You are on page 1of 10

Attachment No.

: 1A

3.5C, PVC, Cu Conductor Cable Selection Table for 415V, 512kW heaters with max. allowed voltage drop of 0.5%

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
3.93
24.55
30.28
36.01
49.10
130.94
147.31
163.68
401.01
491.03
507.40
621.97
654.70
695.62
736.54
777.46
800.38
818.38
838.02
900.22
941.14
998.42
1014.79

[V]
[pf]
[%]
[%] / [V]
[m]
[m]

Continuous
415
0.85
100
0.50
0.686
1
5,000

Starting

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachment no. 13.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid in trays in cable cellar

Min. Cross Section sq. mm


for Short Circuit
25
0.8700
0.097
90
61.74

35
0.6270
0.097
110
75.46

1929
309
250
210
154
58
51
46

2611
418
339
285
209
78
70
63

50
0.4630
0.0940
135
92.61

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.

70
0.3210
0.0900
165
113.19

95
0.2310
0.0900
200
137.20

120
0.1840
0.0870
230
157.78

150
0.1490
0.0870
265
181.79

185
0.1200
0.0870
305
209.23

240
0.0912
0.0870
355
243.53

300
0.0739
0.0860
400
274.40

400
0.0592
0.0860
455
312.13

1001
812
682
500
188
167
150
61
50
48
40
38

1206
978
823
603
226
201
181
74
60
58
48
45
43
40
38

1415
1147
964
707
265
236
212
87
71
68
56
53
50
47
45
43
42
41
39

1650
1338
1125
825
309
275
248
101
83
80
65
62
58
55
52
51
50
48
45
43
41
40

1978
1604
1349
989
371
330
297
121
99
96
78
74
70
66
62
61
59
58
54
52
49
48

2257
1830
1539
1128
423
376
338
138
113
109
89
85
80
75
71
69
68
66
62
59
55
55

2552
2069
1740
1276
478
425
383
156
128
123
101
96
90
85
81
78
77
75
70
67
63
62

Cable Length [m]

Load [KW]
2.40
15.00
18.50
22.00
30.00
80.00
90.00
100.00
245.00
300.00
310.00
380.00
400.00
425.00
450.00
475.00
489.00
500.00
512.00
550.00
575.00
610.00
620.00

2.1

3442
551
446
375
275
103
92
83
34

4761
762
618
519
381
143
127
114
47
38
37

Attachment No. : 1B

3.5C, PVC, Cu Conductor Cable Selection Table for 415V, Lighting Transformer with max. allowed voltage drop of 0.5%

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
3.93
24.55
30.28
36.01
49.10
130.94
147.31
163.68
401.01
491.03
507.40
621.97
654.70
695.62
736.54
777.46
800.38
818.38
838.02
900.22
941.14
998.42
1014.79

[V]
[pf]
[%]
[%] / [V]
[m]
[m]

Continuous
415
0.85
100
0.50
0.686
1
5,000

Starting

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachment no. 13.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid in trays in cable cellar

Min. Cross Section sq. mm


for Short Circuit
25
0.8700
0.097
90
61.74

35
0.6270
0.097
110
75.46

386
62
50
42
31

522
84
68
57
42

50
0.4630
0.0940
135
92.61

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.

70
0.3210
0.0900
165
113.19

95
0.2310
0.0900
200
137.20

120
0.1840
0.0870
230
157.78

150
0.1490
0.0870
265
181.79

185
0.1200
0.0870
305
209.23

240
0.0912
0.0870
355
243.53

300
0.0739
0.0860
400
274.40

400
0.0592
0.0860
455
312.13

1251
200
162
136
100
38

1508
241
196
165
121
45
40

1768
283
229
193
141
53
47
42

2063
330
268
225
165
62
55
50

2472
396
321
270
198
74
66
59

2821
451
366
308
226
85
75
68

3189
510
414
348
255
96
85
77

Cable Length [m]

Load [KW]
2.40
15.00
18.50
22.00
30.00
80.00
90.00
100.00
245.00
300.00
310.00
380.00
400.00
425.00
450.00
475.00
489.00
500.00
512.00
550.00
575.00
610.00
620.00

2.1

688
110
89
75
55

952
152
124
104
76

Attachment No. : 2

3.5C, PVC, Cu Conductor Cable Selection Table for 415V, 2.4kW heaters with max. allowed voltage drop of 2.5%.

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
0.90
1.23
1.80
2.46
3.93
6.06
9.00
12.28
18.00
19.64
30.28
36.01
73.65
99.84
160.40
199.68
401.01
507.40
572.87
654.70
671.07
800.38
818.38

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
27
13.88

Continuous
Starting
415
0.85
100
2.5
10.4
0.514
1
5,000
4
6
10
5.5200
3.6900
2.1900
0.116
0.11
0.1
36
45
60
18.50
23.13
30.84

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachment no. 13
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
16
1.3800
0.097
77
39.58

25
0.8700
0.097
99
50.89

35
0.6270
0.097
120
61.68

50
0.4630
0.0940
145
74.53

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.3210
0.0900
175
89.95

95
0.2310
0.0900
210
107.94

120
0.1840
0.0870
240
123.36

150
0.1490
0.0870
270
138.78

185
0.1200
0.0870
300
154.20

4058
2730
2002
1365
1251
812
682
334
246

4891
3290
2413
1645
1508
978
823
402
297

3858
2829
1929
1768
1147
964
472
348

4501
3301
2251
2063
1338
1125
550
406

240
0.0912
0.0870
345
177.33

300
0.0739
0.0860
385
197.89

3956
2697
2472
1604
1349
659
486
303

4513
3077
2821
1830
1539
752
555
345

400
0.0592
0.0860
425
218.45

Cable Length [m]

Load [KW]
0.55
0.75
1.10
1.50
2.40
3.70
5.50
7.50
11.00
12.00
18.50
22.00
45.00
61.00
98.00
122.00
245.00
310.00
350.00
400.00
410.00
489.00
500.00

875
642
438
321
201
130
88
64

1400
1027
700
513
321
208
140
103
70

2083
1528
1042
764
477
310
208
153
104
95

3476
2549
1738
1275
797
517
348
255
174
159
103

3986
2718
1993
1246
808
544
399
272
249
162
136

4208
3086
1929
1251
842
617
421
386
250
210

4177
2611
1694
1139
835
570
522
339
285

3442
2232
1502
1101
751
688
446
375
184

4761
3089
2078
1524
1039
952
618
519
254

3479
3189
2069
1740
851
627
391
314

Attachment No. : 3A

3C, PVC, Cu or Al Conductor Cable Selection Table for 415V, motors below 75kW with max. allowed voltage drop of 5% & starting voltage drop of 15%

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
0.64
1.29
1.89
2.58
3.78
6.44
9.45
12.88
18.89
25.76
31.78
37.79
51.53
64.41
77.29
94.47
128.82
154.58
188.93
226.72
257.64
274.81
317.75

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
27
13.88

Continuous
Starting
415
0.9
0.25
90
5.0
20.8
15
0.514
50
2,000
4
6
10
5.5200
3.6900
3.7000
0.116
0.11
0.1
36
45
46
18.50
23.13
23.64

1. The resistance, reactance and ampacity data is based on vendor's catalogue

Starting Current

700

refer attachment no. 15 & 16.


2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:

62.3

Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
16
2.2900
0.097
60
30.84

25
1.4400
0.097
76
39.06

35
1.0400
0.097
92
47.29

50
0.7700
0.0940
110
56.54

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
135
69.39

95
0.3850
0.0900
165
84.81

120
0.3050
0.0870
185
95.09

150
0.2500
0.0870
210
107.94

185
0.2000
0.0870
235
120.79

1488
1207
1015
744
595
496
406

1769
1434
1206
884
707
590
482

1730
1455
1067
854
711
582

240
0.1520
0.0870
275
141.35

300
400
0.1230 0.0975
0.0860 0.0860
305
335
156.77 172.19

Cable Length [m]

Load [KW]
0.37
0.75
1.10
1.50
2.20
3.75
5.50
7.50
11.00
15.00
18.50
22.00
30.00
37.50
45.00
55.00
75.00
90.00
110.00
132.00
150.00
160.00
185.00

[%]

1157
789
579
395
231
158
116

1853
1264
927
632
371
253
185

1882
1380
941
552
376
276
188

1880
1378
940
551
376
276
188

1507
884
603
442
301
221

1390
948
695
474
347
282
237

1901
1296
951
648
475
385
324

1728
1267
864
634
514
432
317

1795
1224
898
728
612
449
359

1644
1206
977
822
603
482
402

1815
1331
1065
887
726
532

1569
1255
1046
856
628
523

1857
1485
1238
1013
743
619

Attachment No. : 3B

3C, PVC, Cu or Al Conductor Cable Selection Table for 415V, motors above 75kW with max. allowed voltage drop of 5% & starting voltage drop of 15%

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
0.64
1.29
1.89
2.58
3.78
6.44
9.45
12.88
18.89
25.76
31.78
37.79
51.53
64.41
77.29
94.47
128.82
154.58
188.93
226.72
257.64
274.81
317.75

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
27
13.88

Continuous
Starting
415
0.9
0.25
90
5.0
20.8
15
0.514
50
2,000
4
6
10
5.5200
3.6900
3.7000
0.116
0.11
0.1
36
45
46
18.50
23.13
23.64

1. The resistance, reactance and ampacity data is based on vendor's catalogue

Starting Current

600

refer attachment no. 15 & 16.


2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:

62.3

Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
16
2.2900
0.097
60
30.84

25
1.4400
0.097
76
39.06

35
1.0400
0.097
92
47.29

50
0.7700
0.0940
110
56.54

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
135
69.39

95
0.3850
0.0900
165
84.81

120
0.3050
0.0870
185
95.09

150
0.2500
0.0870
210
107.94

1488
1191
992
812
595
496
406

1769
1415
1179
965
707
590
482

185
0.2000
0.0870
235
120.79

240
0.1520
0.0870
275
141.35

300
400
0.1230 0.0975
0.0860 0.0860
305
335
156.77 172.19

Cable Length [m]

Load [KW]
0.37
0.75
1.10
1.50
2.20
3.75
5.50
7.50
11.00
15.00
18.50
22.00
30.00
37.50
45.00
55.00
75.00
90.00
110.00
132.00
150.00
160.00
185.00

[%]

1578
1157
789
463
316
231
158
116

1853
1264
741
505
371
253
185
150

1882
1104
753
552
376
276
224
188

1880
1103
752
551
376
276
224
188

1769
1206
884
603
442
359
301
221

1895
1390
948
695
563
474
347
278
232

1901
1296
951
771
648
475
380
317
259

1728
1267
1027
864
634
507
422
346

1795
1456
1224
898
718
598
490
359

1955
1644
1206
964
804
658
482
402

1707
1423
1164
854
711
582
485

1774
1452
1065
887
726
605
532
499

1712
1255
1046
856
713
628
588

1485
1238
1013
844
743
696
602

Attachment No. : 4

3.5C, PVC, Al Conductor Cable Selection Table for 415V, Lighting & Power Panels & Welding Receptacles with max. allowed voltage drop of 3%.

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
0.82
1.64
2.46
3.27
7.37
8.18
12.28
14.73
19.64
24.55
29.46
40.92
49.10
60.56
65.47
81.84
98.21
147.31
180.04
216.05
245.51
261.88
302.80

[V]
[pf]
[%]
[%] / [V]
[m]
[m]

Continuous
415
0.85
100
3.0
0.514
50
2,000

Starting

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachemnt no. 14.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
25
1.4400
0.097
76
39.06

35
1.0400
0.097
92
47.29

50
0.7700
0.0940
110
56.54

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6 sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
135
69.39

95
0.3850
0.0900
165
84.81

120
0.3050
0.0870
185
95.09

1563
1302
977
781
651
469
391
317
293
234

1919
1599
1200
960
800
576
480
389
360
288

150
0.2500
0.0870
210
107.94

185
0.2000
0.0870
235
120.79

240
0.1520
0.0870
275
141.35

300
0.1230
0.0860
305
156.77

400
0.0975
0.0860
335
172.19

1889
1417
1133
944
680
567
459
425
340
283

1696
1357
1130
814
678
550
509
407
339

1673
1394
1004
836
678
627
502
418

1954
1628
1172
977
792
733
586
488
326

1903
1371
1142
926
857
685
571
381

Cable Length [m]

Load [KW]
0.50
1.00
1.50
2.00
4.50
5.00
7.50
9.00
12.00
15.00
18.00
25.00
30.00
37.00
40.00
50.00
60.00
90.00
110.00
132.00
150.00
160.00
185.00

12.5

1722
765
689
459
383
287
230
191

1044
939
626
522
391
313
261
188

1386
1248
832
693
520
416
347
250
208

1953
1758
1172
977
733
586
488
352
293
238
220

Attachment No. : 5

3C, PVC, Cu or Al Conductor Cable Selection Table for 240V, 1, Lighting fixtures, PDC Panels & Convenience Receptacles with
max. allowed voltage drop of 1.5%.
Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
2.31
4.63
6.94
7.41
9.26
13.89
18.52
23.15
50.93
69.44
85.65
115.74
138.89
171.30
208.33
254.63
347.22
416.67
509.26
611.11
694.44
740.74
856.48

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
24
16.46

Continuous
Starting
240
0.9
100
1.5
3.6
0.686
20
2,000
4
6
10
5.5200
3.6900
3.7000
0.116
0.11
0.1
30
39
40
20.58
26.75
27.44

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachment no. 15 & 16.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid in trays.

Min. Cross Section sq. mm


for Short Circuit
16
2.2900
0.097
51
34.99

25
1.4400
0.097
70
48.02

35
1.0400
0.097
86
59.00

370
185
123
116
92
62
46
37

581
291
194
182
145
97
73
58

795
397
265
248
199
132
99
79
36

50
0.7700
0.0940
105
72.03

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
130
89.18

95
0.3850
0.0900
155
106.33

120
0.3050
0.0870
180
123.48

150
0.2500
0.0870
205
140.63

185
0.2000
0.0870
240
164.64

1008
672
630
504
336
252
202
92
67
54

1244
830
778
622
415
311
249
113
83
67
50

1479
986
924
739
493
370
296
134
99
80
59
49

1784
1189
1115
892
595
446
357
162
119
96
71
59

240
300
0.1520 0.1230
0.0870 0.0860
280
315
192.08 216.09

400
0.0975
0.0860
375
257.25

Cable Length [m]

Motor [KW]
0.50
1.00
1.50
1.60
2.00
3.00
4.00
5.00
11.00
15.00
18.50
25.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
150.00
160.00
185.00

97
48
32
30
24

155
77
52
48
39
26

231
115
77
72
58
38
29
23

230
115
77
72
58
38
29
23

1059
530
353
331
265
177
132
106
48
35

1501
751
500
469
375
250
188
150
68
50
41

1483
1391
1113
742
556
445
202
148
120
89
74
60

1749
1640
1312
875
656
525
239
175
142
105
87
71
58

1940
1552
1035
776
621
282
207
168
124
103
84
69
56

Attachment No. : 6

PVC, Cu or Al Conductor Cable Selection Table for 110V, 1 loads with max. allowed voltage drop of 5%.

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
5.35
10.70
16.04
17.11
21.39
32.09
42.78
53.48
117.65
160.43
197.86
235.29
320.86
395.72
481.28
588.24
802.14
962.57
1176.47
1411.76
1604.28
1711.23
1978.61

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
27
13.88

Continuous
Starting
110
0.85
100
5.0
5.5
0.514
50
2,000
4
6
10
5.5200
3.6900
3.7000
0.116
0.11
0.1
36
45
46
18.50
23.13
23.64

1. The resistance, reactance and ampacity data is based on vendor's catalogue


refer attachment no. 15 & 16.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
16
2.2900
0.097
60
30.84

25
1.4400
0.097
76
39.06

35
1.0400
0.097
92
47.29

257
129
86
80
64

403
202
134
126
101
67

550
275
183
172
137
92
69

50
0.7700
0.0940
110
56.54

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
135
69.39

95
0.3850
0.0900
165
84.81

120
0.3050
0.0870
185
95.09

150
0.2500
0.0870
210
107.94

1373
686
458
429
343
229
172
137

1686
843
562
527
421
281
211
169

1991
995
664
622
498
332
249
199

185
0.2000
0.0870
235
120.79

240
0.1520
0.0870
275
141.35

300
0.1230
0.0860
305
156.77

1191
794
745
596
397
298
238
108

1469
979
918
735
490
367
294
134

1716
1144
1072
858
572
429
343
156

400
0.0975
0.0860
335
172.19

Cable Length [m]

Motor [KW]
0.50
1.00
1.50
1.60
2.00
3.00
4.00
5.00
11.00
15.00
18.50
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
150.00
160.00
185.00

68

108
54

161
80
54
50

161
80
54
50

730
365
243
228
183
122
91
73

1029
515
343
322
257
172
129
103

1337
1254
1003
669
501
401
182
134

Attachment No. : 7

PVC, Cu or Al Conductor Cable Selection Table for 110V, DC loads with max. allowed voltage drop of 5%.

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]

[KW]

1
2
3
4
5
6
7
8
9
10
12
14
16
18
20
25
30
35
40
50
60
70
80

24
48
72
96
120
144
168
192
216
240
288
336
384
432
480
600
720
840
960
1200
1440
1680
1920

Continuous
Starting
24
100
2.5
0.6
0.790
[m]
1
[m]
500
2.5
4
6
10
7.4100
4.6100
3.0800
3.0800
-

1. The resistance and Reactance data is based on vendor's catalogue

[V]
[%]
[%]
[%] / [V]

refer attachment no. 15 & 16.


2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

16
1.9100
-

25
1.2000
-

35
0.8680
-

50
0.6410
-

70
0.4430
-

95
0.3200
-

120
0.2530
-

150
0.2060
-

185
0.1640
-

240
0.1250
-

30

40

50

65

84

110

135

161

194

232

263

293

327

375

24

32

40

51

66

87

107

127

153

183

208

231

258

296

300
0.1000
305
241

40
20
13
10
8
7
6
5
4
4
3
3
3
2
2

65
33
22
16
13
11
9
8
7
7
5
5
4
4
3
3
2

97
49
32
24
19
16
14
12
11
10
8
7
6
5
5
4
3
3

97
49
32
24
19
16
14
12
11
10
8
7
6
5
5
4
3
3
2
2

157
79
52
39
31
26
22
20
17
16
13
11
10
9
8
6
5
4
4
3
3

250
125
83
63
50
42
36
31
28
25
21
18
16
14
13
10
8
7
6
5
4
4
3

346
173
115
86
69
58
49
43
38
35
29
25
22
19
17
14
12
10
9
7
6
5
4

469
313
234
188
156
134
117
104
94
78
67
59
52
47
38
31
27
23
19
16
13
12

395
296
237
198
169
148
132
119
99
85
74
66
59
47
40
34
30
24
20
17
15

485
364
291
243
208
182
162
146
121
104
91
81
73
58
49
42
36
29
24
21
18

457
366
305
261
229
203
183
152
131
114
102
91
73
61
52
46
37
30
26
23

480
400
343
300
267
240
200
171
150
133
120
96
80
69
60
48
40
34
30

429
375
333
300
250
214
188
167
150
120
100
86
75
60
50
43
38

400
0.0778
335
265

482
428
386
321
275
241
214
193
154
129
110
96
77
64
55
48

Cable Length [m]


468
234
156
117
94
78
67
59
52
47
39
33
29
26
23
19
16
13
12
9
8
7
6

339
226
169
135
113
97
85
75
68
56
48
42
38
34
27
23
19
17
14
11
10
8

Attachment No. : 8

3C, PVC, Cu or Al Conductor Cable Selection Table for 1 loads like Space Heaters with max. allowed voltage drop of 1.5%.

Condition
Rated Voltage
Power Factor
Efficiency
Acceptable Voltage Drop
Rating Factor
Minimum Cable Length
Maximum Cable Length
Cable Size [sq. mm]
Resistance [ohm/km]
Reactance [ohm/km]
Ampacity
[A]
Derated Ampacity [A]
FLC [A]
0.69
1.85
4.63
7.41
9.26
13.89
18.52
23.15
50.93
69.44
85.65
101.85
138.89
171.30
208.33
254.63
347.22
416.67
509.26
611.11
694.44
740.74
856.48

[V]
[pf]
[%]
[%] / [V]
[m]
[m]
2.5
8.8700
0.119
27
18.52

Continuous
Starting
240
0.9
100
1.5
3.6
0.686
20
2,000
4
6
10
5.5200
3.6900
3.7000
0.116
0.11
0.1
36
45
46
24.70
30.87
31.56

1. The resistance and Reactance data is based on vendor's catalogue


refer attachment no. 15 & 16.
2. The Ampacity data was derived from vendor's catalogue under the

No. of cable runs

following conditions:
Cables laid direct in ground.

Min. Cross Section sq. mm


for Short Circuit
16
2.2900
0.097
60
41.16

25
1.4400
0.097
76
52.14

1232
462
185
116
92
62
46
37

1937
726
291
182
145
97
73
58
26

35
1.0400
0.097
92
63.11

50
0.7700
0.0940
110
75.46

1.50 3. The rating factor was calculated in accordance with vendor's catalogue.
4. All cables upto and including 6sqmm shall be with Cu conductor & above 6 sq mm
shall be with Al conductor.

70
0.5320
0.0900
135
92.61

95
0.3850
0.0900
165
113.19

120
0.3050
0.0870
185
126.91

150
0.2500
0.0870
210
144.06

185
0.2000
0.0870
235
161.21

1008
630
504
336
252
202
92
67
54
46

1244
778
622
415
311
249
113
83
67
57

1479
924
739
493
370
296
134
99
80
67
49

1784
1115
892
595
446
357
162
119
96
81
59

240
300
0.1520 0.1230
0.0870 0.0860
275
305
188.65 209.23

400
0.0975
0.0860
335
229.81

Cable Length [m]

Motor [KW]
0.15
0.40
1.00
1.60
2.00
3.00
4.00
5.00
11.00
15.00
18.50
22.00
30.00
37.00
45.00
55.00
75.00
90.00
110.00
132.00
150.00
160.00
185.00

323
121
48
30
24

516
194
77
48
39
26

769
289
115
72
58
38
29
23

768
288
115
72
58
38
29
23

994
397
248
199
132
99
79
36

1324
530
331
265
177
132
106
48
35

1876
751
469
375
250
188
150
68
50
41

1391
1113
742
556
445
202
148
120
101
74
60

1640
1312
875
656
525
239
175
142
119
87
71
58

1940
1552
1035
776
621
282
207
168
141
103
84
69