1.39 1.50 1.60 1.65
2.40 2.53 2.77 2.99 3.20 3.30
4.80 5.06 5.54 5.99 6.40 6.60
9.60 10.1 11.1 12.0 12.8 13.2
2.40 2.53 2.77 2.99 3.20 3.30

10C
5
6.06
2.27
1.52
3.03
6.06
12.1
3.03

7
7.17
2.69
1.79
3.59
7.17
14.3
3.59

9
8.14
3.05
2.03
4.07
8.14
16.3
4.07

10
8.58
3.22
2.14
4.29
8.58
17.2
4.29

12
9.39
3.52
2.35
4.70
9.39
18.8
4.70

-20C
7
5.67
2.13
1.42
2.83
5.67
11.3
2.83

9
6.43
2.41
1.61
3.21
6.43
12.9
3.21

10
6.77
2.54
1.69
3.39
6.77
13.5
3.39

Gold areas are standard conditions.


Liquid Temperature Entering AEV
Refrigerant -10C 0C 10C 20C 30C 40C 50C 60C
Correction Factor
R-404A
1.98 1.79 1.60 1.41 1.21 1.00 0.79 0.56
R-507
1.89 1.71 1.53 1.35 1.17 0.98 0.78 0.53

12
7.42
2.78
1.86
3.71
7.42
14.8
3.71

14
8.02
3.01
2.00
4.01
8.02
16.0
4.01

-10C
5
5.58
2.09
1.39
2.79
5.58
11.2
2.79

7
6.60
2.48
1.65
3.30
6.60
13.2
3.30

9
7.48
2.81
1.87
3.74
7.48
15.0
3.74

10
7.89
2.96
1.97
3.94
7.89
15.8
3.94

12
8.64
3.24
2.16
4.32
8.64
17.3
4.32

14
9.33
3.50
2.33
4.67
9.33
18.7
4.67

16
4.12
1.55
1.03
2.06
4.12
8.24
2.06

17
4.25
1.59
1.06
2.12
4.25
8.50
2.12

-40C
9
3.09
1.16
0.77
1.55
3.09
6.18
1.55

10
3.26
1.22
0.81
1.63
3.26
6.52
1.63

12
3.57
1.34
0.89
1.78
3.57
7.14
1.78

14
3.86
1.45
0.96
1.93
3.86
7.71
1.93

These factors include corrections for liquid refrigerant density and net refrigerating effect, and are based
on an evaporator temperature of -15C. However, they may be used for any evaporator temperature from
-40C to 10C since the variation in the actual factors across this range is insignificant.
AEV Capacity = AEV Rating x CF Liquid Temperature Example: Actual capacity of an A7-B using R-507
at a 0C evaporator, 12 bar pressure drop across the AEV, and a 30C liquid temperature entering the
AEV = 9.11 (from rating chart) x 1.17 (CF liquid temperature) = 10.7 kW

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

Parker Hannifin Corporation, Climate and Industrial Controls Group, Cleveland, OH

CLIMATE CONTROL
Accumulators

Hose & fittings

CO2 controls

Pressure regulating valves

Electronic controllers

Refrigerant distributors

Filter-driers

Safety relief valves

Hand shut-off valves

Solenoid valves

Heat exchangers

Thermostatic expansion

valves

AEROSPACE

ELECTROMECHANICAL

FILTRATION

Flight control systems & components

AC/DC drives &systems

Analytical gas generators

Brass fittings & valves

Fluid conveyance systems

Electric actuators, gantry robots


& slides

Compressed air & gas filters

Diagnostic equipment

Condition monitoring

Fluid conveyance systems

Engine air, fuel & oil filtration & systems

Industrial hose

Hydraulic, lubrication & coolant filters

PTFE & PFA hose, tubing &


plastic fittings

Fluid metering delivery & atomization


devices

Electrohydrostatic actuation systems

Fuel systems & components

Electromechanical actuation systems

Hydraulic systems & components

Human machine interfaces

Inert nitrogen generating systems

Linear motors

Process, chemical, water &


microfiltration filters

Pneumatic systems & components

Stepper motors, servo motors, drives &


controls

Nitrogen, hydrogen & zero air generators

Wheels & brakes

FLUID & GAS HANDLING

Quick disconnects
Rubber & thermoplastic hose
& couplings
Tube fittings & adapters

Structural extrusions

HYDRAULICS

PNEUMATICS

PROCESS CONTROL

SEALING & SHIELDING

Diagnostic equipment

Air preparation

Dynamic seals

Hydraulic cylinders & accumulators

Brass fittings & valves

Analytical sample conditioning


products & systems

Hydraulic motors & pumps

Manifolds

EMI shielding

Hydraulic systems

Pneumatic actuators, grippers, valves,


controls & accessories

Fluoropolymer chemical delivery


fittings, valves & pumps

Hydraulic valves & controls

Quick disconnects

Power take-offs

Rotary actuators

Quick disconnects
Rubber & thermoplastic hose & couplings
Tube fittings & adapters

Rubber & thermoplastic hose &


couplings
Structural extrusions

High purity gas delivery fittings, valves


& regulators
Instrumentation fittings, valves &
regulators
Medium pressure fittings & valves
Process control manifolds

Thermoplastic tubing & fittings

Elastomeric o-rings
Extruded & precision-cut, fabricated
elastomeric seals
Homogeneous & inserted
elastomeric shapes
High temperature metal seals
Metal & plastic retained composite
seals
Thermal management

Vacuum generators, cups & sensors

Parker Hannifin Corporation


Climate and Industrial Controls Group
2445 South 25th Avenue Broadview, IL 60155-3891 USA
phone 800 742 2681 fax 800 241 2872
www.parker.com/coolparts

102007 / Catalog E-1