You are on page 1of 5

FOR B12-1 WELL PLATFORM.

Page 1 of 5
P
C
8
0
1
2
3
0
1
-
0
0


PROJECT: C SERIES PROJECT 4 WELL HEAD PLATFORM PROJECT
ELECTRICAL LOAD LIST FOR B12-1 WELL PLATFORM



Notes:

1. Load list is based on preliminary instrumentation loads.

OIL AND NATURAL GAS
CORPORATION LTD. INDIA

TECHNIP KT INDIA PVT LTD.




CLIENT: ONGC TITLE :
ELECTRICAL LOAD LIST


A
30.05.2012
SGBM
30.05.2012
SKVS
30.05.2012
SIS
ISSUED FOR ENQUIRY A
PEM
STATUS
MADE
BY & DATE

BY & DATE
APP
BY & DATE

STATUS
REV































DOCUMENT NO. : P4901-LS-EL-003



(Amp.)
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
Page 2 of 5


TECHNIP KT INDIA LIMITED.

ELECTRICAL LOAD LIST
(B12-1 - System I : 24V DC ) RTU
SYSTEM
Client: ONGC

Sr.
No.

Load Description


Qty.


Rated
Voltage
Unit
Load
(Watt)
Total
Load
(Watt)
Run Up
Time In
Hrs./Day
Energy
Consumed in
Ah/Day
Energy
Consumed
in WH/Day
Unit Load
@ 24V DC
(Amp.)
Total
Load 24V
DC
(Amp.)
Duty
Cycle/
Load
Factor
Average
Current
Drawn @ 24V
Status

Remarks

1 TIC PLC

1.1 Multivariable Transmitter 1 24 35 35 24 35 840 1.458 1.458 P
1.2 Electronic Transmitter (TT, PT) 32 24 0.5 16 24 16 384 0.0208 0.667 P
1.3 Pig Detectors 1 24 1.2 1.2 0.01 0.0005 0.012 0.050 0.050 P
1.4 Isolating Barriers 32 24 1.6 51.2 24 51.2 1228.8 0.067 2.133 P
1.5 RTU PLC System 1 24 300 300 24 300 7200 12 12 P

1.6

Microwave Radio during Transmit Micro Radio during
Receive Microwave Radio during Sleep Mode

1

24 272 272 24 272 6528 11.333

11.333 P
Limit Switches
24 1.2 9.6 9.6 230.4 0.4 P
1.8 Level Switch / Pressure Switch 5 24 1.2 24 6 144 0.050 0.25 P



TOTAL 691 690 16555

10% MARGIN

69 69 1655


TOTAL (WITH 10% MARGIN )


760

759

18,210

32



TOTAL AVERAGE DEMAND: Amps
TOTAL PEAK DEMAND: 33 Amps


1.7

8 24 0.050
6.0
29
3
Project No. : P4901
Date: 30/05/2012
Rev: A
24V (Amp.)
assumed.
P: PRELIMINARY D: DESIGN APPROVED F: FINAL
SH. 3 OF 5
ELECTRICAL LOAD LIST (B12-1-
System II: 24V DC) LIGHTING, INST.
GAS FILTER SEPARATOR
Client: ONGC

Sr.
No.

Load Description


Qty.


Rated
Voltage
Unit Load
(Watt)
Total Load
(Watt)
Run Up
Time In
Hrs./Day
Energy
Consumed
in Ah/Day
Energy
Consumed
in WH/Day
Unit Load
@ 24V
DC
(Amp.)
Total
Load 24V
DC
(Amp.)
Duty
Cycle/
Load
Factor
Average
Current
Drawn @
Status

Remarks



1

Illumination for Level Gauge

3

24 50 150 0.25 1.56 37.5 2.083

6.25 P
Run-Up time of 0.25hr/day is

2 INST. GAS FILTER SEPARATOR

2.1
Illumination for Level Gauge
2 24 50 100 0.25 1.042 25 2.083 4.167 P
2.2 Level Switch 1 24 1.2 1.2 0.01 0.0005 0.012 0.05 0.05 P
3 Lighting System

3.1 Electrical/Telemetry Room Lighting 2 24 60 120 3 15 360 2.5 5 P
3.2 Battery Room Lighting 2 24 60 120 3 15 360 2.5 5 P
3.3 Shelter House Lighting 2 24 60 120 3 15 360 2.5 5 P





TOTAL

611 48 1142.5
25.5


10% MARGIN

61 5 114.25 2.5

TOTAL (WITH 10% MARGIN )

672 53 1257 28

TOTAL AVERAGE DEMAND:
Amps

TOTAL PEAK DEMAND: 28 Amps





TECHNIP KT INDIA LIMITED.








































Project No. : P4901
Date: 30/05/2012
Rev: A
Current
24V
P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F : Final
SH. 4 OF 5

ELECTRICAL LOAD LIST (B12-1
- System III : 24V DC ) FIRE &
GAS, HIPPS SYSTEM
Client: ONGC


Sr. No.



Load Description



Qty.


Rated
Voltage


Unit Load
(Watt)

Total Load
(Watt)

Run Up
Time In
Hrs./Day
Energy
Consume
d in
Ah/Day
Energy
Consumed
in WH/Day
Unit Load
@ 24V
DC
(Amp.)

Total Load
24V DC
(Amp.)
Duty Cycle/
Load
Factor
Average
Drawn @
(Amp.)

Status


Remarks


1 FIRE AND GAS PLC

1.1 Hydrogen Detectors 3 24 4.6 13.8 24 13.8 331.2 0.192 0.575 P
1.2 HC Gas Detectors 32 24 7.5 240 24 240 5760 0.313 10 P

1.3 Heat Detectors 10 24 0.25 2.5 24 2.5 60 0.010 0.104 P
1.4 Smoke Detectors 43 24 0.25 10.75 24 10.75 258 0.010 0.43 P
1.5 Flashing beacons 4 24 33.6 134.4 0.25 1.4 33.6 1.400 5.6 P Run-Up time of 0.25hr/day is assumed.
1.6 Electronic hooter 2 24 6 12 0.25 0.25 3 0.250 0.5000 P Run-Up time of 0.25hr/day is assumed.
1.7 Relays & Timers 0 24 6 0 0.25 0.000 0 0.250 0.000 P Run-Up time of 0.25hr/day is assumed.
1.8 F&G PLC 1 24 300 300 24 300 7200 12.5 12.5 P
2 HIPPS

2.1 Pressure Switch 3 24 1.2 3.6 0.01 0.015 0.036 0.050 0.15 P
2.2 Solenoid Valve 4 24 24 96 0.01 0.04 0.96 1.000 4 P
2.3 PLC System 1 24 300 300 24 300 7200 12.5 12.5 1.0000 12.5000 P

TOTAL 1113 968 20,847 46
10% MARGIN 119
94
2265 5
TOTAL (WITH 10% MARGIN ) 1307 1038 24192 54.5


TOTAL AVERAGE DEMAND: Amps
TOTAL PEAK DEMAND: 54.5 Amps



TECHNIP KT INDIA LIMITED.

Shutdown Panel 3 1 24 75 75 24 75 1800 3.12 3.12
P




























Project No. : P4901
Date: 30/05/2012
Rev: A
1188 49.5 944 22647



P: PRELIMINARY D: DESIGN APPROVED C: CERTIFIED F: Final

SH. 5 OF 5


ELECTRICAL LOAD LIST
(B157 - System IV : 24V DC )
NAV-AID SYSTEM

PROJECT NO.: P4901
DATE: 30/05/2012
REV: A



TECHNIP KT INDIA LIMITED.

Client ONGC
Morse code U Nav-Aids Lanterns 15 Sec.
Sr.
no.
Load description Qty.
Rated
voltage
ON OFF ON OFF ON OFF
Duty
cycle
Av
Lamp
current
incl
Surge
Flasher
Quiesce
nt
current
(A)
AVDaily
power
drain
@24V
AV Daily power
drain including
battery charger/
discharger,
efficiency
AV Daily
power
drain @
worse case
(Ah/Day)
Status Remarks

1 Nav Aid Lanterns 4 24 0.4 0.5 0.4 0.50 1.2 12.00 0.13 3.33 0.005 7.22 7.6 30.42 P












Total 1.2 0.13 0.005 7.60 30.42



Total Daily load = 30.42 AH/DAY