You are on page 1of 24

Reduce to 390 ppm TDS CW from 400 ppm

Evap = 75 L/s
TDS = 0 mg/L
CW = 5000 L/s
TDS = 400 mg/L
2,000,000 mg/s
Maintain 400 ppm TDS CW
Evap = 75 L/s
TDS = 0 mg/L
CW = 5000 L/s
TDS = 400 mg/L
2,000,000 mg/s

FILL/SPLASH BAR
OF
COOLING TOWER

FILL/SPLASH BAR
OF
COOLING TOWER
BD = 125 L/s
TDS = 406 mg/L
50,761 mg/s
With blowdown :
CW =
TDS =
RCW = 4925 L/s
TDS = 406 mg/L
2,000,000 mg/s Without Blow Down :
CW =
TDS =
MU =
TDS =
MU = 200 L/s
TDS = 10 mg/L TDS =
2000 mg/s
BD = 11 L/s
TDS = 406 mg/L
4,277 mg/s
With Blow Down :
CW =
TDS =
RCW = 4925 L/s
TDS = 406 mg/L
2,000,000 mg/s Without Blow Down :

BASIN
OF
COOLING TOWER

BASIN
OF
COOLING TOWER
CW =
TDS =
MU =
TDS =
MU = 86 L/s
TDS = 50 mg/L TDS =
4277 mg/s
With blowdown :
5000 L/s
1,951,239 mg/s
390 mg/L
Without Blow Down :
4925 L/s
2,000,000 mg/s
75 L/s
2000 mg/s
400.4 mg/L
With Blow Down :
5000 L/s
2,000,000 mg/s
400 mg/L
Without Blow Down :
4925 L/s
2,000,000 mg/s
75 L/s
4277 mg/s
400.86 mg/L
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11
GPSA Sect 11

You might also like