Profibus - Manual

AERtronic AS 300 V1.07 and later


The Profibus EM5 Module works with 64 word input and 8 word output data.
Data from client to AERtronic:

1. Byte Acknowledge status
Place this byte to hex value 5A and the most recent status will be acknowledged. It
is recommended to only enter this value in the register for 1-2 seconds and then to
overwrite it with hex value 00.
2. Byte: Remote on / off
Bit 0: compressor on
Bit 1 Bit 6: 0
Bit 7: release or enable compressor on / off
The remote on / off control will only be active if the controller parameters have been
set to active and the release Bit 7 has been set. When properly activated the local on /
off screen buttons show a lock symbol and the machine may be started with Bit 0 =1
and stopped with Bit 0 =0. The parameter remote on/off must set to
Modbus/Profibus. (main menu control misc. remote on/off)
3. Byte Remote pressure control
Bit 0: remote pressure control on
Bit 1 Bit 6: 0
Bit 7: release or enable remote pressure control
The remote pressure control will only be active if the controller parameters have been
set to active and the release Bit 7 has been set.
In this case the pressure control may be activated with Bit 0. Bit 0 =1 will put the
compressor into load mode or it starts from standby mode in case the shut-down-
operation (main menu control system misc. operation mode) has been set. Set
Bit 0 =0 then the machine will go into unload and idle mode and will place it into
standby mode (main motor off) upon elapsing the minimum run-on time (main menu
machine parameter). The shut-down-operation must be set to active also.
4. Byte Remote pressure set value
Bit 0 Bit 5: 0
Bit 6: release or enable remote RPM set value
Bit 7: release or enable remote pressure set value
The pressure set value is only active if Bit 7 is set. Within this value the set value may
be provided in Byte 5 and 6.
The RPM set value is only active if Bit 6 is set. Within this value the RPM may be
controlled with Byte 7 and 8. The RPM will only be visible/ displayed once the main
motor has reached at least min speed. This is also for the HMI display; at standstill the
value would be e.g. 0%.
5. Byte: \ Actual pressure set value [mbar] / word (16bit) integer
6. Byte: /
7. Byte: \ Actual RPM set value [0,1 %] / word (16bit) integer
8. Byte: / The information [0,1 %] refers to the decimal point. Example: At a speed
demand of 45,8% the value 458 must be transmitted
9. Byte
16. Byte Free
Data from AERtronic to client:
Shutdown status message:
With an active shut down the corresponding Bit is set =1. In the attached list all possible shut downs
or trips are detailed. Which ones are selected depends on the type of machine (i.e. Blower,
Compressor single stage, or two stage) and the chosen configuration.
Principle:
- Trip signals must lead to the shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or shut down signal

1. Byte: Bit 0: Shutdown voltage breakdown
Bit 1: Shutdown Emergency OFF Digital Input
Bit 2: Shutdown main motor over load Digital Input
Bit 3: Shutdown main motor over temperature Digital Input
Bit 4: Shutdown fan (electric) over load Digital Input
Bit 5: Shutdown electric oil demister over load Digital Input
Bit 6: Shutdown electric oil demister 2 over load Digital Input
Bit 7: Shutdown oil pump over load
2. Byte: Bit 0: Shutdown vibration Digital Input
Bit 1: Shutdown condition monitoring Digital Input
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free
3. Byte: Bit 0: Shutdown suction pressure Limit exceeded
Bit 1: Shutdown compression ratio Limit exceeded
Bit 2: Shutdown discharge pressure Limit exceeded
Bit 3: Shutdown discharge temperature Limit exceeded
Bit 4: Shutdown system (header) temperature Limit exceeded
Bit 5: Shutdown oil pressure Limit exceeded
Bit 6: Shutdown oil temperature Limit exceeded
Bit 7: Shutdown intake temperature 2 Limit exceeded
4. Byte: Bit 0: Shutdown discharge pressure 2 Limit exceeded
Bit 1: Shutdown discharge temperature 2 Limit exceeded
Bit 2: Shutdown oil pressure 2 Limit exceeded
Bit 3: Shutdown oil temperature 2 Limit exceeded
Bit 4: Free
Bit 5: Shutdown RPM (revolutions per minute) Limit exceeded
Bit 6: Shutdown oil level Limit exceeded
Bit 7: Free

5. Byte: Bit 0: Shutdown sensor suction pressure Signal fault
Bit 1: Shutdown sensor ambient temperature Signal fault
Bit 2: Shutdown sensor discharge pressure Signal fault
Bit 3: Shutdown sensor discharge temperature Signal fault
Bit 4: Shutdown sensor system (header) pressure Signal fault
Bit 5: Shutdown sensor system (header) temperature Signal fault
Bit 6: Shutdown sensor oil pressure Signal fault
Bit 7: Shutdown sensor oil temperature Signal fault

6. Byte: Bit 0: Shutdown sensor intake temperature 2 Signal fault
Bit 1: Shutdown sensor discharge pressure 2 Signal fault
Bit 2: Shutdown sensor discharge temperature 2 Signal fault
Bit 3: Shutdown sensor oil pressure 2 Signal fault
Bit 4: Shutdown sensor oil temperature 2 Signal fault
Bit 5: Shutdown sensor RPM (revolutions per minute) Signal fault
Bit 6: Free
Bit 7: Shutdown sensor external set value Signal fault
7. Byte: Bit 0: Shutdown sensor oil level Signal fault
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Shutdown vibration 1S1 Limit exceeded
Bit 5: Shutdown vibration G1 Limit exceeded
Bit 6: Shutdown vibration 3S1 Limit exceeded
Bit 7: Shutdown vibration 1S2 Limit exceeded
8. Byte: Bit 0: Shutdown vibration G2 Limit exceeded
Bit 1: Shutdown vibration 3S2 Limit exceeded
Bit 2: Shutdown sensor vibration 1S1 Signal fault
Bit 3: Shutdown sensor vibration G1 Signal fault
Bit 4: Shutdown sensor vibration 3S1 Signal fault
Bit 5: Shutdown sensor vibration 1S2 Signal fault
Bit 6: Shutdown sensor vibration G2 Signal fault
Bit 7: Shutdown sensor vibration 3S2 Signal fault
9. Byte: Bit 0: Free
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free
10. Byte: Bit 0: Free
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free
11. Byte: Bit 0: Shutdown communication module address 1 internal
Bit 1: Shutdown communication module address 2 internal
Bit 2: Shutdown communication module address 3 internal
Bit 3: Shutdown communication module address 4 internal
Bit 4: Shutdown communication module address 5 internal
Bit 5: Shutdown communication module address 6 internal
Bit 6: Shutdown communication module address 7 internal
Bit 7: Shutdown communication module address 8 internal
12. Byte: Bit 0: Shutdown communication module address 9 internal
Bit 1: Shutdown communication module address 10 internal
Bit 2: Shutdown communication module address 11 internal
Bit 3: Shutdown communication module address 12 internal
Bit 4: Shutdown communication module address 13 internal
Bit 5: Shutdown communication module address 14 internal
Bit 6: Shutdown communication module address 15 internal
Bit 7: Shutdown parameter invalid internal
Warning / alarm:
With an active alarm the corresponding Bit is set =1. In the attached list all possible alarms are
detailed. Which ones are selected depends on the type of machine (i.e. Blower, Compressor single
stage, or two stage) and the chosen configuration.
Principle:
- Alarm and warning signals dont lead to a shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or warning signal



13. Byte: Bit 0: Free
Bit 1: Warning / alarm suction pressure Limit exceeded
Bit 2: Warning / alarm ambient temperature low Limit exceeded
Bit 3: Warning / alarm ambient temperature high Limit exceeded
Bit 4: Warning / alarm discharge pressure Limit exceeded
Bit 5: Warning / alarm discharge temperature Limit exceeded
Bit 6: Warning / alarm system (header) temperature Limit exceeded
Bit 7: Warning / alarm oil pressure Limit exceeded
14. Byte: Bit 0: Warning / alarm oil temperature Limit exceeded
Bit 1: Warning / alarm intake temperature 2 Limit exceeded
Bit 2: Warning / alarm discharge pressure 2 Limit exceeded
Bit 3: Warning / alarm discharge temperature 2 Limit exceeded
Bit 4: Warning / alarm oil pressure 2 Limit exceeded
Bit 5: Warning / alarm oil temperature 2 Limit exceeded
Bit 6: Free
Bit 7: Warning / alarm RPM (revolutions per minute) Limit exceeded
15. Byte: Bit 0: Warning / alarm oil level Limit exceeded
Bit 1: Warning / alarm compression ratio Limit exceeded
Bit 2: Warning / alarm cooling water flow Digital input
Bit 3: Warning / alarm condensate drain 1 Digital input
Bit 4: Warning / alarm condensate drain 2 Digital input
Bit 5: Warning / alarm after cooler 1 Digital input
Bit 6: Warning / alarm after cooler 2 Digital input
Bit 7: Free

16. Byte: Bit 0: Warning / alarm vibration 1S1 Limit exceeded
Bit 1: Warning / alarm vibration G1 Limit exceeded
Bit 2: Warning / alarm vibration 3S1 Limit exceeded
Bit 3: Warning / alarm vibration 1S2 Limit exceeded
Bit 4: Warning / alarm vibration G2 Limit exceeded
Bit 5: Warning / alarm vibration 3S2 Limit exceeded
Bit 6: Free
Bit 7: Free
17. Byte: Bit 0: Free
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free
18. Byte: Bit 0: Free
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Warning / alarm BLC-Module internal
Maintenance:
If a maintenance required or necessary the corresponding Bit is set =1. The maintenance message is
so long active until the reset in the menu acknowledge maintenance
19. Byte: Bit 0: Maintenance intake filter service needed
Bit 1: Maintenance pressure filter service needed
Bit 2: Maintenance cooling air in / out service needed
Bit 3: Maintenance drive V-belts service needed
Bit 4: Maintenance coupling service needed
Bit 5: Maintenance pressure relief valve service needed
Bit 6: Maintenance lube oil service needed
Bit 7: Maintenance oil filter service needed
20. Byte: Bit 0: Maintenance check valve service needed
Bit 1: Maintenance oil demister service needed
Bit 2: Maintenance water cooling service needed
Bit 3: Maintenance water condensate drain service needed
Bit 4: Maintenance main motor service needed
Bit 5: Maintenance 1.inspection service needed
Bit 6: Maintenance main inspection service needed
Bit 7: Maintenance battery service needed
Status display:
21. Byte: Bit 0: Start temperature too low Limit exceeded =1
No start possible
Bit 1: Start / stops exceeded Number of motor starts
per hour exceeded =1
No start possible
Bit 2: Re-start-delay active Active =1
No start possible
Bit 3: Waiting for timer Waiting =1
Bit 4: Automatic re-starts After voltage breakdown
Automatic start =1
Bit 5: Free
Bit 6: Free
Bit 7: Free
22. Byte: Free
Status:
23. Byte: Bit 0: System ready Machine ready to
start =1. After the start
up and during operation
the Bit is set to 1. Also
during shut-down
operation and standby
mode the Bit is set to 1

Bit 1: System waiting (Timer, Automatic restart delay) Timer or automatic
restart delay active =1
Bit 2: System standby Machine is in standby
mode =1
(main motor off)
Bit 3: System Motor Starting / ramp up Only during start up of
the motor is the Bit =1
Bit 4: System in idle / unload (cont. operation) Bit is set =1, when the
machine is running and
in unload. Only active
by continuously
operation mode
Bit 5: System in load Bit is set =1, when the
machine is running and
in load

Bit 6: System in ramp down (shut down operation) Bit is set =1, when the
shut-down operation is
active and the machine
is in unload. The
machine switches into
standby mode when the
Min. run-on time is
expired (main motor off)
Bit 7: System in soft ramp down Bit is set =1, when the
machine is within the
switch off time. The
machine stop is
activated but it remains
running in idle mode for
a present time before the
main motor is stopped.

24. Byte: Bit 0: Control ON/OFF enabled over Profibus Bit is set =1. when the
parameter remote
on/off is set to
Profibus and the
release Bit 7 from
Byte 2 is set to 1
Bit 1: Control Load enabled over Profibus Bit is set =1, when the
parameter
remote load/idle is set
to Profibus and the
release Bit 7 from
Byte 3 is set to 1
Bit 2: System is initiate (start command) Bit is set =1, when the
machine is initiate. In
this case the machine
can be running or is in
standby mode
Bit 3: System main motor running Bit is set =1, when the
main motor is running
Bit 4: System re-start block active Bit is set =1, when the
re-start is blocked (max
starts, start-up temp.,
etc.)
Bit 5: System maintenance active Bit is set =1, when a
maintenance is needed
Bit 6: System warning / alarm active Bit is set =1, when a
warning or an alarm is
active
Bit 7: System shut down active Bit is set =1, when a
shut down is active
Digital Inputs:
25. Byte: Bit 0: Input Emergency Stop fixed dedicated
Bit 1: Input 2 on Address 1
Bit 2: Input 3 on Address 1
Bit 3: Input main motor temperature too high fixed dedicated
Bit 4: Input 1 on Address 2
Bit 5: Input 2 on Address 2
Bit 6: Input 3 on Address 2
Bit 7: Free
26. Byte: Bit 0: Input 1 on Address 3
Bit 1: Input 2 on Address 3
Bit 2: Input 3 on Address 3
Bit 3: Input 4 on Address 3
Bit 4: Input 1 on Address 4
Bit 5: Input 2 on Address 4
Bit 6: Input 3 on Address 4
Bit 7: Input 4 on Address 4
27. Byte: Bit 0: Input 1 on Address 5
Bit 1: Input 2 on Address 5
Bit 2: Input 3 on Address 5
Bit 3: Input 4 on Address 5
Bit 4: Input 1 on Address 6
Bit 5: Input 2 on Address 6
Bit 6: Input 3 on Address 6
Bit 7: Input 4 on Address 6
28. Byte: Bit 0: Input 1 on Address 7
Bit 1: Input 2 on Address 7
Bit 2: Input 3 on Address 7
Bit 3: Input 4 on Address 7
Bit 4: Input 1 on Address 8
Bit 5: Input 2 on Address 8
Bit 6: Input 3 on Address 8
Bit 7: Input 4 on Address 8
29. Byte: Bit 0: Input 1 on Address 9
Bit 1: Input 2 on Address 9
Bit 2: Input 3 on Address 9
Bit 3: Input 4 on Address 9
Bit 4: Input 1 on Address 10
Bit 5: Input 2 on Address 10
Bit 6: Input 3 on Address 10
Bit 7: Input 4 on Address 10
30. Byte: Free

Digital outputs:
31. Byte: Bit 0: Output 1 on Address 1
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Output 1 on Address 2
Bit 5: Output 2 on Address 2
Bit 6: Output 3 on Address 2
Bit 7: Free
32. Byte: Bit 0: Output 1 on Address 3
Bit 1: Output 2 on Address 3
Bit 2: Output 3 on Address 3
Bit 3: Output 4 on Address 3
Bit 4: Output 1 on Address 4
Bit 5: Output 2 on Address 4
Bit 6: Output 3 on Address 4
Bit 7: Output 4 on Address 4
33. Byte: Bit 0: Output 1 on Address 5
Bit 1: Output 2 on Address 5
Bit 2: Output 3 on Address 5
Bit 3: Output 4 on Address 5
Bit 4: Output 1 on Address 6
Bit 5: Output 2 on Address 6
Bit 6: Output 3 on Address 6
Bit 7: Output 4 on Address 6
34. Byte: Bit 0: Output 1 on Address 7
Bit 1: Output 2 on Address 7
Bit 2: Output 3 on Address 7
Bit 3: Output 4 on Address 7
Bit 4: Output 1 on Address 8
Bit 5: Output 2 on Address 8
Bit 6: Output 3 on Address 8
Bit 7: Output 4 on Address 8
35. Byte: Bit 0: Output 1 on Address 9
Bit 1: Output 2 on Address 9
Bit 2: Output 3 on Address 9
Bit 3: Output 4 on Address 9
Bit 4: Output 1 on Address 10
Bit 5: Output 2 on Address 10
Bit 6: Output 3 on Address 10
Bit 7: Output 4 on Address 10
36. Byte: Free

Analog input:
The configured and connected analog inputs will be transmitted as (16Bit) integer. The information
[0,1 %] refers to the decimal point. In that case the value must divide by 10.
(Example 457% / 10 =45,7%)

37. Byte: \ Actual set value for variable speed drive [0,1 %] Value divide by 10
38. Byte: /
39. Byte: \ External set value (pressure) [0,1 %] Value divide by 10
40. Byte: /
41. Byte: \ Actual RPM (revolutions per minute) [UpM]
42. Byte: /
43. Byte: \ Suction pressure [mbar]
44. Byte: /
45. Byte: \ Ambient temperature [C]
46. Byte: /
47. Byte: \ Discharge pressure [mbar]
48. Byte: /
49. Byte: \ Discharge temperature [C]
50. Byte: /
51. Byte: \ Oil pressure [mbar]
52. Byte: /
53. Byte: \ Oil temperature [C]
54. Byte: /
55. Byte: \ System (header) pressure [mbar]
56. Byte: /
57. Byte: \ System (header) temperature [C]
58. Byte: /
59. Byte: \ Intake temperature 2 [C]
60. Byte: /
61. Byte: \ Discharge pressure 2 [mbar]
62. Byte: /
63. Byte: \ Discharge temperature 2 [C]
64. Byte: /
65. Byte: \ Oil pressure 2 [mbar]
66. Byte: /
67. Byte: \ Oil temperature 2 [C]
68. Byte: /
69. Byte: \ Free
70. Byte: /
71. Byte: \ Oil level [%]
72. Byte: /
73. Byte: \ Vibration 1S1 / 3S1 [%] Only the highest value
74. Byte: / will transmitted
75. Byte: \ Vibration G1 [%]
76. Byte: /
77. Byte: \ Vibration 1S2 / 3S2 [%] Only the highest value
78. Byte: / will transmitted
79. Byte: \ Reserve
80. Byte: /
Hours:
The following hours will transmitted as (32Bit) double integer
81. Byte: \
82. Byte: \ Operating hours [h]
83. Byte: /
84. Byte: /
85. Byte: \
86. Byte: \ Loaded hours [h]
87. Byte: /
88. Byte: /
89. Byte: \
90. Byte: \ Idle / no load hours [h]
91. Byte: /
92. Byte: /
93. Byte: \
94. Byte: \ Rented hours [h]
95. Byte: /
96. Byte: /

Maintenance interval:
The following remaining times will transmitted (16Bit) integer
97. Byte: \ Maintenance interval intake filter remaining time [h]
98. Byte: /
99. Byte: \ Maintenance interval pressure filter remaining time [h]
100. Byte: /
101. Byte: \ Maintenance interval cooling air in / out remaining time [h]
102. Byte: /
103. Byte: \ Maintenance interval drive V-belts remaining time [h]
104. Byte: /
105. Byte: \ Maintenance interval coupling remaining time [h]
106. Byte: /
107. Byte: \ Maintenance interval pressure relief valve remaining time [h]
108. Byte: /
109. Byte: \ Maintenance interval lube oil remaining time [h]
110. Byte: /
111. Byte: \ Maintenance interval oil filter remaining time [h]
112. Byte: /
113. Byte: \ Maintenance interval check valve remaining time [h]
114. Byte: /
115. Byte: \ Maintenance interval oil demister remaining time [h]
116. Byte: /
117. Byte: \ Maintenance interval water cooling remaining time [h]
118. Byte: /
119. Byte: \ Maintenance interval water condensate drain remaining time [h]
120. Byte: /
121. Byte: \ Maintenance interval 1.inspection remaining time [h]
122. Byte: /
123. Byte: \ Maintenance interval main inspection remaining time [10h] Value must be
124. Byte: / multiplied by 10
125. Byte: \ Maintenance interval main motor remaining time [h]
126. Byte: /

Communication status:
127. Byte: Free
128. Byte: Bit 0: Free
Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Live Bit / control bit sent every second The Bit changed each
second the status.
Therefore it is very easy
to monitoring the
communication
Bit 7: Communication with main controller ok Bit is set =1, when the
communication between
the Profibus module
EM5 and the AS300
internal is established